Features

S200U-K, 240 V AC S200U-Z, 240 V AC S200UP-K, 480Y/277 V AC S200UP-Z, 480Y/277 V AC SU200PR-K, 480Y/277 V AC S200UDC-K, 1 pole 60 VDC, 2 pole 125 VDC S200UDC-Z, 1 pole 60 VDC, 2 pole 125 VDC Accessories T echnical data Dimensions UL 1077 Series Or dering details Description & featur es S200-B, 480Y/277 V AC S200-C, 480Y/277 V AC S200-D, 480Y/277 V AC S200-K, 480Y/277 V AC S200-Z, 480Y/277 V AC S200P-B, 480Y/277 V AC S200P-C, 480Y/277 V AC S200P-D, 480Y/277 V AC S200P-K, 480Y/277 V AC S200P-Z, 480Y/277 V AC S200PR-K, 240 V AC, Ring tongue S280UC-K, 500 VDC S280UC-Z, 500 VDC Accessories T echnical data Dimensions Cir Circuit breaker current limitation Selective coordination and series ratings Miniature circuit breaker cutaway UL 489 Series Or dering details Description & featur es S800U-K, 240 V AC S800U-Z, 240 V AC S803W-SCL-SR UL Short cir cuit current limiter IEC Series Or dering details Description & featur es S800S-B, 690 V AC S800S-C, 690 V AC S800S-D, 690 V AC S800S-K, 690 V AC UL & IEC Series Accessories T echnical data Dimensions Or dering details Description & featur es S500-K, UL 600Y/277 V AC / IEC 690 VAC S500UC-B, 250 VDC per pole (600 VDC 4P) S500UC-K, 250 VDC per pole (600 VDC 4P) Accessories T echnical data Dimensions 15 - Miniature circuit breakers

15.B Low Voltage Products & Systems 1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www .abb.us/lowvoltage Miniature circuit breakers 15 15 Notes

Low Voltage Products & Systems 15.1 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A S200 UL 489 Series

Description

The S200 Series miniature circuit breaker offers a compact solution for protection requirements. The S200U AND S200UP devices are UL 489 tested current limiting and DIN rail mounted. The S200U and S200UP is available with application-specific trip characteristics to provide maximum circuit protection. The breakers offer thermal-magnetic trip protection according to K and Z characteristics. For the worldwide market, the breakers carry UL, CSA, IEC, CE and many other agency approvals and certifications.

  • UL current limiting
  • Fast breaking time (2.3 – 2.5 ms)
  • Bus connection system
  • Wide range of accessories
  • Available with variable depth handle mechanism
  • CE certified and marked
  • DIN rail mounting
  • Finger safe terminals
  • Multi-function terminals
  • Suitable for reverse feed but S200UDC has polarity
  • UL 489 Listed - branch circuit protective device. UL File #E212323 S200U S200UP SU200PR S200UDC Amperage 0.2 – 63 0.2 – 25 0.2 – 35A ; 40 – 63A 1 – 63 Voltage 240 VAC 480Y/277VAC 480Y/277 VAC ; 240 VAC 60-125 VDC Poles 1, 2, 3, 4 1, 2, 3, 4 1, 2, 3, 4 1, 2 Trip characteristics K, Z K, Z K K, Z Interrupting ratings Up to 25 kA : IEC 60947-2 10 kA : UL 489 10 kA : CSA 22.2 No. 5 Up to 25 kA : IEC 60947-2 10 kA : UL 489 10 kA : CSA 22.2 No. 5 10kA: UL489 10kA: CSA 22.2 No.5 14 kA : UL489 14 kA: CSA 22.2 No. 5 Auxiliary contacts Yes Yes Yes Yes Bell alarm Yes Yes Yes Yes Shunt trip Yes Yes Yes Yes Bus bar Yes Yes No Yes S200 UL 489 Series Miniature circuit breakers

15.2 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 K No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.2 S201U-K0.2 0.2 S203U-K0.2 0.3 S201U-K0.3 0.3 S203U-K0.3 0.5 S201U-K0.5 0.5 S203U-K0.5 0.75 S201U-K0.75 0.75 S203U-K0.75

1 S201U-K1 1 S203U-K1

1.6 S201U-K1.6 1.6 S203U-K1.6

2 S201U-K2 2 S203U-K2

3 S201U-K3 3 S203U-K3

4 S201U-K4 4 S203U-K4

5 S201U-K5 5 S203U-K5

6 S201U-K6 6 S203U-K6

8 S201U-K8 8 S203U-K8

10 S201U-K10 10 S203U-K10

15 S201U-K15 15 S203U-K15

16 S201U-K16 16 S203U-K16

20 S201U-K20 20 S203U-K20

25 S201U-K25 25 S203U-K25

30 S201U-K30 30 S203U-K30

32 S201U-K32 32 S203U-K32

40 S201U-K40 40 S203U-K40

50 S201U-K50 50 S203U-K50

60 S201U-K60 60 S203U-K60

63 S201U-K63 63 S203U-K63

0.2 S202U-K0.2 0.2 S204U-K0.2 0.3 S202U-K0.3 0.3 S204U-K0.3 0.5 S202U-K0.5 0.5 S204U-K0.5 0.75 S202U-K0.75 0.75 S204U-K0.75

1 S202U-K1 1 S204U-K1

1.6 S202U-K1.6 1.6 S204U-K1.6

2 S202U-K2 2 S204U-K2

3 S202U-K3 3 S204U-K3

4 S202U-K4 4 S204U-K4

5 S202U-K5 5 S204U-K5

6 S202U-K6 6 S204U-K6

8 S202U-K8 8 S204U-K8

10 S202U-K10 10 S204U-K10

15 S202U-K15 15 S204U-K15

16 S202U-K16 16 S204U-K16

20 S202U-K20 20 S204U-K20

25 S202U-K25 25 S204U-K25

30 S202U-K30 30 S204U-K30

32 S202U-K32 32 S204U-K32

40 S202U-K40 40 S204U-K40

50 S202U-K50 50 S204U-K50

60 S202U-K60 60 S204U-K60

63 S202U-K63 63 S204U-K63

240 VAC

  • K Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.9 - 15.13 Technical data – See page 15.14 -15.16 S200U-K, 240 VAC Branch circuit protection UL 489, CSA 22.2 No. 5 Note: This breaker for AC use only

Low Voltage Products & Systems 15.3 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Z No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.5 S201U-Z0.5 0.5 S203U-Z0.5

1 S201U-Z1 1 S203U-Z1

1.6 S201U-Z1.6 1.6 S203U-Z1.6

2 S201U-Z2 2 S203U-Z2

3 S201U-Z3 3 S203U-Z3

4 S201U-Z4 4 S203U-Z4

5 S201U-Z5 5 S203U-Z5

6 S201U-Z6 6 S203U-Z6

8 S201U-Z8 8 S203U-Z8

10 S201U-Z10 10 S203U-Z10

15 S201U-Z15 15 S203U-Z15

16 S201U-Z16 16 S203U-Z16

20 S201U-Z20 20 S203U-Z20

25 S201U-Z25 25 S203U-Z25

30 S201U-Z30 30 S203U-Z30

32 S201U-Z32 32 S203U-Z32

40 S201U-Z40 40 S203U-Z40

50 S201U-Z50 50 S203U-Z50

60 S201U-Z60 60 S203U-Z60

63 S201U-Z63 63 S203U-Z63

0.5 S202U-Z0.5 0.5 S204U-Z0.5

1 S202U-Z1 1 S204U-Z1

1.6 S202U-Z1.6 1.6 S204U-Z1.6

2 S202U-Z2 2 S204U-Z2

3 S202U-Z3 3 S204U-Z3

4 S202U-Z4 4 S204U-Z4

5 S202U-Z5 5 S204U-Z5

6 S202U-Z6 6 S204U-Z6

8 S202U-Z8 8 S204U-Z8

10 S202U-Z10 10 S204U-Z10

15 S202U-Z15 15 S204U-Z15

16 S202U-Z16 16 S204U-Z16

20 S202U-Z20 20 S204U-Z20

25 S202U-Z25 25 S204U-Z25

30 S202U-Z30 30 S204U-Z30

32 S202U-Z32 32 S204U-Z32

40 S202U-Z40 40 S204U-Z40

50 S202U-Z50 50 S204U-Z50

60 S202U-Z60 60 S204U-Z60

63 S202U-Z63 63 S204U-Z63

S200U-Z, 240 VAC Branch circuit protection UL 489, CSA 22.2 No. 5 Tripping characteristic Z UL 489

  • Z Curve
  • Designed to provide maximum protection with a very low short circuit trip setting
  • Example: semiconductors, control circuits Accessories & technical data Accessories – See page 15.9 - 15.13 Technical data – See page 15.14 -15.16 Note: This breaker for AC use only

15.4 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 K No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.2 S201UP-K0.2 0.2 S203UP-K0.2 0.3 S201UP-K0.3 0.3 S203UP-K0.3 0.5 S201UP-K0.5 0.5 S203UP-K0.5 0.75 S201UP-K0.75 0.75 S203UP-K0.75

1 S201UP-K1 1 S203UP-K1

1.6 S201UP-K1.6 1.6 S203UP-K1.6

2 S201UP-K2 2 S203UP-K2

3 S201UP-K3 3 S203UP-K3

4 S201UP-K4 4 S203UP-K4

5 S201UP-K5 5 S203UP-K5

6 S201UP-K6 6 S203UP-K6

8 S201UP-K8 8 S203UP-K8

10 S201UP-K10 10 S203UP-K10

15 S201UP-K15 15 S203UP-K15

16 S201UP-K16 16 S203UP-K16

20 S201UP-K20 20 S203UP-K20

25 S201UP-K25 25 S203UP-K25

0.2 S202UP-K0.2 0.2 S204UP-K0.2 0.3 S202UP-K0.3 0.3 S204UP-K0.3 0.5 S202UP-K0.5 0.5 S204UP-K0.5 0.75 S202UP-K0.75 0.75 S204UP-K0.75

1 S202UP-K1 1 S204UP-K1

1.6 S202UP-K1.6 1.6 S204UP-K1.6

2 S202UP-K2 2 S204UP-K2

3 S202UP-K3 3 S204UP-K3

4 S202UP-K4 4 S204UP-K4

5 S202UP-K5 5 S204UP-K5

6 S202UP-K6 6 S204UP-K6

8 S202UP-K8 8 S204UP-K8

10 S202UP-K10 10 S204UP-K10

15 S202UP-K15 15 S204UP-K15

16 S202UP-K16 16 S204UP-K16

20 S202UP-K20 20 S204UP-K20

25 S202UP-K25 25 S204UP-K25

S200UP-K, 480Y/277 VAC Branch circuit protection UL 489, CSA 22.2 No. 5 Tripping characteristic K UL 489 480Y/277 VAC 10 kA Inductive loads

  • K Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.9 - 15.13 Technical data – See page 15.14 -15.16 Note: This breaker for AC use only

Low Voltage Products & Systems 15.5 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Z No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.5 S201UP-Z0.5 0.5 S203UP-Z0.5

1 S201UP-Z1 1 S203UP-Z1

1.6 S201UP-Z1.6 1.6 S203UP-Z1.6

2 S201UP-Z2 2 S203UP-Z2

3 S201UP-Z3 3 S203UP-Z3

4 S201UP-Z4 4 S203UP-Z4

5 S201UP-Z5 5 S203UP-Z5

6 S201UP-Z6 6 S203UP-Z6

8 S201UP-Z8 8 S203UP-Z8

10 S201UP-Z10 10 S203UP-Z10

15 S201UP-Z15 15 S203UP-Z15

16 S201UP-Z16 16 S203UP-Z16

20 S201UP-Z20 20 S203UP-Z20

25 S201UP-Z25 25 S203UP-Z25

0.5 S202UP-Z0.5 0.5 S204UP-Z0.5

1 S202UP-Z1 1 S204UP-Z1

1.6 S202UP-Z1.6 1.6 S204UP-Z1.6

2 S202UP-Z2 2 S204UP-Z2

3 S202UP-Z3 3 S204UP-Z3

4 S202UP-Z4 4 S204UP-Z4

5 S202UP-Z5 5 S204UP-Z5

6 S202UP-Z6 6 S204UP-Z6

8 S202UP-Z8 8 S204UP-Z8

10 S202UP-Z10 10 S204UP-Z10

15 S202UP-Z15 15 S204UP-Z15

16 S202UP-Z16 16 S204UP-Z16

20 S202UP-Z20 20 S204UP-Z20

25 S202UP-Z25 25 S204UP-Z25

S200UP-Z, 480Y/277 VAC Branch circuit protection UL 489, CSA 22.2 No. 5 Tripping characteristic Z UL 489 480Y/277 VAC 10 kA Resistive loads

  • Z Curve
  • Designed to provide maximum protection with a very low short circuit trip setting
  • Example: semiconductors, control circuits Accessories & technical data Accessories – See page 15.9 - 15.13 Technical data – See page 15.14 -15.16 Note: This breaker for AC use only

15.6 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 SU200PR-K, 480Y/277 VAC, Ring tongue Branch circuit protection UL489, CSA 22.2 No.5 K No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.2 SU201PR-K0.2 0.2 SU203PR-K0.2 0.3 SU201PR-K0.3 0.3 SU203PR-K0.3 0.5 SU201PR-K0.5 0.5 SU203PR-K0.5 0.75 SU201PR-K0.75 0.75 SU203PR-K0.75

1 SU201PR-K1 1 SU203PR-K1

1.6 SU201PR-K1.6 1.6 SU203PR-K1.6

2 SU201PR-K2 2 SU203PR-K2

3 SU201PR-K3 3 SU203PR-K3

4 SU201PR-K4 4 SU203PR-K4

5 SU201PR-K5 5 SU203PR-K5

6 SU201PR-K6 6 SU203PR-K6

8 SU201PR-K8 8 SU203PR-K8

10 SU201PR-K10 10 SU203PR-K10

13 SU201PR-K13 13 SU203PR-K13

15 SU201PR-K15 15 SU203PR-K15

16 SU201PR-K16 16 SU203PR-K16

20 SU201PR-K20 20 SU203PR-K20

25 SU201PR-K25 25 SU203PR-K25

30 SU201PR-K30 30 SU203PR-K30

32 SU201PR-K32 32 SU203PR-K32

35 SU201PR-K35 35 SU203PR-K35

40 SU201PR-K40 40 SU203PR-K40

50 SU201PR-K50 50 SU203PR-K50

60 SU201PR-K60 60 SU203PR-K60

63 SU201PR-K63 63 SU203PR-K63

0.2 SU202PR-K0.2 0.2 SU204PR-K0.2 0.3 SU202PR-K0.3 0.3 SU204PR-K0.3 0.5 SU202PR-K0.5 0.5 SU204PR-K0.5 0.75 SU202PR-K0.75 0.75 SU204PR-K0.75

1 SU202PR-K1 1 SU204PR-K1

1.6 SU202PR-K1.6 1.6 SU204PR-K1.6

2 SU202PR-K2 2 SU204PR-K2

3 SU202PR-K3 3 SU204PR-K3

4 SU202PR-K4 4 SU204PR-K4

5 SU202PR-K5 5 SU204PR-K5

6 SU202PR-K6 6 SU204PR-K6

8 SU202PR-K8 8 SU204PR-K8

10 SU202PR-K10 10 SU204PR-K10

13 SU202PR-K13 13 SU204PR-K13

15 SU202PR-K15 15 SU204PR-K15

16 SU202PR-K16 16 SU204PR-K16

20 SU202PR-K20 20 SU204PR-K20

25 SU202PR-K25 25 SU204PR-K25

30 SU202PR-K30 30 SU204PR-K30

32 SU202PR-K32 32 SU204PR-K32

35 SU202PR-K35 35 SU204PR-K35

40 SU202PR-K40 40 SU204PR-K40

50 SU202PR-K50 50 SU204PR-K50

60 SU202PR-K60 60 SU204PR-K60

63 SU202PR-K63 63 SU204PR-K63

  • K Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.9 - 15.13 Technical data – See page 15.14 -15.16 SU201PR-K0.2 SU202PR-K0.2 SU203PR-K0.2 SU204PR-K0.2 K characteristic

Low Voltage Products & Systems 15.7 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A S200UDC-K, 1 pole 60 VDC, 2 pole 125 VDC Branch circuit protection UL 489, CSA 22.2 No. 5 No. of poles Rated current Catalog number No. of poles Rated current Catalog number

1 S201UDC-K1

1 S202UDC-K1

1.6 S201UDC-K1.6 1.6 S202UDC-K1.6

2 S201UDC-K2 2 S202UDC-K2

3 S201UDC-K3 3 S202UDC-K3

4 S201UDC-K4 4 S202UDC-K4

5 S201UDC-K5 5 S202UDC-K5

6 S201UDC-K6 6 S202UDC-K6

8 S201UDC-K8 8 S202UDC-K8

10 S201UDC-K10 10 S202UDC-K10

13 S201UDC-K13 13 S202UDC-K13

15 S201UDC-K15 15 S202UDC-K15

16 S201UDC-K16 16 S202UDC-K16

20 S201UDC-K20 20 S202UDC-K20

25 S201UDC-K25 25 S202UDC-K25

30 S201UDC-K30 30 S202UDC-K30

32 S201UDC-K32 32 S202UDC-K32

40 S201UDC-K40 40 S202UDC-K40

50 S201UDC-K50 50 S202UDC-K50

60 S201UDC-K60 60 S202UDC-K60

63 S201UDC-K63 63 S202UDC-K63

NOTE: Standard UL 489 (only DC; please note polarity of device). S201UDC-K1 S202UDC-K1 K Tripping characteristic K UL 489 480Y/277 VAC 14 kA Inductive loads

  • K Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.9 - 15.13 Technical data – See page 15.14 -15.16 120 0.6 0.4 0.2 0.1 0.06 0.04 0.02 0.01 1 1.5 2 3 4 5 6 8 10 15 20 30 Multiple of rated current MinutesSeconds = marginal characteristic measured in cold status I = 1.0 x I1 n I = 1.35 x I2 n ϑ = 25°CR K I2I1 DC Tripping time

15.8 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 No. of poles Rated current Catalog number No. of poles Rated current Catalog number

