S8JX (15/35/50/100/150/300/600-W Models) Wide Variety of Output Voltage Variations: 48 V for 15 to 150 W, and 5 or 12 V for 150 W
- Easy Mounting: Mounting Bracket provided as a standard feature. (except for DIN Rail-mounting models) Mounts to DIN Rail. (except 600-W model) Screw-mount at the top. (except 300-/600-W models) Safety standards: UL 508/60950-1 cUL CSA C22.2 No. 107.1 cUR CSA C22.2 No. 60950-1 EN 50178 (= VDE 0160) EN 60950-1 (= VDE 0805 Teil 1) EMC: Conforms to EN 61204-3 Class A. Input conditions: The input voltage range of 15-W, 35-W, 50-W, 100-W, and 150-W models has been increased to 80 to 370 VDC (EC Directives and safety standards do not apply.). Note: Refer to Safety Precautions on page 24. Model Number Structure Model Number Legend Note: 1. Not all combinations are possible. Refer to List of Models in Ordering Information on page 2. 2. Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for details. 1. Power Ratings 015: 15 W 035: 35 W 050: 50 W 100: 100 W 150: 150 W 2. Output Voltage 05: 5 V 12: 12 V 15: 15 V 24: 24 V 48: 48 V 3. Configuration (15/35/50/100/150 W model) None: Open-frame C: Covered 4. Configuration/mounting None: Front-mounting D: DIN Rail-mounting 1. Power Ratings 300: 300 W 600: 600 W 2. Output Voltage 24: 24 V 3. Configuration/mounting (covered type) C: Front-mounting CD: DIN Rail-mounting Note: Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for details. EMI: EN55011 EMS: EN61000-4() 12 3 4 300-/600-W Models 1 2 3
Ordering Information
Note: For details on normal stock models, contact your nearest OMRON representative. *1. The front-mounting bracket is included as standard with the product. *2. A front-mounting bracket is not included with the product. *3. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC). Configuration Input voltage Power ratings Output voltage (VDC) Output current Model Open-frame Power Supplies Front-mounting *1 100 to 240 VAC (free) (80 to 370 VDC *3) S8JX-G15005@: Switchable between 100 to 120 VAC and 200 to 240 VAC. (DC power cannot be input.) 15 W
5 V 3 A S8JX-G01505
12 V 1.3 A S8JX-G01512
15 V 1 A S8JX-G01515
24 V 0.65 A S8JX-G01524 48 V 0.35 A S8JX-G01548 35 W
5 V 7 A S8JX-G03505
12 V 3 A S8JX-G03512
15 V 2.4 A S8JX-G03515 24 V 1.5 A S8JX-G03524 48 V 0.75 A S8JX-G03548 50 W
5 V 10 A S8JX-G05005
12 V 4.2 A S8JX-G05012 24 V 2.1 A S8JX-G05024 48 V 1.1 A S8JX-G05048 100 W
5 V 20 A S8JX-G10005
12 V 8.5 A S8JX-G10012 24 V 4.5 A S8JX-G10024 48 V 2.1 A S8JX-G10048 150 W
5 V 30 A S8JX-G15005
12 V 13 A S8JX-G15012
24 V 6.5 A S8JX-G15024 48 V 3.3 A S8JX-G15048 DIN Rail-mounting *2 15 W
5 V 3 A S8JX-G01505D
12 V 1.3 A S8JX-G01512D
15 V 1 A S8JX-G01515D
24 V 0.65 A S8JX-G01524D 48 V 0.35 A S8JX-G01548D 35 W
5 V 7 A S8JX-G03505D
12 V 3 A S8JX-G03512D
15 V 2.4 A S8JX-G03515D 24 V 1.5 A S8JX-G03524D 48 V 0.75 A S8JX-G03548D 50 W
5 V 10 A S8JX-G05005D
12 V 4.2 A S8JX-G05012D 24 V 2.1 A S8JX-G05024D 48 V 1.1 A S8JX-G05048D 100 W
5 V 20 A S8JX-G10005D
12 V 8.5 A S8JX-G10012D 24 V 4.5 A S8JX-G10024D 48 V 2.1 A S8JX-G10048D 150 W
5 V 30 A S8JX-G15005D
12 V 13 A S8JX-G15012D
24 V 6.5 A S8JX-G15024D 48 V 3.3 A S8JX-G15048D
*1. The front-mounting bracket is included as standard with the product. *2. A front-mounting bracket is not included with the product. *3. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC). Configuration Input voltage Power ratings Output voltage (VDC) Output current Model Covered Power Supplies Front-mounting *1 100 to 240 VAC (free) (80 to 370 VDC *3) S8JX-G15005@@: Switchable between 100 to 120 VAC and 200 to 240 VAC. (DC power cannot be input.) 15 W
5 V 3 A S8JX-G01505C
12 V 1.3 A S8JX-G01512C
15 V 1 A S8JX-G01515C
24 V 0.65 A S8JX-G01524C 48 V 0.35 A S8JX-G01548C 35 W
5 V 7 A S8JX-G03505C
12 V 3 A S8JX-G03512C
15 V 2.4 A S8JX-G03515C 24 V 1.5 A S8JX-G03524C 48 V 0.75 A S8JX-G03548C 50 W
5 V 10 A S8JX-G05005C
12 V 4.2 A S8JX-G05012C 24 V 2.1 A S8JX-G05024C 48 V 1.1 A S8JX-G05048C 100 W
5 V 20 A S8JX-G10005C
12 V 8.5 A S8JX-G10012C 24 V 4.5 A S8JX-G10024C 48 V 2.1 A S8JX-G10048C 150 W
5 V 30 A S8JX-G15005C
12 V 13 A S8JX-G15012C
24 V 6.5 A S8JX-G15024C 48 V 3.3 A S8JX-G15048C DIN Rail-mounting *2 15 W
5 V 3 A S8JX-G01505CD
12 V 1.3 A S8JX-G01512CD
15 V 1 A S8JX-G01515CD
24 V 0.65 A S8JX-G01524CD 48 V 0.35 A S8JX-G01548CD 35 W
5 V 7 A S8JX-G03505CD
12 V 3 A S8JX-G03512CD
15 V 2.4 A S8JX-G03515CD 24 V 1.5 A S8JX-G03524CD 48 V 0.75 A S8JX-G03548CD 50 W
5 V 10 A S8JX-G05005CD
12 V 4.2 A S8JX-G05012CD 24 V 2.1 A S8JX-G05024CD 48 V 1.1 A S8JX-G05048CD 100 W
5 V 20 A S8JX-G10005CD
12 V 8.5 A S8JX-G10012CD 24 V 4.5 A S8JX-G10024CD 48 V 2.1 A S8JX-G10048CD 150 W
5 V 30 A S8JX-G15005CD
12 V 13 A S8JX-G15012CD
24 V 6.5 A S8JX-G15024CD 48 V 3.3 A S8JX-G15048CD Front-mounting *1 100 to 120 VAC 200 to 240 VAC (Swichable) 300 W 24 V
14 A S8JX-G30024C
600 W 27 A S8JX-G60024C
DIN Rail-mounting *2 300 W 14 A S8JX-G30024CD
