Datasheet search site | www.alldatasheet.com

Document overview

  • Manufacturer or author: OMRON
  • PDF pages: 34

Technical content

S8FS-G (15/30/50/100/150/300/600-W Models) Superior Basic Performance That Ensures Reliability. Wide Range of Standards Certification and Greater Usability.

  • Superior basic performance that ensures reliability Ambient temperatures up to 70°C, greater resistance to rusting with aluminum/stainless steel case, and applications at altitudes up to 3,000 m.
  • Certification for Global Standards North America: UL 508 (Listing)*, CSA C22.2 Europe: Overvoltage Category III (EN 50178) EMI: Class B (EN 61204-3) No need for control circuit transformers for which the Machinery Directive is specified. (EN/IEC 61558-2-16) * Refer to pages 4 to 10 for certified models.
  • Greater Usability The Terminal Block Cover prevents screws from dropping out and the Front Cover prevents ingress of foreign matter. Lineup Model Number Structure Model Number Legend Note: Not all combinations are possible. Refer to List of Models in Ordering Information, below. ! Refer to Safety Precautions for All Power Supplies and Safety Precautions on page 29. Output voltage Power rating

15 W 30 W 50 W 100 W 150 W 300 W 600 W

5 V Yes Yes Yes Yes Yes --- ---

12 V Yes Yes Yes Yes Yes Yes Yes

15 V Yes Yes Yes Yes Yes Yes Yes

24 V Yes Yes Yes Yes Yes Yes Yes

48 V --- --- --- --- Yes Yes Yes

  1. Power Ratings 015: 15 W 030: 30 W 050: 50 W *1 100: 100 W *2 150: 150 W *3 300: 300 W 600: 600 W 3. Configuration C: With cover/Direct mounting CD: With cover/DIN Rail mounting 4. Option (1) None: Screw terminal block E: Connectors *4 2. Output voltage 05: 5 V 12: 12 V 15: 15 V 24: 24 V 48: 48 V 5. Option (2) *5 None: None W: Parallel operation 6. Option (3) *6 None: None R: Remote control 7. Option (4) *7 None: None H: Extended hold time *1. The output electric power is 40 W for products with an output voltage of 5 V. *2. The output electric power is 80 W for products with an output voltage of 5 V. *3. The output electric power is 105 W for products with an output voltage of 5 V. *4. Applicable only for 150 W or less and 24 V. *5. Applicable only for 600 W and 24 V. *6. Applicable only for 100 W or more and 24 V. *7. Applicable only for 300 W or more and 24 V.

Ordering Information

Note: For details on normal stock models, contact your nearest OMRON representative. With Cover/DIN Rail Mounting Note: Ask your OMRON representative for pricing information on optional models. *1. The output electric power is 40 W. *2. The output electric power is 80 W. *3. The output electric power is 105 W. *4. Applicable to products produced from May 2018. With Cover/DIN Rail Mounting (Extended hold time type) Power ratings Input voltage Output voltage (VDC) Output current Built-in fan Model 15 W 100 to 240 VAC (Permissible range 85 to 264 VAC, 80 to 370 VDC)

5 V 3 A

12 V 1.3 A S8FS-G01512CD

15 V 1 A S8FS-G01515CD

24 V 0.65 A S8FS-G01524CD 30 W

5 V 6 A S8FS-G03005CD

12 V 3 A S8FS-G03012CD

15 V 2.4 A S8FS-G03015CD 24 V 1.5 A S8FS-G03024CD 50 W

5 V 8 A *1 S8FS-G05005CD

12 V 4.3 A S8FS-G05012CD 15 V 3.5 A S8FS-G05015CD 24 V 2.2 A S8FS-G05024CD 100 W

5 V 16 A *2 S8FS-G10005CD

12 V 8.5 A S8FS-G10012CD

15 V 7 A S8FS-G10015CD

24 V 4.5 A S8FS-G10024CD 150 W

5 V 21 A *3 S8FS-G15005CD

12 V 13 A S8FS-G15012CD

15 V 10 A S8FS-G15015CD

24 V 6.5 A S8FS-G15024CD 48 V 3.3 A S8FS-G15048CD 300 W 100 to 240 VAC (Permissible range 85 to 264 VAC, 120 to 370 VDC)

12 V 25 A

15 V 20 A S8FS-G30015CD

24 V 14 A S8FS-G30024CD

48 V 7 A S8FS-G30048CD

(Permissible range 85 to 264 VAC, 120 to 350 VDC)

12 V 50 A S8FS-G60012CD

15 V 40 A S8FS-G60015CD

24 V 27 A S8FS-G60024CD

48 V 13 A S8FS-G60048CD

Power ratings Input voltage Output voltage (VDC) Output current Built-in fan Model 300 W 100 to 240 VAC (Permissible range 85 to 264 VAC, 120 to 370 VDC) 24 V 14 A Yes S8FS-G30024CD-H 600 W 100 to 240 VAC (Permissible range 85 to 264 VAC, 120 to 350 VDC)

27 A S8FS-G60024CD-H

With Cover/Direct Mounting Note: 1. Ask your OMRON representative for pricing information on optional models. 2. Front-mounting is not possible. To mount a Power Supply from the front, purchase a DIN Rail-mounting Power Supply and a Front-mounting Bracket (sold separately). Refer to page 27. With Cover/Direct Mounting (Extended hold time type) With Cover/Direct Mounting (Connector type) *1. The output electric power is 40 W. *2. The output electric power is 80 W. *3. The output electric power is 105 W. *4. Applicable to products produced from May 2018. Power ratings Input voltage Output voltage (VDC) Output current Built-in fan Model 15 W 100 to 240 VAC (Permissible range 85 to 264 VAC, 80 to 370 VDC) 12 V 1.3 A S8FS-G01512C

15 V 1 A S8FS-G01515C

24 V 0.65 A S8FS-G01524C 30 W

5 V 6 A S8FS-G03005C

12 V 3 A S8FS-G03012C

15 V 2.4 A S8FS-G03015C 24 V 1.5 A S8FS-G03024C 50 W

5 V 8 A *1 S8FS-G05005C

12 V 4.3 A S8FS-G05012C 15 V 3.5 A S8FS-G05015C 24 V 2.2 A S8FS-G05024C 100 W

5 V 16 A *2 S8FS-G10005C

12 V 8.5 A S8FS-G10012C

15 V 7 A S8FS-G10015C

24 V 4.5 A S8FS-G10024C 150 W

5 V 21 A *3 S8FS-G15005C

12 V 13 A S8FS-G15012C

15 V 10 A S8FS-G15015C

24 V 6.5 A S8FS-G15024C 48 V 3.3 A S8FS-G15048C 300 W 100 to 240 VAC (Permissible range 85 to 264 VAC, 120 to 370 VDC)

15 V 20 A S8FS-G30015C

24 V 14 A S8FS-G30024C

48 V 7 A S8FS-G30048C

(Permissible range 85 to 264 VAC, 120 to 350 VDC)

12 V 50 A S8FS-G60012C

15 V 40 A S8FS-G60015C

24 V 27 A S8FS-G60024C

48 V 13 A S8FS-G60048C

Power ratings Input voltage Output voltage (VDC) Output current Built-in fan Model 300 W 100 to 240 VAC (Permissible range 85 to 264 VAC, 120 to 370 VDC) 24 V 14 A Yes S8FS-G30024C-H 600 W 100 to 240 VAC (Permissible range 85 to 264 VAC, 120 to 350 VDC)

27 A S8FS-G60024C-H

Power ratings Input voltage Output voltage (VDC) Output current Built-in fan Model 15 W 100 to 240 VAC (Permissible range 85 to 264 VAC, 80 to 370 VDC) 24 V 0.65 A None S8FS-G01524CE 30 W 1.5 A S8FS-G03024CE 50 W 2.2 A S8FS-G05024CE 100 W 4.5 A S8FS-G10024CE 150 W 6.5 A S8FS-G15024CE