1 S201UDC-Z1

1 S202UDC-Z1

1.6 S201UDC-Z1.6 1.6 S202UDC-Z1.6

2 S201UDC-Z2 2 S202UDC-Z2

3 S201UDC-Z3 3 S202UDC-Z3

4 S201UDC-Z4 4 S202UDC-Z4

5 S201UDC-Z5 5 S202UDC-Z5

6 S201UDC-Z6 6 S202UDC-Z6

8 S201UDC-Z8 8 S202UDC-Z8

10 S201UDC-Z10 10 S202UDC-Z10

13 S201UDC-Z13 13 S202UDC-Z13

15 S201UDC-Z15 15 S202UDC-Z15

16 S201UDC-Z16 16 S202UDC-Z16

20 S201UDC-Z20 20 S202UDC-Z20

25 S201UDC-Z25 25 S202UDC-Z25

30 S201UDC-Z30 30 S202UDC-Z30

32 S201UDC-Z32 32 S202UDC-Z32

40 S201UDC-Z40 40 S202UDC-Z40

50 S201UDC-Z50 50 S202UDC-Z50

60 S201UDC-Z60 60 S202UDC-Z60

63 S201UDC-Z63 63 S202UDC-Z63

NOTE: Standard UL 489 (only DC; please note polarity of device). S201UDC-K1 S202UDC-K1 Z Tripping characteristic Z UL 489 480Y/277 VAC 14 kA Resistive loads

  • Z Curve
  • Designed to provide maximum protection with a very low short circuit trip setting
  • Example: semiconductors, control circuits Accessories & technical data Accessories – See page 15.9 - 15.13 Technical data – See page 15.14 -15.16 S200UDC-Z, 1 pole 60 VDC, 2 pole 125 VDC Branch circuit protection UL 489, CSA 22.2 No. 5 Z Tripping time MinutesSeconds marginal characteristic measured in cold status Multiple of rated current

Low Voltage Products & Systems 15.9 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A S2C-H6RU S2C-S6RU Auxiliary contacts The auxiliary contacts will signal whether the breaker is in the ON or OFF position. Description Catalog number For field mounting: right side S2C-H6RU Bell alarm The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically the contacts would be connected to an alarm or bell to signal the operator that an overcurrent trip has occurred. The bell alarm also includes a test button for testing the alarm contacts without opening the breaker. Description Catalog number For field mounting: right side S2C-S6RU Rotary operating mechanism Allows “through the door” operation. Description Catalog number Handle mechanism S2C-DH Shunt trip For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens the breaker after control voltage is applied. Description Catalog number For field mounting: right side 12…60 VAC/DC S2C-A1U For field mounting: right side 110…415 VAC S2C-A2U 110…250 VDC NOTE: For shafts and handles, refer to parts in the MCCB section. S2C-A1U S2C-DH Possible mounting arrangements of MCB accessories Accessories S200U, S200UP , SU200PR & S200UDC UL 489, CSA 22.2 No. 5 +ST+S/H+S/H (H)+S/H (H) +ST+H+H+H) Legend Auxiliary contact H Bell alarm/Auxiliary contact S/H Bell alarm/Auxiliary contact used as auxiliary contact S/H (H) Shunt trip ST NOTE: Right hand mount accessories cannot be used in conjunction with S2C-DH, Rotary operating mechanism.

15.10 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Shunt trip in OFF position Connection drawings Bell alarm S2C-S6RU Auxiliary contact in ON position Auxiliary contact in OFF position Auxiliary contact S2C-H6RU Shunt trip S2C-A...U In ON and OFF position after hand operation S2C-A1U S2C-A2U In OFF position after tripping Accessories S200U, S200UP , S200UDC & SU200PR UL 489, CSA 22.2 No. 5 S200U-UP S2C-A....U Mounting Addition of a S2C-H6RU auxiliary contact Addition of a S2C-S6RU bell alarm contact Addition of a S2C-A..U shunt trip

Low Voltage Products & Systems 15.11 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A H Auxiliary conta ct S2C-H6RU S Signal contac t S2C-S6RU ST Shunt trip S2C-A...U SU200PR Accessory overview SU200PR Instructions for use Accessories SU200PR UL 489, CSA 22.2 No. 5

15.12 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 BSK-BP For use on: Amp rating Number of poles Phases Busbar length (mm) Catalog number S200U S200UP S201UDC 103.2 208.8 314.4 PS 1/6/16BP PS 1/12/16BP PS 1/18/16BP S200U S200UP S201UDC 103.2 208.8 314.4 PS 2/6/16BP PS 2/12/16BP PS 2/18/16BP S200U S200UP S201UDC 103.2 208.8 314.4 PS 3/6/16BP PS 3/12/16BP PS 3/18/16BP UL approved busbars UL file # E250145 UL 489 busbar cannot be cut. Accessories S200U, S200UP & S200UDC UL 489, CSA 22.2 No. 5 Busbar tooth covers for BS...BP (UL 489) Description Catalog number Covers three unused poles of busbar BSK-BP

1 Phase

Feeder terminals for PS...BP (UL 489) Description Catalog number Terminal, insulated with pin contact AST35/15BP Feeder Terminal, single-pole terminal, can be mounted side by side, feed on the pin of the busbar SZ-ESK BP

2 Phase

3 Phase

Low Voltage Products & Systems 15.13 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Technical data S200U S200UP SU200PR S200UDC Specifications: UL 489, C 22.2 No. 5, IEC 60947-2 UL 489, VDE 0660 UL File-Number: E 212323, UL, Current limiting series ratings E212323, UL No. of poles: 1, 2, 3 & 4 1, 2 Tripping characteristics: K, Z K K, Z Rated voltage: Single pole: 240VAC Multi pole: 240VAC Single pole: 277VAC Multi pole: 480Y/277VAC Single pole: 277VAC (<=35A); 240VAC (>35A) Multi pole: 480Y/277VAC (<=35A); 240VAC (>35A) 1P: 60 V DC 2P:125 V DC 1 Short circuit capacity: 10 kA 14 kA Frequency: 50/60 Hz 50/60 Hz Degree of protection: IP 20 IP20, IP40 in enclosure w/cover IP 20 Mounting position: Vertical and horizontal Any Vertical and horizontal Fixing: 35 mm DIN rail 35 mm DIN rail Clamps only for Cu: 18-4 AWG (0.75 … 25 mm2) 18-4 AWG (0.75 … 25 mm2) Service life, mech. and at rated load: 20,000 operations 6000 operations (AC) 1 cycle (1s-ON, 9S-OFF) 20,000 operations Tightening torque: 25 in. lbs (2.8 Nm) 25 in. lbs (2.8 Nm) Ambient temperature: – 25 °C … + 55 °C/– 13 °F … + 131 °F – 25 °C … + 55 °C/– 13 °F … + 131 °F Shock resistance: 30 g at least 2 impacts shock, duration 13 ms 25 g, 2 shocks - 13ms 30 g at least 2 impacts shock, duration 13 ms Auxiliary contact S2C-H6RU and S2C-S6RU Rated current: 10 Rated voltage AC / DC: 24 Contact: 1 pole double throw Connection capacity mm2 18 – 14 AWG (0.75…2.5 mm2) Tightening torque: 11 in.Ibs (1.2 Nm) Mechanical service life: 10,000 operations Shunt trip Type S2C-A1U S2C-A2U Rated voltage AC DC V V 12 ... 60 12 ... 60 110 ... 415 110 ... 250 Max. release duration ms < 10 < 10 Min. release voltage AC DC V V Consumption on release AC DC VA VA 40 ... 200 40 ... 200 55 ... 210 55 ... 110 Coil resistance Ω 3.7 225 Terminals AWG/mm 2 18…6 / 0.75 – 16 18…6 / 0.75 – 16 Tightening torque in.Ibs/Nm 18 / 2 18 / 2 Technical data S200U, S200UP , SU200PR & S200UDC UL 489, CSA 22.2 No. 5 1 Poles connected in series.

15.14 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Internal resistance and power loss Internal resistance per pole in mz, power loss per pole in W. Type Rated current Device series K Device series Z A mz W mz W S200U S200UP 0.2 42500 1.7 – – 0.3 20000 1.8 – – 0.5 6340 1.6 10100 2.5 0.75 2500 1.4 – – 1 1400 1.4 2270 2.3 1.6 625 1.6 1100 2.8 2 460 1.8 619 2.5 3 211 1.9 211 1.9 4 163 2.6 163 2.6 6 6 7 2.4 104 3.7 8 45 2.9 55 3.5 10 1 9 1.9 21 2.1 13 – – – – 16 8 . 2 2.1 10.9 2.8 20 7 . 3 2.9 7 . 3 2.9 25 5 . 6 3.5 5 . 6 3.5 32 4.1 4.2 4.1 4.2 40 4.0 6.4 4.0 6.4 50 1.2 3.0 1 . 8 4.4 63 1 . 3 5.2 1.3 5.2 Technical data S200U, S200UP , SU200PR & S200UDC UL 489, CSA 22.2 No. 5 Type Rated current Device series K Device series Z A mz W mz W S200UDC 1 1400 1.4 2270 2.3 1.6 625 1.6 1100 2.8 2 460 1.8 619 2.5 3 211 1.9 211 1.9 4 153 2.6 163 2.5 6 67 2.4 104 3,7 8 45 2.9 55 3.5 10 19 1.9 21 2.1 13 – – – – 16 8.2 2.1 10.9 2.8 20 7.3 2.0 7.3 2.9 25 5.6 3.5 5.6 3.5 32 4.1 4.2 4.1 4.2 40 4.0 6.4 4.0 6.4 50 1.2 3.0 1.8 4.4 63 1.3 5.2 1.3 5.2 4) Internal resistances and power loss are subject to application-specific and environment- specific conditions and are therefore to be considered as typical values. SU200PR Rated current Internal resistance per pole 1) Power loss per pole 1) A mΩ W 0.2 25300 1.01 0.3 13700 1.23 0.5 4740 1.19 0.75 2067 1.16 1 1270 1.27 1.5 610 1.56 2 442 1.77 3 140 1.26 4 109 1.75 5 50 1.26 6 54 1.94 8 22 1.41 10 18.2 1.82 13 14.8 2.50 15 8.1 1.83 16 11.1 2.83 20 8.5 3.40 25 5.5 3.43 30 3.8 3.39 32 4.6 4.70 35 3.9 4.76 40 2.8 4.40 50 1.7 4.25 60 1.7 6.18 63 1.9 7.56

Low Voltage Products & Systems 15.15 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A K and Z Ambient temperature T (°C/°F) In (A) – 40/– 40 – 30/– 22 – 20/– 4 – 10/14 0/32 10/50 20/68 30/86 40/104 50/122 60/140 70/158 Temperature derating Max. operating current values depending on the ambient temperature for a circuit-breaker of characteristics type K and Z Tripping characteristic Z (68 °F) Breaker calibration temperature 68°F See chart below for temperature DeRating Tripping characteristic K (68 °F) Breaker calibration temperature 68°F See chart below for temperature DeRating Technical data S200U, S200UP , SU200PR & S200UDC UL 489, CSA 22.2 No. 5

15.16 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Approximate dimensions in mm S200U S2C-H6RU, S2C-S6RU S2C-A..U S200UP S200UDC Approximate dimensions S200U, S200UP , S200UDC & SU200PR UL 489, CSA 22.2 No. 5 SU200PR

Low Voltage Products & Systems 15.17 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A S200 Supplementary protective devices UL 1077 Series The S200 UL 1077 Series miniature supplementary protector offers a compact solution for protection requirements. The S200 devices are DIN rail mounted. The S200 is available with application-specific trip characteristics to provide maximum circuit protection. The supplementary protectors offer thermal- magnetic trip protection according to B, C, D, K and Z characteristics. For the worldwide market, the breakers carry UL, CSA, IEC, CE and many other agency approvals and certifications.

  • Energy limiting
  • Fast breaking time (2.3 – 2.5 ms)
  • Bus connection system
  • Wide range of accessories
  • Available with variable depth handle mechanism
  • CE certified and marked
  • DIN rail mounting
  • Finger safe terminals
  • Multi-function terminals
  • Suitable for reverse feed
  • UL1077 Recognized supplemental protective device. UL file # E76126 S200 UL 1077 Series S200 S200P S200PR S280UC Amperage 0.5 – 63 A 0.2 – 63 A 0.2 – 63A 0.2 – 63 A Voltage 480Y/277 VAC 480Y/277 VAC 240 VAC 250/500 VDC Poles 1, 2, 3, 4 1, 2, 3, 4 1, 2, 3, 4 1, 2, 3, 4 Trip characteristics B, C, D, K B, C, D, K, Z K K, Z Interrupting ratings 6 kA : IEC 60898 6 kA : UL 1077 6 kA : CSA 22.2 No. 235 Up to 25kA : IEC 60947-2 10kA : UL 1077 10kA: UL1077 10kA: CSA 22.2 No.235 Up to 6kA : IEC 60947-2 10kA : UL 1077 6 kA : CSA 22.2 No. 235 Auxiliary contacts Yes Yes Yes Yes Bell alarm Yes Yes Yes Yes Shunt trip Yes Yes Yes Yes Undervoltage release Yes Yes Yes Yes Bus bar Yes Yes No Yes Supplementary protective devices

15.18 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 B No. of poles Rated current Catalog number No. of poles Rated current Catalog number

6 S201-B6

6 S203-B6

10 S201-B10 10 S203-B10

13 S201-B13 13 S203-B13

16 S201-B16 16 S203-B16

20 S201-B20 20 S203-B20

25 S201-B25 25 S203-B25

32 S201-B32 32 S203-B32

40 S201-B40 40 S203-B40

50 S201-B50 50 S203-B50

63 S201-B63 63 S203-B63

6 S201-B6NA

6 S203-B6NA

10 S201-B10NA 10 S203-B10NA

13 S201-B13NA 13 S203-B13NA

16 S201-B16NA 16 S203-B16NA

20 S201-B20NA 20 S203-B20NA

25 S201-B25NA 25 S203-B25NA

32 S201-B32NA 32 S203-B32NA

40 S201-B40NA 40 S203-B40NA

50 S201-B50NA 50 S203-B50NA

63 S201-B63NA 63 S203-B63NA

6 S202-B6

6 S204-B6

10 S202-B10 10 S204-B10

13 S202-B13 13 S204-B13

16 S202-B16 16 S204-B16

20 S202-B20 20 S204-B20

25 S202-B25 25 S204-B25

32 S202-B32 32 S204-B32

40 S202-B40 40 S204-B40

50 S202-B50 50 S204-B50

63 S202-B63 63 S204-B63

S200-B, 480Y/277 VAC Supplemental protectors UL 1077, CSA 22.2, No. 235 Tripping characteristic B UL 1077 480Y/277VAC 6 kA Resistive loads

  • B Curve
  • Designed for use in cable protection

applications

  • Example: control circuits, lighting Accessories & technical data Accessories – See page 15.31 - 15.34 Technical data – See page 15.35 - 15.36 Note: Switching neutral is noted by “NA” in the catalog number. S202-B

Low Voltage Products & Systems 15.19 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A C No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.5 S201-C0.5 0.5 S203-C0.5

1 S201-C1 1 S203-C1

1.6 S201-C1.6 1.6 S203-C1.6

2 S201-C2 2 S203-C2

3 S201-C3 3 S203-C3

4 S201-C4 4 S203-C4

6 S201-C6 6 S203-C6

8 S201-C8 8 S203-C8

10 S201-C10 10 S203-C10

13 S201-C13 13 S203-C13

16 S201-C16 16 S203-C16

20 S201-C20 20 S203-C20

25 S201-C25 25 S203-C25

32 S201-C32 32 S203-C32

40 S201-C40 40 S203-C40

50 S201-C50 50 S203-C50

63 S201-C63 63 S203-C63

0.5 S201-C0.5NA NA 0.5 S203-C0.5NA

1 S201-C1NA 1 S203-C1NA

1.6 S201-C1.6NA 1.6 S203-C1.6NA

2 S201-C2NA 2 S203-C2NA

3 S201-C3NA 3 S203-C3NA

4 S201-C4NA 4 S203-C4NA

6 S201-C6NA 6 S203-C6NA

8 S201-C8NA 8 S203-C8NA

10 S201-C10NA 10 S203-C10NA

13 S201-C13NA 13 S203-C13NA

16 S201-C16NA 16 S203-C16NA

20 S201-C20NA 20 S203-C20NA

25 S201-C25NA 25 S203-C25NA

32 S201-C32NA 32 S203-C32NA

40 S201-C40NA 40 S203-C40NA

50 S201-C50NA 50 S203-C50NA

63 S201-C63NA 63 S203-C63NA

0.5 S202-C0.5 0.5 S204-C0.5

1 S202-C1 1 S204-C1

1.6 S202-C1.6 1.6 S204-C1.6

2 S202-C2 2 S204-C2

3 S202-C3 3 S204-C3

4 S202-C4 4 S204-C4

6 S202-C6 6 S204-C6

8 S202-C8 8 S204-C8

10 S202-C10 10 S204-C10

13 S202-C13 13 S204-C13

16 S202-C16 16 S204-C16

20 S202-C20 20 S204-C20

25 S202-C25 25 S204-C25

32 S202-C32 32 S204-C32

40 S202-C40 40 S204-C40

50 S202-C50 50 S204-C50

63 S202-C63 63 S204-C63

S200-C, 480Y/277 VAC Supplemental protectors UL 1077, CSA 22.2, No. 235 Tripping characteristic C UL 1077 480Y/277 VAC 6 kA Resistive loads

  • C Curve
  • Designed for use with medium magnetic start up currents
  • Example: lighting, control panels Accessories & technical data Accessories – See page 15.31 - 15.34 Technical data – See page 15.35 - 15.36 Note: Switching neutral is noted by “NA” in the catalog number.