Ratings, Characteristics, and Functions *1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not start. Refer to Overload Protection on page 15. *2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. *3. Rated input voltage: 100 or 200 VAC at 100% load. *4. Output characteristics: Specified at power supply output terminals. *5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged. *6. For details, refer to Overload Protection on page 15. *7. To reset the protection, turn OFF the input power for seven minutes or longer and then turn it back ON. *8. The weight indicated is a for Front-mounting, Open-frame Power Supply. *9. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC). Input specification 100 to 240 V input Item Power ratings *1 15 W 35 W Efficiency 68% min. 73% min. Input Voltage *2 100 to 240 VAC (allowable range: 85 to 264 VAC) 80 to 370 VDC *9 Note: This range is not applicable for the safety standards. Frequency *2 50/60 Hz (47 to 450 Hz) Current *3 100 V input 0.4 A max. 1 A max. 200 V input 0.25 A max. 0.6 A max. Power factor --- Harmonic current emissions --- Leakage current *3 100 V input 0.5 mA max. 200 V input 1 mA max. Inrush current (for a cold start at 25°C) *3 100 V input 20 A max. 200 V input 40 A max. Noise filter Yes Output *4 Voltage adjustment range *5 −10% to 15% (with V. ADJ) (48-V models: ±10%) Ripple *3 2% (p-p) max. Input variation influence 0.4% max. with AC input voltage Load variation influence 0.8% max. (0 to 100% load, rated input voltage) Temperature variation influence 0.05%/°C max. (at rated input and output) Startup time 500 ms max. (up to 90% of output voltage at rated input and output) Hold time *3 20 ms min. Additional functions Overload protection *6 105% to 175% of rated load current, voltage drop, intermittent, automatic reset Overvoltage protection *7 Yes Overheat protection No Parallel operation No Series operation Yes (For up to two Power Supplies; external diodes required.) Protective circuit operation indicator No Other Ambient operating temperature Refer to the derating curve in Engineering Data on page 13 (with no icing or condensation). Storage temperature −25 to 65°C (with no icing or condensation) Ambient operating humidity 25% to 85% (Storage humidity: 25% to 90%) Dielectric strength 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA) Insulation resistance 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions Output indicator Yes (Color: Green) EMI Conducted Emissions Conforms to EN 55011 Group 1 Class A and based on FCC Class A Radiated Emissions Conforms to EN 55011 Group 1 Class A EMS Electrostatic Discharge Confirms to EN61000-4-2 Radiated Electromagnetic Field Confirms to EN61000-4-3 Surge Confirms to EN61000-4-5 Conducted Disturbance Confirms to EN61000-4-6 Voltage Dips/Short Interruptions Confirms to EN61000-4-11 Approved standards *9 UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition) cUL Listed: CSA C22.2 No.107.1 cUR: CSA C22.2 No. 60950-1 EN/VDE: EN50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) SEMI SEMI F47-0200 (200-VAC input) Weight *8 250 g max.
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not start. Refer to Overload Protection on page 15. *2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. *3. Rated input voltage: 100 or 200 VAC at 100% load. *4. Output characteristics: Specified at power supply output terminals. *5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged. *6. For details, refer to Overload Protection on page 15. *7. To reset the protection, turn OFF the input power for seven minutes or longer and then turn it back ON. *8. The weight indicated is a for Front-mounting, Open-frame Power Supply. *9. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC). Input specification 100 to 240 V input Item Power ratings *1 50 W 100 W Efficiency 76% min. Input Voltage *2 100 to 240 VAC (allowable range: 85 to 264 VAC) 80 to 370 VDC *9 Note: This range is not applicable for the safety standards. Frequency *2 50/60 Hz (47 to 450 Hz) Current *3 100 V input 1.4 A max. 2.5 A max. 200 V input 0.8 A max. 1.5 A max. Power factor --- Harmonic current emissions --- Leakage current *3 100 V input 0.5 mA max. 200 V input 1 mA max. Inrush current (for a cold start at 25°C) *3 100 V input 20 A max. 200 V input 40 A max. Noise filter Yes Output *4 Voltage adjustment range *5 −10% to 15% (with V. ADJ) (48-V models: ±10%) Ripple *3 2% (p-p) max. Input variation influence 0.4% max. (with AC input voltage) Load variation influence 0.8% max. (0 to 100% load, rated input voltage) Temperature variation influence 0.05%/°C max. (at rated input and output) Startup time 500 ms max. (up to 90% of output voltage at rated input and output) Hold time *3 20 ms min. Additional functions Overload protection *6 105% to 175% of rated load current, voltage drop, intermittent, automatic reset Overvoltage protection *7 Yes Overheat protection No Parallel operation No Series operation Yes (For up to two Power Supplies; external diodes required.) Protective circuit operation indicator No Other Ambient operating temperature Refer to the derating curve in Engineering Data on page 13 (with no icing or condensation). Storage temperature −25 to 65°C (with no icing or condensation) Ambient operating humidity 25% to 85% (Storage humidity: 25% to 90%) Dielectric strength 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA) Insulation resistance 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions Output indicator Yes (Color: Green) EMI Conducted Emissions Conforms to EN 55011 Group 1 Class A and based on FCC Class A Radiated Emissions Conforms to EN 55011 Group 1 Class A EMS Electrostatic Discharge Confirms to EN61000-4-2 Radiated Electromagnetic Field Confirms to EN61000-4-3 Surge Confirms to EN61000-4-5 Conducted Disturbance Confirms to EN61000-4-6 Voltage Dips/Short Interruptions Confirms to EN61000-4-11 Approved standards *9 UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition) cUL Listed: CSA C22.2 No.107.1 cUR: CSA C22.2 No. 60950-1 EN/VDE: EN50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) SEMI SEMI F47-0200 (200-VAC input) Weight *8 300 g max. 550 g max.