  • Refer to Ratings, Characteristics, and Functions on page 11. Power rating 15 W Item Output voltage 5 V 12 V 15 V 24 V Efficiency * 100 VAC input 80% typ. 84% typ. 84% typ. 85% typ. 200 VAC input 80% typ. 84% typ. 84% typ. 86% typ. 230 VAC input 80% typ. 84% typ. 84% typ. 86% typ. Input Voltage range * Single phase, 85 to 264 VAC, 80 to 370 VDC Frequency * 50/60 Hz (47 to 450 Hz) Current * 100 VAC input 0.32 A typ. 200 VAC input 0.2 A typ. Power factor --- Leakage current * 100 VAC input 0.5 mA max. 200 VAC input 1 mA max. Inrush current * (for a cold start at 25°C) 100 VAC input 14 A typ. 200 VAC input 28 A typ. Output Rated Output Current 3 A 1.3 A 1 A 0.65 A Voltage adjustment range * −10% to 15% (with V.ADJ) Ripple & Noise voltage * 100 to 240 VAC input 40 mVp-p max. 40 mVp-p max. 40 mVp-p max. 60 mVp-p max. Input variation influence * 0.5% max. Load variation influence * 1.0% max. Temperature variation influence 100 to 240 VAC input 0.05%/°C max. Startup time * 100 VAC input 1,000 ms max. 200 VAC input 1,000 ms max. Hold time * 100 VAC input 15 ms typ. 14 ms typ. 15 ms typ. 15 ms typ. 200 VAC input 75 ms typ. 70 ms typ. 75 ms typ. 70 ms typ. Additional functions Overload protection Yes, automatic reset Overvoltage protection * Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) Overheat protection No Series operation Yes (For up to two Power Supplies, external diodes are required.) Parallel operation No (However, backup operation is possible, external diodes are required.) Remote sensing No Remote control No Output indicator Yes (LED: Green) Insulation Withstand voltage 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA Insulation resistance 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC Environment Ambient operating temperature −20 to 70°C (Derating is required according to the temperature.) (with no condensation or icing) Storage temperature −25 to 75°C (with no condensation or icing) Ambient operating humidity 90% max. (Storage humidity: 90% max.) Vibration resistance 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions Reliability MTBF 135,000 hrs min. Life expectancy * 10 years min. Construction Dimensions (W×H×D) Refer to Dimensions on page 19. Weight 250 g Cooling fan No Degree of protection --- Standards Harmonic current emissions Conforms to EN 61000-3-2 EMI * Conducted Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B Radiated Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B EMS Conforms to EN 61204-3 high severity levels Safety Standards UL 508 (Listing, excluding models with connector option) UL 60950-1, UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option) CSA C22.2 No.60950-1, No.62368-1 (excluding models with connector option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN/IEC 60950-1, EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) Marine Standards No SEMI Conforms to F47-0706 (200 VAC input)
  • Refer to Ratings, Characteristics, and Functions on page 11. Power rating 30 W Item Output voltage 5 V 12 V 15 V 24 V Efficiency * 100 VAC input 81% typ. 84% typ. 86% typ. 86% typ. 200 VAC input 81% typ. 86% typ. 88% typ. 88% typ. 230 VAC input 81% typ. 86% typ. 88% typ. 89% typ. Input Voltage range * Single phase, 85 to 264 VAC, 80 to 370 VDC Frequency * 50/60 Hz (47 to 450 Hz) Current * 100 VAC input 0.72 A typ. 200 VAC input 0.43 A typ. Power factor --- Leakage current * 100 VAC input 0.5 mA max. 200 VAC input 1 mA max. Inrush current * (for a cold start at 25°C) 100 VAC input 14 A typ. 200 VAC input 28 A typ. Output Rated Output Current 6 A 3 A 2.4 A 1.5 A Voltage adjustment range * −10% to 15% (with V.ADJ) Ripple & Noise voltage * 100 to 240 VAC input 50 mVp-p max. 60 mVp-p max. 50 mVp-p max. 60 mVp-p max. Input variation influence * 0.5% max. Load variation influence * 1.0% max. Temperature variation influence 100 to 240 VAC input 0.05%/°C max. Startup time * 100 VAC input 1,000 ms max. 200 VAC input 1,000 ms max. Hold time * 100 VAC input 11 ms typ. 10 ms typ. 11 ms typ. 10 ms typ. 200 VAC input 60 ms typ. 50 ms typ. 50 ms typ. 55 ms typ. Additional functions Overload protection Yes, automatic reset Overvoltage protection * Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) Overheat protection No Series operation Yes (For up to two Power Supplies, external diodes are required.) Parallel operation No (However, backup operation is possible, external diodes are required.) Remote sensing No Remote control No Output indicator Yes (LED: Green) Insulation Withstand voltage 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA Insulation resistance 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC Environment Ambient operating temperature −20 to 70°C (Derating is required according to the temperature.) (with no condensation or icing) Storage temperature −25 to 75°C (with no condensation or icing) Ambient operating humidity 90% max. (Storage humidity: 90% max.) Vibration resistance 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions Reliability MTBF 135,000 hrs min. Life expectancy * 10 years min. Construction Dimensions (W×H×D) Refer to Dimensions on page 19. Weight 250 g Cooling fan No Degree of protection --- Standards Harmonic current emissions Conforms to EN 61000-3-2 EMI * Conducted Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B Radiated Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B EMS Conforms to EN 61204-3 high severity levels Safety Standards UL 508 (Listing, excluding models with connector option) UL 60950-1, UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option) CSA C22.2 No.60950-1, No.62368-1 (excluding models with connector option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN/IEC 60950-1, EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) Marine Standards No SEMI Conforms to F47-0706 (200 VAC input)
  • Refer to Ratings, Characteristics, and Functions on page 11. Power rating 50 W Item Output voltage 5 V 12 V 15 V 24 V Efficiency * 100 VAC input 81% typ. 84% typ. 86% typ. 86% typ. 200 VAC input 82% typ. 86% typ. 88% typ. 89% typ. 230 VAC input 82% typ. 86% typ. 88% typ. 89% typ. Input Voltage range * Single phase, 85 to 264 VAC, 80 to 370 VDC Frequency * 50/60 Hz (47 to 450 Hz) Current * 100 VAC input 1.1 A typ. 200 VAC input 0.62 A typ. Power factor --- Leakage current * 100 VAC input 0.5 mA max. 200 VAC input 1 mA max. Inrush current * (for a cold start at 25°C) 100 VAC input 14 A typ. 200 VAC input 28 A typ. Output Rated Output Current 8 A 4.3 A 3.5 A 2.2A Voltage adjustment range * −10% to 15% (with V.ADJ) Ripple & Noise voltage * 100 to 240 VAC input 40 mVp-p max. 40 mVp-p max. 40 mVp-p max. 60 mVp-p max. Input variation influence * 0.5% max. Load variation influence * 1.0% max. Temperature variation influence 100 to 240 VAC input 0.05%/°C max. Startup time * 100 VAC input 1,000 ms max. 200 VAC input 1,000 ms max. Hold time * 100 VAC input 14 ms typ. 11 ms typ. 10 ms typ. 10 ms typ. 200 VAC input 75 ms typ. 60 ms typ. 60 ms typ. 55 ms typ. Additional functions Overload protection Yes, automatic reset Overvoltage protection * Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) Overheat protection No Series operation Yes (For up to two Power Supplies, external diodes are required.) Parallel operation No (However, backup operation is possible, external diodes are required.) Remote sensing No Remote control No Output indicator Yes (LED: Green) Insulation Withstand voltage 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA 500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA Insulation resistance 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC Environment Ambient operating temperature −20 to 70°C (Derating is required according to the temperature.) (with no condensation or icing) Storage temperature −25 to 75°C (with no condensation or icing) Ambient operating humidity 90% max. (Storage humidity: 90% max.) Vibration resistance 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions Reliability MTBF 135,000 hrs min. Life expectancy * 10 years min. Construction Dimensions (W×H×D) Refer to Dimensions on page 20. Weight 300 g Cooling fan No Degree of protection --- Standards Harmonic current emissions Conforms to EN 61000-3-2 EMI * Conducted Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B Radiated Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B EMS Conforms to EN 61204-3 high severity levels Safety Standards UL 508 (Listing, excluding models with connector option) UL 60950-1, UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option) CSA C22.2 No.60950-1, No.62368-1 (excluding models with connector option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN/IEC 60950-1, EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) Marine Standards No SEMI Conforms to F47-0706 (200 VAC input)
  • Refer to Ratings, Characteristics, and Functions on page 11. Power rating 100 W Item Output voltage 5 V 12 V 15 V 24 V Efficiency * 100 VAC input 79% typ. 84% typ. 85% typ. 87% typ. 200 VAC input 81% typ. 86% typ. 87% typ. 89% typ. 230 VAC input 81% typ. 86% typ. 87% typ. 89% typ. Input Voltage range * Single phase, 85 to 264 VAC, 80 to 370 VDC Frequency * 50/60 Hz (47 to 450 Hz) Current * 100 VAC input 2.1 A typ. 200 VAC input 1.2 A typ. Power factor --- Leakage current * 100 VAC input 0.5 mA max. 200 VAC input 1 mA max. Inrush current * (for a cold start at 25°C) 100 VAC input 14 A typ. 200 VAC input 28 A typ. Output Rated Output Current 16 A 8.5 A 7 A 4.5 A Voltage adjustment range * −10% to 15% (with V.ADJ) Ripple & Noise voltage * 100 to 240 VAC input 70 mVp-p max. 90 mVp-p max. 100 mVp-p max. 80 mVp-p max. Input variation influence * 0.5% max. Load variation influence * 1.0% max. Temperature variation influence 100 to 240 VAC input 0.05%/°C max. Startup time * 100 VAC input 1,000 ms max. 200 VAC input 1,000 ms max. Hold time * 100 VAC input 12 ms typ. 11 ms typ. 11 ms typ. 10 ms typ. 200 VAC input 70 ms typ. 55 ms typ. 55 ms typ. 55 ms typ. Additional functions Overload protection Yes, automatic reset Overvoltage protection * Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) Overheat protection No Series operation Yes (For up to two Power Supplies, external diodes are required.) Parallel operation No (However, backup operation is possible, external diodes are required.) Remote sensing No Remote control Yes (Only for models with remote control option) Output indicator Yes (LED: Green) Insulation Withstand voltage 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA Only Remote control 500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA Insulation resistance 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC Environment Ambient operating temperature −20 to 70°C (Derating is required according to the temperature. Refer to Engineering Data) (with no condensation or icing) Storage temperature −25 to 75°C (with no condensation or icing) Ambient operating humidity 90% max. (Storage humidity: 90% max.) Vibration resistance 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions Reliability MTBF 135,000 hrs min. Life expectancy * 10 years min. Construction Dimensions (W×H×D) Refer to Dimensions on page 21. Weight 400 g Cooling fan No Degree of protection --- Standards Harmonic current emissions Conforms to EN 61000-3-2 EMI * Conducted Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B Radiated Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B EMS Conforms to EN 61204-3 high severity levels Safety Standards UL 508 (Listing, excluding models with connector option or remote control option) UL 508 (Recognition, models with remote control option) UL 60950-1, UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option or remote control option) CSA C22.2 No.60950-1, No.62368-1 (excluding models with connector option or remote control option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN/IEC 60950-1, EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) Marine Standards No SEMI Conforms to F47-0706 (200 VAC input)

