SC110 MSYSTEM | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 12

Technical content

MODEL: SC110 SC110 SPECIFICATIONS ES-6339 Rev.17 Page 1/12 http://www.m-system.co.jp/ Single Loop Controller Series MULTI-FUNCTION PID CONTROLLER (color LCD with touch-panel, MV output backup) 144 (5.67) (2.83) mm (inch) *Selectable with option code MODEL: SC110–[1]0–[2][3]

ORDERING INFORMATION

  • Code number: SC110-[1]0-[2][3] Specify a code from below for each of [1] through [3]. (e.g. SC110-10-M2/3/M2/E/1/T/Q)
  • Specify the specification for option code /Q (e.g. /C01/S01) [1] DISCRETE OUTPUT 1: Relay contact 2: Photo MOSFET relay MODBUS 0:None [2] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 50/60 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [3] OPTIONS (multiple selections) Housing Depth (must be specified) /300: 300 mm (Discontinued, select /3) /400: 400 mm (Discontinued, select /4) /600: 600 mm (Discontinued, select /6) /3: 300 mm /4: 400 mm /6: 600 mm Backup Module Power Supply blank: Single supply /M2: 100 – 240 V AC (dual supply) (Operational voltage range 85 – 264 V AC; 50/60 Hz) /R: 24 V DC (dual supply) (Operational voltage range 24 V DC ±10 %; ripple 10 %p-p max.) Control/Backup modules are powered from common terminals with 'single' supply type; powered from independent terminals with 'dual' supply type. Language blank: Japanese /E: English (Language (Japanese or English) can be chosen by front panel setting.) Configurator Interface blank: Infrared /1: Stereo jack (If external noise interference is a concern, stereo jack type is recommended.) Terminal block blank: One block terminal /T: Separable terminal Other Options blank: none /Q: Option other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel FUNCTIONS & FEATURES Functions & Features
  • Color LCD with touch panel
  • Five Operation views (digital display, bargraph, dual-loop bargraph, short trend and user's parameter table views)
  • Enhanced screen functions for engineering (configuration, programming and tuning views)
  • Universal input x 2 points, analog input x 4 points, discrete input x 6 points, pulse input x 5 points, high speed pulse input x 1 point
  • Current output (4-20 mA) x 2 points, voltage output (1-5 V) x 2 points, relay or photo-MOSFET relay output x 5 points
  • RUN contact output (relay) x 1 point
  • Computation cycle selectable between 50 msec. and 3 sec. (control cycle selectable between 1 and 64 times of the computation cycle)
  • Two PID function blocks

MODEL: SC110 SC110 SPECIFICATIONS ES-6339 Rev.17 Page 2/12 http://www.m-system.co.jp/

  • Advanced computation and sequence control functions
  • Auto-tuning function
  • Parameter input and changing with touch panel
  • Function parameter setting, list printing and data downloading/uploading available with Loop Configuration Builder Software (model: SFEW3E)
  • Display parameter setting, saving and transfer with PC Configurator Software (model: SCCFG)
  • Backup module (applicable to Mv2 only) is incorporated for manual loading: MV output is automatically switched to manual control in case of control module abnormality
  • Independent power supply usable for the manual loader
  • Control module can be extracted at the front for replacement while MV output is maintained
  • Selectable housing depth for ease of using existing wires in replacement: 300 mm, 400 mm and 600 mm
  • Separable terminal block Typical Applications
  • Replacement of conventional controllers
  • Panel operation for small-scale instrumentation