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not start. Refer to Overload Protection on page 15. *2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. *3. Rated input voltage: 100 or 200 VAC at 100% load. *4. Output characteristics: Specified at power supply output terminals. *5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged. *6. For details, refer to Overload Protection on page 15. *7. To reset the protection, turn OFF the input power for seven minutes or longer and then turn it back ON. *8. The weight indicated is a for Front-mounting, Open-frame Power Supply. *9. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC). Input specification 100/200 V switchable 100 to 240 V input Item Power ratings *1 150 W at 5 V 150 W at 12 V 150 W at 24 or 48 V Efficiency 78% min. 79% min. 85% min. Input Voltage *2 Switchable between 100 to
120 VAC (allowable range:
85 to 132 VAC) and 200 to
240 VAC (allowable range:
170 to 264 VAC). 100 to 240 VAC (allowable range: 85 to 264 VAC) 80 to 370 VDC *9 Frequency *2 50/60 Hz (47 to 450 Hz) Power factor --- Harmonic current emissions --- Leakage current *3 100 V input 0.5 mA max. 200 V input 1 mA max. Inrush current (for a cold start at 25°C) *3 100 V input 20 A max. 200 V input 40 A max. Noise filter Yes Output *4 Voltage adjustment range *5 −10% to 15% (with V. ADJ) (48-V models: ±10%) Ripple *3 2% (p-p) max. Input variation influence 0.4% max. (with AC input voltage) Load variation influence 0.8% max. (0 to 100% load, rated input voltage) Temperature variation influence 0.05%/°C max. (at rated input and output) Startup time 500 ms max. (up to 90% of output voltage at rated input and output) Hold time *3 20 ms min. Additional functions Overload protection *6 105% to 175% of rated load current, voltage drop, automatic reset 105% to 175% of rated load current, voltage drop, intermittent, automatic reset Overvoltage protection *7 Yes Overheat protection No Parallel operation No Series operation Yes (For up to two Power Supplies; external diodes required.) Protective circuit operation indicator No Other Ambient operating temperature Refer to the derating curve in Engineering Data on page 13 (with no icing or condensation). Storage temperature −25 to 65°C (with no icing or condensation) Ambient operating humidity 25% to 85% (Storage humidity: 25% to 90%) Dielectric strength 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA) Insulation resistance 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions Output indicator Yes (Color: Green) EMI Conducted Emissions Conforms to EN 55011 Group 1 Class A and based on FCC Class A Radiated Emissions Conforms to EN 55011 Group 1 Class A EMS Electrostatic Discharge Confirms to EN61000-4-2 Radiated Electromagnetic Field Confirms to EN61000-4-3 Surge Confirms to EN61000-4-5 Conducted Disturbance Confirms to EN61000-4-6 Voltage Dips/Short Interruptions Confirms to EN61000-4-11 Approved standards *9 UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition) cUL Listed: CSA C22.2 No.107.1 cUR: CSA C22.2 No. 60950-1 EN/VDE: EN50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) SEMI --- SEMI F47-0200 (200-VAC input) Weight *8 800 g max. 700 g max. 600 g max.
*1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the Power Supply may not start. Refer to Overload Protection on page 15. *2. Do not use an Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. *3. Rated input voltage: 100 or 200 VAC at 100% load. *4. Output characteristics: Specified at power supply output terminals. *5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than the allowable voltage range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that load is not damaged. *6. For details, refer to Overload Protection on page 15. *7. To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON. *8. The weight indicated is a for Front-mounting, Open-frame Power Supply. *9. The protection-ON alarm indicator will light as soon as the output is interrupted. For resetting, turn OFF the input power, leave for more than three minutes , and then turn it back ON again. *10.The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC). Input specification 100/200 V (Selected) Item Power ratings *1 300 W 600 W Efficiency 82% min. 80% min. Input Voltage *2 100 to 120 VAC (allowable range: 85 to 132 VAC) 200 to 240 VAC (allowable range: 170 to 264 VAC) (Switchable) Frequency *2 50/60 Hz (47 to 450 Hz) Current *3 100 V input 8 A max. 14 A max. 200 V input 4.5 A max. 8 A max. Power factor --- Harmonic current emissions --- Leakage current *3 100 V input 0.5 mA max. 200 V input 1 mA max. Inrush current (for a cold start at 25°C) *3 100 V input 25 A max. 30 A max. 200 V input 50 A max. 60 A max. Noise filter Yes Output *4 Voltage adjustment range *5 −10% to 15% (with V. ADJ) Ripple *3 2% (p-p) max. Input variation influence 0.4% max. Load variation influence 0.8% max. (0 to 100% load, rated input voltage) Temperature variation influence 0.05%/°C max. Startup time 650 ms max. 500 ms max. Hold time *3 20 ms min. Additional functions Overload protection *6 105% to 175% of rated load current, voltage drop, intermittent, automatic reset 105% to 175% of rated load current, Inverted L voltage drop, the circuit will be shut OFF when the overload exceeds 5 s. Overvoltage protection *7 Yes Yes *9 Overheat protection No Yes *9 Parallel operation Yes (up to 5 units) Series operation Yes (For up to two Power Supplies; external diodes required.) Protective circuit operation indicator No Yes (color: red) Other Ambient operating temperature Refer to the derating curve in Engineering Data on page 13 (with no icing or condensation). Storage temperature −25 to 65°C (with no icing or condensation) Ambient operating humidity 25% to 85% (Storage humidity: 25% to 90%) Dielectric strength 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 25 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 25 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 25 mA) Insulation resistance 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500 VDC Vibration resistance 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions Output indicator Yes (Color: Green) EMI Conducted Emissions *3 Conforms to EN 55011 Group 1 Class A and based on FCC Class A Radiated Emissions Conforms to EN 55011 Group 1 Class A EMS Electrostatic Discharge Confirms to EN61000-4-2 Radiated Electromagnetic Field Confirms to EN61000-4-3 Surge Confirms to EN61000-4-5 Conducted Disturbance Confirms to EN61000-4-6 Voltage Dips/Short Interruptions Confirms to EN61000-4-11 Approved standards *10 UL UR: UL 508 (Recognition), UL UR: UL 60950-1 (Recognition) cUL Listed: CSA C22.2 No.107.1 cUR: CSA C22.2 No. 60950-1 EN/VDE: EN50178 (= VDE 0160), EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) SEMI SEMI F47-0200 (200-VAC input) Weight *8 1,600 g max. 2,500 g max.