15.20 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 D No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.5 S201-D0.5 0.5 S203-D0.5

1 S201-D1 1 S203-D1

1.6 S201-D1.6 1.6 S203-D1.6

2 S201-D2 2 S203-D2

3 S201-D3 3 S203-D3

4 S201-D4 4 S203-D4

6 S201-D6 6 S203-D6

8 S201-D8 8 S203-D8

10 S201-D10 10 S203-D10

13 S201-D13 13 S203-D13

16 S201-D16 16 S203-D16

20 S201-D20 20 S203-D20

25 S201-D25 25 S203-D25

32 S201-D32 32 S203-D32

40 S201-D40 40 S203-D40

50 S201-D50 50 S203-D50

63 S201-D63 63 S203-D63

0.5 S201-D0.5NA NA 0.5 S203-D0.5NA

1 S201-D1NA 1 S203-D1NA

1.6 S201-D1.6NA 1.6 S203-D1.6NA

2 S201-D2NA 2 S203-D2NA

3 S201-D3NA 3 S203-D3NA

4 S201-D4NA 4 S203-D4NA

6 S201-D6NA 6 S203-D6NA

8 S201-D8NA 8 S203-D8NA

10 S201-D10NA 10 S203-D10NA

13 S201-D13NA 13 S203-D13NA

16 S201-D16NA 16 S203-D16NA

20 S201-D20NA 20 S203-D20NA

25 S201-D25NA 25 S203-D25NA

32 S201-D32NA 32 S203-D32NA

40 S201-D40NA 40 S203-D40NA

50 S201-D50NA 50 S203-D50NA

63 S201-D63NA 63 S203-D63NA

0.5 S202-D0.5 0.5 S204-D0.5

1 S202-D1 1 S204-D1

1.6 S202-D1.6 1.6 S204-D1.6

2 S202-D2 2 S204-D2

3 S202-D3 3 S204-D3

4 S202-D4 4 S204-D4

6 S202-D6 6 S204-D6

8 S202-D8 8 S204-D8

10 S202-D10 10 S204-D10

13 S202-D13 13 S204-D13

16 S202-D16 16 S204-D16

20 S202-D20 20 S204-D20

25 S202-D25 25 S204-D25

32 S202-D32 32 S204-D32

40 S202-D40 40 S204-D40

50 S202-D50 50 S204-D50

63 S202-D63 63 S204-D63

S200-D, 480Y/277 VAC Supplemental protectors UL 1077, CSA 22.2, No. 235 Tripping characteristic D UL 1077 480Y/277 VAC 6 kA Inductive loads

  • D Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.31 - 15.34 Technical data – See page 15.35 - 15.36 Note: Switching neutral is noted by “NA” in the catalog number.

Low Voltage Products & Systems 15.21 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A K S201-K S202-K S203-K S204-K No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.5 S201-K0.5 0.5 S203-K0.5

1 S201-K1 1 S203-K1

1.6 S201-K1.6 1.6 S203-K1.6

2 S201-K2 2 S203-K2

3 S201-K3 3 S203-K3

4 S201-K4 4 S203-K4

5 S201-K5 5 S203-K5

6 S201-K6 6 S203-K6

8 S201-K8 8 S203-K8

10 S201-K10 10 S203-K10

13 S201-K13 13 S203-K13

15 S201-K15 15 S203-K15

16 S201-K16 16 S203-K16

20 S201-K20 20 S203-K20

25 S201-K25 25 S203-K25

32 S201-K32 32 S203-K32

40 S201-K40 40 S203-K40

50 S201-K50 50 S203-K50

60 S201-K60 60 S203-K60

63 S201-K63 63 S203-K63

0.5 S201-K0.5NA NA 0.5 S203-K0.5NA

1 S201-K1NA 1 S203-K1NA

1.6 S201-K1.6NA 1.6 S203-K1.6NA

2 S201-K2NA 2 S203-K2NA

3 S201-K3NA 3 S203-K3NA

4 S201-K4NA 4 S203-K4NA

6 S201-K6NA 6 S203-K6NA

8 S201-K8NA 8 S203-K8NA

10 S201-K10NA 10 S203-K10NA

13 S201-K13NA 13 S203-K13NA

16 S201-K16NA 16 S203-K16NA

20 S201-K20NA 20 S203-K20NA

25 S201-K25NA 25 S203-K25NA

32 S201-K32NA 32 S203-K32NA

40 S201-K40NA 40 S203-K40NA

50 S201-K50NA 50 S203-K50NA

63 S201-K63NA 63 S203-K63NA

0.5 S202-K0.5 0.5 S204-K0.5

1 S202-K1 1 S204-K1

1.6 S202-K1.6 1.6 S204-K1.6

2 S202-K2 2 S204-K2

3 S202-K3 3 S204-K3

4 S202-K4 4 S204-K4

5 S202-K5 5 S204-K5

6 S202-K6 6 S204-K6

8 S202-K8 8 S204-K8

10 S202-K10 10 S204-K10

13 S202-K13 13 S204-K13

15 S202-K15 15 S204-K15

16 S202-K16 16 S204-K16

20 S202-K20 20 S204-K20

25 S202-K25 25 S204-K25

32 S202-K32 32 S204-K32

40 S202-K40 40 S204-K40

50 S202-K50 50 S204-K50

60 S202-K60 60 S204-K60

63 S202-K63 63 S204-K63

S200-K, 480Y/277 VAC Supplemental protectors UL 1077, CSA 22.2, No. 235 Tripping characteristic K UL 1077 480Y/277 VAC 6 kA Inductive loads

  • K Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.31 - 15.34 Technical data – See page 15.35 - 15.36 Note: Switching neutral is noted by “NA” in the catalog number.

15.22 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 S200-Z, 480Y/277 VAC Supplemental protectors UL 1077, CSA 22.2, No. 235 Z No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.5 S201-Z0.5 0.5 S203-Z0.5

1 S201-Z1 1 S203-Z1

1.6 S201-Z1.6 1.6 S203-Z1.6

2 S201-Z2 2 S203-Z2

3 S201-Z3 3 S203-Z3

4 S201-Z4 4 S203-Z4

6 S201-Z6 6 S203-Z6

10 S201-Z10 10 S203-Z10

13 S201-Z13 13 S203-Z13

16 S201-Z16 16 S203-Z16

20 S201-Z20 20 S203-Z20

25 S201-Z25 25 S203-Z25

32 S201-Z32 32 S203-Z32

40 S201-Z40 40 S203-Z40

50 S201-Z50 50 S203-Z50

63 S201-Z63 63 S203-Z63

0.5 S202-Z0.5 0.5 S204-Z0.5

1 S202-Z1 1 S204-Z1

1.6 S202-Z1.6 1.6 S204-Z1.6

2 S202-Z2 2 S204-Z2

3 S202-Z3 3 S204-Z3

4 S202-Z4 4 S204-Z4

6 S202-Z6 6 S204-Z6

10 S202-Z10 10 S204-Z10

13 S202-Z13 13 S204-Z13

16 S202-Z16 16 S204-Z16

20 S202-Z20 20 S204-Z20

25 S202-Z25 25 S204-Z25

32 S202-Z32 32 S204-Z32

40 S202-Z40 40 S204-Z40

50 S202-Z50 50 S204-Z50

63 S202-Z63 63 S204-Z63

  • Z Curve
  • Designed to provide maximum protection with a very low shirt circuit trip setting
  • Example: semiconductors Accessories & technical data Accessories – See page 15.31 - 15.34 Technical data – See page 15.35 - 15.36 S201-Z0.5 S203-Z0.5 S204-Z0.5 S202-Z0.5

Low Voltage Products & Systems 15.23 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A S200P-B, 480Y/277 VAC Supplemental protectors UL 1077, CSA 22.2, No. 235 No. of poles Rated current Catalog number No. of poles Rated current Catalog number

6 S201P-B6

6 S203P-B6

10 S201P-B10 10 S203P-B10

13 S201P-B13 13 S203P-B13

16 S201P-B16 16 S203P-B16

20 S201P-B20 20 S203P-B20

25 S201P-B25 25 S203P-B25

32 S201P-B32 32 S203P-B32

40 S201P-B40 40 S203P-B40

50 S201P-B50 50 S203P-B50

63 S201P-B63 63 S203P-B63

6 S202P-B6

6 S204P-B6

10 S202P-B10 10 S204P-B10

13 S202P-B13 13 S204P-B13

16 S202P-B16 16 S204P-B16

20 S202P-B20 20 S204P-B20

25 S202P-B25 25 S204P-B25

32 S202P-B32 32 S204P-B32

40 S202P-B40 40 S204P-B40

50 S202P-B50 50 S204P-B50

63 S202P-B63 63 S204P-B63

B Tripping characteristic B UL 1077 480Y/277 VAC 10 kA Resistive loads

  • B Curve
  • Designed for use in cable protection
  • Example: Control circuits, lighting Accessories & technical data Accessories – See page 15.31 - 15.34 Technical data – See page 15.35 - 15.36

15.24 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 S200P-C, 480Y/277 VAC Supplemental protectors UL 1077, CSA 22.2, No. 235 No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.5 S201P-C0.5 0.5 S203P-C0.5

1 S201P-C1 1 S203P-C1

1.6 S201P-C1.6 1.6 S203P-C1.6

2 S201P-C2 2 S203P-C2

3 S201P-C3 3 S203P-C3

4 S201P-C4 4 S203P-C4

6 S201P-C6 6 S203P-C6

8 S201P-C8 8 S203P-C8

10 S201P-C10 10 S203P-C10

13 S201P-C13 13 S203P-C13

16 S201P-C16 16 S203P-C16

20 S201P-C10 20 S203P-C10

25 S201P-C25 25 S203P-C25

32 S201P-C32 32 S203P-C32

40 S201P-C40 40 S203P-C40

50 S201P-C50 50 S203P-C50

63 S201P-C63 63 S203P-C63

0.5 S202P-C0.5

1 S202P-C1

1.6 S202P-C1.6

2 S202P-C2

3 S202P-C3

4 S202P-C4

6 S202P-C6

8 S202P-C8

10 S202P-C10

13 S202P-C13

16 S202P-C16

20 S202P-C10

25 S202P-C25

32 S202P-C32

40 S202P-C40

50 S202P-C50

63 S202P-C63

C Tripping characteristic C UL 1077 480Y/277 VAC 10 kA Resistive loads

  • C Curve
  • Designed for use with medium magnetic start up currents
  • Example: Lighting, control panels Accessories & technical data Accessories – See page 15.31 - 15.34 Technical data – See page 15.35 - 15.36

Low Voltage Products & Systems 15.25 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A S200P-D, 480Y/277 VAC Supplemental protectors UL 1077, CSA 22.2, No. 235 No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.5 S201P-D0.5 0.5 S203P-D0.5

1 S201P-D1 1 S203P-D1

1.6 S201P-D1.6 1.6 S203P-D1.6

2 S201P-D2 2 S203P-D2

3 S201P-D3 3 S203P-D3

4 S201P-D4 4 S203P-D4

6 S201P-D6 6 S203P-D6

8 S201P-D8 8 S203P-D8

10 S201P-D10 10 S203P-D10

13 S201P-D13 13 S203P-D13

16 S201P-D16 16 S203P-D16

20 S201P-D10 20 S203P-D10

25 S201P-D25 25 S203P-D25

32 S201P-D32 32 S203P-D32

40 S201P-D40 40 S203P-D40

50 S201P-D50 50 S203P-D50

63 S201P-D63 63 S203P-D63

0.5 S202P-D0.5

1 S202P-D1

1.6 S202P-D1.6

2 S202P-D2

3 S202P-D3

4 S202P-D4

6 S202P-D6

8 S202P-D8

10 S202P-D10

13 S202P-D13

16 S202P-D16

20 S202P-D10

25 S202P-D25

32 S202P-D32

40 S202P-D40

50 S202P-D50

63 S202P-D63

S201P-D0.5 S202P-D0.5 S203P-D0.5 D Tripping characteristic D UL 1077 480Y/277 VAC 10 kA Inductive loads

  • D Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.31 - 15.34 Technical data – See page 15.35 - 15.36

15.26 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 K No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.2 S201P-K0.2 0.2 S203P-K0.2 0.3 S201P-K0.3 0.3 S203P-K0.3 0.5 S201P-K0.5 0.5 S203P-K0.5 0.75 S201P-K0.75 0.75 S203P-K0.75

1 S201P-K1 1 S203P-K1

1.6 S201P-K1.6 1,6 S203P-K1,6

2 S201P-K2 2 S203P-K2

3 S201P-K3 3 S203P-K3

4 S201P-K4 4 S203P-K4

6 S201P-K6 6 S203P-K6

8 S201P-K8 8 S203P-K8

10 S201P-K10 10 S203P-K10

13 S201P-K13 13 S203P-K13

16 S201P-K16 16 S203P-K16

20 S201P-K20 20 S203P-K20

25 S201P-K25 25 S203P-K25

32 S201P-K32 32 S203P-K32

40 S201P-K40 40 S203P-K40

50 S201P-K50 50 S203P-K50

63 S201P-K63 63 S203P-K63

0.2 S202P-K0.2 0.3 S202P-K0.3 0.5 S202P-K0.5 0.75 S202P-K0.75

1 S202P-K1

1.6 S202P-K1,6

2 S202P-K2

3 S202P-K3

4 S202P-K4

6 S202P-K6

8 S202P-K8

10 S202P-K10

13 S202P-K13

16 S202P-K16

20 S202P-K20

25 S202P-K25

32 S202P-K32

40 S202P-K40

50 S202P-K50

63 S202P-K63

S200P-K, 480Y/277 VAC Supplemental protectors UL 1077, CSA 22.2, No. 235 Tripping characteristic K UL 1077 480Y/277 VAC 10 kA Inductive loads

  • K Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.31 - 15.34 Technical data – See page 15.35 - 15.36 S201P-K S202P-K

Low Voltage Products & Systems 15.27 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Z No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.5 S201P-Z0.5 0.5 S203P-Z0.5

1 S201P-Z1 1 S203P-Z1

1.6 S201P-Z1.6 1.6 S203P-Z1.6

2 S201P-Z2 2 S203P-Z2

3 S201P-Z3 3 S203P-Z3

4 S201P-Z4 4 S203P-Z4

6 S201P-Z6 6 S203P-Z6

8 S201P-Z8 8 S203P-Z8

10 S201P-Z10 10 S203P-Z10

16 S201P-Z16 16 S203P-Z16

20 S201P-Z20 20 S203P-Z20

25 S201P-Z25 25 S203P-Z25

32 S201P-Z32 32 S203P-Z32

40 S201P-Z40 40 S203P-Z40

50 S201P-Z50 50 S203P-Z50

63 S201P-Z63 63 S203P-Z63

0.5 S202P-Z0.5

1 S202P-Z1

1.6 S202P-Z1.6

2 S202P-Z2

3 S202P-Z3

4 S202P-Z4

6 S202P-Z6

8 S202P-Z8

10 S202P-Z10

16 S202P-Z16

20 S202P-Z20

25 S202P-Z25

32 S202P-Z32

40 S202P-Z40

50 S202P-Z50

63 S202P-Z63

S200P-Z, 480Y/277 VAC Supplemental protectors UL 1077, CSA 22.2, No. 235 S202P-Z Tripping characteristic Z UL 1077 480Y/277 VAC 10 kA Resistive loads

  • Z Curve
  • Designed to provide maximum protection with a very low short circuit trip setting
  • Example: semiconductors Accessories & technical data Accessories – See page 15.31 - 15.34 Technical data – See page 15.35 - 15.36

15.28 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 S200PR-K, 240 VAC, Ring tongue Supplemental protectors UL1077, CSA 22.2 No. 235 No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.2 S201PR-K0.2 0.2 S203PR-K0.2 0.3 S201PR-K0.3 0.3 S203PR-K0.3 0.5 S201PR-K0.5 0.5 S203PR-K0.5 0.75 S201PR-K0.75 0.75 S203PR-K0.75

1 S201PR-K1 1 S203PR-K1

1.6 S201PR-K1.6 1.6 S203PR-K1.6

2 S201PR-K2 2 S203PR-K2

3 S201PR-K3 3 S203PR-K3

4 S201PR-K4 4 S203PR-K4

5 S201PR-K5 5 S203PR-K5

6 S201PR-K6 6 S203PR-K6

8 S201PR-K8 8 S203PR-K8

10 S201PR-K10 10 S203PR-K10

13 S201PR-K13 13 S203PR-K13

15 S201PR-K15 15 S203PR-K15

16 S201PR-K16 16 S203PR-K16

20 S201PR-K20 20 S203PR-K20

25 S201PR-K25 25 S203PR-K25

30 S201PR-K30 30 S203PR-K30

32 S201PR-K32 32 S203PR-K32

35 S201PR-K35 35 S203PR-K35

40 S201PR-K40 40 S203PR-K40

50 S201PR-K50 50 S203PR-K50

60 S201PR-K60 60 S203PR-K60

63 S201PR-K63 63 S203PR-K63

0.2 S202PR-K0.2 0.2 S204PR-K0.2 0.3 S202PR-K0.3 0.3 S204PR-K0.3 0.5 S202PR-K0.5 0.5 S204PR-K0.5 0.75 S202PR-K0.75 0.75 S204PR-K0.75

1 S202PR-K1 1 S204PR-K1

1.6 S202PR-K1.6 1.6 S204PR-K1.6

2 S202PR-K2 2 S204PR-K2

3 S202PR-K3 3 S204PR-K3

4 S202PR-K4 4 S204PR-K4

5 S202PR-K5 5 S204PR-K5

6 S202PR-K6 6 S204PR-K6

8 S202PR-K8 8 S204PR-K8

10 S202PR-K10 10 S204PR-K10

13 S202PR-K13 13 S204PR-K13

15 S202PR-K15 15 S204PR-K15

16 S202PR-K16 16 S204PR-K16

20 S202PR-K20 20 S204PR-K20

25 S202PR-K25 25 S204PR-K25

30 S202PR-K30 30 S204PR-K30

32 S202PR-K32 32 S204PR-K32

35 S202PR-K35 35 S204PR-K35

40 S202PR-K40 40 S204PR-K40

50 S202PR-K50 50 S204PR-K50

60 S202PR-K60 60 S204PR-K60

63 S202PR-K63 63 S204PR-K63

K S201PR-K0.2 S202PR-K0.2 S203PR-K0.2 S203PR-K0.2 Tripping characteristic K UL 1077 480Y/277 VAC 10 kA Inductive loads

  • K Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.31 - 15.34 Technical data – See page 15.35 - 15.36

Low Voltage Products & Systems 15.29 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A K S281UC-K S282UC-K S283UC-K No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0,2 S281UC-K0.2 0.2 S283UC-K0.2 0,3 S281UC-K0.3 0.3 S283UC-K0.3 0,5 S281UC-K0.5 0.5 S283UC-K0.5 0,75 S281UC-K0.75 0.75 S283UC-K0.75

1 S281UC-K1 1 S283UC-K1

1,6 S281UC-K1.6 1.6 S283UC-K1.6

2 S281UC-K2 2 S283UC-K2

3 S281UC-K3 3 S283UC-K3

4 S281UC-K4 4 S283UC-K4

6 S281UC-K6 6 S283UC-K6

8 S281UC-K8 8 S283UC-K8

10 S281UC-K10 10 S283UC-K10

16 S281UC-K16 16 S283UC-K16

20 S281UC-K20 20 S283UC-K20

25 S281UC-K25 25 S283UC-K25

32 S281UC-K32 32 S283UC-K32

40 S281UC-K40 40 S283UC-K40

50 S281UC-K50 50 S283UC-K50

63 S281UC-K63 63 S283UC-K63

0,2 S282UC-K0.2 0,3 S282UC-K0.3 0,5 S282UC-K0.5 0,75 S282UC-K0.75

1 S282UC-K1

1,6 S282UC-K1.6

2 S282UC-K2

3 S282UC-K3

4 S282UC-K4

6 S282UC-K6

8 S282UC-K8

10 S282UC-K10

16 S282UC-K16

20 S282UC-K20

25 S282UC-K25

32 S282UC-K32

40 S282UC-K40

50 S282UC-K50

63 S282UC-K63

500 VDC

S280UC-K, 500 VDC Supplemental protectors UL 1077, CSA 22.2, No. 235 Tripping characteristic K UL 1077 250/500 VDC 10 kA Inductive loads

  • K Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformer Accessories & technical data Accessories – See page 15.31 - 15.34 Technical data – See page 15.35 - 15.36 Direct current applications The S280UC differs from standard minia- ture circuit breakers in that the UC versions include a permanent magnet which aids in the extinguishing of the arc during medium and high level faults. It is necessary to observe the correct polarity and current direction when connecting the UC breakers. Two examples of correct connection are shown. Termination points are marked on all UC type MCBs, points one (1) and four (4) are negative and points two (2) and three (3) are positive.