RELATED PRODUCTS

  • PC Configurator cable (model: COP-US)
  • Loop configuration builder software (model: SFEW3E Ver. 1.40 or later)
  • Infrared communication adaptor (model: COP-IRDA)
  • PC configurator software (model: SCCFG Ver.1.50 or later) Builder software and configurator software are downloadable at M-System’s web site. ACCESSORIES
  • Precision resistor module (model: REM4): 2
  • Cold junction sensor: 2
  • Mounting brackets: 2
  • Connector adapter: 1 (included in Stereo jack type. The jack on the unit and the plug of PC Configurator cable (not included in the product) are different in size.) GENERAL SPECIFICATIONS Construction: Panel flush mounting Degree of protection: IP55; ensured for the front panel of the unit independently mounted to a panel Connection Terminal screws: M3.5 screw terminals (torque 1.0 N·m) Terminal fixing screws: M4 screw terminals (torque 1.2 N·m) Backup module power supply terminal (option /M2, /R): Euro terminal block (applicable wire size: dia. 2.4 max., 0.5 – 2.5 mm2, stripped length 10 mm) Screw terminal Terminal screws: Nickel-plated steel (standard) or stainless steel Terminal fixing screws: Chrome-plated steel Housing material: Flame-resistant resin (gray), steel Isolation: Pv1 to Pv2 to supply output to Ai1 or Ai2 or Ai3 or Ai4 to Di1 or Di2 or Di3 or Di4 or Di5 or Pi1 or Pi2 or Pi3 or Pi4 or Pi5 to Di6 or Pi6 to Mv1 to Mv2 or Mv2B to Ao1 or Ao2 to Do1 to Do2 to Do3 to Do4 to Do5 to Do6 to power to backup module power to FG PID control: Single loop, cascade, advanced Proportional band (P): 1 to 1000 % Integral time (I): 0.01 to 100 minutes Derivative time (D): 0.01 to 10 minutes Auto-tuning: Limit cycle method Alarm: PV high & low, deviation, rate of change Computation: 48 functions blocks available for arithmetic operations, time functions, signal selection, limit, alarm and other functions Sequence operation: Logic sequence and step sequence (max. 1068 commands) Computation cycle: 50 msec. to 3 sec. (control cycle selectable among 1, 2, 4, 8, 16, 32 and 64 times of the computation cycle) MV output range: -15 - +115 % Parameter setting: With touch panel or PC (Loop Configuration Builder Software model: SFEW3E) Self diagnostics: CPU monitoring with a watchdog timer RUN contact: OFF in error detected by diagnostic Infrared communication: Transmission distance max. 0.2 meter (for use with the COP-IRDA) ■ Display Display device: 4.3-inch TFT LCD Display colors: 256 Resolution: 480 × 272 pixels Pixel pitch: 0.198 × 0.198 mm (128 × 128 DPI) Backlight: LED Backlight life: Approx. 50 000 hours (at 50 % brightness) Note: The backlight can be replaced in M-System factory. The LCD must be replaced at the same time. Screen saver standby time: 1 to 99 minutes Scaling range: -32000 to +32000 Decimal point position: 10-1, 10-2, 10-3, 10-4, 10-5 or none Scale divisions: 2 to 10 Engineering unit indication: Max. 8 characters Auto/Man indicator: Green/Amber LED Backup mode MV output setting indicator: Blue LED MV output setting indicator: Blue LED

MODEL: SC110 SC110 SPECIFICATIONS ES-6339 Rev.17 Page 3/12 http://www.m-system.co.jp/ FACTORY DEFAULT CAS PID G02 1 – 5 V DC P : 100% I : No integral action D : No derivative action Mv 1Pv 1Ai 1 1 – 5 V DC *1. Factory default setting Use Loop Configuration Builder Software (model: SFEW3E) to modify setting. H L AL2AL1 SEQ G81 4 – 20 mA DC ■ LOOP 1 ■ LOOP 2 Reverse Action (PV /MV ) *1*1 CAS PID G03 1 – 5 V DC P : 100% I : No integral action D : No derivative action Mv 2Pv 2Ai 2 1 – 5 V DC H L AL4AL3 SEQ G81 4 – 20 mA DC *1*1 Reverse Action (PV /MV ) SUPPLY OUTPUT Output voltage:

24 V DC ±10 % with no load

18 V DC min. at 20 mA Current rating: ≤ 22 mA DC ∙Shortcircuit protection Current limited: Approx. 30 mA INPUT SPECIFICATIONS ■ Pv1, Pv2 (universal input) ∙Current input: 4 – 20 mA DC with input resistance 250 Ω (REM4) ∙Voltage input: -10 – +10 V DC -1 – +1 V DC 0 – 10 V DC 1 – 5 V DC 0 – 1 V DC Input resistance: ≥ 1 MΩ ∙Thermocouple input: K, E, J, T, B, R, S, C, N, U, L, P, PR (See Table 1) Input resistance: ≥ 30 kΩ Burnout sensing: ≤ 0.3 µA Burnout indication: 115 % of the measuring range (upscale) ∙RTD input: Pt100 (JIS ’97, IEC), Pt100 (JIS ’89), JPt100 (JIS ’89), Pt50Ω (JIS ’81), Ni100 (See Table 2) Maximum lead wire resistance: 100 Ω per wire Burnout indication: 115 % of the measuring range (upscale) Sensing current: ≤ 1 mA ∙Potentiometer input: Total resistance 100 Ω to 10 kΩ Minimum span: 50 % of total resistance Excitation: ≤ 0.6 V DC ■ Ai1, Ai2, Ai3, Ai4 ∙Voltage input: 1 – 5 V DC Input resistance: ≥ 1 MΩ ■ Pi1, Pi2, Pi3, Pi4, Pi5: Dry contact (Di1 through Di5 are assigned to the same terminals respectively.) Maximum frequency: 20 Hz Minimum pulse width: 25 msec. Common: Negative common per 5 points Sensing: Approx. 12 V DC, 6 mA ON voltage/resistance: ≤ 2.25 V, ≤ 1.5 kΩ OFF voltage/resistance: ≥ 11.25 V ≥ 15 kΩ ■ Pi6: Dry contact (Di6 is assigned to the same terminal.) Maximum frequency: 10 kHz Minimum pulse width: 0.05 msec. Common: Negative common Sensing: Approx. 12 V DC, 12 mA ON voltage/resistance: ≤ 2 V, ≤ 1.5 kΩ OFF voltage/resistance: ≥ 11 V, ≥ 15 kΩ Excitation: 12 V DC ±10%, 15 mA Current limiting circuit: Approx. 30 mA ■ Di1, Di2, Di3, Di4, Di5: Dry contact (Pi1 through Pi5 are assigned to the same terminals respectively.) Common: Negative common per 5 points Sensing: Approx. 12 V DC, 6 mA ON voltage/resistance: ≤ 2.25 V, ≤ 1.5 kΩ OFF voltage/resistance: ≥ 11.25 V ≥ 15 kΩ ■ Di6: Dry contact (Pi6 is assigned to the same terminal.) Common: Negative common Sensing: Approx. 12 V DC, 12 mA ON voltage/resistance: ≤ 2 V, ≤ 1.5 kΩ OFF voltage/resistance: ≥ 11 V, ≥ 15 kΩ

MODEL: SC110 SC110 SPECIFICATIONS ES-6339 Rev.17 Page 4/12 http://www.m-system.co.jp/ [Table 1 (Thermocouple input)] T/C USABLE RANGE (°C) CONFORMANCE RANGE (°C) K (CA) -272 to +1472 -150 to +1370 E (CRC) -272 to +1100 -170 to +1000 J (IC) -260 to +1300 -180 to +1200 T (CC) -272 to +500 -170 to +400 B (RH) 24 to 1920 1000 to 1760 R -100 to +1860 380 to 1760 S -100 to +1860 400 to 1760 C (WRe 5-26) -52 to +2416 100 to 2315 N -272 to +1400 -130 to +1300 U -252 to +700 -200 to +600 L -252 to +1000 -200 to +900 P (Platinel II ) -52 to +1496 0 to 1395 (PR) -52 to +1860 300 to 1760 Overrange input (out of the usable range) is handled as burnout. [Table 2 (RTD input)] RTD USABLE RANGE (°C) CONFORMANCE RANGE (°C) Pt 100 (JIS ’97 , IEC) -240 to +900 -200 to +850 Pt 100 (JIS ’89) -240 to +900 -200 to +660 JPt 100 (JIS ’89) -236 to +560 -200 to +510 Pt 50Ω (JIS ’81) -236 to +700 -200 to +649 Ni 100 -100 to +252 -80 to +250 Overrange input (out of the usable range) is handled as burnout. OUTPUT SPECIFICATIONS ■ Mv1, Mv2, Mv2B ∙Current output: 4 – 20 mA DC Load resistance: ≤ 600 Ω (Mv2B is the output from backup unit.) ■ Ao1, Ao2 ∙Voltage output: 1 – 5 V DC Load resistance: ≥ 10 kΩ ■ Discrete Output ∙Do1, Do2, Do3, Do4, Do5, RUN contact (Do6): Relay contact Rated load: 250 V AC @1 A (cos ø = 1)