2.0 A AC (L) INPUT AC (N) Rectifier Smoothing circuit Rectifier/ Smoothing circuit Overvoltage detection circuit S8JX-G01505@@ (15 W) S8JX-G01512@@ (15 W) S8JX-G01515@@ (15 W) S8JX-G01524@@ (15 W) Voltage detection circuit Photocoupler Overvoltage detection circuit Drive control circuitOvercurrent detection circuit DC OUTPUT Rectifier/ smoothing circuit Noise filter Inrush current protection Fuse: 2.0 A AC (L) INPUT AC (N) Rectifier Smoothing circuit S8JX-G01548@@ (15 W) Voltage detection Photocoupler Drive control Circuit Overcurrent detection circuit DC OUTPUT Noise filter Inrush current protection Fuse 3.15 A AC (L) INPUT AC (N) Rectifier Smoothing circuit Rectifier/ Smoothing circuit Overvoltage detection circuit S8JX-G03505@@ (35 W) S8JX-G03512@@ (35 W) S8JX-G03515@@ (35 W) S8JX-G03524@@ (35 W) Voltage detection circuit Photocoupler Overvoltage detection circuit Drive control circuitOvercurrent detection circuit DC OUTPUT Rectifier/ smoothing circuit Noise filter Inrush current protection Fuse: 3.15 A AC (L) INPUT AC (N) Rectifier Smoothing circuit S8JX-G03548@@ (35 W)
6.3 A AC (L) INPUT AC (N) Rectifier Smoothing circuit Rectifier/ Smoothing circuit Overvoltage detection circuit S8JX-G05005@@ (50 W) S8JX-G05012@@ (50 W) S8JX-G05024@@ (50 W) Voltage detection circuit Photocoupler Overvoltage detection circuit Drive control circuitOvercurrent detection circuit DC OUTPUT Rectifier/ smoothing circuit Noise filter Inrush current protection Fuse: 6.3 A AC (L INPUT AC (N) Rectifier Smoothing circuit S8JX-G05048@@ (50 W) DC OUTPUTINPUT Voltage detection Noise filter Inrush current protection Fuse 8 A AC (L) AC (N) Rectifier Photocoupler Drive control Circuit Overcurrent detection circuit Smoothing circuit Rectifier/ Smoothing circuit Overvoltage detection circuit
Fuse: 8 A AC (L) INPUT AC (N) Drive control circuit Overcurrent detection circuit 㧗V 㧙V DC OUTPUT Inrush current protection Rectifier/ smoothing circuit Rectifier/ smoothing circuit S8JX-G15005@@ (150 W) Note: Set the input voltage switch to "115V" for 100 to 120 VAC and to "230V" for 200 to 240 VAC. INPUT DC OUTPUT Voltage detection Noise filter Inrush current protection Fuse 10 A AC (L) AC (N) Rectifier Photocoupler Drive control Circuit Overcurrent detection circuit Smoothing circuit Overvoltage detection circuit Rectifier/ Smoothing circuit S8JX-G15012@@ (150 W) S8JX-G15024@@ (150 W) S8JX-G15048@@ (150 W)
AC (L) AC (N) Photocoupler Drive control Circuit Overcurrent detection circuit Overvoltage detection circuit Rectifier/ Smoothing circuit Rectifier/ Smoothing circuit Parallel operation selector 100/200V (Selectable) S8JX-G30024@@ (300 W) Note: Short-circuit the input voltage selector terminals if the input is 100 to 120 VAC. Keep the terminals open if the input is 200 to 240 VAC. Fan INPUT DC OUTPUT Voltage detection Noise filter Inrush current protection Fuse 10 A AC (L) AC (N) Photocoupler Drive control Circuit Overcurrent detection circuit Overheat detection circuit Overvoltage detection circuit Rectifier/ Smoothing circuit Rectifier/ Smoothing circuit Parallel operation selector 100/200V (Selectable) S8JX-G60024@@ (600 W) Note: Short-circuit the input voltage selector terminals if the input is 100 to 120 VAC. Keep the terminals open if the input is 200 to 240 VAC.
Construction and Nomenclature Nomenclature *1. The fuse is located on the (L) side. It is NOT user-replaceable. *2. This is the protective earth terminal specified in the safety standards. Always ground this terminal. Reference Values E D A C B AC (L) AC (N) 100 to 120 VAC 200 to 240 VAC E F D A C B AC (L) Bottom AC (N) *1. The fuse is located on the (L) side. It is NOT user-replaceable. For a DC power input, connect the low side to the positive (+) terminal. *2. This is the protective earth terminal specified in the safety standards. Always ground this terminal. No. Name Function
1 DC Output
Terminals (−V), (+V) Connect the load lines to these terminals.
2 AC Input Terminals
(L), (N) Connect the input lines to these terminals. *1
3 Protective Earth
Terminal (PE) ( ) Connect the ground line to these terminals. *2
4 Output Voltage
Adjuster (V. ADJ) Use to adjust the voltage.
5 Output Indicator
(DC ON: Green) Lights green while a direct current (DC) output is ON.
6 Input voltage switch
Switches the internal circuits according to the input voltage. "115V": 100 to 120 VAC "230V": 200 to 240 VAC Note: The S8JX-G05024CD is shown above. Note: The S8JX-G15005C is shown above. 300-W Model AC (L) AC (N) Bottom E F D C H A B 600-W Model AC (L) AC (N) Side+V +V−V−V G E F D A C H B No. Name Function 1 DC Output Terminals ( +V), (−V) Connect the load lines to these terminals. 2 AC Input Terminals (L), (N) Connect the input lines to these terminals. *1 3 Protective Earth Terminal (PE) ( ) Connect the ground line to these terminals. *2 4 Input Voltage Selector Terminals Short-circuit the terminals if the input is 100 to 120 VAC and open the terminals if the input is 200 to 230 VAC. 5 Output Indicator (DC ON: Green) Lights while a Direct Current (DC) output is ON. 6 Output Voltage Adjuster (V. ADJ) It is possible to increase or decrease the output voltage.