15.30 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Z No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.5 S281UC-Z0.5 0.5 S283UC-Z0.5

1 S281UC-Z1 1 S283UC-Z1

1.6 S281UC-Z1.6 1.6 S283UC-Z1.6

2 S281UC-Z2 2 S283UC-Z2

3 S281UC-Z3 3 S283UC-Z3

4 S281UC-Z4 4 S283UC-Z4

6 S281UC-Z6 6 S283UC-Z6

8 S281UC-Z8 8 S283UC-Z8

10 S281UC-Z10 10 S283UC-Z10

16 S281UC-Z16 16 S283UC-Z16

20 S281UC-Z20 20 S283UC-Z20

25 S281UC-Z25 25 S283UC-Z25

32 S281UC-Z32 32 S283UC-Z32

40 S281UC-Z40 40 S283UC-Z40

50 S281UC-Z50 50 S283UC-Z50

63 S281UC-Z63 63 S283UC-Z63

0.5 S282UC-Z0.5

1 S282UC-Z1

1.6 S282UC-Z1.6

2 S282UC-Z2

3 S282UC-Z3

4 S282UC-Z4

6 S282UC-Z6

8 S282UC-Z8

10 S282UC-Z10

16 S282UC-Z16

20 S282UC-Z20

25 S282UC-Z25

32 S282UC-Z32

40 S282UC-Z40

50 S282UC-Z50

63 S282UC-Z63

S280UC-Z, 500 VDC Supplemental protectors UL 1077, CSA 22.2, No. 235 S201DC S282UC

  • Z Curve
  • Designed to provide maximum protection with a very low short circuit trip setting
  • Example: semiconductors Accessories & technical data Accessories – See page 15.31 - 15.34 Technical data – See page 15.35 - 15.36 Direct current applications The S280UC differs from standard minia- ture circuit breakers in that the UC versions include a permanent magnet which aids in the extinguishing of the arc during medium and high level faults. It is necessary to observe the correct polarity and current direction when connecting the UC breakers. Two examples of correct connection are shown. Termination points are marked on all UC type MCBs, points one (1) and four (4) are negative and points two (2) and three (3) are positive.

Low Voltage Products & Systems 15.31 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Auxiliary contacts The auxiliary contacts will signal whether the breaker is in the ON or OFF position. Description Catalog number For field mounting: right side S2C-H6R Bell alarm - signal contact The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically the contacts would be connected to an alarm or bell to signal the operator that an overcurrent trip has occurred. The bell alarm also includes a test button for testing the alarm contacts without opening the breaker. Description Catalog number For field mounting: right side S2C-S/H6R 1 Shunt trip For remote tripping of breaker, a shunt trip device can be added to the MCB. The solenoid device opens the breaker after control voltage is applied. Description Catalog number For field mounting: right side A1-12-60 VAC (12 – 60 VDC) A2-110-415 VAC (110 – 250 VDC) S2C-A1 S2C-A2 Undervoltage release When control voltage drops below approximately 50 % of rated voltage, the UVR opens the breaker. The breaker can not be operated unless proper control voltage is first applied to the UVR coil. Description Catalog number For field mounting: right side

12 VDC

24 VAC/VDC

48 VAC/VDC

110 VAC/VDC

220 VAC/VDC

380 VAC

S200, S200P & S200PR UL 1077, CSA 22.2, No. 235 1 Combination bell alarm/auxiliary contact. Possible mounting arrangements of MCB accessories +ST+S/H+S/H (H)+S/H (H) +ST+H+H+H) Legend Auxiliary contact H Bell alarm/Auxiliary contact S/H Bell alarm/Auxiliary contact used as auxiliary contact S/H (H) Shunt trip ST Undervoltage release UR SA 1 SA 2 Locking devices Description Catalog number Locking devices, 3 mm SA1 Padlock with 2 keys SA2

15.32 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 H Auxiliary conta ct S2C-H6R H-R Auxiliary conta ct S2C-H6- ...R S/H Signal/Auxiliary conta ct S2C-S/ H6R S/H (H) Signal/Auxiliary conta ct S2C-S/ H6R used as auxilia ry co ntact ST Shunt trip S2C-A... UR Undervol tage release S2C -UA S200PR Accessory overview Accessories S200PR UL 1077, CSA 22.2, No. 235 S200PR Instructions for use

Low Voltage Products & Systems 15.33 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Accessories S280UC UL 1077, CSA 22.2, No. 235 S2-A1 I S2-A2 I S 290 A1 S 290 A2 S9-T24, S9-T130, S9-T415 S5 AL Installation only on left 11 21 31 12 22 32 13 23 33 14 24 34 11 21 33 12 22 34 11 23 33 12 24 34 11 21 12 22 13 23 14 24 13 21 14 22 S2-H11 S2-H20 S2-H02 S2-H21 S2-H12 S2-H30 S2-H03 S2-h11 X S2-H20 X S2-H02 X 96 98 96 98 96 98 12 14 96 98 12 14 96 98 12 14 96 98 Automatic opening Manual opening Automatic opening Manual opening S2-S 96 98 96 98 96 98 12 14 96 98 12 14 96 98 12 14 96 98 Automatic opening Manual opening Automatic opening Manual opening S2-S/H Shunt trips Function: remote opening of the device when a voltage is applied Suitable for MCBs S 280 and S 280 UC series Description Catalog number 12-60 VAC/VDC shunt trip S2-A1 110-415 VAC and 110-250 VDC shunt trip S2-A2 Auxiliary contacts Function: indication of the position of the device’s contacts Suitable for MCBs S 280 and S 280 UC series Signal contacts Function: indication of the position of the device’s contacts only after the automatic release of the MCBs and RCBOs due to an overload or a short-circuit Suitable for MCBs S 280 and S 280 UC series Description Catalog number Auxiliary contact 1 NO + 1 NC (1/2 module) S2-H11 Auxiliary contact 2 NO (1/2 module) S2-H20 Auxiliary contact 2 NC (1/2 module) S2-H02 Auxiliary contact 1 NO + 1 NC (1/2 module) with Faston connections S2-H11X Auxiliary contact 2 NO (1/2 module) with Faston connections S2-H20X Auxiliary contact 2 NC (1/2 module) with Faston connections S2-H02X Auxiliary contact 2 NO + 1 NC (1/2 module) S2-H21 Auxiliary contact 1 NO + 2 NC (1/2 module) S2-H12 Auxiliary contact 3 NO (1/2 module) S2-H30 Auxiliary contact 3 NC (1/2 module) S2-H03 Signal contact (1/2 module) S2-S Signal contact + Auxiliary contact (1/2 module) S2-S/H Undervoltage release Function: protection of the load in the event of a voltage drop (between 70% and 35% of its rated value); positive safety (device’s tripping when the voltage is disconnected) emergency stop by means of a button. Suitable for MCBs S 280 and S 280 UC series Description Catalog number Undervoltage release 12V DC (1 module) S2-UA12 Undervoltage release 24V AC/DC (1 module) S2-UA24 Undervoltage release 48V AC/DC (1 module) S2-UA48 Undervoltage release 110V AC/DC (1 module) S2-UA110 Undervoltage release 220V AC/DC (1 module) S2-UA220 Undervoltage release 380V AC (1 module) S2-UA380 S2-A1 S2-UA12

15.34 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Accessories S280UC UL 1077, CSA 22.2, No. 235 Hand operated neutral The hand operated neutral has to be mounted to the left side of the MCB and be snapped on the DIN rail. It is used for measuring duties where the neutral conductor must be in the open position. Due to the special design of the handle - when switching ON the MCB – the neutral will make before the MCB is closed. The S2C - Nt is not to switch with a tool (screw driver). Description Catalog number Hand operated neutral S2-NT

Low Voltage Products & Systems 15.35 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A ST UR UR ST S/H H S S 280 H S S/H S H Auxiliary contact S Signal contact UR Undervoltare release ST Shunt trip Combination between auxiliary elements and S 280 Technical characteristics of auxiliary and signal contacts Type S2-H11 I S2-H20 I S2-H02 I S2-H21 S2-H12 S2-H30 S2-H03 S2-H11 X S2-H20 X S2-H02 X Description 1NO+1NC 2NO 2NC 2NO+1NC 1NO+2NC 3NO 3NC Min.operating voltage [V] 12 a.c.-12 d.c. Min. operating current [mA] 12 Terminals [mm 2] up to 2x1.5 Dielectric strength [kV] 3 Resistance to short-circuit at 240 V a.c. [A] 1000 (protected with S 2 breaker characteristic K - 6 A) Impulse voltage withstand capacity [kV] 4 Tightening torque [Nm] 0.7 Dimensions (WxDxH) [mm] 8.75x68x90 NB: the auxiliary contacts S2-H11 X, S2-H20 X, S2-H02 X differ from the contacts S2-H11, S2-H20, S2-H02 in that they do not have a terminal to tighten the cable which is replaced by a bayonet for the Faston connection. Schemes for combination and technical features Auxiliary elements for MCBs S 280 series

15.36 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Technical characteristics of undervoltage releases Type S2-UA 12 S2-UA 24 S2-UA 48 S2-UA 110 S2-UA 220 S2-UA 380 Standards VDE0660 part I - IEC EN 60947.1 Rated [V] a.c. - 24 48 110 220-240 380 voltage [V] d.c. 12 24 - 110 220-240 380 Frequency [Hz] 50...60 Release trip [V] 0.35 Un≤V≤0.7 Un Terminals [mm2] 2 x 1.5 Consumption [mA] 10 Resistance to corrosion [°C/RH] const. climatic cond.: 23/83-40/93-55/20; var. climatic cond.: 25/95-40/93 Protection degree IP20 Tightening torque [Nm] 0.4 Dimensions (WxDxH) [mm] 17.5x68x90 Technical characteristics of shunt trips Type S2-A1 S2-A2 Rated voltage [V] a.c. 12 - 60 110 - 415 d.c. 12 - 60 110 - 250 Max. release duration [ms] <10 <10 Min. release [V] voltage a.c. 7 55 d.c. 10 80 Consumption on release [VA] 12 V a.c. 35 12 V d.c. 30 24 V a.c. 140 24 V d.c. 100 48 V a.c. 600 48 V d.c. 330 110 V a.c. 40 110 V d.c. 40 220 V a.c. 180 220 V d.c. 170 Coil resistance [Ω] 3.7 225 Terminals [mm2] 25 25 Tightening torque [Nm] 2 2 Dimens.(WxDxH) [mm] 17.5x68x90 17.5x68x90 S2-S S2-SH 1 change over 2 change over 240 415 6 2 250 110 60 24 0.5 1 1 4 12 a.c.-12 d.c. up to 2x1.5 1000 (protected with S 2 breaker characteristic K - 6 A) 0.7 8.75x68x90 Technical features Auxiliary elements for MCBs S 280 series

Low Voltage Products & Systems 15.37 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A For use on: Amp rating Number of poles Phases Busbar length (mm) End cap catalog number Catalog number S200 S200 P 986 986 PS-END0 PS-END0 PS1/60SP PS1/60/16SP For use on: Amp rating Number of poles Phases Busbar length (mm) End cap catalog number Catalog number S200 S200 P 1035 1035 PS-ENDSP PS-ENDSP PS2/58SP PS2/58/16SP For use on: Amp rating Number of poles Phases Busbar length (mm) End cap catalog number Catalog number S200 S200 P 1065 1065 PSB-ENDSP PSB-ENDSP PS3/60SP PS3/60/16SP For use on: Amp rating Number of poles Phases Busbar length (mm) End cap catalog number Catalog number S200 80 60 4 1056 PS-END1 PS4/60/16SP

4 Phase

ALL BUSBARS MAY BE CENTER FED IN ORDER TO INCREASE AMPACITY UP TO 130 A. NOTE BUSBARS MAY BE USED ON LINE OR LOAD SIDE OF MCBS Accessories S200 & S200P UL 1077, CSA 22.2, No. 235 (suitable for cutting)

15.38 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 For use on: Amp rating Number of poles Phases Busbar length (mm) End cap catalog number Catalog number S200 & S200 P 1044 1044 PS1/38H PS1/38/16HFor use on: Amp rating Number of poles Phases Busbar length (mm) End cap catalog number Catalog number S200 & S200 P 80 58 4 1048 PS-END1SP PS4/58/16NSP

1 Phase with 1 auxiliary

use on: Amp rating Number of poles Phases Busbar length (mm) End cap catalog number Catalog number S200 & S200 P 80 48 2 1065 PS-ENDSP PS2/48/16SP For use on: Amp rating Number of poles Phases Busbar length (mm) End cap catalog number Catalog number S200 & S200 P 80 39 3 980 PS-ENDSP PS3/39/16SP

3 Phase with 1 auxiliary

2 Phase with 1 auxiliary

3 Phase + N, for use with 2 pole-MCBs on 3 phase/4W system

S200 & S200P UL 1077, CSA 22.2, No. 235 NOTE ALL BUSBARS MAY BE CENTER FED IN ORDER TO INCREASE AMPACITY UP TO 130 A. NOTE BUSBARS MAY BE USED ON LINE OR LOAD SIDE OF MCBS

1 Phase + Aux

2 Phase + Aux

3 Phase + Aux

3 Phase + N

Low Voltage Products & Systems 15.39 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A BSK-SP Busbar tooth covers Description Catalog number Covers five unused poles of busbar BSK-SP AST35/15SP PS2/6/16 SP Accessories S200 & S200P UL 1077, CSA 22.2, No. 235 SZ-ESK SP Feeder terminals Description Catalog number Insulated with pin contact, 35mm sq. AST35/15SP For side by side mounting; feed on pin of busbar, 50mm sq. SZ-ESKSP

15.40 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Technical data S200, S200P , S200PR & S280UC UL 1077, CSA 22.2, No. 235 Technical data S200 S200P S200PR S280UC Specifications: UL 1077, CSA C 22.2, VDE 0660, 60898, 60947-2 UL1077, CSA 22.2 No. 235, IEC 60947-2 UL1077, CSA 22.2, No. 235 UL File-Number: E 76126 UL CL E 76126 UL CL E 76126 UL CL – No. of poles: 1, 2, 3 & 4 1, 2, 3 & 4 1, 2, 3 & 4 1, 2, 3 Tripping characteristics: B, C, D, K & Z B, C, D, K & Z K K, Z Rated current: 0.5-63 A 0.2-63 A 0.2-63 A 0.2-63 A Rated voltage: Multi pole, 480Y/277 VAC 1 pole, 277 VAC, Multi pole, 480Y/277 VAC 1 pole, 250 VDC, 230 VAC, Multipole, 500 VDC, 480 VAC Short circuit capacity: S200 6kA; S200P 10 kA 10 kA 4.5 kA (10 kA, 60 VD 1P , 125 VDC, 2P Frequency: 50/60 Hz 50/60 Hz 50/60 Hz Degree of protection: IP 20 IP 20, IP40 in enclosure w/cover IP 20 Mounting position: Vertical, horizontal Any Any Fixing: 35mm DIN rail Clamps only for Cu: 18-4 AWG Service life, mech. and at rated load: 20,000 operations 6000 ops (AC), 1 cycle (1s -ON, 9s -OFF) 6000 ops (AC/DC), 1 cycle (1s -ON, 9s -OFF) Shock resistance: 30 g at least 3 impacts, shock duration of 11 ms 25g, 2 shocks, 13ms 30g, 3 shocks, 11ms Auxiliary contact S2C-H6R and Signal contact S2C-S6R for S200, S200P & S200PR Rated current: 10 Rated voltage AC / DC: 24 Contact: 1 pole, single throw Connection capacity mm2 18 – 14 AWG (0.75…2.5) Tightening torque: 11 in. Ibs (1.2 Nm) Mechanical service life: 10,000 operations Shunt trip S2C-A1 S2C-A2 Rated voltage AC DC 12 ... 60 V 12 ... 60 V 110 ... 415 V 110 ... 250 V Max. release duration < 10 ms < 10 ms Min. release voltage AC DC 7 V 10 V 55 V 80 V Consumption on release AD DC 40 ... 200 VA 40 ... 200 VA 55 ... 210 VA 55 ... 110 VA Coil resistance 3.7 Ω 225 Ω Terminals 18…6/0.75 – 16 AWG/mm 2 18…6/0.75 – 16 AWG/mm2 Tightening torque 18/2 in.Ibs/Nm 18/2 in.Ibs/Nm Undervoltage release S2C-UA 12 DC S2C-UA 24 AC S2C-UA 24 DC S2C-UA 48 AC S2C-UA 48 DC S2C-UA 110 AC S2C-UA 110 DC S2C-UA 230 AC S2C-UA 230 DC S2C-UA 400 AC Standards IEC/EN 60947-1 Rated voltage AC DC 12 V 24 V 24 V 48 V 48 V 110 V 110 V 230 V 230 V 400 V Frequency 50 ... 60 Hz Release trip 0.35 UnOVO 0.7 Un V Terminals 2 x 16/2 x 1.5 AWG/mm2 Resistance to corrosion constant atmosphere: 23/83 – 40/93 – 55/20; variable atmosphere: 25/95 – 40/93 °C/RH Protection degree IPXXB / IP2X Tightening torque 3.5/0.4 in.Ibs/Nm

