S8PE OMRON | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 8
Technical content
Three phase input switch mode Power Supply S8PE L-99 Power Supplies Three phase input switch mode Power Supply S8PE DIN-rail mounting, 3-phase input Switch mode Power Supply with a range of 5A to 40A output current
- 3 phase 400/480 or 200/230 VAC input 5, 10, 20 and 40A; 24 VDC output Higher stability, lower ripple and noise level Compact and attractive design, easily mounted to DIN rail (for 5, 10 and 20A types) Natural ventilation, no fan for less maintenance UL60950 (CSA22.2-60950), UL508 listing (CSA22.2-14) in ad- dition to the CE mark Conform to EN61000-3-2 All types can be used for parallel & serial operation
Ordering Information
Input voltage Power rating Output voltage Output current With Front mounting Bracket With DIN rail mounting Bracket 400/480 VAC 3-phase
120 W 24 V 5 A – S8PE-F12024CD
240 W 24 V 10 A – S8PE-F24024CD
480 W 24 V 20 A S8PE-F48024C S8PE-F48024CD
960 W 24 V 40 A S8PE-F96024C –
120 W 24 V 5 A – S8PE-J12024CD
240 W 24 V 10 A – S8PE-J24024CD
480 W 24 V 20 A – S8PE-J48024CD
960 W 24 V 40 A S8PE-J96024C –
- Input Voltage F: 400-480 VAC 3-phase J: 200-230 VAC 3-phase 3. Output Voltage 24: 24 V 2. Power Rating 120: 120 W 240: 240 W 480: 480 W 960: 960 W 4. Configuration C: Covered type with Front-mounting bracket CD: Covered type with DIN-rail track-mounting bracket
L-100 Three phase input switch mode Power Supply S8PE Specifications Note 1. Measured at 25 °C, and cold start condition. (F: Vin = 480 VAC, J: Vin = 230 VAC, duration < 500 µs) 2. For UL and CSA, -105 to 50 °C (de-rating: 2%/°C for 40-50 °C only for 40 A model). 3. Under the ambient temperature of 40 °C, and a load rate of 50%. 4. Over voltage protection is provided for 5A, 10A and 20A models. For 40A model, no overvoltage protection is provided. Nominal Output Current 5 A 1 0 A2 0 A4 0 A 5 A 1 0 A2 0 A4 0 A Efficiency (typical) (Vin = 400 VAC, Pmax) (Vin = 480 VAC, Pmax) (Vin = 230 VAC, Pmax) 85% 84% 88% 88% 87% 87% 90% 90% 86% 88% 89% 91% Frequency 50/60 Hz Current (max.) (Vin = Range min., Pmax) Power factor (typical) (Vin = 400 VAC, Pmax) (Vin = 480 VAC, Pmax) (Vin = 230 VAC, Pmax) 0.58 0.52 0.64 0.59 0.89 0.84 0.89 0.84 0.55 0.55 0.9 0.89 Leakage current (max.) (Vin = 400 VAC, Pmax) (Vin = 480 VAC, Pmax) (Vin = 230 VAC, Pmax) 0.4 mA 0.5 mA 0.9 mA 1.1 mA 1.3 mA 1.6 mA 0.7 mA 0.9 mA 0.3 mA 0.4 mA 0.7 mA 1.4 mA Inrush current (max.) (Pmax) (Note 1) 3 0 A3 0 A4 0 A5 0 A3 5 A3 5 A7 5 A7 5 A T olerance adjustment accuracy ± 0.5% Ripple & noise (Pmax.) 200 mV max. Load variation influence ± 2% max. Input variation influence ± 0.5% max. T emperature variation influence ± 0.01%/°C Startup time (max.) 1.7 s Hold time (min.) (Vin = 200 VAC, Pmax) (Vin = 400 VAC, Pmax) (Vin = 480 VAC, Pmax) (Vin = 230 VAC, Pmax) 21 ms 25 ms 17 ms 26 ms 11 ms 24 ms 14 ms 26 ms 10 ms 20 ms 4 ms 10 ms 4 ms 8 ms 5 ms 13 ms Protection - Short circuit protection with automatic reset - Over load protection - Over voltage protection (Note 4) Parallel operation Y es (for two units) Serial operation Y es (for two units) Indicator Ye s ( G r e e n L E D ) Others Heat radiation Natural air cooling Ambient temperature (Note 2) -10..60 °C (de-rating: 2%/°C for 50..60 °C) Storage temperature -25..85 °C Ambient humidity 25..85% Dielectric strength 500 VAC 50/60 Hz (Output - P .E.) Comply to EN60950 F: 2.5 kVAC 50/60 Hz (Input - P .E.) J: 1.5 kVAC 50/60 Hz (Input - P .E.) Insulation resistance 500 M Ω min. at 500 VDC: P .E. - Output EMC EN55022 class A, EN55011 class A, EN50081-2 EN61000-6-2, EN61000-3-2 class A Approved standards IEC60950, EN60950, UL60950, CSA22.2-60950 UL508 (Listing), CSA22.2-14, EN50178, EN60204-1 Life expectancy (Note 3) 10 years (typical)
Three phase input switch mode Power Supply S8PE L-101 Power Supplies Engineering Data IDefinition of Inrush Current, Start up Time and Hold Time IOverload Protction The Power supply is provided with an overload protec tion function that protect the load and the power sup ply from possible damage by over current. When the output current rises above between 105 to 130% of the rated current, the protection function is triggered, decreasing the output voltage. When output current falls within the rated range, the overload protection function is automatically cleared. IDe-rating Curve For UL and CSA the maximum temperature is 50% (with derating of 2%/°C from 40 °C to 50 °C, only for 40 A model) IOvervoltage Protction (except for 40 A model) If output voltage exceed the rated voltage more than 20% (50% at maximum) by some reason, then the output voltage will be turned OFF automatically for safety. T o restart the S8PE, turn OFF the input voltage, wait for about one minute, then apply the input power again. Input ON Input OFF AC input current Output voltage Hold time 96.5%90% Start up time Inrush current input application AC input voltage Load (%) Ambient temperature (°C)
L-102 Three phase input switch mode Power Supply S8PE Operation IBlock Diagram S8PE-F12024CD/J12024CD (5 A) S8PE-F24024CD/J24024CD (10 A) S8PE-F48024C (20 A) S8PE-F48024CD/J48024CD (20 A) S8PE-F96024C/J96024C (40 A) Supply Voltage Control And Adjustment Module Control Module Opto-isolator RFI filter Input Line Fuses P. E . Control Module Opto-isolator Output Voltage Control Module Input Line Fuses RFI filter DrivingP. E . Output Voltage Control Module Opto-isolator Control Module Driving RFI filter Input Line Fuses P. E .