30 V DC @1 A (resistive load)

Maximum switching voltage: 250 V AC or 30 V DC Maximum switching power: 250 VA or 60 W Minimum load: 5 V DC @10 mA Mechanical life: 2 × 107 cycles ∙Do1, Do2, Do3, Do4, Do5: Photo MOSFET relay Rating: 200 V AC/DC @0.5 A (resistive load) ON resistance: 2.1 Ω Maximum frequency: 4 Hz @24 V, 10 mA ON delay time: ≤ 5.0 msec. OFF delay time: ≤ 3.0 msec. INSTALLATION Power input ∙AC: Control module ≤ 25 VA at 100 V AC ≤ 40 VA at 240 V AC Backup module ≤ 10 VA at 100 V AC ≤ 15 VA at 240 V AC

  • DC Control module: ≤ 650 mA Backup module: ≤ 150 mA Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 5 to 90 %RH (non-condensing) Mounting: Panel flush mounting (high-density mounting in horizontal direction) Weight: Approx. 2.0 kg (4.41 lb) for 300 mm depth type Approx. 2.5 kg (5.51 lb) for 400 mm depth type Approx. 3.0 kg (6.61 lb) for 600 mm depth type PERFORMANCE Accuracy DC input: ±0.1 % ±1 digit Thermocouple input: ±1℃ ±1 digit ±2℃ ±1 digit for B, R, S, C and PR RTD input: ±1℃ ±1 digit Potentiometer input: ±0.2 % ±1 digit DC output: ±0.1 % Precision resistor module (REM4): ±0.1 % Cold junction compensation: ±2°C at 25°C ±10°C ±4°C for S, R and PR Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) DC input: ±0.015 %/°C (±0.008 %/°F) Thermocouple input: ±0.015 %/°C (±0.008 %/°F) RTD input: ±0.015 %/°C (±0.008 %/°F) Potentiometer input: ±0.015 %/°C (±0.008 %/°F) DC output: ±0.015 %/°C (±0.008 %/°F) Precision resistor module (REM4): ±0.015 %/°C (±0.008 %/°F) Line voltage effect: ±0.1 % over voltage range Calendar clock accuracy: Monthly deviation 3 minutes at 25°C RAM memory duration in power failure for hot start: 10 minutes assured Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength:

1500 V AC @ 1 minute

(Pv1 or supply output to Pv2 or Ai1 or Ai2 or Ai3 or Ai4 to Di1 or Di2 or Di3 or Di4 or Di5 or Pi1 or Pi2 or Pi3 or Pi4 or Pi5 to Di6 or Pi6 to Mv1 to Mv2 or Mv2B or Ao1 or Ao2 to

MODEL: SC110 SC110 SPECIFICATIONS ES-6339 Rev.17 Page 5/12 http://www.m-system.co.jp/ Do1 to Do2 or Do3 or Do4 or Do5 or Do6 to power to backup module power to FG)

500 V AC @ 1 minute (Pv2 to Ai1 or Ai2 or Ai3 or Ai4)

500 V AC @ 1 minute (Mv2 or Mv2B to Ao1 or Ao2)

500 V AC @ 1 minute (Do2 to Do3 to Do4 to Do5 to Do6)

500 V AC @ 1 minute (Pv1 to supply output)

STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Measurement Category II (contact output) Installation Category II (power) Pollution degree 2 Input or output to contact output – Basic insulation (300 Input or output to power - Reinforced insulation (300 V) RoHS Directive EN 50581 Protection against access to the terminal blocks: Finger protection (VDE 0660-514)

MODEL: SC110 SC110 SPECIFICATIONS ES-6339 Rev.17 Page 6/12 http://www.m-system.co.jp/ EXTERNAL VIEW Auto/Man ■ CONTROL MODULE FRONT VIEW

  • Infrared communication type 4 5 6 7
  • Stereo jack type ■ BACKUP MODULE 4 5 6 7