Low Voltage Products & Systems 15.41 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Internal resistance and power loss Internal resistance per pole in mz, power loss per pole in W Type Rated current Device series B, C, D1 Device series K Device series Z A mz W mz W mz W S200 & S200P 0.5 5500 1.4 6340 1.6 10100 2.5 1 1440 1.4 1550 1.6 2270 2.3 1.6 630 1.6 695 1.8 1100 2.8 2 460 1.8 460 1.9 619 2.5 3 150 1.3 165 1.5 202 1.8 4 110 1.8 120 2.0 149 2.4 6 55 2.0 52 1.9 104 3.7 8 15 1.0 38 2.5 53.9 3.45 13 13.3 2.3 12.6 1.26 - - 1 Current intensities 0.5 - 4 apply exclusively to C-type trip characteristics Technical data S200, S200P & S200PR UL 1077, CSA 22.2, No. 235 Temperature derating Max operating current depending on the ambient temperature of a circuit breaker characteristics type B, C and D B, C, D, K, & Z Ambient Temperatures T (Cº/Fº) Amps -40/-40 -30/-22 -20/-4 -10/14 0/32 10/50 20/68 30/86 40/104 50/122 60/140 70/158 S200PR Rated current Internal resistance per pole 4) Power loss per pole 4) A mΩ W 0.2 25300 1.01 0.3 13700 1.23 0.5 4740 1.19 0.75 2067 1.16 1 1270 1.27 1.5 610 1.56 2 442 1.77 3 140 1.26 4 109 1.75 5 50 1.26 6 54 1.94 8 22 1.41 10 18.2 1.82 13 14.8 2.50 15 8.1 1.83 16 11.1 2.83 20 8.5 3.40 25 5.5 3.43 30 3.8 3.39 32 4.6 4.70 35 3.9 4.76 40 2.8 4.40 50 1.7 4.25 60 1.7 6.18 63 1.9 7.56

15.42 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Technical data S200 & S200P UL 1077, CSA 22.2, No. 235 Tripping characteristic B Tripping characteristic C Tripping characteristic D Tripping characteristic K Tripping characteristic Z

Low Voltage Products & Systems 15.43 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Approximate dimensions S200, S200P , S200PR UL 1077, CSA 22.2, No. 235 S200, S200P S200PR SU200PR Instructions for use

15.44 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 LS Addition of S2C-A...U Approximate dimensions S280UC, S2C-H6R, S2C-A...U UL 1077, CSA 22.2, No. 235 S2C-H6R, S2C-A... S2C S280UC

Low Voltage Products & Systems 15.45 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Miniaturecircuit breakers Application guide Miniature circuit breaker Application guide Introduction The circuit breaker plays an important role in providing over-current protection and a disconnect means in electrical networks. Recent advancements in circuit breaker technology has increased breaker performance and protection. Overload A slow and small overcurrent situation that causes the ampacity and temperature of the circuit to gradually increase over time. This type of event is characterized by a slight increase in the load (ampacity) on the circuit and is interrupted by the thermal trip unit of the breaker. Thermal Example 10A Breaker Light 15A The light draws more than 10 amps for an extended period of time creating a thermal overload. Short circuit A rapid and intense overcurrent situation that causes the ampacity of the circuit to increase. This type of event is characterized by a dramatic increase in the load (ampacity) on the circuit and is interrupted by the magnetic trip unit of the breaker. Magnetic Example 10A Breaker Light 10A The wire connected between the light and breaker is cut and shorted to ground creating a short circuit. Breaker definition A breaker is a device designed to isolate a circuit during an overcurrent event without the use of a fusible element. A breaker is a resettable protective device that protects against two types of overcurrent situations; Overload and Short Circuit. ABB current limiting breaker Tripping lever Operating mechanism Operator Electro-magnetic protection Upper terminal Thermal protection- bimetal Arc chamber Fixed contact Moving contact DIN rail holderLower terminal Space for identification marker

15.46 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Miniature circuit breakers Application guide Circuit breaker construction Thermal / Magnetic trip units definition ABB Current Limiting Breakers use an electromechanical (Thermal / Magnetic) trip unit to open the breaker contacts during a overcurrent event. The thermal trip unit is temperature sensitive and the magnetic trip unit is current sensitive. Both units act independently and mechanically with the breaker’s trip mechanism to open the breaker’s contacts. Overload protection The thermal trip unit protects against a continuous overload. The thermal unit is comprised of a bimetal element located behind the circuit breaker trip bar and is part of the breaker’s current carrying path. When there is an overload, the increased current flow heats the bimetal causing it to bend. As the bimetal bends it pulls the trip bar which opens the breaker’s contacts. The time required for the bimetal to bend and trip the breaker varies inversely with the current. Because of this, the tripping time becomes quicker as current increases in magnitude. Overload protection is applicable to any installation, conductor, or component which can be subjected to low-magnitude but long-time over- currents. Low-magnitude, long-time over-currents can be dangerous because they reduce the life of the electrical installation, conductor, and components and if left unchecked could result in fire. Magnetic trip units (short circuit protection) The Magnetic trip unit protects against a short circuit. The magnetic trip unit is comprised of an electromagnet and an armature. Components of a magnetic trip unit When there is a short circuit, a high magnitude of current passes through the coils creating a magnetic field that attracts the movable armature towards the fixed armature. The hammer trip is pushed against the movable contact and the contacts are opened. The opening of the breakers contacts during a short circuit is complete in .5 milli-seconds. Current Flow During Operation All highlighted components are energized during operation Magnetic Trip Unit Thermal Trip Unit Trip Bar Operating Mechanism Thermal Trip Unit Armature and Plunger Movable Contact Magnet Trip Unit

Low Voltage Products & Systems 15.47 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Miniaturecircuit breakers Application guide Circuit breaker construction Arc runners / Arc chutes The arc runner and arc chute limit and dissipate the arc energy during the interruption of an overload or short circuit event. During an overload or short circuit event, the contacts of the breaker separate and an electrical arc is formed between the contacts through air. The arc is moved into the arch chute by “running” the arc down the interior of the breaker along the arc runner. When the arc reaches the arc chute it is broken into small segmented arcs. The segmented arcs split the overall energy level into segments less than 25V. Each 25V segment does not have a high enough energy level to maintain an arc and all energy is naturally dissipated. Breaker curves Thermal Trip Unit (region one) The first sloping region of the breaker curve is a graphical representation of the tripping characteristics of the thermal trip unit. This portion of the curve is sloped due to the nature of the thermal trip unit. The trip unit bends to trip the breaker’s trip bar in conjunction with a rise in amperage (temperature) over time. As the current on the circuit increases, the temperature rises, the faster the thermal element will trip. Example using the curve below: If you had a 10A breaker and the circuit was producing 30 amps of current, the breaker would trip between 2 seconds and 1 minute. In this example you would find the circuit current on the bottom of the graph (Multiples of rated current). The first line is 10 amps (10 amp breaker x a multiple of one), the second line is 20 amps (10 amp breaker x multiple of 2), and the third line is 30 amps (10amp breaker x multiple of 3). Next you would trace the vertical 30A line up until it intersects the red portion of the breaker thermal curve. If you follow the horizontal lines, on both sides of the red curve, to the left you will see that the breaker can trip as fast as 2 seconds and no slower than 1 minute. Magnetic Trip Unit (region two) This region of the breaker curve is the instantaneous trip unit. ABB’s miniature circuit breaker’s instantaneous trip unit interrupts a short circuit in 2.3 to 2.5 milliseconds. Because of this the curve has no slope and is graphically represented as a vertical straight line. Example using the curve above: If you had a 10 amp breaker the magnetic trip element would interrupt a short circuit between 10 and 30 amps (10 amp breaker x multiple of 2 and 3) in 2.3 to 2.5 milliseconds. Breaker Contacts (region three) This region of the curve is the time required for the contacts of the breaker to begin to separate. The contacts will open in less than .5 milliseconds and is graphically represented by the bottom vertical portion of the curve. Arc Runner Arc Chute Magnetic Trip Unit (Region Two) Thermal Trip Unit (Region One) Moving Contacts (Region Three)

15.48 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Miniature circuit breakers Application guide Circuit breaker current limitation Current limiting definitions All ABB Miniature Circuit Breakers are UL tested and certified as current limiting protective devices. Current limiting circuit breakers provide a higher level of circuit protection than a typical zero point external breakers. UL AC 60Hz cycle UL defines an AC cycle as the potential energy of the wave form traveling from Zero-to-Positive amplitude, Positive-to-Zero amplitude, Zero-to- Negative amplitude, Negative-to-Zero amplitude 60 times in one second. One cycle is completed every 16.6 milliseconds. UL breaker current limiting UL defines breaker current limitation as a breaker that interrupts and isolates a fault in less than 1/2 of an AC cycle. 1/2 a cycle is completed in 8.3 milliseconds. NEC240.2 current limiting A device that, when interrupting current in its current-limiting range, reduces the current flowing in the faulted circuit to a magnitude substantially less than that obtainable in the same circuit if the device were replaced with a solid conductor having comparable impedance. IEC 60947-2 current limiting circuit breaker A circuit breaker with sufficiently short trip time to prevent the short-circuit current from reaching the peak value which would otherwise be reached. ABB current limiting breakers ABB current limiting breakers can interrupt and isolate a fault in 1/8 of an AC cycle. The breaker fault interruption is completed in 2.3 to 2.5 milliseconds. Zero point extinguishing breakers A typical zero point extinguishing breaker interrupts a fault and does not isolate the energy. The breaker allows an arc to be present between the open contacts until the AC wave form crosses zero. When the wave form crosses zero, the potential energy is zero and the arc (fault) naturally extinguishes. The arc could be present for up to 8.3 milliseconds. Current limiting breakers and electrical networks Current Limitation When a short-circuit condition occurs, the “ideal” current limiting circuit breaker opens before the current waveform can reach its full potential magnitude which occurs at ¼ cycle (4.17ms). ABB’s current limiting breakers can interrupt a fault in about ½ cycle or 2.3ms to 2.5ms. ABB’s current limiting breakers interrupt a short circuit in less than 1/8 cycle and limit the amount of current that can reach a circuit. Limiting the available current on the circuit provides additional protection against network, breaker, or bus damage and prevents the tripping of upstream breakers (selective coordination). IsqT The true destructive nature of a short circuit is measured by the time it is available combined with the peak value of the short circuit. The IsqT (Amps Squared over Time) value represents the amount of energy available on a network during a short circuit and is represented by the shaded area on the graph below. During a short circuit both magnetic forces and thermal energy combine to damage devices on the electrical network. The level of thermal energy and magnetic forces are directly proportional to the square of the current. The magnetic forces vary as a square of the peak current available and the thermal energy varies as a square of the RMS (root mean square) current available. ABB’s current limiting breakers will limit the let-through energy to a fraction (1/100 th) of the value which is available from the network. By comparison, a Zero Crossing breaker would let-through approximately 100 times as much destructive energy as the current limiting circuit breaker [ (100,000A / 10,000A) squared – 100X]. ABB’s current limiting breakers limit the short circuit current to a relatively small magnitude in a extremely short time, which dramatically limits a short circuit’s destructive energy.

Low Voltage Products & Systems 15.49 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Miniaturecircuit breakers Application guideCircuit breaker current limitation Current limiting and zero crossing breakers During the initial stages of a short circuit a breaker’s contacts open to interrupt the circuit. After the contacts open an arc forms in the air between the contacts on both the current limiting and zero crossing breaker contacts. What distinguishes a current limiting breaker from a zero crossing breaker is what each breaker does after an arc is formed between the open contacts. A current limiting breaker “runs” the arc down the breaker arc runner into an arc chute that extinguishes the arc. A zero crossing breaker does not attempt to extinguish the arc. The breaker is designed to withstand the energy of the arc long enough for the waveform to cross zero. When the wave form crosses zero the potential energy is zero and the arc naturally extinguishes itself. ABB’s current limiting breakers interrupt the arc energy in 2.3ms to 2.5ms (1/8 cycle) and a zero crossing breaker allows the arc to be present for up to 8.3ms (1/2 cycle). A zero crossing breaker will let through 100 times as much energy as an ABB current limiting breaker. Current limiting example The lab test report below details a 20A S200 series current limiting breaker interrupting a 28kA fault in 1.7 milliseconds. The total “I Square T” value is 32.0kA. Zero crossing example The test report below details a 20A Zero Point Extinguishing breaker interrupting a 9kA fault in 9 milliseconds. The total "I Square T" value is 104.0kA. 500 -500 V U-L2 100 /div -400 -300 -200 -100 100 200 300 400 kSample499.93 Sample/div -10 kA I-L2 2 k/div Time A Time B Legend Voltage Amps 500 -500 V U-BCP L2 100 /div -400 -300 -200 -100 100 200 300 400 kSample499.93 Sample/div -10 kA I-L2 2 k/div Time A Time B Legend Voltage Amps

15.50 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Miniature circuit breakers Application guide Selective coordination and series ratings IEC 60497-1 selective coordination definition Coordination between the operating characteristics of two or more over- current protection devices, so that when an over-current within established limits occurs, the device designated to operate within those limits trips whereas the other do not trip. Example of breaker coordination When an over-current event occurs at the branch breaker level (CB1), and the event is within the operating characteristics of the breaker, then the branch breaker should interrupt the circuit (open) and the main breaker should remain closed and energized. The chart below gives a graphical representation of a down stream branch breaker (B curve) and a main breaker (A curve) with coordination. The separation between the curves allows the branch breaker to react to the fault and the main breaker remain closed and energized. Example of no breaker coordination Selective breaker coordination is not achieved when there is an overload event at the branch breaker level (MCB1) and both the branch breaker and main breaker interrupt the circuit (open). When there is no breaker coordination several circuits lose power that should remain operational during and after the overload event. The chart below gives a graphical representation of a down stream branch breaker (B curve) and a main breaker (A curve) without coordination. There is no separation between the curves. The branch breaker will react to a fault and the main breaker will open and de-energize all circuits down stream. Problems in coordination occur when the branch breaker allows the "I Square T" value of the short circuit to rise to a level that is in the operating range of the up-stream main breaker. Proper breaker coordination is easier to achieve with the use of current limiting breakers at the branch level. Selective coordination and current limiting breakers Recent improvements in ABB circuit breaker technology has pushed the performance of breakers to the same level as fuses. The reaction time and tripping characteristics of current limiting breakers are now on par with fuses. This allows ABB to provide a high level of coordination between branch breakers and the main. A current limiting branch breaker will limit the “I Square T” value well below the level of the operating range of the up- stream main breaker. ABB’s current limiting branch breakers can coordinate between the main breaker up to 35kA. Selective coordination and zero crossing breakers Zero crossing breakers do not limit the “I Square T” value. They wait for the wave form to cross zero and allow a high level of let-through energy to pass through the system. The “I Square T” value of a zero crossing breaker is high enough that the main breaker will likely trip during a short circuit. With zero crossing breakers it is extremely difficult to coordinate between branch and main breakers. A typical zero crossing breaker’s coordination level is below 10kA. There are a few manufactures that have achieved coordination between a branch zero crossing breaker and the main by slowing the performance (protection) of the main breaker. Main breaker CB1 CB2 CB3 CB4 Short circuit

Low Voltage Products & Systems 15.51 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Miniaturecircuit breakers Application guideSelective coordination and series ratings Series ratings –vs- selective coordination Selective coordination Selective coordination is achieved when there is a short circuit on a branch circuit breaker, the branch breaker opens and isolates the fault, and the main breaker remains closed. The rating is usually a value above the “stand alone” interrupting rating of the branch breaker and the “stand alone” rating of the main breaker. Example: 65kA rated main breaker 10kA rated branch breaker Coordination between the two breakers up to 35kA There can be a short circuit on the branch breaker up to 35kA where the branch will open (CB1) and the main breaker will remain closed. Although the branch has a 10kA “stand alone” rating both the breakers work together to limit the available short circuit to allow the branch (CB1) to isolate the fault. Series ratings Series ratings are different from coordination ratings. Unlike coordination ratings where the branch opens and the main remains closed, a series rated combination is one where both the branch and main breakers open and work together to isolate the fault. The series rating combination of two breakers is equal to the “stand alone” interrupting value of the main breaker. This is a result of the main breaker let-through value being lower than the “stand alone” interrupting value of the branch breaker. During a short circuit the main breaker will limit the energy to a level that is below the “stand alone” value of the branch breaker. Example: 65kA rated main breaker 10kA rated branch breaker Series combination rating between the two breakers up to 65kA There can be a short circuit on the branch breaker up to 65kA where the branch will open and the main breaker will open. Although the branch breaker (CB1) has a 10kA “stand alone” rating the main breaker has a let- through value below 10kA. If there is a fault up to 65kA on the network the main breaker will limit the energy to a value less than the rating of the branch breaker (CB1). Both breakers will trip (no coordination) but the network can safely withstand a fault of 65kA. Main breaker 65 kA CB1 10 kA CB2 10 kA CB3 10 kA CB4 10 kA 35 kA or 65 kA short circuit

15.52 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Miniature circuit breakers Application guide Tripping lever Operating mechanism Operator Electro-magnetic protection Upper terminal Thermal protection-bimetal Arc chamber Fixed contact Moving contact DIN rail clipLower terminal Space for identification marker Miniature circuit breaker cutaway

Low Voltage Products & Systems 15.53 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Amperage Voltage Poles Trip characteristics Interrupting ratings Auxiliary contacts Bell alarm Shunt trip Undervoltage release Ring tongue S800U 10 – 100 A 1, 2, 3, 4 poles Z, K 30kA: UL 489, single pole 50kA: UL 489, multi-pole Yes Yes Yes Yes Yes S800 High performance circuit breakers UL 489 Series The S800 high performance MCB offers a compact solution to circuit protection. The S800 devices are DIN rail mounted. The S800 is available with application-specific trip characteristics to provide maximum circuit protection. The breakers offer thermal-magnetic trip protection according to Z and K characteristics. For the worldwide market, the breakers carry CSA, IEC, CE and many other agency approvals.