Note: Refer to Ratings, Characteristics, and Functions on page 11. Power rating 150 W Item Output voltage 5 V 12 V 15 V 24 V 48 V Efficiency *1 Input Voltage range * Single phase, 85 to 264 VAC, 80 to 370 VDC Frequency * 50 /60 Hz (47 to 450 Hz) Current * 100 VAC input 3 A typ. 200 VAC input 1.8 A typ. Power factor --- Leakage current * 100 VAC input 0.5 mA max. 200 VAC input 1 mA max. Inrush current * (for a cold start at 25°C) 100 VAC input 14 A typ. 200 VAC input 28 A typ. Output Rated Output Current 21 A 13 A 10 A 6.5 A 3.3 A Voltage adjustment range * −10% to 15% (with V.ADJ) Ripple & Noise voltage * Input variation influence * 0.5% max. Load variation influence * 1.0% max. Temperature variation influence 100 to 240 VAC input 0.05%/°C max. Startup time * 100 VAC input 1,000 ms max. 200 VAC input 1,000 ms max. Additional functions Overload protection Yes, automatic reset Overvoltage protection * Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) Overheat protection No Series operation Yes (For up to two Power Supplies, external diodes are required.) Parallel operation No (However, backup operation is possible, external diodes are required.) Remote sensing No Remote control Yes (Only for models with remote control option) Output indicator Yes (LED: Green) Insulation Withstand voltage 3 kVAC for 1 min.(between all input terminals and output terminals) current cutoff 20 mA 2 kVAC for 1 min.(between all input terminals and PE terminals) current cutoff 20 mA 1 kVAC for 1 min.(between all output terminals and PE terminals) current cutoff 20 mA Only Remote control 500 VAC for 1 min.(between all output terminals and RC terminals) current cutoff 20 mA Insulation resistance 100 MΩ min.(between all output terminals and all input terminals/PE terminals) at 500 VDC Environment Ambient operating temperature −20 to 70°C (Derating is required according to the temperature. Refer to Engineering Data) (with no condensation or icing) Storage temperature −25 to 75°C (with no condensation or icing) Ambient operating humidity 90% max. (Storage humidity: 90% max.) Vibration resistance 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions Reliability MTBF 135,000 hrs min. Life expectancy * 10 years min. Construction Dimensions (W×H×D) Refer to Dimensions on page 23. Weight 500 g Cooling fan No Degree of protection --- Standards Harmonic current emissions Conforms to EN 61000-3-2 (Applicable at 80% or less of the rated load.) EMI * Conducted Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B Radiated Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B EMS Conforms to EN 61204-3 high severity levels Safety Standards UL 508 (Listing, excluding models with connector option or remote control option) UL 508 (Recognition, models with remote control option) UL 60950-1, UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with connector option or remote control option) CSA C22.2 No.60950-1, No.62368-1 (excluding models with connector option or remote control option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN/IEC 60950-1, EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) Marine Standards No SEMI Conforms to F47-0706 (200 VAC input)