Three phase input switch mode Power Supply S8PE L-103 Power Supplies Dimensions and Installation Note: All dimensions shown are in millimeters. S8PE-F12024CD/J12024CD (5 A) S8PE-F24024CD/J24024CD (10 A) x AC INPUT L1 } Output Voltage adjustment trimmer V .ADJ y AC INPUT L2 ~ DC OUTPUT -V z AC INPUT L3 DC OUTPUT +V { Protective Earth (P .E.) 35 mm DIN-rail attachment | DC OUTPUT indicator side view bottom viewtop view front view side view front viewbottom viewtop view
L-104 Three phase input switch mode Power Supply S8PE S8PE-F48024C (20 A) S8PE-F48024CD/J48024CD (20 A) S8PE-F96024C/J96024C (40 A) x AC INPUT L1 } Output Voltage adjustment trimmer V .ADJ y AC INPUT L2 ~ DC OUTPUT -V z AC INPUT L3 DC OUTPUT +V { Protective Earth (P .E.) 35 mm DIN-rail attachment for S8PE- F48024CD/J48024CD type only | DC OUTPUT indicator Fixing bracket for S8PE-F48024C type only side view side viewfront view top view bottom view top view bottom view front viewside view
Three phase input switch mode Power Supply S8PE L-105 Power Supplies Notice Three phase input operation when one phase is missing The S8PE will in most cases continue to operate even after the loss of one phase of the supply. The perfor mance specifications are of course not guaranteed under these conditions. As the loss of one phase puts additional stress on some components, the life span of the unit could be shortened. It is prudent therefore to regularly check for signs of the following possible conditions. 1. Input terminals wiring open/loose. 2. Incorrect / no voltage on one or more phases of the supply. 3. Abrupt or periodical loss of input voltage. Three phase input switch off In order to switch off the Power Supply completely: all 3 phases need to be switched off. Mounting T o improve and maintain the reliability of the Power Supply over a long period, adequate consideration must be taken to heat radiation. The S8PE is designed to radiate heat by natural air cooling, there- fore, mount the S8PE so that enough air flow takes place around the power supply. If installing S8PEs closely, keep the minimum dis tance of 10 cm at 50 °C ambient, 5 cm at 20 °C am bient. Generating (±±±±) Output Voltage An output of ± can be generated as shown below, since the S8PE has a floating output. Serial Operation As shown below, the output voltage from each S8PE can be added. T ypes must be the same. Parallel Operation As shown below, The Power supply can use for paral lel operation. All the output voltage of each S8PEs should be exactly the same. Also, make sure that the thickness and the length of all wires con- nected to the load are the same to ensure that the wires will have no voltage drop difference. T ypes must be the same. + V − V + V − V LoadLoad Load + V − V + V − V Load
L-106 Three phase input switch mode Power Supply S8PE Safety Precautions ISafety Signal words This document uses the following signal words to mark safety precautions for the S8PE. These precautions pro vide important information for the safe application of the product. Y ou must be sure to follow the instructions pro vided with safety signal words. !WARNING Be sure to connect the grounding line Not doing so may result in electric shock. !Caution Do not attempt to disassemble the Power Supply or touch its inter- nal parts while power is being supplied. Doing so may result in electric shock. !Caution Do not touch the S8PE while the power is being supplied or imme- diately after the power is turned OFF. Otherwise hot Switching Power Supply. Indicates information that, if ignored, could possibly result in loss of life or seriously injury. !WARNING Indicates information that, if ignored, could result in relatively serious or minor injury, damage to the product, or faulty operation. !Caution In the interest of product improvement, specifications are subject to change without notice. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. T o convert millimeters into inches, multiply by 0.03937. T o convert grams into ounces, multiply by 0.03527. Cat. No. M044-E1-04