  • Energy limiting
  • Fast breaking time (2.3 – 2.5 ms)
  • Wide range of accessories
  • DIN rail mounting
  • Finger safe terminals
  • Multi-function terminals
  • Ring tongue compatible
  • UL489 File # E312425 S800 UL 489 Series High performance circuit breakers

15.54 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 S800U-K, 240 VAC Branch circuit protection UL 489 K No. of poles Rated current Catalog number No. of poles Rated current Catalog number

10 S801U-K10

10 S803U-K10

15 S801U-K15 15 S803U-K15

20 S801U-K20 20 S803U-K20

25 S801U-K25 25 S803U-K25

30 S801U-K30 30 S803U-K30

40 S801U-K40 40 S803U-K40

50 S801U-K50 50 S803U-K50

60 S801U-K60 60 S803U-K60

70 S801U-K70 70 S803U-K70

80 S801U-K80 80 S803U-K80

90 S801U-K90 90 S803U-K90

100 S801U-K100 100 S803U-K100

10 S802U-K10

10 S804U-K10

15 S802U-K15 15 S804U-K15

20 S802U-K20 20 S804U-K20

25 S802U-K25 25 S804U-K25

30 S802U-K30 30 S804U-K30

40 S802U-K40 40 S804U-K40

50 S802U-K50 50 S804U-K50

60 S802U-K60 60 S804U-K60

70 S802U-K70 70 S804U-K70

80 S802U-K80 80 S804U-K80

90 S802U-K90 90 S804U-K90

100 S802U-K100 100 S804U-K100

30 kA, single pole 50 kA, multi-pole Resistive loads

  • K Curve
  • Designed for use in cable protection
  • Example: control circuits, lighting Accessories & technical data Accessories – See page 15.52 Technical data – See page 15.76 - 15.82 10 000 1000 100 2 10 20 301 3 0.1 0.01 seconds multiple of rated current

Low Voltage Products & Systems 15.55 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Z No. of poles Rated current Catalog number No. of poles Rated current Catalog number

10 S801U-Z10

10 S803U-Z10

15 S801U-Z15 15 S803U-Z15

20 S801U-Z20 20 S803U-Z20

25 S801U-Z25 25 S803U-Z25

30 S801U-Z30 30 S803U-Z30

40 S801U-Z40 40 S803U-Z40

50 S801U-Z50 50 S803U-Z50

60 S801U-Z60 60 S803U-Z60

70 S801U-Z70 70 S803U-Z70

80 S801U-Z80 80 S803U-Z80

90 S801U-Z90 90 S803U-Z90

100 S801U-Z100 100 S803U-Z100

10 S802U-Z10

10 S804U-Z10

15 S802U-Z15 15 S804U-Z15

20 S802U-Z20 20 S804U-Z20

25 S802U-Z25 25 S804U-Z25

30 S802U-Z30 30 S804U-Z30

40 S802U-Z40 40 S804U-Z40

50 S802U-Z50 50 S804U-Z50

60 S802U-Z60 60 S804U-Z60

70 S802U-Z70 70 S804U-Z70

80 S802U-Z80 80 S804U-Z80

90 S802U-Z90 90 S804U-Z90

100 S802U-Z100 100 S804U-Z100

S800U-Z, 240 VAC Branch circuit protection UL 489 Tripping characteristic Z UL 489 30 kA, single pole 50 kA, multi-pole Resistive loads

  • Z Curve
  • Designed for use in cable protection
  • Example: control circuits, lighting Accessories & technical data Accessories – See page 15.52 Technical data – See page 15.76 - 15.82 10 000 1000 100 2 10 20 301 3 5 0.1 0.01 seconds multiple of rated current

15.56 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 S803W-SCL-SR UL Short circuit current limiter Self-resetting S803W-SCL-SR UL version short circuit current limiter, self resetting, 3 pole Item Catalog number 32A Self resetting current limiter S803W-SCL32-SR 63A Self resetting current limiter S803W-SCL63-SR 100A Self resetting current limiter S803W-SCL100-SR Approved combinations with motor starter Downstream devices Upstream devices S803W-SCL-SR Self resetting short-circuit limiter Rated current Ie [A] 32 63 100 MS/MO325 0.1–2.5 ■ ■ ■ 4 ■ ■ ■ 6.3 ■ ■ ■ 9 ■ ■ ■ 12.5 ■ ■ ■ 16 ■ ■ ■ 20 ■ ■ 25 ■ ■ MS/MO132 0.1–2.5 ■ ■ 4 ■ ■ 6.3 ■ ■ ■ 10 ■ ■ ■ 16 ■ ■ ■ 20 ■ ■ 25 ■ ■ 32 ■ ■ – Combinations with S500-K and S500-KM on request ■ Applies for all voltages according to the table below S803W-SCL-SR Rated ultimate short-circuit breaking capacity Short-circuit rating according to UL 508, CSA 22.2 (AC) 50/60 Hz 480 V [kA] 65 (AC) 50/60 Hz 600 V [kA] 65 Icu = Ics according to IEC 60947-2 (AC) 50/60 Hz 240/415 V [kA] 100 (AC) 50/60 Hz 254/440 V [kA] 100 (AC) 50/60 Hz 277/480 V [kA] 65 (AC) 50/60 Hz 289/500 V [kA] 65 (AC) 50/60 Hz 346/600 V [kA] 65 (AC) 50/60 Hz 400/690 V [kA] 50 Technical data Rated voltage 600 VAC per UL508 Short circuit current rating according to UL508, CSA 22.2 480 VAC 50/60 Hz, 65 kA

600 VAC 50/60 Hz, 65 kA

Low Voltage Products & Systems 15.57 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A S803W-SCL-SR UL508 Short circuit current limiter Approximate dimensions x Minimum cable length between S803W-SCL-SR and downstream devices (Connection has to be short-circuit proofed acc. to IEC 61439-1) MS/M0325 MS/M0132 S800 S800-SCL-SR min. length X min. cross section

32 A 80 mm 6 mm2

63 A 80 mm 16 mm2

15.58 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 S800W-RSU Remote sensing unit UL489 S800W-RSU S800W-RSU mounted on MCB Key Features

  • The remote Switching unit S800W-RSU has a brushless high precision DC motor to ensure fast remote control operation.
  • Low power consumption
  • Short switching times
  • The S800W-RSU is mounted on any multipole S800 High Performance MCB
  • Installation and wiring can be field installable
  • The connection is done by a 10-pole Micro Fit 3.0 (not included in delivery)
  • The S800W-RSU can be operated by a standard pushbutton or drive by a PLC Switching times
  • OFF -> ON <<500ms from signal to contact closing
  • ON -> OFF <<250ms from signal to contact opening
  • TRIP -> OFF -> ON <<1500ms from signal to contact closing For differing requirements, please contact your local ABB partner Safety intelligence
  • Inputs are deactivated when detecting manual use
  • All outputs become active when spindle is rotated more than 360 degrees
  • S800W-RSU is locked for 5 minutes after three switching attempts leading to a trip
  • Manual switch off possible for 3 & 4 pole devices Remote switching unit Item Catalog number Remote switching unit S800W-RSU S800W-RSU S800-RSU cable including plug Item Catalog number 3 meter cable 0.5mm2 (AWG20) inclusing 10 pole Micro Fit 3.0 plug S800-RSU-CP S800-RSU-CP Technical specifications Operational voltage 24 VDC Current consumption Irms 2,5 Standby current IStandby < 50mA Switching time OFF-ON < 500 msec Switching time ON-OFF <250 mse Ambient operation temperature -25…+70°C Number of switching operations 10.000 Maximum cable lengths(AWG20/ 0.5mm2) 10m Degree of protection (mounted) IP2 Weight 300 gr Connection 10 pole Micro Fit 3.0 Approximate dimensions

Low Voltage Products & Systems 15.59 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A S800 High performance circuit breakers IEC Series The S800 high performance MCB offers a compact solution to circuit protection. The S800 devices are IEC tested current limiting and DIN rail mounted. The S800 is available with application-specific trip characteristics to provide maximum circuit protection. The breakers offer thermal-magnetic trip protection according to B, C, D & K characteristics. For the worldwide market, the breakers carry CSA, IEC, CE and many other agency approvals.

  • Current limiting
  • Fast breaking time (2.3 – 2.5 ms)
  • Wide range of accessories
  • DIN rail mounting
  • Finger safe terminals
  • Multi-function terminals
  • Ring tongue compatible S800 IEC Series S800S Amperage 10 – 125 A Voltage 690 VAC Poles 1, 2, 3, 4 Trip characteristics B, C, D, K Interrupting ratings 50 kA : IEC Auxiliary contacts Yes Bell alarm Yes Shunt trip Yes Undervoltage release Yes Ring tongue Yes High performance circuit breakers

15.60 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 B S804U-B S803U-B S802U-B S801U-B S800S-B, 690 VAC IEC No. of poles Rated current Catalog number No. of poles Rated current Catalog number

10 S801S-B10

10 S803S-B10

13 S801S-B13 13 S803S-B13

16 S801S-B16 16 S803S-B16

20 S801S-B20 20 S803S-B20

25 S801S-B25 25 S803S-B25

32 S801S-B32 32 S803S-B32

40 S801S-B40 40 S803S-B40

50 S801S-B50 50 S803S-B50

63 S801S-B63 63 S803S-B63

80 S801S-B80 80 S803S-B80

100 S801S-B100 100 S803S-B100

125 S801S-B125 125 S803S-B125

10 S802S-B10

10 S804S-B10

13 S802S-B13 13 S804S-B13

16 S802S-B16 16 S804S-B16

20 S802S-B20 20 S804S-B20

25 S802S-B25 25 S804S-B25

32 S802S-B32 32 S804S-B32

40 S802S-B40 40 S804S-B40

50 S802S-B50 50 S804S-B50

63 S802S-B63 63 S804S-B63

80 S802S-B80 80 S804S-B80

100 S802S-B100 100 S804S-B100

125 S802S-B125 125 S804S-B125

690 VAC

  • B Curve
  • Designed for use in cable protection
  • Example: control circuits, lighting Accessories & technical data Accessories – See page 15.52 Technical data – See page 15.76 - 15.82 10 000 1000 100 2 10 20 301 3 5 0.1 0.01 seconds multiple of rated current

Low Voltage Products & Systems 15.61 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A C S804S-C S803S-C S802S-C S801S-C S800S-C, 690 VAC IEC No. of poles Rated current Catalog number No. of poles Rated current Catalog number

10 S801S-C10

10 S803S-C10

13 S801S-C13 13 S803S-C13

16 S801S-C16 16 S803S-C16

20 S801S-C20 20 S803S-C20

25 S801S-C25 25 S803S-C25

32 S801S-C32 32 S803S-C32

40 S801S-C40 40 S803S-C40

50 S801S-C50 50 S803S-C50

63 S801S-C63 63 S803S-C63

80 S801S-C80 80 S803S-C80

100 S801S-C100 100 S803S-C100

125 S801S-C125 125 S803S-C125

10 S802S-C10

10 S804S-C10

13 S802S-C13 13 S804S-C13

16 S802S-C16 16 S804S-C16

20 S802S-C20 20 S804S-C20

25 S802S-C25 25 S804S-C25

32 S802S-C32 32 S804S-C32

40 S802S-C40 40 S804S-C40

50 S802S-C50 50 S804S-C50

63 S802S-C63 63 S804S-C63

80 S802S-C80 80 S804S-C80

100 S802S-C100 100 S804S-C100

125 S802S-C125 125 S804S-C125

  • C Curve
  • Designed for use with medium magnetic start up currents
  • Example: lighting, control panels Accessories & technical data Accessories – See page 15.52 Technical data – See page 15.76 - 15.82 10 000 1000 100 2 10 20 301 3 5 0.1 0.01 seconds multiple of rated current

15.62 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 S800S-D, 690 VAC IEC D No. of poles Rated current Catalog number No. of poles Rated current Catalog number

10 S801S-D10

10 S803S-D10

13 S801S-D13 13 S803S-D13

16 S801S-D16 16 S803S-D16

20 S801S-D20 20 S803S-D20

25 S801S-D25 25 S803S-D25

32 S801S-D32 32 S803S-D32

40 S801S-D40 40 S803S-D40

50 S801S-D50 50 S803S-D50

63 S801S-D63 63 S803S-D63

80 S801S-D80 80 S803S-D80

100 S801S-D100 100 S803S-D100

125 S801S-D125 125 S803S-D125

10 S802S-D10

10 S804S-D10

13 S802S-D13 13 S804S-D13

16 S802S-D16 16 S804S-D16

20 S802S-D20 20 S804S-D20

25 S802S-D25 25 S804S-D25

32 S802S-D32 32 S804S-D32

40 S802S-D40 40 S804S-D40

50 S802S-D50 50 S804S-D50

63 S802S-D63 63 S804S-D63

80 S802S-D80 80 S804S-D80

100 S802S-D100 100 S804S-D100

125 S802S-D125 125 S804S-D125

  • D Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.52 Technical data – See page 15.76 - 15.82 S804S-D S803S-D S802S-D S801S-D 10 000 1000 100 2 10 20 301 3 0.1 0.01 seconds multiple of rated current

Low Voltage Products & Systems 15.63 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A K S800S-K, 690 VAC IEC No. of poles Rated current Catalog number No. of poles Rated current Catalog number

10 S801S-K10

10 S803S-K10

13 S801S-K13 13 S803S-K13

16 S801S-K16 16 S803S-K16

20 S801S-K20 20 S803S-K20

25 S801S-K25 25 S803S-K25

32 S801S-K32 32 S803S-K32

40 S801S-K40 40 S803S-K40

50 S801S-K50 50 S803S-K50

63 S801S-K63 63 S803S-K63

80 S801S-K80 80 S803S-K80

100 S801S-K100 100 S803S-K100

125 S801S-K125 125 S803S-K125

10 S802S-K10

10 S804S-K10

13 S802S-K13 13 S804S-K13

16 S802S-K16 16 S804S-K16

20 S802S-K20 20 S804S-K20

25 S802S-K25 25 S804S-K25

32 S802S-K32 32 S804S-K32

40 S802S-K40 40 S804S-K40

50 S802S-K50 50 S804S-K50

63 S802S-K63 63 S804S-K63

80 S802S-K80 80 S804S-K80

100 S802S-K100 100 S804S-K100

125 S802S-K125 125 S804S-K125

  • K Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.52 Technical data – See page 15.76 - 15.82 10 000 1000 100 2 10 20 301 3 0.1 0.01 seconds multiple of rated current

15.64 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 S800-SOR S800-UVR Shunt trip For remote tripping of breaker, a shunt trip device can be added to the MCB. The device opens the breaker after control voltage is applied. Description (for field mounting, left side) Catalog number Shunt operation release 24 VAC/DC S800-SOR24 Shunt operation release 48...130 VAC/DC S800-SOR130 Shunt operation release 110...250 VAC/DC S800-SOR250 Undervoltage release When control voltage drops below approximately 50 % of rated voltage, the UVR opens the breaker. The breaker can not be operated unless proper control voltage is first applied to the UVR coil. Description Catalog number Under voltage release 24...36 VAC/DC Under voltage release 48...60 VAC/DC Under voltage release 110...130 VAC/DC Under voltage release 220...250 VAC/DC S800-UVR36 S800-UVR60 S800-UVR130 S800-UVR250Auxiliary contacts The auxiliary contacts will signal whether the breaker is in the ON or OFF position. Description Catalog number Auxiliary contact S800-AUX Bell alarm The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically the contacts would be connected to an alarm or bell to signal the operator that an overcurrent trip has occurred. The bell alarm also includes a test button for testing the alarm contacts without opening the breaker. Description Catalog number Bell alarm S800-AUX/ALT S800-AUX S800-AUX/ALT Accessories S800U & S800S UL & IEC

Low Voltage Products & Systems 15.65 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Accessories S800U & S800S UL & IEC S800-RD S800-RHE-H S800-RHE-EM S800-RHE-S Ring tongue adaptor Description Catalog number Ring terminal cable connection, 40-125A S800-RT2125 Rotary operating mechanism Allows “through the door” operation. Description Catalog number Handle mechanism S800-RD Description Catalog number Grey rotary handle S800-RHE-H Description Catalog number Red rotary handle S800-RHE-EM Description Catalog number Shaft extension S800-RHE-S S800-RT2125 UL Locking device Description Catalog number Padlock not included S800U-PLL S800U-PLL

15.66 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 [A] [V] [kA] [kA] [V] [kA] [kA] [kA] [kA] [Hz] [Nm] [°C] S800U K, Z 10...100 1...4 240 14–2 AWG 8–1 AWG 3,5 (31 in.lb.) IP40 (actuating end only) any cadmium-free –25...+60 UL 489 IEC 60947-2 CSA22.2 NO.5-02 cULus File E312425 Characteristics Rated operational current I e Pole Rated operational voltage U e compliant to UL 489 (AC) 50/60 Hz Rated ultimate short-circuit breaking capacity compliant to UL489 (AC) 50/60 Hz 240 V Single-pole (AC) 50/60 Hz 240 V Multipole Rated operational voltage U e compliant to IEC 60947-2 (AC) Rated ultimate short-circuit breaking capacity I cu compliant to IEC 60947-2 (AC) 50/60 Hz 240/415 V Single-pole (AC) 50/60 Hz 240/415 V Multipole Rated service short-circuit breaking capacity I cs compliant to IEC 60947-2 (AC) 50/60 Hz 240/415 V Single-pole (AC) 50/60 Hz 240/415 V Multipole Connections C u 10...30 A 40...100 A Rated frequency Tightening torque Protection category Mounting position Contacts Permissible ambient temperature Standards Approval Technical data S800U UL

Low Voltage Products & Systems 15.67 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A [A] 100 [W] K, Z 1.5 2.7 3.5 4.2 2.8 3.7 4.3 5.8 4.9 6.4 6.5 8.3 Typical internal resistances and power losses at 25°C ambient temperature Rated current I n Internal resistance R i Power loss P v S800U-K, -Z In [A] 100 10 °C 10.9 16.5 22.0 27.5 33.1 44.0 55.1 66.2 76.9 88.0 99.1 110.5 15 °C 10.7 16.0 21.4 26.8 32.1 42.8 53.5 64.2 74.9 85.6 96.3 107.0 20 °C 10.4 15.6 20.8 26.0 31.2 41.6 52.0 62.4 72.8 83.2 93.6 104.0 25 °C 10.0 15.0 20.0 25.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0 30 °C 9.6 14.4 19.2 24.0 28.8 38.4 48.0 57.6 67.2 76.8 86.4 96.0 35 °C 9.3 14.0 18.6 23.3 27.9 37.2 46.5 55.8 65.1 74.4 83.7 93.0 40 °C 9.0 13.5 18.0 22.5 27.0 36.0 45.0 54.0 63.0 72.0 81.0 90.0 45 °C 8.7 13.0 17.4 21.8 26.1 34.8 43.5 52.2 60.9 69.6 78.3 87.0 50 °C 8.4 12.6 16.8 21.0 25.2 33.6 42.0 50.4 58.8 67.1 75.6 83.8 55 °C 8.0 12.0 16.0 20.0 24.0 32.0 40.0 48.0 56.0 64.0 72.0 80.0 60 °C 7.6 11.4 15.2 19.0 22.9 30.9 38.3 46.0 53.4 61.6 69.5 77.8 Influence of ambient temperature Devices mounted singly (specifications in A) Technical data S800U UL [mΩ] K, Z 15.2 12.1 8.7 6.8 3.1 2.3 1.7 1.6 1.0 1.0 0.8 0.8