  • Refer to Ratings, Characteristics, and Functions on page 11. Power rating 300 W Item Output voltage 12 V 15 V 24 V 48 V Efficiency * 100 VAC input 81% typ. 81% typ. 82% typ. 82% typ. 200 VAC input 85% typ. 85% typ. 87% typ. 87% typ. 230 VAC input 85% typ. 86% typ. 87% typ. 87% typ. Input Voltage range * Single phase, 85 to 264 VAC, 120 to 370 VDC Frequency * 50/60 Hz (47 to 63 Hz) Current * 100 VAC input 4.2 A typ. 200 VAC input 2.1 A typ. Power factor 0.9 min. Leakage current * 100 VAC input 0.5 mA max. 200 VAC input 1 mA max. Inrush current * (for a cold start at 25°C) 100 VAC input 14 A typ. 200 VAC input 28 A typ. Output Rated Output Current 25 A 20 A 14 A 7 A Voltage adjustment range * −10% to 15% (with V.ADJ) Ripple & Noise voltage * 100 to 240 VAC input 140 mVp-p max. 270 mVp-p max. 150 mVp-p max. 330 mVp-p max. Input variation influence * 0.5% max. Load variation influence * 1.0% max. Temperature variation influence 100 to 240 VAC input 0.05%/°C max. Startup time * 100 VAC input 1,000 ms max. 200 VAC input 1,000 ms max. Hold time * 100 VAC input 30 ms typ. 30 ms typ. 30 ms typ. 40 ms typ. (Extended hold time type) 30 ms typ. 200 VAC input 30 ms typ. 25 ms typ. 30 ms typ. 40 ms typ. (Extended hold time type) 30 ms typ. Additional functions Overload protection Yes, automatic reset Overvoltage protection * Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) Overheat protection Yes, power shut off (shut off the input voltage and turn on the input again) Series operation Yes (For up to two Power Supplies, external diodes are required.) Parallel operation No (However, backup operation is possible, external diodes are required.) Remote sensing No Remote control Yes (Only for models with remote control option) Output indicator Yes (LED: Green) Insulation Withstand voltage 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA Only Remote control 500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA Insulation resistance 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC Environment Ambient operating temperature −20 to 70°C (Derating is required according to the temperature.) (with no condensation or icing) Storage temperature −25 to 75°C (with no condensation or icing) Ambient operating humidity 90% max. (Storage humidity: 90% max.) Vibration resistance 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions Reliability MTBF 135,000 hrs min. Life expectancy * 10 years min. Construction Dimensions (W×H×D) Refer to Dimensions on page 25 Weight 700 g Cooling fan Yes Degree of protection --- Standards Harmonic current emissions Conforms to EN 61000-3-2 EMI * Conducted Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B Radiated Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B EMS Conforms to EN 61204-3 high severity levels Safety Standards UL 508 (Listing, excluding models with remote control option) UL 508 (Recognition, models with remote control option) UL 60950-1, UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with remote control option) CSA C22.2 No.60950-1, No.62368-1 (excluding models with remote control option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN/IEC 60950-1, EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) Marine Standards No SEMI Conforms to F47-0706 (200 VAC input)
  • Refer to Ratings, Characteristics, and Functions on page 11. Power rating 600 W Item Output voltage 12 V 15 V 24 V 48 V Efficiency * 100 VAC input 84% typ. 84% typ. 85% typ. 88% typ. 200 VAC input 88% typ. 88% typ. 89% typ. 92% typ. 230 VAC input 88% typ. 88% typ. 90% typ. 92% typ. Input Voltage range * Single phase, 85 to 264 VAC, 120 to 350 VDC Frequency * 50 /60 Hz(47 to 63 Hz) Current * 100 VAC input 7.7 A typ. 200 VAC input 3.8 A typ. Power factor 0.9 min. Leakage current * 100 VAC input 0.5 mA max. 200 VAC input 1 mA max. Inrush current * (for a cold start at 25°C) 100 VAC input 14 A typ. 200 VAC input 28 A typ. Output Rated Output Current 50 A 40 A 27 A 13 A Voltage adjustment range * −10% to 15% (with V.ADJ) Ripple & Noise voltage * 100 to 240 VAC input 170 mVp-p max. 170 mVp-p max. 280 mVp-p max. 340 mVp-p max. Input variation influence * 0.5% max. Load variation influence * 1.0% max. Temperature variation influence 100 to 240 VAC input 0.05%/°C max. Startup time * 100 VAC input 1,000 ms max. 200 VAC input 1,000 ms max. Hold time * 100 VAC input 30 ms typ. 25 ms typ. 30 ms typ. 40 ms typ. (Extended hold time type) 30 ms typ. 200 VAC input 30 ms typ. 25 ms typ. 30 ms typ. 40 ms typ. (Extended hold time type) 30 ms typ. Additional functions Overload protection Yes, automatic reset Overvoltage protection * Yes, 120% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again) Overheat protection Yes, power shut off (shut off the input voltage and turn on the input again) Series operation Yes (For up to two Power Supplies, external diodes are required.) Parallel operation Yes (up to five Power Supplies, S8FS-G60024 (models with parallel operation option) only). Remote sensing No Remote control Yes (Only Remote control) Output indicator Yes (LED: Green) Insulation Withstand voltage 3 kVAC for 1 min. (between all input terminals and output terminals) current cutoff 20 mA 2 kVAC for 1 min. (between all input terminals and PE terminals) current cutoff 20 mA 1 kVAC for 1 min. (between all output terminals and PE terminals) current cutoff 20 mA Only Remote control 500 VAC for 1 min. (between all output terminals and RC terminals) current cutoff 20 mA Insulation resistance 100 MΩ min. (between all output terminals and all input terminals/PE terminals) at 500 VDC Environment Ambient operating temperature −20 to 70°C (Derating is required according to the temperature.) (with no condensation or icing) Storage temperature −25 to 75°C (with no condensation or icing) Ambient operating humidity 90% max. (Storage humidity: 90% max.) Vibration resistance 10 to 55 Hz, 4.5 G max., 0.375-mm half amplitude for 2 h each in X, Y, and Z directions Shock resistance 150 m/s2, 3 times each in ±X, ±Y, ±Z directions Reliability MTBF 135,000 hrs min. Life expectancy * 10 years min. Construction Dimensions (W×H×D) Refer to Dimensions on page 26. Weight 1,050 g Cooling fan Yes Degree of protection --- Standards Harmonic current emissions Conforms to EN 61000-3-2 EMI * Conducted Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B Radiated Emissions Conforms to EN 61204-3 Class B, EN 55011 Class B EMS Conforms to EN 61204-3 high severity levels Safety Standards UL 508 (Listing, excluding models with remote control option) UL 508 (Recognition, models with remote control option) UL 60950-1, UL 62368-1 (Recognition, OVCII [≤ 3,000 m], Pol2) CSA C22.2 No.107.1 (excluding models with remote control option) CSA C22.2 No.60950-1, No.62368-1 (excluding models with remote control option) EN 50178 (OVCIII [≤ 2,000 m], OVCII [> 2,000 m and ≤ 3,000 m], Pol2) EN/IEC 60950-1, EN/IEC 62368-1 (OVCII [≤ 3,000 m], Pol2) Conforms to EN/IEC 61558-2-16 Conforms to PELV (EN/IEC 60204-1) Marine Standards No SEMI Conforms to F47-0706 (200 VAC input)

Ratings, Characteristics, and Functions Standard Compliance

  • The input voltage range for compliance with EC Directives and other safety standards (UL, EN, etc.) is 90 to 264 VAC.
  • EN/IEC 61558-2-16 To comply with EN/IEC 60204-1 (Machine Safety), a transformer is required in the control circuit. If, however, a Power Supply that has a built- in transformer that complies with EN/IEC 6155-8-2-16 is used, an external transformer is not required.
  • Safety standard targets during a DC input * During a DC input, UL 62368-1, cUR (CSA C22.2 No. 62368-1), EN/IEC 62368-1, EN 50178, EN/IEC 61558-2-16, and EN/IEC 60204-1 are safety standard targets. (However, the input voltage range is 120 to 320 VDC. The safety standards during DC input are not acquired for the S8FS-G60048@.) It is possible to comply with the safety standards by connecting a UL-authenticated fuse. Select a UL-authenticated fuse that satisfies the following conditions: S8FS-G015@@/030@@ (320 VDC or above, 3 A) S8FS-G050@@ (320 VDC or above, 4 A) S8FS-G100@@ (320 VDC or above, 8 A) S8FS-G150@@ (320 VDC or above, 10 A) S8FS-G300@@ (320 VDC or above, 12 A) S8FS-G600@@ (320 VDC or above, 20 A)
  • To comply with the PELV output of the EN/IEC 60204-1, ground the output negative side (-V) to PE. * * Applicable to products produced from May 2018 Efficiency The value is when both rated output voltage and rated output current are satisfied. Input Voltage range Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.Frequency Current The value is when both rated output voltage and rated output current are satisfied. Leakage current The values are determined according to the Act on Power Supply Safety of Electrical Appliances and Materials. Inrush current (for a cold start at 25°C) For a cold start at 25°C. Refer to the following figure. Output Voltage adjustment range If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged. Ripple & Noise voltage The value is when both rated output voltage and rated output current are satisfied. A characteristic when the ambient operating temperature is 25°C. Input variation influence This is the maximum variation in the output voltage when the input voltage is gradually changed within the allowable input voltage range at the rated output voltage and rated output current. Load variation influence This is the value when the output current is changed from 0 A to the rated output current while the input voltage is within the allowable input voltage. Startup time The value is when both rated output voltage and rated output current are satisfied. For a cold start at 25°C. Refer to the following figure. Hold time The value is when both rated output voltage and rated output current are satisfied. At 25°C. Refer to the following figure. Additional functions Overvoltage protection Refer to Overvoltage Protection on page 18 for the time when input voltage shuts off and input turns on again. Reliability Life expectancy Refer to Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance on page 33 for details. Standards EMI Conducted Emissions The 150-W and higher models conform to Class B when an aluminum plate is set under the Power Supply.Radiated Emissions

Inrush Current, Startup Time, Output Hold Time Note: The total inrush current of all of the Power Supplies will flow for parallel operation or backup operation. Sufficiently check the fusing characteristics of fuses and the operating characteristics of breakers and select fuses and breakers so that external fuses will not burn out or breakers will not operate due to inrush current. Ripple Noise Voltage The specified standard for the ripple voltage noise was measured with a measurement circuit that is based on JEITA standard RC-9131A. 90% 96.5% Startup time AC input voltage AC input current Output voltage Inrush current on input application Input OFFInput ON Hold time 150mm S8FS-G Oscilloscope Frequency band:

100 MHz

C1:100µF C2:0.47µF Coaxial cable

250 VAC

15/30 W: 3.15 A

50 W: 4 A

AC(L) INPUT AC(N) Rectifier Smoothing circuit Rectifier smoothing circuit S8FS-G015@@@ (15 W) S8FS-G030@@@ (30 W) S8FS-G050@@@ (50 W) S8FS-G100@@@ (100 W) S8FS-G150@@@ (150 W) DC OUTPUT +RC -RC REMOTE CONTROL Only Remote control AC(L) INPUT AC(N)

100 W: 8 A

150 W: 10 A

+RC -RC REMOTE CONTROL Only Remote control Rectifier smoothing circuit Harmonic current suppression (power factor improvement) Rectifier smoothing circuit Noise filter Fuse Inrush current protection AC(L) INPUT AC(N) Rectifier Smoothing circuit Drive circuit S8FS-G300@@@ (300 W) S8FS-G600@@@ (600 W) Voltage detection circuit Photocoupler Over voltage detection circuit Over current detection circuit Current detection circuit Overheat detection circuit FAN DC OUTPUT +RC -RC REMOTE CONTROL Only Remote control ONL Y FOR PARALLEL OPERATION TYPE Rectifier smoothing circuit Harmonic current suppression (power factor improvement) Rectifier smoothing circuit Parallel operation selector Control circuit Over current detection circuit Overheat detection circuit Noise filter Fuse Inrush current protection AC(L) INPUT AC(L) Rectifier Smoothing circuit