7 Protection-ON Alarm Indicator
(DC ON: Red) The red indicator will be lit if the overvoltage (for a 600-W model) or overheat protection (for a 600-W model) circuit is triggered. This indicator will also be lit when overload (for a 600-W model) is detected. 8 Selector of Parallel Operation Set the selector to PARALLEL if the Units are in parallel operation. Reliability (MTBF) S8JX-G15012@@ and S8JX-G15005@@ Other models 240,000 hrs 250,000 hrs Definition MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures, and indicates reliability of devices. Therefore, it does not necessarily represent a life of the product. Life expectancy 10 yrs. min. Definition The life expectancy indicates average operating hours under the ambient temperature of 40°C and a load rate of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor.
Derating Curves (Standard Mounting) Open-frame Power Supplies Covered Power Supplies Note: 1. Internal parts may occasionally deteriorate or be damaged. Do not use the Power Supply in areas outside the derating curve (i.e., the area shown by shading A in the above graph). 2. If there is a derating problem, use forced air-cooling. 3. For Customers Using a DC Input When using an input voltage of less than 100 VDC, reduce the load calculated with the above derating curve by at least the following coefficients. 35-W and 100-W (5-V or 12-V output) models: 0.8 50-W/150-W models: 0.85 (DC power cannot be input only to the S8JX-G15005@@.) 15-W and 100-W (24-V or 48-V output): 0.9 Single Unit Operation Parallel Operation Note: 1. Internal parts may occasionally deteriorate or be damaged. Do not use the Power Supply in areas outside the derating curve (i.e., the area shown by shading A in the above graph). 2. If there is a derating problem, use forced air-cooling. 300-/600-W Models −20 −10 0 10 20 30 40 50 60 70 80 120 100 Load rate (%) − 20 −10 0 10 20 30 40 50 60 70 80 120 100 Load rate (%) Ambient Temperature (°C) Ambient Temperature (°C) A A Solid line Dotted line Front-mounting, Bottom-mounting, DIN Rail mounting, Side mounting (600W) Side mounting (300W) −20 −10 0 10 20 30 40 50 60 70 80 120 100 Load rate (%) − 20 −10 0 10 20 30 40 50 60 70 80 120 100 Load rate (%) Ambient Temperature (°C) Ambient Temperature (°C) A A
The following three mounting methods are possible. A. Front-mounting: Refer to Mounting Bracket Provided with Front-mounting Power Supplies a on page 20. B. Bottom-mounting C. Side-mounting Note: Additional mounting methods are also available using DIN Rail-mounting models. Standard Mounting Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Use the standard mounting method only. 2. When mounting the Power Supply, mounting it to a metal plate (*) is recommended. 3. Install the Power Supply so that the air flow circulates around the Power Supply, as the Power Supply is designed to radiate heat by means of natural air flow. 300-W Model 600-W Model B C Front-mounting DIN Rail-mounting Bottom-mounting Vertical Side-mounting Horizontal Side-mounting Front-mounting 20mm min. 20mm min. 20mm min.20mm min. Bottom-mounting Side-mounting DIN Rail mounting Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Use the standard mounting method only. 2. When mounting the Power Supply, mounting it to a metal plate (*) is recommended. 3. Install the Power Supply so that the air flow circulates around the Power Supply, as the Power Supply is designed to radiate heat by means of natural air flow. Front-mounting 20mm min.20mm min. 20mm min.20mm min. Bottom-mounting Side-mounting Note: 1. Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Use the standard mounting method only. 2. When mounting the Power Supply, mounting it to a metal plate (*) is recommended. 3. Install the Power Supply so that the air flow circulates around the Power Supply, as the Power Supply is designed to radiate heat by means of natural air flow.
The Power Supply is provided with an overload protection function that protects the power supply from possible damage by overcurrent. When the output current rises above 105% to 175% min. of the rated current, the protection function is triggered, decreasing the output voltage. When the output current falls within the rated range, the overload protection function is automatically cleared. (Reference value) If an excessive current flows for 5 s or more, the output will be turned OFF and simultaneously the protection-ON alarm indicator will be lit. To reset the S8JX, turn OFF the power, leave the S8JX for at least three minutes, and then turn it ON again. Note: 1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the power supply may not start. 2. Internal parts may occasionally deteriorate or be damaged if a short-circuited or overcurrent state continues during operation. 3. Internal parts may possibly deteriorate or be damaged if the Power Supply is used for applications with frequent inrush current or overloading at the load end. Do not use the Power Supply for such applications. 150-W, 5-V Models 300-W Model Intermittent operation Load rate (%) 100 Output voltage (V) Load rate (%) 10050 Output voltage [V] Intermittent operation Load rate (%) 100 Output voltage (V) 600-W Model Output interrupted Load rate (%) 100 Output voltage (V)