15.68 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Internal resistance and power loss Internal resistance per pole in mz, power loss per pole in W Type Rated current A Device series B C D K mz Power loss B C D K W S800S 10 15.2 1.5 13 12.1 2.0 16 12.1 3.1 20 8.7 3.5 25 6.8 4.2 32 3.1 3.1 40 2.3 3.7 50 1.7 4.3 63 1.6 6.2 80 1.0 6.4 100 0.8 8.3 125 0.6 9.4 Technical data S800S IEC Temperature derating Max. operating current values depending on the ambient temperature for a circuit-breaker in load circuit of type B, C, D, & K characteristics. S800S-K Ambient temperature T (°C/°F) In [A] 100 125 11.9 15.6 19.1 23.9 29.9 38.2 47.8 59.7 75.3 95.6 119.5 149.4 11.6 15.1 18.6 23.2 29.1 37.2 46.5 58.1 73.2 93.0 116.2 145.3 11.2 14.6 17.9 22.4 28.0 35.8 44.8 56.0 70.6 89.6 112.0 140.0 11.0 14.3 17.6 22.0 27.5 35.2 44.0 55.0 69.3 88.0 110.0 137.5 10.7 13.9 17.1 21.4 26.8 34.2 42.8 53.5 67.4 85.6 107.0 133.8 10.4 13.5 16.6 20.8 26.0 33.3 41.6 52.0 65.5 83.2 104.0 130.0 10.0 13.0 16.0 20.0 25.0 32.0 40.0 50.0 63.0 80.0 100.0 125.0 9.6 12.5 15.4 19.2 24.0 30.7 38.4 48.0 60.5 76.8 96.0 120.0 9.3 12.1 14.9 18.6 23.3 29.8 37.2 46.5 58.6 74.4 116.3 9.0 11.7 14.4 18.0 22.5 28.8 36.0 45.0 56.7 72.0 90.0 112.5 8.7 11.3 13.9 17.4 21.8 27.8 34.8 43.5 54.8 69.6 87.0 108.8 S800S-B, -C, -D Ambient temperature T (°C/°F) In [A] 100 125 11.2 14.6 17.9 22.4 28.0 35.8 44.8 56.0 70.6 89.6 112.0 140.0 11.0 14.3 17.6 22.0 27.5 35.2 44.0 55.0 69.3 88.0 110.0 137.5 10.7 13.9 17.1 21.4 26.8 34.2 42.8 53.5 67.4 85.6 107.0 133.8 10.4 13.5 16.6 20.8 26.0 33.3 41.6 52.0 65.5 83.2 104.0 130.0 10.0 13.0 16.0 20.0 25.0 32.0 40.0 50.0 63.0 80.0 100.0 125.0 9.6 12.5 15.4 19.2 24.0 30.7 38.4 48.0 60.5 76.8 96.0 120.0 9.3 12.1 14.9 18.6 23.3 29.8 37.2 46.5 58.6 74.4 93.0 116.3 9.0 11.7 14.4 18.0 22.5 28.8 36.0 45.0 56.7 72.0 90.0 112.5 8.7 11.3 13.9 17.4 21.8 27.8 34.8 43.5 54.8 69.6 87.0 108.8 8.4 10.9 13.4 16.8 21.0 26.9 33.6 42.0 52.9 67.2 84.0 105.0 8.0 10.4 12.8 16.0 20.0 25.6 32.0 40.0 50.4 64.0 80.0 100.0

Low Voltage Products & Systems 15.69 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Technical data S800S IEC 10 000 1000 100 2 10 20 301 3 0.1 0.01 seconds multiple of rated current 10 000 1000 100 2 10 20 301 3 0.1 0.01 seconds multiple of rated current 10 000 1000 100 2 10 20 301 3 5 0.1 0.01 seconds multiple of rated current 10 000 1000 100 2 10 20 301 3 5 0.1 0.01 seconds multiple of rated current 10 000 1000 100 2 10 20 301 3 5 0.1 0.01 seconds multiple of rated current Tripping Characteristic B Tripping Characteristic C Tripping Characteristic D Tripping Characteristic ZTripping Characteristic K

15.70 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Technical data S800U & S800S Accessories Auxiliary contact S800-AUX S800-AUX Usage category AC15 400/2 A-UL AC15 240/ -UL DC13 250/0.55 A125 V/1.1A-IEC DC13 125 V/1.1A DC13 60 V/2A DC13 24 V/4A Continuous thermal current In 6 A Rated insulation voltage Ui 690 V Number of contacts 2 Surge Utest (1.2/50µs) 6 kV Degree of protection 3 Function of contact Changeover contacts Connection Cu 1 x 2.5 mm2 2 x 1.5 mm2 Tightening torque 1 Nm Ensured contacts during shake test 5g, 20 frequency cycle acc. to IEC 68-2-6 at 24 VAC/DC, 5mA brief interrupt <10 ms AC/DC supply any EN 60715 Mounting on DIN top hat rail EN 60715 IP20 Type of protection IP20 Mechanical device service life 6000 switching cycles Icu with S450E 1000 A Resistance to vibration IEC 60068-2-27; IEC 60068-2; EN 61373 Cat.1/class B Undervoltage release S800-UVR S800-UVR36 S800-UVR60 S800-UVR130 S800-UVR250 Rated voltage Ue 24...36 VAC/DC 48...60 VAC/DC 110...130 VAC/DC 220...250 VAC/DC Operating range Operating opening 35...70% Ue Operating clothing 85% Ue Rated insulation voltage Ui 690 V Coil pull in consumption 1 W, 14 vA 1 W, 25 vA 1 W, 41 vA 1 W, 91 vA Rated frequency DC; 50/60 Hz Protection degree 3 Connection Cu 1...35 cable Tightening torque min.3/ max.4 Nm AC/DC supply any DIN top hat rail EN 60715 Type of protection IP20 IP40 (only actuation side) Resistance to vibration IEC 60068-2-27; IEC 60068-2; EN61373 Cat.1/class B

Low Voltage Products & Systems 15.71 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Technical data S800U & S800S Accessories Combined auxiliary and bell alarm Usage category AC15 400/2A-UL AC15 240/6A-UL DC13 250/0.55A125V/1.1A-IEC DC13 125V/1.1A-IEC DC13 60V/2A DC13 24V/4A Continuous thermal current In 6 A Rated insulation voltage Ui 690 V Number of contacts 2 (1x AUX, 1 x AUX/ALT) Surge Utest (1.2/50µs) 6 kV Degree of protection 3 Function of contact Changeover contacts Connection Cu 1 x 2.5 mm2 2 x 1.5 mm2 Tightening torque 1 Nm Ensured contacts during shake test 5g, 20 frequency cycle at 24VAC/DC, 5mA brief interrupt <10ms AC/DC supply any EN 60715 Mounting on DIN top hat rail EN 60715 Type of protection IP20 mech. Device service life 6000 switching cycles Icu with S450E 1000 A Resistance to vibration IEC 60068-2-27; IEC 60068-2; EN 61373 Cat.1/class B Shunt operation release – S800-SOR S800-SOR24 S800-SOR130 S800-SOR250 S800-SOR400 Operating range 70... 110% Ue Rated insulation voltage Ui 690 V Coil pull in consumption 19.2 W/vA On request Rated frequency DC; 50/60 Hz Degree of protection 3 Connection Cu 1...35 AWG Tightening torque min.3/ max.4 Nm AC/DC supply any DIN top hat rail EN 60715 Type of protection IP20; IP40 (only actuation side) Resistance to vibration IEC 60068-2-27; IEC 60068-2; EN61373 Cat.1/class B

15.72 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Technical data Backup S800S - S200 @ 230/400 V E. S800S Char. B, C, D, K L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 B 6 6 50 50 50 50 50 50 50 50 10 50 50 50 50 50 50 50 50 13 50 50 50 50 50 50 50 50 16 50 50 50 50 50 50 50 50 20 50 50 50 50 50 50 50 25 50 50 50 50 50 50 32 50 50 50 50 50 40 50 50 50 50 50 50 50 50 63 50 50 E. S800S Char. B, C, D, K L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 C 6 0.5…6 50 50 50 50 50 50 50 50 8 50 50 50 50 50 50 50 50 10 50 50 50 50 50 50 50 50 13 50 50 50 50 50 50 50 50 16 50 50 50 50 50 50 50 50 20 50 50 50 50 50 50 50 25 50 50 50 50 50 50 32 50 50 50 50 50 40 50 50 50 50 50 50 50 50 63 50 50 E. S800S Char. B, C, D, K L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P B 6…16 50 50 50 50 50 50 50 50 20 50 50 50 50 50 50 50 25 50 50 50 50 50 50 32 50 50 50 50 50 40 50 50 50 50 50 50 50 50 63 50 50 E. S800S Char. B, C, D, K L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P C 0.5…16 50 50 50 50 50 50 50 50 20 50 50 50 50 50 50 50 25 50 50 50 50 50 50 32 50 50 50 50 50 40 50 50 50 50 50 50 50 50 63 50 50 LEGEND E. = supply side L. = load side Back-up limit values are specified in kA

Low Voltage Products & Systems 15.73 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Technical data Selectivity S800S - S200 @ 230/400 V E. S800S Char. B L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 D 6

0.5 T T T T T T T T

1 0.8 4.5 T T T T T T 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.3 T T T T 4 0.4 0.4 0.7 1 1.7 3 T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800S Char. B L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 K 6 1 0.8 5 T T T T T T 1.6 0.5 1 2.1 T T T T T 2 0.3 0.5 0.7 2.1 T T T T 4 0.4 0.4 0.7 1 1.7 3 T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800S Char. B L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 B 6 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800S Char. B L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 C 6 1 3.3 T T T T T T T 1.6 0.6 1.3 T T T T T T 2 0.4 0.7 1.3 T T T T T 8 0.4 0.6 0.7 1 1.4 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 LEGEND E. = supply side L. = load side Back-up limit values are specified in kA

15.74 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 E. S800S Char. C L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 D 6 1 2.1 T T T T T T T 1.6 0.8 2.3 T T T T T T 2 0.4 0.7 2.3 T T T T T 13 0.7 1 1.4 2 16 1 1.4 2 20 1 1.4 25 1.4 E. S800S Char. C L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 K 6 1 2.1 T T T T T T T 1.6 0.8 2.3 T T T T T T 2 0.4 0.7 2.3 T T T T T 13 0.7 1 1.4 2 16 1 1.4 2 20 1 1.4 25 1.4 E. S800S Char. C L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 B 6 32 0.5 0.6 0.8 1 1.4 40 0.6 0.8 1 1.4 50 0.7 0.9 1.3 63 0.9 1.2 E. S800S Char. C L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 C 6

1 T T T T T T T T

1.6 0.6 T T T T T T T 2 0.5 1 T T T T T T 32 0.5 0.6 0.8 1 1.4 40 0.6 0.8 1 1.4 50 0.7 0.9 1.3 63 0.9 1.2 Technical data Selectivity S800S - S200 @ 230/400 V LEGEND E. = supply side L. = load side Back-up limit values are specified in kA

Low Voltage Products & Systems 15.75 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Technical data Selectivity S800S - S200 @ 230/400 V LEGEND E. = supply side L. = load side Back-up limit values are specified in kA E. S800S Char. D L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 D 6

1.6 T T T T T T T T

2 2.3 T T T T T T T 3 0.7 1.3 4.4 T T T T T 4 0.7 1 2.2 4.4 T T T T 25 1.1 1.8 2.2 3.2 32 1.7 2 2.9 40 1.9 2.6 50 2.2 E. S800S Char. D L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 K 6 2 2.3 T T T T T T T 3 0.7 1.3 4.4 T T T T T 4 0.7 1 2.2 4.4 T T T T 25 1.1 1.8 2.2 3.2 32 1.7 2 2.9 40 1.9 2.6 50 2.2 E. S800S Char. D L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 B 6 6 0.5 1 1.2 2 2.8 T T T 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 E. S800S Char. D L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 C 6

2 T T T T T T T T

3 0.7 2.2 4.4 T T T T T 4 0.7 1.3 2.2 4.4 T T T T 6 0.5 1 1.2 2 2.8 T T T 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3

15.76 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Technical data Selectivity S800S - S200 @ 230/400 V E. S800S Char. B L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P K

0.2 T T T T T T T T

0.3 T T T T T T T T

0.75 T T T T T T T T

1 0.8 5 T T T T T T 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.1 T T T T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800S Char. B L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P B 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800S Char. B L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P C 1 3.3 T T T T T T T 1.6 0.6 1.3 T T T T T T 2 0.4 0.7 1.2 T T T T T 4 0.6 0.7 1 1.7 3.1 7 8 0.4 0.6 0.7 1 1.4 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800S Char. C L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P K 1 0.8 5 T T T T T T 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.3 T T T T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800S Char. C L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P B 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800S Char. C L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P C 1 3.3 T T T T T T T 1.6 0.6 1.3 T T T T T T 2 0.4 0.7 1.3 T T T T T 8 0.4 0.6 0.7 1 1.4 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 LEGEND E. = supply side L. = load side Back-up limit values are specified in kA

Low Voltage Products & Systems 15.77 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Technical data Selectivity S800S - S200P @ 230/400 V E. S800S Char. D L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P K 2 2.3 T T T T T T T 3 0.7 1.3 4.4 T T T T T 4 0.7 1 2.2 4.4 7.7 T T T 25 1.8 2.2 3.2 32 1.7 2 2.9 40 1.9 2.6 50 2.2 E. S800S Char. D L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P B 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 E. S800S Char. D L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P C 3 0.7 2.2 4.4 T T T T T 6 0.5 1 1.2 2 2.8 9.9 22 T 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 LEGEND E. = supply side L. = load side Back-up limit values are specified in kA

15.78 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 E. S800S Char. B, C, D, K L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S280 B 10 6 50 50 50 50 50 50 50 50 10 50 50 50 25 20 16 16 16 13 50 50 50 25 20 16 16 16 16 50 50 50 25 20 16 16 16 20 50 50 25 20 16 16 16 25 50 25 20 16 16 16 32 25 20 16 16 16 40 20 16 16 16 50 16 16 16 63 16 16 E. S800S Char. B, C, D, K L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S280 C 3 50 50 50 50 50 50 50 50 4 50 50 50 50 50 50 50 50 6 50 50 50 50 50 50 50 50 8 50 50 50 25 20 16 16 16 10 50 50 50 25 20 16 16 16 13 50 50 50 25 20 16 16 16 16 50 50 50 25 20 16 16 16 20 50 50 25 20 16 16 16 25 50 25 20 16 16 16 32 25 20 16 16 16 40 20 16 16 16 50 16 16 16 63 16 16 E. S800S Char. B, C, D, K L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S280 K, Z 3 50 50 50 50 50 50 50 50 4 50 50 50 50 50 50 50 50 6 50 50 50 50 50 50 50 50 8 50 50 50 25 20 16 16 16 10 50 50 50 25 20 16 16 16 13 50 50 50 25 20 16 16 16 16 50 50 50 25 20 16 16 16 20 50 50 25 20 16 16 16 25 50 25 20 16 16 16 15 32 25 20 16 16 16 40 20 16 16 16 50 16 16 16 63 16 16 E. S800S Char. B, C, D, K L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S400E B 6 6 50 50 50 50 50 50 50 50 10 50 50 50 50 50 50 50 50 13 50 50 50 50 50 50 50 50 16 50 50 50 50 50 50 50 50 20 50 50 50 50 50 50 50 25 50 50 50 50 50 50 32 50 50 50 50 50 40 50 50 50 50 50 50 50 50 63 50 50 E. S800S Char. B, C, D, K L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S400E C 6 0.5…6 50 50 50 50 50 50 50 50 8 50 50 50 50 50 50 50 50 10 50 50 50 50 50 50 50 50 13 50 50 50 50 50 50 50 50 16 50 50 50 50 50 50 50 50 20 50 50 50 50 50 50 50 25 50 50 50 50 50 50 32 50 50 50 50 50 40 50 50 50 50 50 50 50 50 63 50 50 Technical data Selectivity S800S - S280 @ 230/400 V LEGEND E. = supply side L. = load side Back-up limit values are specified in kA

Low Voltage Products & Systems 15.79 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Approximate dimensions S800U & S800S UL & IEC Dimension drawings in mm S800S & S800U S800-AUX S800-AUX/ALT 79.5 26.5 1P 2P 3P 4P 106 2CCC413010Z0001 76.5 82.56 T 2CCC413017Z0001 76.5 82.569 RT T 2CCC413018Z0001 76.5 82.569 S800-RD & S800-RHE S800-SOR & S800-UVR 26.5 76.5 82.56 76 6781 max. 500mm

15.80 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Notes

Low Voltage Products & Systems 15.81 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A S500 Series UL 1077 S500 UL 1077 Series Miniature circuit breakers The S500 high performance MCB offers a compact solution to circuit protection. The S500 devices are UL tested current limiting and DIN rail mounted. The S500 is available with application-specific trip characteristics to provide maximum circuit protection. The breakers offer thermal-magnetic trip protection according to B and K characteristics. For the worldwide market, the breakers carry CSA, IEC, CE and many other agency approvals.