Construction and Nomenclature Nomenclature *1. The fuse is located on the (L) side. It is not user-replaceable. For a DC input, connect the positive voltage to the L terminal. *2. This is the protective earth terminal specified in the safety standards. Always ground this terminal. Input and Output Connectors (Connector type) Note: The female connectors that are required for wiring are not provided with the Power Supply. S8FS-G015@@@ S8FS-G030@@@ S8FS-G050@@@ S8FS-G100@@@ S8FS-G150@@@ S8FS-G300@@@ S8FS-G600@@@ No. Terminal name Name Function (1) L Input terminals Connect the input lines to these terminals. *1(2) N (3) PE Protective Earth terminal () Connect the ground line to this terminal. *2 (4) +V1 DC output terminals Connect the load lines to these terminals.(5) +V2 (6) -V1 (7) -V2 (8) --- Output indicator (DC ON: green) Lights while a direct current (DC) output is ON. (9) --- Output voltage adjuster (V .ADJ) Use to adjust the voltage. (10) +RC Remote control terminals Wire for remote control.(11) -RC (12) --- Parallel operation switch To operate in parallel, set the switch to the “PARALLEL” side. Applicable connector Housing Terminals Applicable crimp tool Input side All models CN110 B3P5-VH (LF) (SN) VHR-5N Reel: SVH-21T-P1.1 Bulk: BVH-21T-P1.1 YC-160ROutput side S8FS-G01524@E S8FS-G03024@E S8FS-G05024@E CN510 B4P-VH (LF) (SN) VHR-4N S8FS-G10024@E S8FS-G15024@E B6P-VH (LF) (SN) VHR-6N (1) (2) (3) (8)(9) (4) (6) (1) (2) (3) (8) (7) (5) (9) (4) (6) (1) (2) (3) (8) (7) (5) (9) (4) (6) (9) (6) (4) (8) (1) (2) (3) (1) (2) (3) (10) (11) (8) (7) (4) (5) (9) (6) (8) (1) (2) (3) (9) (10) (11) (12) (7) (4) (5) (6)

15 W, 30 W, 50 W, 100 W, and 150 W 300 W and 600 W

Note: 1. (For customers using the unit with an AC input) At a voltage below 100 VAC, reduce the load below the range of the derating curve shown above by the solid line, at the rate of 1.3%/V.s (40°C < Ambient temperature ≤ 70°C) 2. (For customers using the unit with a DC input) At a voltage below 100 VDC, reduce the load below the range of the derating curve shown above by the dashed line, by multiplying with the coefficient 0.9. Note: At a voltage below 100 VAC, reduce the load at the rate of 1.3%/V. Parallel Operation For Models with Parallel Operation Option Note: At a voltage below 100 VAC, reduce the load at the rate of 1.3%/V.

100 VAC or above

100 VDC or above

-30 -20 -10 01 02 03 04 05 06 07 08 0 Ambient Temperature (°C) 100 120Load rate (%) 100 120 -30 -20 -10 01 02 03 04 05 06 07 08 0 Load rate (%) Ambient Temperature (°C) 100 120 -30 -20 -10 0 10 20 30 40 50 60 70 80 Load rate (%) Ambient Temperature (°C)

This Power Supply can be used at an altitude of 3,000 m. Between 2,000 and 3,000 m, derate the load according to the following derating curve.

15 W to 150 W (During an AC input) 15 W to 150 W (During a DC input)

Note: At a voltage below 100 VAC, reduce the load at the rate of 1.3%/V. (40°C < Ambient temperature ≤ 70°C) Note: At a voltage below 100 VDC, reduce the load by multiplying with the coefficient 0.9.

300 W and 600 W

Note: At a voltage below 100 VAC, reduce the load at the rate of 1.3%/V. 70% 45°C max. 50°C 60°C 70°C 0 500 1,000 1,500 2,000 2,500 3,000 3,500 100% 85% 55% 25% 120 100 Altitude (m) Load rate (%) 120 100 100% 90% 50% 70% 30% 35°C max. 40°C 50°C 60°C 70°C 0 500 1,000 1,500 2,000 2,500 3,000 3,500 Load rate (%) Altitude (m) 0 500 1,000 1,500 2,000 2,500 3,000 3,500 120 100 45°C max. 50°C 60°C 70°C 100% 70% 40% 10% Load rate (%) Altitude (m)

The load and the Power Supply are automatically protected from overcurrent damage by this function. Overload protection is activated if the output current rises above 105 to 160% of the rated current. When the output current returns within the rated range overload protection is automatically cleared. Note: 1. Internal parts may occasionally deteriorate or be damaged if a short-circuited or overcurrent state continues during operation. 2. Internal parts may possibly deteriorate or be damaged if the Power Supply is used for applications with frequent inrush current or overloading at the load end. Do not use the Power Supply for such applications. Overvoltage Protection Consider the possibility of an overvoltage and design the system so that the load will not be subjected to an excessive voltage even if the feedback circuit in the Power Supply fails. If an excessive voltage that is 120% of the rated voltage or more is output, the output voltage is shut OFF. Reset the input power by turning it OFF for at least three minutes and then turning it back ON again. Overheating Protection (300 W and 600 W) If the internal temperature of the Power Supply rises excessively as a result of fan failure or any other reason, the overheat protection circuit will be triggered to shut OFF the output voltage. To restore operation, turn OFF the input power supply long enough for the Power Supply to cool sufficiently and then turn it ON again. Remote Control Function (Only Remote control) This function is to turn ON/OFF the output by applying a voltage to the remote control connector from a DC power Supply (external power supply) other than this Power Supply. Connectors used: Note: 1. When the external power supply is 4.5 to 12.5 V, the current limiting resistor R is not required. When it is 12.5 to 24.5 V, insert 1.5 kΩ as the current limiting resistor R. 2. Reverse connection of the connector may cause damage on the internal parts. 3. The +RC and -RC terminals are the secondary circuit of the Power Supply. Use an SELV output power supply for an external power supply. The remote control circuit is insulated from the secondary output of the Power Supply (functional insulation). Reference Value 05 0 100 Output current (%) Output voltage (V) Intermittent operation Output current (%) Output voltage (V) 500 100 Built-in resistance Ri (Ω) Voltage between +RC and −RC (V) Inrush current (mA)Output ON Output OFF 780 4.5 to 12.5 0 to 0.5 20 max. CN61 Applicable connector Applicable contact Model B2B-XH-AM XHP-2 SXH-001T-P0.6 or SXH-002T-P0.6 Reliability (MTBF) Value Single phase model 15W: 970,000 30W: 970,000 50W: 880,000 100W: 730,000 150W: 620,000 300W: 200,000 600W: 190,000 Definition MTBF stands for Mean Time Between Failures, which is calculated according to the probability of accidental device failures, and indicates reliability of devices. Therefore, it does not necessarily represent a life of the product. Life expectancy 10 yrs. Min. Definition The life expectancy indicates average operating hours under the ambient temperature of 40°C and a load rate of 50%. Normally this is determined by the life expectancy of the built-in aluminum electrolytic capacitor. External power supply (SELV output) Switch R Inflowing current +RC −RC Ri Inside the power supply Remote control connector (CN61) Usage example of the remote control Note 1

Dimensions (Unit: mm) Power Supplies

15 W and 30 W

40±0.5 40.5 6.5 20.5 Five, M3.5 Two, M3 (Depth 5 mm max.) Two, M3 (Depth 3 mm max.) 82±1 35±1 55±0.5 74±0.5 88.5±0.5 87±0.5 3.5 17.5 3.5 99±1 3.5 dia. 3.5 dia. 5 (14.3) 8.29.5 S8FS-G015@@C S8FS-G030@@C Panel mounting holes dimensions Using the mounting holes in the Power Supply Using the screw holes in the Power Supply Side Mounting Bottom Mounting 88.5±0.5 40±0.5 Two, M3 55±0.5 Two, 3.5 dia. Two, M3 87±0.5 Two, 3.5 dia. 74±0.5 5 max. 32.5 117.7±1 (14.3) 8.29.5 Five, M3.5 36.2±1 49.5 3.5 (Sliding: 6.2 max.) S8FS-G015@@CD S8FS-G030@@CD 17.5 55±0.5 20.5 40±0.5 40.5 82±1 35±1 3.5 Output (-) Output (+) Input (L) Input (N) 18 74±0.5 6.5 87±0.5 Two, M3 (Depth 5 mm max.) 99±1 5 88.5±0.5 3.5 3.5 dia. 3.5 dia. Two, M3 (Depth 3 mm max.) S8FS-G015@@E S8FS-G030@@E Panel mounting holes dimensions Using the mounting holes in the Power Supply Using the screw holes in the Power Supply Side Mounting Bottom Mounting 88.5±0.5 40±0.5 Two, M3 55±0.5 Two, 3.5 dia. Two, M3 87±0.5 Two, 3.5 dia. 74±0.5