Consider the possibility of an overvoltage and design the system so that the load will not be subjected to an excessive voltage even if the feedback circuit in the power supply fails. When an excessive voltage that is approximately 130% of the rated voltage or more is output, the output voltage is shut OFF, preventing damage to the load due to overvoltage. Reset the input power by turning it OFF for at least seven minutes and then turning it back ON again. Consider the possibility of an overvoltage and design the system so that the load will not be subjected to an excessive voltage even if the feedback circuit in the Power Supply fails. When an excessive voltage that is approximately 120% of the rated voltage or more is output, the output voltage is shut OFF, preventing damage to the load due to overvoltage. Reset the input power by turning it OFF for at least three minute and then turning it back ON again. (Reference value) Note: Do not turn ON the power again until the cause of the overvoltage has been removed. Overheat Protection If the internal temperature rises excessively as a result of fan failure or any other reason, the overheat protection circuit will be triggered to shut OFF the output voltage and simultaneously the protection-ON alarm indicator will be lit. Reset the input power by turning it OFF for at least three minutes and then turning it back ON again. Inrush Current, Startup Time, Output Hold Time Note: A maximum startup time of 500 ms is required (650 ms for 300 W). Construct a system configuration that considers the startup time of other devices. 300-/600-W Models 600-W Model Output voltage (V) Overvoltage protection Operating Variable range Rated output Voltage 0 V Startup time Hold time (20 ms min.) AC input voltage AC input current Output voltage Inrush current on input application 90% 96.5% Input ON Input OFF
Dimensions (Unit: mm) Front-mounting Models Panel mounting holes dimensions Surface screw mounting Side Mounting Bottom Mounting Two, M3 75±0.5 82±0.5 Two, M3 78±0.5 Five, M3.5 Label Cover 3.5 dia. 3.5 dia. Two, M3 (Depth 4 mm max.) 35.5±1 39.5±1 82±0.5 78±0.5 91±1 75±0.5 90±110 max. 5 max. 50±0.5 8.29.5 4.5 8.5 3.5 26.5 17.5 7.5 3.5 S8JX-G015@@ (15 W) S8JX-G015@@C (15 W) S8JX-G035@@ (35 W) S8JX-G035@@C (35 W) Panel mounting holes dimensions Surface screw mounting Side Mounting Bottom Mounting Two, M3 75±0.5 92±0.5 Two, M3 92±0.5 3.5 dia. 3.5 dia. 3.5 Two, M3 (Depth 4 mm max.) 8.29.5 Five, M3.5 10 max. 100±1 92±1 75±0.5 3.5 36±1 40±1 4.5 4.5 92±0.5 92±0.5 65±0.520 26.5 5 max. Label Cover S8JX-G050@@ (50 W) S8JX-G050@@C (50 W) Panel mounting holes dimensions Surface screw mounting Side Mounting Bottom Mounting Two, M3 75±0.5 141±0.5 Two, M3 141±0.5 3.5 dia. 3.5 dia. 150 W 8.2 9.5 Five, M3.5 48±1 50±1 10 max. 150±1 5 max. 3.5 5 141±0.5 Two, M3 (Depth 4 mm max.) 122±0.516 3.5 5 141±0.5 92±1 75±0.5 100·150 W100 W Label Cover S8JX-G100@@ (100 W) S8JX-G100@@C (100 W) S8JX-G15024 (150 W) S8JX-G15024C (150 W) S8JX-G15048 (150 W) S8JX-G15048C (150 W)
92±1 3633.5 3.5 3.5 5max.12max. 68±0.5 860±1 2-M4 9.58.2 169±0.5 169±0.5 140±0.5 Input voltage switch14 178±1 Two, M3 (Depth: 4 mm max.) 3.5 dia. 3.5 dia.3-M3.5 Label Cover Panel mounting holes dimensions Surface screw mounting Side Mounting Bottom Mounting 169±0.5 68±0.5 Two, M3 169±0.5 Two, M3 S8JX-G15005 (150 W) S8JX-G15005C (150 W) 92±1 3633.5 3.5 3.5 5max.10max. 68±0.5 860±1 9.5 8.2 169±0.5 169±0.5 140±0.5 178±1 Two, M3 (Depth: 4 mm max.) 3.5 dia. 3.5 dia.5-M3.5 Label Cover Panel mounting holes dimensions Surface screw mounting Side Mounting Bottom Mounting 169±0.5 68±0.5 Two, M3 169±0.5 Two, M3 S8JX-G15012 (150 W) S8JX-G15012C (150 W)
92±1 4 max. 110±1 8.6 Nine, M4 terminal screws 19 136±0.5 90±0.5 167.1±1 19 136±0.5 50±0.5 20 max. Eight, M4 holes (depth: 8 max. on both sides) Four, M4 holes (depth: 8 max.) Panel mounting holes dimensions Surface screw mounting Side Mounting Bottom Mounting 50±0.5 136±0.5 Four, 4.5 dia. 90±0.5 136±0.5 Four, 4.5 dia. S8JX-G30024C (300 W) 10 8.6 159.8±1 24.4±0.5 11124±0.5 50±0.5 20.9 14.8 100±0.5 137±0.5 8.6 10 150±1 92±1 Nine, M4 terminal screws Eight, M4 holes (depth: 8 max. on both sides) Four, M4 holes (depth: 8 max.) Panel mounting holes dimensions Surface screw mounting Side Mounting Bottom Mounting 50±0.5 124±0.5 Four, 4.5 dia. 100±0.5 137±0.5 Four, 4.5 dia. S8JX-G60024C (600 W)
Mounting Bracket Provided with Front-mounting Power Supplies a S82Y-J00F Front-mounting Bracket Front-mounting Method Temporarily attach the enclosed mounting bracket as shown in the illustration on the right, hook the holes (parts a) in the Power Supply on hooks on the mounting bracket (parts b), and secure the Power Supply with two mounting screws. Dimensions Mounting dimensions 1.5 205 31.5 20.5 4.7 4.6 4.6 15 ±0.2 74Two, 3.5 dia. t = 1.0 Material: Stainless steel Two, M3 b b a a Power Supply Mounting bracket Note: Mounting screws are not provided. 300-/600-W Models Front-mounting Bracket (S82Y-J30F) Dimensions with Mounting Brackets Attaching the Mounting Brackets 7.5 7.5 160 32±0.2 145±0.3 R2.5 10 dia. Two, 5 dia. t = 1.6 Note: Mounting Brackets are provided in a set, one for the right side and one for the left side. 145±0.3 80±0.5 Four, M4 300-W Model 300-W Model Note: To provide ventilation space, the body will shift forward by 21.6 mm from the mounting surface. 145±0.3 120±0.5 Four, M4 600-W Model 600-W Model Note: To provide ventilation space, the body will shift forward by 23.6 mm from the mounting surface.