8 Auto/Man

1 . TFT Color LCD with touch panel Provides operation and engineering views to facilitate monitoring and setting 2. MV output setting indicator LEDs for the backup mode 3. Infrared communication port Used to communicate with PC via IRDA Communication Adaptor (model: COP-IRDA) to program and change parameters using Loop Configuration Builder Software (model: SFEW3E) or PC Configurator Software (model: SCCFG) 4. MV value (DOWN) button 5. Acceleration button (Accelerates MV signal’s changing speed by pressing simultaneously with MV value button) 6. MV value (UP) button 7 . Auto / Man selector (changes the control mode for MV output) 8. Configurator jack and cap Connects with a PC where Loop Configuration Builder Software (model: SFEW3E) or PC configurator software (model: SCCFG) is installed via a PC configurator cable (model: COP-US) and enables programming and parameter setting 9. MV output setting indicators 10. Configurator jack 11 . MV value (UP) button 12. Acceleration button (Accelerates MV signal’s changing speed by pressing simultaneously with MV value button) 13. MV value (DOWN) button

MODEL: SC110 SC110 SPECIFICATIONS ES-6339 Rev.17 Page 7/12 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 60 61 62 63 144 (5.67) 164 (6.46) MOUNTING BRACKETS BACKUP MODULE POWER INPUT TERMINAL TERMINAL COVER 72 (2.83) 80 (3.15) (.94) 210 (8.27) max. 175 (6.89) *2. Option /3: 300 mm (11.81”) Option /4: 400 mm (15.75”) Option /6: 600 mm (23.62”) *1. Option /M2, /R only 52–M3.5 SCREW 67.5 (2.66) 137.5 (5.41) 7.6 (.30) 52–M3.5 SCREW 4–M4 SCREW FOR FIXING TERMINAL 67.5 (2.66) 137.5 (5.41) 7.2 (.28) ■ INFRARED COMMUNICATION TYPE

  • ONE BLOCK TERMINAL (without option /T)
  • SEPARABLE TERMINAL (with option /T)

MODEL: SC110 SC110 SPECIFICATIONS ES-6339 Rev.17 Page 8/12 http://www.m-system.co.jp/ 60 61 62 63 144 (5.67) 164 (6.46) MOUNTING BRACKETS BACKUP MODULE POWER INPUT TERMINAL TERMINAL COVER 72 (2.83) 80 (3.15) (.94) 210 (8.27) max. 175 (6.89) *2. Option /3: 300 mm (11.81”) Option /4: 400 mm (15.75”) Option /6: 600 mm (23.62”) *1. Option /M2, /R only Jack cap 1 (.04) 52–M3.5 SCREW 67.5 (2.66) 137.5 (5.41) 7.6 (.30) 52–M3.5 SCREW 4–M4 SCREW FOR FIXING TERMINAL 67.5 (2.66) 137.5 (5.41) 7.2 (.28)

  • ONE BLOCK TERMINAL (without option /T)
  • SEPARABLE TERMINAL (with option /T) ■ STEREO JACK TYPE

MODEL: SC110 SC110 SPECIFICATIONS ES-6339 Rev.17 Page 9/12 http://www.m-system.co.jp/ MOUNTING REQUIREMENTS unit: mm 138 68 [68+72×(n - 1)] +0.7 Panel thickness 2.3 – 20 138 ■ PANEL CUTOUT unit: mm

  • Single mounting • Clustered mounting n = number of units ■ Caution
  • IP55 is ensured for the front panel of the unit mounted independently to according to a panel. Test the sealing at the mounting surface once the device is installed.
  • Set the unit on a vertical surface with its operation buttons at the lower side. Mounting in other directions may cause heat built up inside the unit and shorten its life span or degrade its performance.
  • Ensure that there is sufficient space for ventilation inside a panel. Do not install above the devices that generate high heat such as heaters, transformers or resistors. Leave at least 30 mm (1.2 inch) space above, below and behind the unit for maintenance purpose (e.g. wiring, removing or installing).