6.5 20.5 97±1 36±1 55±0.5 74±0.5 87±0.5 3.5 18.5 (14.3) 8.29.5 89±0.5 99±1 4.5 55.5±0.5 45.5 3.5 Two, M3 (Depth 3 mm max.) Two, M3 (Depth 5 mm max.) 3.5 dia. 3.5 dia. Five, M3.5 S8FS-G050@@C Panel mounting holes dimensions Using the mounting holes in the Power Supply Using the screw holes in the Power Supply Side Mounting Bottom Mounting 89±0.5 55.5±0.5 Two, M3 55±0.5 Two, 3.5 dia. 87±0.5 Two, M3 74±0.5 Two, 3.5 dia. 8.29.5 5117.7±1 (14.3) 37.2±1 49.5 47.5 5.5 (Sliding: 8.2 max.) 5 max. Five, M3.5 S8FS-G050@@CD 18.5 55±0.5 20.5 55.5±0.5 45.5 97±1 36±1 3.5 3.5 6.5 87±0.5 99±1 18 74±0.5 4.5 89±0.5 3.5 dia. 3.5 dia. Two, M3 (Depth 3 mm max.) Two, M3 (Depth 5 mm max.) Output (-) Output (+) Input (L) Input (N) S8FS-G050@@E Panel mounting holes dimensions Using the mounting holes in the Power Supply Using the screw holes in the Power Supply Side Mounting Bottom Mounting 89±0.5 55.5±0.5 Two, M3 55±0.5 Two, 3.5 dia. 87±0.5 Two, M3 74±0.5 Two, 3.5 dia.

28.5 129±1 8.2 9.5 6.5 4.5 77±0.5 3.5 5.25 3.5 13±0.5 18±0.5 38±1 120±0.5 122.5±0.5 (14.3) 28.5 33±0.5 97±1 85.5±0.5 Two, M3 (Depth 5 mm max.) Seven, M3.5 3.5 dia. 3.5 dia. Three, M3 (Depth 6 mm max.) S8FS-G100@@C Panel mounting holes dimensions Using the mounting holes in the Power Supply Using the screw holes in the Power Supply Side Mounting Bottom Mounting 122.5±0.5 85.5±0.5 Two, M3 33±0.5 Two, 3.5 dia. 120±0.5 13±0.5 Three, M3 77±0.5 9±0.5 18±0.5 Three, 3.5 dia. 8.2 9.5 48.5 48.5 147.7±1 (14.3) 39.2±1 4.5 Seven, M3.5 5 max. (Sliding: 7.2 max.) S8FS-G100@@CD

28.5 5.25 85.5±0.5 97±1 3.5 6.5 120±0.5 28.5 32 77±0.5 3.5 13±0.5 38±1 33±0.5 18±0.5 4.5 122.5±0.5 129±1 Output (-) Output (+) Input (L) Input (N) 3.5 dia. 3.5 dia. Three, M3 (Depth 6 mm max.) Two, M3 (Depth 5 mm max.) S8FS-G100@@E Panel mounting holes dimensions Using the mounting holes in the Power Supply Using the screw holes in the Power Supply Side Mounting Bottom Mounting 122.5±0.5 85.5±0.5 Two, M3 33±0.5 Two, 3.5 dia. 120±0.5 13±0.5 Three, M3 77±0.5 9±0.5 18±0.5 Three, 3.5 dia.

28.5 8.29.5 3.5 22 117±0.5 10.5 18±0.5 28.5 6.5 4.5 150±0.5 78±0.5 152.5±0.5 159±1 (14.3) 13±0.5 38±1 97±1 84.5±0.5 5.5 3.5 Three, M3 (Depth 6 mm max.) 3.5 dia. 3.5 dia. Seven, M3.5 Two, M3 (Depth 5 mm max.) S8FS-G150@@C Panel mounting holes dimensions Using the mounting holes in the Power Supply Using the screw holes in the Power Supply Side Mounting Bottom Mounting 152.5±0.5 84.5±0.5 Two, M3 78±0.5 Two, 3.5 dia. 150±0.5 13±0.5 Three, M3 117±0.5 8.5±0.5 18±0.5 Three, 3.5 dia. 177.7±1 5 8.2 9.5 (14.3) 49.1 47.9 39.2±1 3.9 (Sliding: 6.6 max.) 5 max. Seven, M3.5 S8FS-G150@@CD

28.5 5.5 84.5±0.5 97±1 3.5 4.5 152.5±0.5 159±1 3.5 13±0.5 38±118±0.5 10.5 28.5 22 117±0.5 78±0.524 6.5 150±0.5 Two, M3 (Depth 5 mm max.) Three, M3 (Depth 6 mm max.) 3.5 dia. 3.5 dia. Output (-) Output (+) Input (L) Input (N) S8FS-G150@@E Panel mounting holes dimensions Using the mounting holes in the Power Supply Using the screw holes in the Power Supply Side Mounting Bottom Mounting 152.5±0.5 84.5±0.5 Two, M3 78±0.5 Two, 3.5 dia. 150±0.5 13±0.5 Three, M3 117±0.5 8.5±0.5 18±0.5 Three, 3.5 dia.

50.5 8.29.5 64±0.528.5 102±1 170±1 74±0.5 20±0.5 41±1 (14.1) (3.5) Seven, M3.5 Two, M4 (Depth 5 mm max.) Four, M4 (Depth 5 mm max.) S8FS-G300@@C Panel mounting holes dimensions Using the screw holes in the Power Supply Side Mounting Bottom Mounting 64±0.5 Two, 4.5 dia. 74±0.5 20±0.5 Four, 4.5 dia. 8.29.5 201±1 (14.1) 48.5 53.5 42.5±1 4.8Seven, M3.5 (Sliding: 7.5 max.) 5 max. S8FS-G300@@CD Note: Use a Front-mounting Bracket (S82Y-FSG-30F) when the DIN Rail is not strong enough for your usage environment.

S8FS-G600@@C Four, M4 Four, M4 (Depth 5 mm max.) 8.29.5 (14.1) 150±0.5 150±0.5 (16.1) (3.7) 190±1 120±1 100±0.5 12.5 38±0.5 61±1 20.5 11 9.7 Four, M4 (Depth 5 mm max.) Three, M3.5 Panel mounting holes dimensions Using the screw holes in the Power Supply Side Mounting Bottom Mounting 150±0.5 100±0.5 Four, 4.5 dia. 150±0.5 38±0.5Four, 4.5 dia. S8FS-G600@@CD Four, M4 8.2 9.5 20.5 10.8 9.7 221±1 (16.1) 62.5 57.5 62.5±1 (14.1) 3.6 5 max. (Sliding: 6.3 max.) Three, M3.5 Note: Use a Front-mounting Bracket (S82Y-FSG-60F) when the DIN Rail is not strong enough for your usage environment.