S8JX-G015@@D (15 W) S8JX-G015@@CD (15 W) S8JX-G035@@D (35 W) S8JX-G035@@CD (35 W) 8.29.5 Five, M3.5 6 max. 44±1 Label Cover 10 max. 90±1 91±1 14.5 max. 98.6 5 max. 7 (Sliding: 16.6 max.) S8JX-G050@@D (50 W) S8JX-G050@@CD (50 W) 8.29.5 Five, M3.5 36±1 40±1 6 max. 44±1 10 max. 100±1 92±1 14.5 max. 108.6 5 max. 7 (Sliding: 16.6 max.) Label Cover S8JX-G100@@D (100 W) S8JX-G100@@CD (100 W) S8JX-G15024D (150 W) S8JX-G15024CD (150 W) S8JX-G15048D (150 W) S8JX-G15048CD (150 W) 8.2 9.5 Five, M3.5 48±1 50±1 10 max. 150±1 5 max. 92±1 7 (Sliding: 16.6 max.) 158.6 6 max. 50±1 14.5 max. 100·150 W150 W100 W Label Cover
92±1 6 max. 60±1 Input voltage switch 12 max. 14.5 max. 5 max. 7 (Sliding: 16.6 max.) 178±1 186.6 2-M4 Label 3-M3.5 Cover 9.58.2 S8JX-G15005D (150 W) S8JX-G15005CD (15 W) 9.5 8.2 10 max. 178±1 5-M3.5 Cover 6 max. 60±1 14.5 max. 92±1 5 max. 7 (Sliding: 16.6 max.)186.6 Label S8JX-G15012D (150 W) S8JX-G15012CD (150 W)
DIN Rail (Order Separately) Note: 1. If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from aluminum abrasion. 2. If the Unit may be subjected to sliding to either side, attach an End Plate (model PFP-M) on each side of the Unit. 92±1 4 max. 4.4 (Sliding: 10 max.) 4.6 max. 110±1 4.6 max. 8.6 Nine, M4 terminal screws 10.2167.1±1 20 max. 46.6 181.3 (17.7) S8JX-G30024CD (300 W) Note: Use a metal DIN Rail when mounting a 300-W model to a DIN Rail. Mounting Rail (Material: Aluminum) 4.5 15 25 25 10 10 1,000 (500) ∗ 25 25 15 (5) * 35±0.3 7.3±0.15 27±0.15 * Value in parentheses are for PFP-50N. Model PFP-100N PFP-50N Mounting Rail (Material: Aluminum) 4.5 15 25 25 10 10 1,000 25 25 15 1 1.5 29.224 27 35±0.3 Model PFP-100N2 1.3 4.8 35.5 35.5 1.8 1.8 M4 spring washer 6.2 M4 × 8 panhead screw 11.5 End Plate Model PFP-M
Refer to Safety Precautions for All Power Supplies. Minor electric shock, fire, or Product failure may occasionally occur. Do not disassemble, modify, or repair the Product to touch the interior of the Product. Minor burns may occasionally occur. Do not touch the Product while power is being supplied or immediately after power is turned OFF. Fire may occasionally occur. Tighten terminal screws to the specified torque of 1.13 N·m. For the 5-V output terminal, tighten the terminal screw to 1.56 N·m. Minor injury due to electric shock may occasionally occur. Do not touch the terminals while power is being supplied. Always close the terminal cover after wiring. Minor electric shock, fire, or Product failure may occasionally occur. Do not allow any pieces of metal or conductors or any clippings or cuttings resulting from installation work to enter the Product. Mounting
- Take adequate measures to ensure proper heat dissipation to increase the long-term reliability of the Product.
- Be sure to allow convection in the atmosphere around devices when mounting. Do not use in locations where the ambient temperature exceeds the range of the derating curve. (except 600 W)
- The S8JX-@60024@ is designed to radiate heat by means of forced air-flow. Do not cover the air holes (provided at fan mounted side and the opposite side) to have enough air-cooling.
- The screws must not protrude beyond the following values inside the Power Supply when screw holes provided on the chassis are used. 15 W, 35 W, 50 W, 100 W, or 150 W: 4 mm min. 300 W or 600 W: 8 mm min. Mounting screw tightening torque (recommended value) : 0.54 N·m.
- Rear mounting is possible using provided mounting bracket.
- When cutting out holes for mounting, make sure that cuttings do not enter the interior of the Products.
- Improper mounting will interfere with heat dissipation and may occasionally result in deterioration or damage of internal parts. Use the standard mounting method only.
- The internal parts may occasionally deteriorate and be broken due to adverse heat radiation. Do not loosen the screw on the side face of the main body.
- When mounting two or more Power Supplies side-by-side, allow at least 20 mm spacing between them.
- Provide a space of at least 20 mm back and forth when mounting 300-W and 600-W models as well.
- Use the metal plate as the mounting panel.
- Minor fire may occasionally occur. Set the input voltage switch to the input voltage that is to be used (150-W, 5-V models only). *1. Convection of air *2. 20 mm max. *3. Use a metal plate as the mounting surface. CAUTION Precautions for Safe Use 300-W Model 600-W Model Standard Mounting (Horizontal Mounting) *2 *3 Standard Mounting (Bottom-mounting) *2 *3 *1 *2 Standard Mounting (Front-mounting and DIN Rail-mounting) *3 *2 Standard Mounting (Bottom-mounting) Standard Mounting (Front-mounting and DIN Rail-mounting) *1 *1
- Connect the ground completely. A protective earthing terminal stipulated in safety standards is used. Electric shock or malfunction may occur if the ground is not connected completely.
- Minor fire may possibly occur. Ensure that input and output terminals are wired correctly.
- Do not apply more than 75 N force to the terminal block when tightening it.
- Be sure to remove the sheet covering the Product for machining before power-ON so that it does not interfere with heat dissipation.
- Use the following material for the wires to be connected to the S8JX to prevent smoking or ignition caused by abnormal loads. Recommended Wire Type Installation Environment
- Do not use the Power Supply in locations subject to shocks or vibrations. In particular, install the Power Supply as far away as possible from contactors or other devices that are a vibration source.
- Install the Power Supply well away from any sources of strong, high-frequency noise and surge. Ambient Operating and Storage Environments
- Store the Power Supply at a temperature of −25 to 65°C and a humidity of 25% to 90%.
- The Internal parts may occasionally deteriorate or be damaged. Do not use the Power Supply outside the derating range (i.e., the area shown by shading A in the derating curve diagram on page 13.)
- Use the Power Supply at a humidity of 25% to 85%.
- Do not use the Power Supply in locations subject to direct sunlight.
- Do not use locations where liquids, foreign matter, or corrosive gases may enter the interior of the Product. Overload Protection
- Internal parts may possibly deteriorate or be damaged if a short- circuited or overload state continues during operation.