MODEL: SC110 SC110 SPECIFICATIONS ES-6339 Rev.17 Page 10/12 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. Sensor Excitation Input Circuit A/D Converter A/D Converter A/D Converter Discrete Input Circuit Display / Setting Output Driver Output Driver Output Driver Isolation Output Driver Isolation Output Driver Isolation Isolation Isolation Isolation Isolation Isolation Digital Computation IsolationControl Module Backup Module 42 A1 Di 1 / Pi 1 Di 2 / Pi 2 Di 4 / Pi 4 Di 3 / Pi 3 Di 5 / Pi 5 Di 6 / Pi 6 Pv 1 UNIVERSAL INPUT Pv 2 UNIVERSAL INPUT Ai 1 Ai 2 Ai 3 Ai 4 SENSOR EXC INPUT COM 3 + 4 – U(+) V(–) FG Do 1 Do 2 Do 3 Do 4 Do 5 POWER Ao 2 Ao 1 Mv 1 Do 6 RUN CONTACT Digital Computation Output Switch Backup Module Power Circuit OPERATION BUTTONS ■ BACKUP MODULE POWER SUPPLY: SINGLE SUPPLY MV SETTING INDICATORS PC CONFIGURATOR/ BUILDER SOFTWARE Infrared Port / Jack *2. Connect input resistor module (model: REM4) for current input. *3. Connect CJC sensor for thermocouple input. *4. Connect input resistor module (model: REM4). ■ UNIVERSAL INPUT CONNECTION E.G. A B B RTD A B A B C A B C A B C A B C T/C CJC SENSOR C POTENTIOMETER max. min. *3 *4 R A B C A B C R 2-Wire XMTR VOLT / CURRENT INPUT ■ DISCRETE INPUT PULSE INPUT CONNECTION E.G.: Dry contact +12V Excitation Supply Isolation 2-WIRE TRANSMITTER 1 or 2kΩ *1. Backup is applicable to Mv 2 only. Mv 2B is output of the backup module. Mv 2, Mv 2B *1

MODEL: SC110 SC110 SPECIFICATIONS ES-6339 Rev.17 Page 11/12 http://www.m-system.co.jp/ Sensor Excitation Input Circuit A/D Converter A/D Converter A/D Converter Discrete Input Circuit Display / Setting Output Driver Output Driver Output Driver Output Switch Isolation Output Driver Isolation Output Driver Isolation Isolation Isolation Isolation Isolation Isolation Digital Computation IsolationControl Module Backup Module 42 A1 Di 1 / Pi 1 Di 2 / Pi 2 Di 4 / Pi 4 Di 3 / Pi 3 Di 5 / Pi 5 Di 6 / Pi 6 Pv 1 UNIVERSAL INPUT Pv 2 UNIVERSAL INPUT Ai 1 Ai 2 Ai 3 Ai 4 SENSOR EXC INPUT COM 3 + 4 – U(+) V(–) FG Do 1 Do 2 Do 3 Do 4 Do 5 POWER U(+) V(–) FG Ao 2 Ao 1 Mv 1 Do 6 RUN CONTACT Digital Computation Backup Module Power Circuit OPERATION BUTTONS ■ BACKUP MODULE POWER SUPPLY: DUAL SUPPLY MV SETTING INDICATORS *2. Connect input resistor module (model: REM4) for current input. *3. Connect CJC sensor for thermocouple input. *4. Connect input resistor module (model: REM4). ■ UNIVERSAL INPUT CONNECTION E.G. RTD A B A B C A B C A B C A B C T/C CJC SENSOR C POTENTIOMETER *3 *4 R A B C A B C R 2-Wire XMTR VOLT / CURRENT INPUT ■ DISCRETE INPUT PULSE INPUT CONNECTION E.G.: Dry contact max. min. A B B Excitation Supply Isolation PC CONFIGURATOR/ BUILDER SOFTWARE Infrared Port / Jack 2-WIRE TRANSMITTER BACK UP POWER +12V 1 or 2kΩ Mv 2, Mv 2B *1 *1. Backup is applicable to Mv 2 only. Mv 2B is output of the backup module.

MODEL: SC110 SC110 SPECIFICATIONS ES-6339 Rev.17 Page 12/12 http://www.m-system.co.jp/ SYSTEM CONFIGURATION EXAMPLES ■ SINGLE LOOP CONTROL ■ CASCADE CONTROL Flow Level MV MV PV Multi-Function PID Controller Model: SC110 PV Ai Multi-Function PID Controller Model: SC110 Specifications are subject to change without notice.