Mounting Brackets (Order Separately) Use the Front-mounting Brackets together with DIN Rail-mounting Power Supplies (S8FS-G@@@@@CD). Note: Replacement brackets from the S8JX-N, S8JX-P, and S8VM series are available. Use these brackets for a front mounting configuration using direct mounting models. Refer to the data sheet (Cat. No.: T216-E1, T217-E1, and T218-E1) for more information. Terminal cover (Order Separately) Note: A Terminal Block Cover is provided with the Power Supply as a standard accessory. You can purchase another one if your Cover is damaged or lost. Power rating Mounting direction Model

15 W, 30 W, 50 W

100 W, 150 W and 300 W Front-mounting S82Y-FSG-30F

600 W Front-mounting S82Y-FSG-60F

Power rating Applicable models Terminal Cover model number

15 W S8FS-G015@@@

S82Y-FSG-C5P30 W S8FS-G030@@@

50 W S8FS-G050@@@

100 W S8FS-G100@@@

S82Y-FSG-C7P150 W S8FS-G150@@@

300 W S8FS-G300@@@

600 W S8FS-G600@@@ S82Y-FSG-C7P-L (Input Output)

7.3 (ends) (R1.5) t=1.2 Two, 4.5±0.1 dia 4035 35±0.1 (ends) S82Y-FSG-60F 7.3 (ends) Two, 4.5 ±0.1 dia (R1.5) 4035 35±0.1 (ends) t=1.2

DIN Rail (Order Separately) (Unit: mm) Mounting Rail (Material: Aluminum) PFP-100N PFP-50N Mounting Rail (Material: Aluminum) PFP-100N2 End Plate PFP-M Note: If there is a possibility that the Unit will be subject to vibration or shock, use a steel DIN Rail. Otherwise, metallic filings may result from aluminum abrasion. 4.5 15 25 25 10 10 1,000 (500) * 25 25 15(5) * 35±0.3 7.3±0.15 27±0.15 * Values in parentheses are for the PFP-50N. 4.5 15 25 25 10 10 1,000 25 25 15 1 1.5 29.224 27 35±0.3 1.3 4.8 35.5 35.5 1.8 1.8 6.2 11.5 M4 spring washer M4×8 pan- head screw

Refer to Safety Precautions for All Power Supplies. Warning Indications Meaning of Product Safety Symbols !CAUTION Minor electric shock, fire, or Product failure may occasionally occur. Do not disassemble, modify, or repair the Product or touch the interior of the Product. Minor burns may occasionally occur. Do not touch the Product while power is being supplied or immediately after power is turned OFF. Fire may occasionally occur. Tighten terminal screws to the specified torque. M3.5: 0.74 to 1.13N M4: 1.08 to 1.32N ·m Minor injury due to electric shock may occasionally occur. Do not touch the terminals while power is being supplied. Minor electric shock, fire, or Product failure may occasionally occur. Do not allow any pieces of metal or conductors or any clippings or cuttings resulting from installation work to enter the Product. Ambient Operating and Storage Environments

  • Store the Power Supply at a temperature of −25 to 75°C and a humidity of 90% max.
  • The internal parts may occasionally deteriorate or be damaged. Use the Power Supply within the derating curve.
  • Use the Power Supply at a humidity of 90% max.
  • Do not use locations where liquids, foreign matter, or corrosive gases may enter the interior of the Power supplies. Installation Environment
  • Do not use the Power Supply in locations subject to shocks or vibrations. In particular, install the Power Supply as far away as possible from contractors or other devices that are a vibration source.
  • Install the Power Supply well away from any sources of strong, high-frequency noise and surge. Mounting
  • Take adequate measures to ensure proper heat dissipation to increase the long-term reliability of the Power Supply. Be sure to allow convection in the atmosphere around devices when mounting. Do not use in locations where the ambient temperature exceeds the range of the derating curve. The S8FS-G015@@@ to S8FS-G150@@@ are cooled by natural convection. Mount them so that air convection will occur around them. The S8FS-G300@@@ and S8FS-G600@@@ are cooled by forced airflow. Do not allow the ventilation holes to be blocked. The effectiveness of cooling would be reduced.
  • When cutting out holes for mounting, make sure that cuttings do not enter the interior of the Power supplies.
  • The internal parts may occasionally deteriorate and be broken due to adverse heat radiation. Do not loosen the screws on the Power Supply.
  • If you mount the Power Supply with the holes provided on the chassis, do not exceed the depth given in the dimensional diagrams. Use the following tightening torques. M3 screws: 0.48 to 0.59 N M4 screws: 1.08 to 1.32 N·m CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or in property damage. Precautions for Safe Use Supplementary comments on what to do or avoid doing, to use the product safely. Precautions for Correct Use Supplementary comments on what to do or avoid doing, to prevent failure to operate, malfunction or undesirable effect on product performance. Used to warn of the risk of electric shock under specific conditions. Used to warn of the risk of minor injury caused by high temperatures. Use to indicate prohibition when there is a risk of minor injury from electrical shock or other source if the product is disassembled. Used for general mandatory action precautions for which there is no specified symbol. Precautions for Safe Use

<Standard mounting> Note: Use a metal plate as the mounting surface. *1. Convection of air. *2. 20 mm min. <Other mounting types> *2 *1. 20 mm min. *2. Applicable to products produced from May 2018 <DIN Rail Mounting> To mount the Power Supply to a DIN Rail, hook portion (A) of the Power Supply onto the DIN Rail and press the Power Supply in direction (B) until you hear it lock into place. To dismount the Block, pull down portion (C) with a flat-blade screwdriver and pull out the Block. Wiring

  • Connect the ground completely. A protective earthing terminal stipulated in safety standards is used. Electric shock or malfunction may occur if the ground is not connected completely.
  • Minor fire may possibly occur. Ensure that input and output terminals are wired correctly.
  • Do not apply more than 150-N force to the terminal block when tightening it.
  • Be sure to remove the sheet covering the Power Supply for machining before power-ON so that it does not interfere with heat dissipation.
  • Use the following material for the wires to be connected to the S8FS-G to prevent smoking or ignition caused by abnormal loads. Terminals and Wiring (Screw terminal block type) Note: The current capacity per output terminal is given in the following table. S8FS-G015@@@ to S8FS-G300@@@: 20 A S8FS-G600@@@: 30 A Use two terminals together if the current flow is higher than the rated terminal current. Terminals and Wiring (Connector type) Note: 1. The current capacity per output terminal is 5 A. Use two or more terminals together if the current flow is higher than the rated terminal current. 2. Do not insert and remove any connector more than 20 times. 3. Refer to Input and Output Connectors on page 15 for the model numbers of the input and output connectors. 20 mm min. 20 mm min. 20 mm min. 20 mm min. Bottom mounting Side (horizontal orientation) mounting 20 mm min. 20 mm min. 20 mm min. 20 mm min. Ventilation holes Ventilation holes 30 mm min.30 mm min. 30 mm min.30 mm min. Bottom mounting Side (horizontal orientation) mounting *1*2 DIN rail mounting Side (vertical orientation) mounting Side (upward) mounting Bottom (upward) mounting *1 *1 *1 *1 Rail stopper (C) (A) (B) Terminals Model Recommendes Wire Gauges Input S8FS-G015@@@ AWG12-22 S8FS-G030@@@ to 100@@@ AWG12-20 S8FS-G150@@@ to 600@@@ AWG12-16 Output S8FS-G01512@ to 01524@ AWG12-22S8FS-G03024@ S8FS-G01505@ AWG12-20S8FS-G03012@, 03015@ S8FS-G05015@, 05024@ S8FS-G15048@ S8FS-G05012@ AWG12-18S8FS-G10024@ S8FS-G03005@ AWG12-16S8FS-G10015@ S8FS-G15024@ S8FS-G30048@ S8FS-G05005@ AWG12-14S8FS-G10012@ S8FS-G15015@ S8FS-G10005@ AWG12S8FS-G15005@, 15012@ S8FS-G30012@ to 30024@ S8FS-G60015@ to 60048@ AWG10-12 S8FS-G60012@ AWG10 Protective earth terminal S8FS-G015@@@ to 600@@@ AWG12-14 Terminals Model Recommendes Wire Gauges Input S8FS-G01524 @E to 15024@EA W G 1 8 Output S8FS-G01524 @E to 15024@EA W G 1 8
  • Internal parts may possibly deteriorate or be damaged if a short- circuited, overload, or boost load state continues during operation.
  • Internal parts may possibly deteriorate or be damaged if the Power Supply is used for applications with frequent inrush current or overloading at the load end. Do not use the Power Supply for such applications. Output Voltage Adjuster (V. ADJ)
  • The output voltage adjuster (V. ADJ) may possibly be damaged if it is turned with unnecessary force. Do not turn the adjuster with excessive force.
  • After completing output voltage adjustment, be sure that the output capacity or output current does not exceed the rated output capacity or rated output current. Series Operation Two Power Supplies can be connected in series operation. Note: 1. The diode is connected as shown in the figure. If the load is short-circuited, a reverse voltage will be generated inside the Power Supply. If this occurs the Power Supply may possibly deteriorate or be damaged. Always connect a diode as shown in the figure. Select a diode having the following ratings. 2. Although Power Supply having different specifications can be connected in series, the current flowing through connected in series, the current flowing through the load must not exceed the smaller rated output current. <Making Positive/Negative Outputs>
  • The outputs are floating outputs (i.e., the primary circuits and secondary circuits are separated). You can therefore make positive/negative outputs by using two Power Supplies. You can make positive/negative outputs with any of the models. If you use positive/negative outputs, connect two Power Supplies of the same model as shown below. You can combine models with different output capacities and output voltages. However, use the lower of the two rated rated output currents as the current to the loads.
  • Depending on the model, internal circuits may be damaged due to startup failure when the power is turned ON if loads such as a servomotor or operational amplifier may operate in series. Therefore, connect bypass diodes (D1, D2) as shown in the following figure. If the list of models that support series connection of outputs says that an external diode is not required, an external diode is also not required for positive/negative outputs.
  • Use the following information as a guide to the diode type, dialectic strength, and current. Parallel Operation Parallel operation is used when the output current from one Power Supply is insufficient for the load. Power Supplies are connected in parallel to increase the output current. Parallel operation is not possible. Up to five Power Supplies can be connected in parallel operation. You must meet the following conditions to use parallel operation.
  • The internal parts may occasionally deteriorate or be damaged. To operate in parallel, set the switch to the "PARALLEL" side.
  • For parallel operation, always use Power Supplies with the same model number.
  • Use the output voltage adjusters (V. ADJ) to adjust the difference in the output voltages to 50 mV or less between Power Supplies that are used in parallel operation.
  • The length and thickness of each wire connected to the load must be the same so that there is no difference in the voltage drop value between the load and the output terminals of each Power Supply.
  • Drastic fluctuations in the load (including fluctuations that occur when starting and starting the load) may reduce the output voltage. If fluctuations in the output voltage that result from drastic fluctuations in the load would be a problem, connect external diodes as shown in the following diagram.
  • Use the following information as a guide to the diode type, dialectic strength, and current. Type Schottky Barrier diode Dielectric strength (VRRM) Twice the output voltage or above Forward current (IF) Twice the rated output current or above INPUT INPUT Load INPUT INPUT LoadLoad INPUT INPUT LoadLoad Load Type Schottky Barrier diode Dielectric strength (VRRM) Twice the output voltage or above Forward current (IF) Twice the rated output current or above Power Supplies without the Parallel Operation Option S8FS-G60024@-W@ (Models with the Parallel Operation Option) Type Schottky Barrier diode Dielectric strength (VRRM) Twice the output voltage or above Forward current (IF) Twice the rated output current or above INPUT INPUT S8FS-G S8FS-G Load LoadINPUT INPUT