- Internal parts may possibly deteriorate or be damaged if the Power Supply is used for applications with frequent inrush current or overloading at the load end. Do not use the Power Supply for such applications. Charging a Battery When connecting a battery at the load, connect an overcurrent limiting circuit and overvoltage protection circuit. Output Voltage Adjuster (V.ADJ)
- The output voltage adjuster (V.ADJ) may possibly be damaged if it is turned with unnecessary force. Do not turn the adjuster with excessive force.
- After completing output voltage adjustment, be sure that the output capacity or output current does not exceed the rated output capacity or rated output current. DIN Rail-mounting To mount the Power Supply to a DIN Rail, pull down the rail stopper until you hear it clicks open, hook portion (A) of the Power Supply onto the DIN Rail, press the Power Supply in direction (B), and then push up the rail stopper to lock the Power Supply in place. To dismount the Power Supply, pull down portion (C) with a flat-blade screwdriver and pull out the Power Supply. Series Operation Two power supplies can be connected in series. The (±) voltage output can be accomplished with two Power Supplies. Note: 1. If the load is short-circuited, a reverse voltage will be generated inside the Power Supply. If this occurs the Power Supply may possibly deteriorate or be damaged. Always connect a diode as shown in the figure. Select a diode having the following ratings. 2. Although Products having different specifications can be connected in series, the current flowing through the load must not exceed the smaller rated output current. Parallel Operation The Product is not designed for parallel operation. Parallel operation is possible under 80% of the rated value.
- To operate in parallel, set the switch to the "PARALLEL" side.
- The length and thickness of each wire connected to the load must be the same so that there is no difference in voltage drop value between the load and the output terminals of each Power Supply.
- It is desirable to set the same value on the voltage adjuster of each Power Supply.
15 W, 35 W
AWG12 to AWG20 (a cross section of 0.517 to 3.309 mm UL-certified temperature of at least 75°C 50W, 100W,
150 W (except
for 5 V) AWG12 to AWG16 (a cross section of 1.309 to 3.309 mm UL-certified temperature of at least 60°C or 60/75°C 150 W at 5 V Input side AWG12 to AWG16 (a cross-section of 1.309 to 3.309 mm UL-certified temperature of at least 60°C or 60/75°C Output side AWG8 to AWG14 (a cross-section of 2.081 to 8.368 mm UL-certified temperature of at least 60°C or 60/75°C 300 W, 600 W AWG12 to AWG20 (a cross section of 0.517 to 3.309 mm UL-certified temperature of at least 60°C or 60/75°C Type Schottky Barrier diode Dielectric strength (VRRM) Twice the rated output voltage or above Forward current (IF) Twice the rated output current or above 300-/600-W Models 30 mm min. Track stopper (C) (B) (A) AC (L) AC (N) AC (L) AC (N) AC (L) AC (N) AC (L) AC (N) Series Operation Correct Output Voltage (±) Correct AC (L) AC (N) AC (L) AC (N) Parallel Operation Incorrect AC (L) AC (N) AC (L) AC (N) Parallel Operation Correct
In Case There Is No Output Voltage The possible cause for no output voltage may be that the overcurrent or overvoltage protection has operated. The internal protection may operate if a large amount of surge voltage such as a lightening surge occurs while turning ON the Power Supply. In case there is no output voltage, please check the following points before contacting us:
- Checking overcurrent protected status: Check whether the load is in overcurrent status or is short- circuited. Remove wires to load when checking.
- Checking overvoltage or internal protection: Turn the power supply OFF once, and leave it OFF for at least 7 minutes. Then turn it ON again to see if this clears the condition. Switching the AC Input Voltage between 100 and 200 VAC The input voltage can be switched between 100 V and 200 V by using the input voltage switch. Make the setting shown in the following figure for the voltage that will be used. (The input voltage is factory- set to 200 V.) The input voltage can be switched between 100 and 200 V by shorting or opening the input voltage selection terminals. Set the required voltage as shown below. (The voltage is factory-set to 200 V.) Note: A 300-W model is shown above. Fan Replacement The service life of the fan is approximately 50,000 hours (at 25°C). The service life varies, however, depending on the ambient temperature or other surrounding environmental conditions such as dust. As a preventive maintenance measure, replace the fan within approx. two years if it is used at an ambient temperature of 40°C. Fans (S82Y-JXFAN) are available as replacements. Replace the fan as shown in the following illustration. 150-W, 5-V Models 300-/600-W Models In the interest of product improvement, specifications are subject to change without notice. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. The input voltage switch is at the back on the bottom of the Power Supply. "230V": 200 to 240 VAC "115V": 100 to 120 VAC SHORT BAR N L VOLTAGE SELECT SHORT 100-120V OPEN 200-230V SHORT BAR N L VOLTAGE SELECT SHORT 100-120V OPEN 200-230V 200-V input100-V input Short with the short bar. Remo ve the short bar and leave the terminals open. 600-W Model Fan Set: Fan (above), instruction sheet, and packing case
Read and Understand this Catalog Please read and understand this catalog before purchasing the product. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY , OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABL Y MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS, OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY , NEGLIGENCE, OR STRICT LIABILITY . In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY , REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANAL YSIS CONFIRMS THAT THE PRODUCTS WERE PROPERL Y HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will be used. Know and observe all prohibitions of use applicable to this product. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERL Y RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. PROGRAMMABLE PRODUCTS OMRON shall not be responsible for the user’s programming of a programmable product, or any consequence thereof. Disclaimers CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
Authorized Distributor: In the interest of product improvement, specifications are subject to change without notice. Cat. No. T041-E1-04 Printed in Japan 1110 © OMRON Corporation 2009 All Rights Reserved. OMRON Corporation Industrial Automation Company OMRON ELECTRONICS LLC One Commerce Drive Schaumburg, IL 60173-5302 U.S.A. Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69-2132 JD Hoofddorp The Netherlands Contact: www.ia.omron.com Tokyo, JAPAN OMRON ASIA PACIFIC PTE. LTD. No. 438A Alexandra Road # 05-05/08 (Lobby 2), Alexandra Technopark, Singapore 119967 Tel: (65) 6835-3011/Fax: (65) 6835-2711 OMRON (CHINA) CO., LTD. Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China CSM_9_1_0211 Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200