S803C-C125 ABB | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 4
Technical content
S803C-C125 High Performance MCB S803C-C125 Extended Product Type S803C-C125 Product ID 2CCS883001R0844 EAN 5413656710875 Catalog Description S803C-C125 High Performance MCB Long Description The S803C-C125 is a 3-pole High Performance Circuit breaker with C-characteristic, with cage terminal and a rated current of 125 A. It is a current limiting device with a maximum breaking capacity of 25kA at 240/415V. It can be used for voltages up to 254/440V and in DC as well. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S803C-C125 complies with IEC/EN 60898- 1 and IEC/EN 60947-2 and allows the use for industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S803C-C125 more comfortable. Due to the fast arc extinction of S803C-C125 your application will be secured. General Information PRODUCT-DETAILS Technical IEC/EN 60947-2 IEC/EN 60898-1 Standards Number of Poles Number of Protected Poles C Tripping Characteristic 125 A Rated Current (I n 254/440 V AC
375 V DC
at Rated Operating Conditions per Pole 9.4 W Power Loss
500 V AC
i Maximum 230/400 V AC Minimum 12 V AC Operational Voltage 50...60 Hz Rated Frequency (f) (230 / 400 V AC) 15 kA Rated Short-Circuit Capacity (I cn (240 / 415 V AC) 25 kA (254 / 440 V AC) 15 kA (375 V DC) 10 kA Rated Ultimate Short- Circuit Breaking Capacity (I cu (240 / 415 V AC) 18 kA (254 / 440 V AC) 10 kA (375 V DC) 10 kA Rated Service Short- Circuit Breaking Capacity (I cs Energy Limiting Class IV Overvoltage Category Pollution Degree 8 kV Rated Impulse Withstand Voltage (U imp Insulation group I, RAL 7035 Housing Material I / O Actuator Marking ON / OFF / TRIP Contact Position Indication IP20 Degree of Protection Connection from top and bottom Connecting with CU only IP40 in enclosure with cover Cage terminal with captive screw Remarks 4000 cycle Electrical Endurance 6000 cycle Screw Terminals Terminal Type Stranded 1 ... 50 mm² Flexible 1 ... 70 mm² Connecting Capacity
3.5 N·m
31 in·lb Tightening Torque Pozidriv 2 Recommended Screw Driver TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 Mounting on DIN Rail Any Mounting Position 82.5 mm Built-In Depth ( t Environmental Operation -25...60 °C Ambient Air Temperature acc. to IEC60947-2 30 °C acc. to EN60898-1 30 °C Reference Ambient Air Temperature 5 g 30 ms Resistance to Shock acc. to IEC 60068-2-27 2 - 13.2 Hz / 1mm 13.2 - 100Hz / 0.7g with load 100% x Ie Resistance to Vibrations acc. to IEC 60068-2-6 Damp Heat Cyclic acc. to IEC 60068-2-30 12+12 cycle Damp Heat Cyclic acc. to IEC 60068-2-30 55°C @ 90-96% Damp Heat Cyclic acc. to IEC 60068-2-30 25°C @ 90-100% Dry Heat Test B acc. to IEC 60068-2-2 16 hour @ 55 °C Dry Heat Test B acc. to IEC 60068-2-2 2 hour @ 70 °C Environmental Conditions Following EU Directive 2011/65/EU RoHS Status Dimensions 81 mm Product Net Width 82.5 mm Product Net Depth / Length S803C-C125
Certificates and Declarations (Document Number) 2CCC413016D0601 Declaration of Conformity - CE 2CCY413207D0203 Environmental Information 2CCC413016M0008 Instructions and Manuals 2CCC413008D0206 RoHS Information Popular Downloads 2CCC413003C0208 Data Sheet, Technical Information 2CCC413016M0008 Instructions and Manuals 2CCC413003C0201 Dimension Diagram Classifications F Object Classification Code EC000042 - Miniature circuit breaker (MCB) ETIM 6 EC000042 - Miniature circuit breaker (MCB) ETIM 7 Low Voltage Products and Systems Modular DIN Rail Products High Performance Circuit Breakers HPCBs Categories S803C-C125