Backup operation is possible if you use two Power Supplies of the same model. Even if one Power Supplies fails, operation can be continued with the other Power Supply. Make sure that the maximum load does not exceed the capacity of one Power Supply. Connect the S8VK-R or external diodes as shown in the following figure for backup operation. Refer to the S8VK-R datasheet (Cat. No.: T059) for information on using the S8VK-R. Use the following information as a guide to the diode type, dialectic strength, and current. In Case There Is No Output Voltage There is a possibility that overload protection, overvoltage protection, or overheating protection are functioning. The internal protection may operate if a large amount of surge voltage, such as a lightning inrush, is applied to the input. In addition, other possible causes for some models include stoppage of the built-in fan and the remote control function (OFF). Check the following five points. If there is still no output voltage, contact your OMRON representative.

  • Checking Overload Protection: Remove the load wires and check whether the load is in an overload state or is short-circuited.
  • Checking Overvoltage or Internal Protection: Turn the power supply OFF, leave it OFF for at least three minutes, and then turn it ON again to see if this clears the condition.
  • Checking Overheating Protection (300 W/600 W): Turn OFF the input power supply long enough for the Power Supply to cool sufficiently and then turn it ON again.
  • Checking for Built-in Fan Stoppage (300 W/600 W): Check whether or not the built-in fan has stopped.
  • Confirming Remote Control Operation (Power Supplies with Remote Control): Check whether or not the +RC and -RC terminals are open. Connect the terminals as specified. Charging a Battery If you connect a battery as the load, install overcurrent control and overvoltage protection circuits. Built-in Fan Replacement The built-in fan cannot be replaced. Audible Noise at Power ON A harmonic current suppression circuit is built into the Power Supply. This circuit can create noise when the input is turned ON, but it will last only until the internal circuits stabilize and does not indicate any problem in the Power Supply. Type Schottky Barrier diode Dielectric strength (VRRM) Twice the output voltage or above Forward current (IF) Twice the rated output current or above INPUT S8FS-G S8VK-R S8FS-G INPUT IN 1 IN 2 INPUT INPUT S8FS-G S8FS-G Load Load

Period and Terms of Warranty Warranty Period The Power Supply warranty is valid for a period of five years from the date of shipment from the factory. Terms of Warranty The warranty is valid only for the following operating conditions. 1. Average ambient operating temperature of the Power Supply: 40°C max. (See note.) 2. Average load rate of 80% max. (See note.) 3. Mounting method: Standard mounting 4. Rated input voltage Note: The maximum ratings must be within the derating curve. If the Power Supply fails for reasons attributable to OMRON within the above warranty period, OMRON will repair or replace the faulty part of the Power Supply at the place of purchase or the place where the Power Supply delivered without charge. This warranty does not cover the following types of failures. Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance The recommended replacement period for preventive maintenance is greatly influenced by the application environment of the Power Supply. As a guideline, the recommended replacement period is 7 to 10 years.* To prevent failures or accidents that can be caused by using a Power Supply beyond its service live, we recommend that you replace the Power Supply as early as possible within the recommended replacement period. However, bear in mind that the recommended replacement period is for reference only and does not guarantee the life of the Power Supply. Many electronic components are used in the Power Supply and the Power Supply depends on the correct operation of these components to achieve the original Power Supply functions and performance. However, the influence of the ambient temperature on aluminum electrolytic capacitors is large, and the service life is reduced by half for each 10°C rise in temperature (Arrhenius law). When the capacity reduction life of the electrolytic capacitor is reached, the Power Supply failures or accidents may occur. We therefore recommend that you replace the Power Supply periodically to minimize product failures or accidents in advance. * The recommended replacement period applies under the following conditions: rated input voltage, load rate of 50% max., ambient temperatur e of 40°C max., and the standard mounting method. This Power Supply model is designed with a service life of 10 years minimum under the above conditions. (1) Failures that result from handling or operation of the Power Supply under conditions or in environments that are not given in this document and not given in any other specifications exchanged between OMRON and the customer (2) Failures that originate in causes other than the delivered product itself (3) Failures caused by disassembly, modification, or repair of the Power Supply by anyone other than OMRON (4) Failures caused by applications or uses for which the Power Supply was not originally intended (5) Failures caused by factors that could not be anticipated with the scientific or technical knowledge available when the Power Supply was shipped (6) Failures caused by other causes for which OMRON is not responsible, such as natural disasters and other acts of God This warranty is limited to the individual Power Supply that was delivered and does not cover any secondary, subsequent, or related damages.

OMRON CANADA, INC. • HEAD OFFICE OMRON ELECTRONICS DE MEXICO • HEAD OFFICE OMRON ELECTRONICS DE MEXICO • SALES OFFICE com OMRON ELECTRONICS DE MEXICO • SALES OFFICE Eugenio Garza Sada,León, Gto • 01.800.386.6766 • mela@omron.com OMRON ELETRÔNICA DO BRASIL L TDA • HEAD OFFICE São Paulo, SP , Brasil • 55 11 5171-8920 • automation.omron.com OMRON ARGENTINA • SALES OFFICE mela@omron.com OTHER OMRON LATIN AMERICA SALES Authorized Distributor: Printed on recycled paper. Controllers & I/O

  • Machine Automation Controllers (MAC) • Motion Controllers
  • Programmable Logic Controllers (PLC) • Temperature Controllers • Remote I/O Robotics
  • Industrial Robots • Mobile Robots Operator Interfaces
  • Human Machine Interface (HMI) Motion & Drives
  • Machine Automation Controllers (MAC) • Motion Controllers • Servo Systems
  • Frequency Inverters Vision, Measurement & Identification
  • Vision Sensors & Systems • Measurement Sensors • Auto Identification Systems Sensing
  • Photoelectric Sensors • Fiber-Optic Sensors • Proximity Sensors
  • Rotary Encoders • Ultrasonic Sensors Safety
  • Safety Light Curtains • Safety Laser Scanners • Programmable Safety Systems
  • Safety Mats and Edges • Safety Door Switches • Emergency Stop Devices
  • Safety Switches & Operator Controls • Safety Monitoring/Force-guided Relays Control Components
  • Power Supplies • Timers • Counters • Programmable Relays
  • Digital Panel Meters • Monitoring Products Switches & Relays
  • Limit Switches • Pushbutton Switches • Electromechanical Relays
  • Solid State Relays Software
  • Programming & Configuration • Runtime