SB1XL-S COOPER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 3

Technical content

Eaton’s Bussmann series range of XL package fuse bases with integral shields has been specifically designed to be fitted with Eaton’s Bussmann series XL photovoltaic fuse links (see data sheet 10201). Bussmann series XL Fuse bases for XL Style photovoltaic fuse links BUSSMANN SERIES

XL Fuse bases for XL Style photovoltaic fuse links EATON www.eaton.com Catalogue symbol

  • SB1XL -S to fit 01XL and 1XL PV Fuse links*
  • SB2XL -S to fit 2XL PV fuse links*
  • SB3L -S to fit 3L PV fuse links* * Please refer to data sheet 10201 for details on Eaton’s Bussmann series XL style photovoltaic fuse links T echnical data
  • Rated voltage: 1500 V d.c.
  • Rated current: 250, 400 and 630 A
  • Power acceptance (Watts)
  • Sizes 01XL and 1XL: 56W
  • Size 2XL: 70W
  • Size 3L: 96W
  • Degree of protection level: IP20 with terminal covers and gripping lug cover in place and shielding of any exposed part of the terminal lugs
  • Operating temperature range: -45OC to 80OC (with fuse link derating above 40OC)
  • Dielectric strength: 3820 V d.c. applied for a voltage rating U n of 1500 V d.c. for the base
  • Screw mounting, dimensions and spacing of screw holes are shown on drawing and dimension table page 3
  • Terminal/Lug mounting torque: 32N•m
  • Silver plated copper fuse clips
  • UL94 Flammability rating: base V-2, terminal cover V-0
  • Terminal covers are UV stabilised
  • Weight:
  • SB1XL -S: 0.61 kg
  • SB2XL -S: 0.62 kg
  • SB3L -S: 1 .04 kg Standards/Approvals
  • IEC 60269-1
  • UL Listed (file number E348242) Packaging
  • MOQ: 1 Application note Rated current (In) of the sub-array or array fuse links shall be 1 .25 x Isc_array < In < 2.4 Isc_array in accordance with IEC 60269-6 where Isc_array is the current at the output terminals of a PV array at a particular temperature and irradiance when the device output voltage is equal to or close to zero. Thus the current experienced by the fuse link and fuse base under normal PV array service conditions will not exceed 0.8 x I n . These Eaton recommendations are based on this worst case condition. Accessory Fuse extraction handle available in sizes 01XL to 3L Catalogue number: FEH1500 Unit packing: 1

XL Fuse bases for XL Style photovoltaic fuse links Eaton EMEA Headquarters Route de la Longeraie 7

1110 Morges, Switzerland

Eaton.eu © 2016 Eaton All Rights Reserved Publication No. 10066 February 2016 Eaton is a registered trademark. All other trademarks are property of their respective owners. K Catalogue numbers XL Style fuse link size Maximum fuse rated current Power acceptance A B C D E F G H I K L SB1XL-S 01XL, 1XL 250 56W 59 257 300.5 30 37 102.5 17.5 92 22 M10x25 111 SB2XL-S 2XL 400 70W 64 257 300.5 30 37 107 17.5 92 22 M10x25 119 SB3L-S 3L 630 96W 80 270 328 40 38 122.5 25 96 26 M12x30 134.5 Dimensions - mm Changes to the products, to the information contained in this document, and to prices are reserved; so are errors and omissions. Only order confirmations and technical documentation by Eaton is binding. Photos and pictures also do not warrant a specific layout or functionality. Their use in whatever form is subject to prior approval by Eaton. The same applies to Trademarks (especially Eaton, Moeller, and Cutler-Hammer). The Terms and Conditions of Eaton apply, as referenced on Eaton Internet pages and Eaton order confirmations.