  • High breaking capacity
  • Fast breaking time (2.3 - 2.5 ms)
  • Adjustable trip unit
  • DIN rail mounting
  • Finger safe terminals
  • Multi-functional terminals
  • Wide range of accessories
  • UL 1077 recognized 600 VAC and

600 VDC versions

  • UL1077 AC adjustable K
  • UL1077 DC adjustable B, K
  • UL File # E167556
  • IEC #E60497-2 S500 S500UC Amperage 0.1 – 45 A 0.1 – 63 A Voltage UL: 600Y/277 VAC IEC: 690 VAC UL: 250 VDC per pole (600 VDC for 4P) IEC: 250 VDC per pole (750 VDC for 4P) Poles 1, 2, 3 1, 2, 3, 4 Trip characteristics K B, K Interrupting ratings Up to 30 kA : UL 1077 Up to 30 kA: CSA C22.2 30 kA : UL 1077 30 kA: CSA C22.2 Auxiliary contacts Yes Yes Bell alarm Yes Yes Shunt trip No No Undervoltage release No No Bus bar Yes Yes

15.82 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 S500-K, UL 600Y/277 VAC / IEC 690 VAC Supplemental protection UL 1077, CSA 22.2, IEC S501-K S502-K S503-K Tripping characteristic K UL 1077 IEC

600 VAC 690 VAC

  • K Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.71 Technical data – See page 15.76 - 82 1 2 3 5 10 20 30 0.01 0.1 100 1000 10,000 0.05 0.5 500 5000 AC seconds multiple of rated current 128 No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.1 – 0.15 S501-K0.15 0.1 – 0.15 S503-K0.15 1 – 1.5 S501-K1.5 1 – 1.5 S503-K1.5 2 – 3 S501-K3 2 – 3 S503-K3 5.3 – 8 S501-K8 5.3 – 8 S503-K8 7.3 – 11 S501-K11 7.3 – 11 S503-K11 10 – 15 S501-K15 10 – 15 S503-K15 14 – 20 S501-K20 14 – 20 S503-K20 18 – 26 S501-K26 18 – 26 S503-K26 23 – 32 S501-K32 23 – 32 S503-K32 29 – 37 S501-K37 29 – 37 S503-K37 34 – 41 S501-K41 34 – 41 S503-K41 38 – 45 S501-K45 38 – 45 S503-K45 0.1 – 0.15 S502-K0.15 0.14 – 0.21 S502-K0.21 0.28 – 0.42 S502-K0.42 0.38 – 0.58 S502-K0.58 0.53 – 0.8 S502-K0.8 0.73 – 1.1 S502-K1.1 1 – 1.5 S502-K1.5 2 – 3 S502-K3 5.3 – 8 S502-K8 7.3 – 11 S502-K11 10 – 15 S502-K15 14 – 20 S502-K20 18 – 26 S502-K26 23 – 32 S502-K32 29 – 37 S502-K37 34 – 41 S502-K41 38 – 45 S502-K45 K

Low Voltage Products & Systems 15.83 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A S502UC-B S501UC-B S503UC-B 0.01 0.1 100 1000 10,000 1 2 3 5 10 20 30 0.05 0.5 500 5000 DC seconds multiple of rated current S500UC-B, 250 VDC per pole (600 VDC 4P) UL/IEC (750 VDC 4P) Supplemental protectors, UL1077, CSA 22.2, IEC Tripping characteristic B UL 1077 IEC

250 VDC per pole

(600 VDC 4P) (750 VDC 4P) 30 kA 30 kA Inductive loads

  • B Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.71 Technical data – See page 15.76 - 82 B No. of poles Rated current Catalog number No. of poles Rated current Catalog number

6 S501UC-B6

6 S503UC-B6

10 S501UC-B10 10 S503UC-B10

13 S501UC-B13 13 S503UC-B13

16 S501UC-B16 16 S503UC-B16

20 S501UC-B20 20 S503UC-B20

25 S501UC-B25 25 S503UC-B25

32 S501UC-B32 32 S503UC-B32

40 S501UC-B40 40 S503UC-B40

50 S501UC-B50 50 S503UC-B50

63 S501UC-B63 63 S503UC-B63

6 S502UC-B6

6 S504UC-B6

10 S502UC-B10 10 S504UC-B10

13 S502UC-B13 13 S504UC-B13

16 S502UC-B16 16 S504UC-B16

20 S502UC-B20 20 S504UC-B20

25 S502UC-B25 25 S504UC-B25

32 S502UC-B32 32 S504UC-B32

40 S502UC-B40 40 S504UC-B40

50 S502UC-B50 50 S504UC-B50

63 S502UC-B63 63 S504UC-B63

15.84 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 S500UC-K, 250 VDC per pole (600 VDC 4P) UL/IEC (750 VDC 4P) Supplemental protectors, UL1077, CSA 22.2, IEC S501UC-K S502UC-K S503UC-K S504UC-K 1 2 3 5 10 20 30 0.01 0.1 100 1000 10,000 0.05 0.5 500 5000 DC seconds multiple of rated current Tripping characteristic K UL 1077 IEC (600 VDC 4P) (750 VDC 4P) 30 kA 30 kA Inductive loads

  • K Curve
  • Designed for allowing higher in-rush currents during system start up
  • Example: motors, transformers Accessories & technical data Accessories – See page 15.71 Technical data – See page 15.76 - 82 No. of poles Rated current Catalog number No. of poles Rated current Catalog number 0.1 – 0.15 S501UC-K0.15 0.1 – 0.15 S503UC-K0.15 1 – 1.5 S501UC-K1.5 1 – 1.5 S503UC-K1.5 2 – 3 S501UC-K3 2 – 3 S503UC-K3 5.3 – 8 S501UC-K8 5.3 – 8 S503UC-K8 7.3 – 11 S501UC-K11 7.3 – 11 S503UC-K11 10 – 15 S501UC-K15 10 – 15 S503UC-K15 14 – 20 S501UC-K20 14 – 20 S503UC-K20 18 – 26 S501UC-K26 18 – 26 S503UC-K26 23 – 32 S501UC-K32 23 – 32 S503UC-K32 29 – 37 S501UC-K37 29 – 37 S503UC-K37 34 – 41 S501UC-K41 34 – 41 S503UC-K41 38 – 45 S501UC-K45 38 – 45 S503UC-K45 0.1 – 0.15 S502UC-K0.15 0.1 – 0.15 S504UC-K0.15 1 – 1.5 S502UC-K1.5 1 – 1.5 S504UC-K1.5 2 – 3 S502UC-K3 2 – 3 S504UC-K3 5.3 – 8 S502UC-K8 5.3 – 8 S504UC-K8 7.3 – 11 S502UC-K11 7.3 – 11 S504UC-K11 10 – 15 S502UC-K15 10 – 15 S504UC-K15 14 – 20 S502UC-K20 14 – 20 S504UC-K20 18 – 26 S502UC-K26 18 – 26 S504UC-K26 23 – 32 S502UC-K32 23 – 32 S504UC-K32 29 – 37 S502UC-K37 29 – 37 S504UC-K37 34 – 41 S502UC-K41 34 – 41 S504UC-K41 38 – 45 S502UC-K45 38 – 45 S504UC-K45 K

Low Voltage Products & Systems 15.85 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Accessories S500 UL1077 S500-H11, -H20 Auxiliary contacts The auxiliary contacts will signal whether the breaker is in the ON or OFF position. Description Catalog number For field mounting: left side 1 N.O./1 N.C. S500-H11 2 N.O. S500-H20 Bell alarm The bell alarm includes a set of contacts that will only signal when the breaker has tripped. Typically the contacts would be connected to an alarm or bell to signal the operator that an overcurrent trip has occurred. The bell alarm also includes a test button for testing the alarm contacts without opening the breaker. Description Catalog number For field mounting: left side 1 N.O./1 N.C. S500-S11 2 N.O. S500-S20 Handle mechanism Description Catalog number Handle mechanism S500-RD3 For use with 1-4 pole S500 MCBs and disconnect switch selector handles with 5mm shafts. Power feed terminal - Accepts into 2/0 AWG Description Catalog number Rear mount terminal S500-K2 Rear mount terminal - Accepts into 2/0 AWG Description Catalog number Accepts 4AWG/25mm S500-K1 S500-S11, -S20 S500-RD3 S500-K1

15.86 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Technical data S500-K & S500UC-B, K Tripping characteristic K Tripping characteristic B Technical data S500-K S500UC-B, K Approvals UL 1077 1077 CSA C22.2 - No. 235 C22.2 - No. 235 Number of poles 1, 2, 3 1, 2, 3, 4 Tripping characteristic K B, K Rated currents 0.1 to 45 A B: 6 - 63 A; K: 0.15 - 45 A Rated voltage 480Y/277 VAC, 600Y/346 VAC 250 VDC per pole (600 VDC 4 pole) Frequency 50/60 Hz 50/60 Hz Mounting position vertical, horizontal vertical, horizontal Standard mounting 35mm DIN rail 35mm DIN rail Clamps only for CU 16 - 4 AWG 16 - 4 AWG Service life, mechanical at rated load 20,000 20,000 1 2 3 5 10 20 30 0.01 0.1 100 1000 10,000 0.05 0.5 500 5000 AC DC seconds multiple of rated current 128 0.01 0.1 100 1000 10,000 1 2 3 5 10 20 30 0.05 0.5 500 5000 DC seconds multiple of rated current

Low Voltage Products & Systems 15.87 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Approximate dimensions S500 & Accessories S500 0.24 6 1.14 3.62 2.22 56.5 3.15 1.73 44 3.64 92.5 2.95 1.97 0.98 CL 2.95 75 1.77 45 S500 S500-H11, S500-H20 S500-S11, S500-S20 12.5 6 56.5 S500-RD3 Handle mechanism 3.15 80 1.60 40.7 S500 handle mechanism S500 Front mounting kit S500 FRONT MOUNT 2.91 1.81 L L + 1.02 26 0.31 83.31 84 4.41 112 " L " 2.00 CL CL CUT-OUT 0.24 D 6 D L + 0.51 13

15.88 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 15 15 Notes

Low Voltage Products & Systems 15.89 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Miniaturecircuit breakers Technical data Miniature circuit breakers Technical data Miniature circuit breakers Technical data S200 UL489 UL1077 S800 UL489 IEC S500 UL1077 S201UP-K S201UP-K S201-B S201P-Z S201PR-K0.2 S201UDC-K1 S501-K S801U-B

15.90 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage Miniature circuit breakersTechnical data 15 15 Technical data S200U-K, S200U-Z, S200UP-K, S200UP-Z Item S200U-K S200U-Z S200UP-K S200UP-Z Approvals: UL 489 489 489 489 VDE 0660 0660 0660 0660 IEC 898, 60947-2 898, 60947-2 898, 60947-2 898 Number of Poles: 1,2,3,4 1,2,3,4 1,2,3,4 1,2,3,4 Tripping Characteristic: K Z K Z Rated Currents: 0.2 to 63A 0.2 to 63A 0.2 to 25A 0.2 to 25A Minimum Operating Voltage: 12V 12V 12V 12V UL/CSA Rated Voltage & Interrupting Capacity: Frequency: 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 120VAC 10kA 10kA 10kA 10kA

240 VAC 10kA 10kA 10kA 10kA

277 VAC — — 10kA 10kA

277/480 VAC — — 10kA 10kA 60VDC 15kA 15kA 15kA 15kA 125VDC 15kA 15kA 15kA 15kA 250VDC — — — — 500VDC — — — — IEC Rated Voltage Frequency: 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz Rated Voltage IEC Single Pole 240/415VAC, 220VDC 240/415VAC, 60VDC 240/415VAC, 220VDC 240/415VAC, 220VDC IEC Multi-Pole 415VAC, 440VDC 415VAC, 110VDC 415VAC, 440VDC 415VAC, 440VDC Production Category: IP20 IP20 IP20 IP20 Mounting Position: Vertical / horizontal Vertical / horizontal Vertical / horizontal Vertical / horizontal Standard Mounting: 35mm DIN rail 35mm DIN rail 35mm DIN rail 35mm DIN rail Main and Shunt Trip Terminals: Tool # 2 Posidrive # 2 Posidrive # 2 Posidrive # 2 Posidrive Accessory Terminals Tool # 1 Posidrive # 1 Posidrive # 1 Posidrive # 1 Posidrive Service Life at Rated Load: No Load 20,000 operations No Load 20,000 operations Full Load 10,000 operations No Load 20,000 operations Full Load 10,000 operations No Load 20,000 operations Full Load 10,000 operations Ambient Temperatures: Storage Temperatures: Shock Resistance: 30g minimum of 2 impacts, shock duration of 13ms 30g minimum of 2 impacts, shock duration of 13ms 30g minimum of 2 impacts, shock duration of 13ms 30g minimum of 2 impacts, shock duration of 13ms Vibration Resistance: 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz @ 0.8 ~ In 5g, 20 cycles, 5 Hz, 150 Hz @ 0.8 ~ In Disconnecting Neutral Rating: — — — —

Low Voltage Products & Systems 15.91 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Miniaturecircuit breakers Technical data Technical data SU200PR-K, S200UDC-K, S200UDC-Z Item SU200PR-K S200UDC-K S200UDC-Z Approvals: UL 489 489 489 CSA CS22.2 No. 5 — — VDE 0660 0660 0660 IEC 60947-2 — — Number of Poles: 1,2,3,4 1, 2 1, 2 Tripping Characteristic: K K Z Rated Currents: 0.2 to 63A 1 to 63A 1 to 63A Minimum Operating Voltage: 12 VAC — — UL/CSA Rated Voltage & Interrupting Capacity: Frequency: 50/60 Hz 50/60 Hz 50/60 Hz 120VAC 10 kA — —

240 VAC 10 kA — —

277 VAC 10 kA — —

277/480 VAC 10 kA — — 60VDC — 14 kA 14 kA 125VDC — — — 250VDC — — — 500VDC — — — IEC Rated Voltage Frequency: 50/60 Hz 50/60 Hz 50/60 Hz Rated Voltage IEC Single Pole 240 VAC — — IEC Multi-Pole 400 VAC — — Production Category: IP20 IP20 IP20 Mounting Position: Any Vertical / horizontal Vertical / horizontal Standard Mounting: 35mm DIN rail 35mm DIN rail 35mm DIN rail Main and Shunt Trip Terminals: Tool # 2 Posidrive # 2 Posidrive # 2 Posidrive Accessory Terminals Wire Size 18-16 AWG/.82-1.3 mm2 18-16 AWG/.82-1.3mm2 18-16 AWG/.82-1.3mm2 Tool # 1 Posidrive # 1 Posidrive # 1 Posidrive Service Life at Rated Load: 6000 operations (AC), 1 cycle (1s-ON, 9s-OFF) Full Load 10,000 operations Full Load 10,000 operations Ambient Temperatures: Storage Temperatures: Shock Resistance: 25g minimum of 2 impacts, shock duration of 13 ms 30g minimum of 2 impacts, shock duration of 13 ms 30g minimum of 2 impacts, shock duration of 13 ms Vibration Resistance: 5g, 20 cycles, 5-150, 5Hz with load 0.8in 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz Disconnecting Neutral Rating: — — —

15.92 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage Miniature circuit breakersTechnical data 15 15 Technical data S200-B; S200-C, D; S200-K; S200-Z Item S200-B S200-C, D S200-K S200-Z Approvals: UL 1077 1077 1077 1077 VDE 0641, 0660 0660 0660 0660 IEC 898, 60947-2 898, 60947-2 898, 60947-2 898, 60947-2 Tripping Characteristic: B C, D K K Rated Currents: 6 to 63A 0.5 to 63A 0.5 to 63A 0.5 to 63A Minimum Operating Voltage: 12VAC 12VAC 12 V 12 V UL/CSA Rated Voltage Single pole Multi pole Single pole Multi pole Single pole Multi pole Single pole Multi pole & Interrupting Capacity: Frequency: 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 120VAC 10 kA — 10 kA — 10 kA — 10 kA —

240 VAC 6 kA 10 kA 6 kA 10 kA 6 kA 10 kA 6 kA 10 kA

277 VAC 6 kA — 6 kA — 6 kA — 6 kA —

277/480 VAC — 6 kA — 6 kA — 6 kA — 6 kA 60VDC 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 125VDC 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA IEC Rated Voltage Frequency: 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz Rated Voltage IEC Single Pole 240/415 VAC, 60 VDC 240/415 VAC, 60 VDC 240/415 VAC, 60 VDC 240/415 VAC, 60 VDC IEC Multi-Pole 415 VAC, 110 VDC 415 VAC, 110 VDC 415 VAC, 110 VDC 415 VAC, 110 VDC Production Category: IP20 IP20 IP20 IP20 Mounting Position: Vertical / horizontal Vertical / horizontal Vertical / horizontal Vertical / horizontal Standard Mounting: 35mm DIN rail 35mm DIN rail 35mm DIN rail 35mm DIN rail Main and Shunt Trip Terminals: Tool # 2 Posidrive # 2 Posidrive # 2 Posidrive # 2 Posidrive Accessory Terminals Tool # 1 Posidrive # 1 Posidrive # 1 Posidrive # 1 Posidrive Service Life at Rated Load: No Load 20,000 operations Full Load 10,000 operations No Load 20,000 operations Full Load 10,000 operations No Load 20,000 operations Full Load 10,000 operations No Load 20,000 operations Full Load 10,000 operations Ambient Temperatures: Storage Temperatures: Shock Resistance: 30g minimum of 2 impacts, shock duration of 13 ms 30g minimum of 2 impacts, shock duration of 13 ms 30g minimum of 2 impacts, shock duration of 13 ms 30g minimum of 2 impacts, shock duration of 13 ms Vibration Resistance: 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz Disconnecting Neutral Rating: 6 kA switching 6 kA switching 6 kA switching 6 kA switching

Low Voltage Products & Systems 15.93 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Miniaturecircuit breakers Technical data Item S200P-B S200P-C S200P-D S200P-K Approvals: UL 1077 1077 1077 1077 VDE 0660 0660 0660 0660 IEC 898, 60947-2 898, 60947-2 898, 60947-2 898, 60947-2 Tripping Characteristic: K K K K Rated Currents: 0.5 to 63A 0.5 to 63A 0.5 to 63A 0.2 to 63A Minimum Operating Voltage: 12 V 12 V 12 V 12 V UL/CSA Rated Voltage Single pole Multi pole Single pole Multi pole Single pole Multi pole Single pole Multi pole & Interrupting Capacity: Frequency: 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 120VAC 10 kA — 10 kA — 10 kA — 10 kA —

240 VAC 6 kA 10 kA 6 kA 10 kA 6 kA 10 kA 10 kA 10 kA

277 VAC 6 kA — 6 kA — 6 kA — 10 kA —

277/480 VAC — 6 kA — 6 kA — 6 kA — 10 kA 60VDC 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 15 kA 15 kA 125VDC 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA 15 kA 15 kA IEC Rated Voltage Frequency: 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz Rated Voltage IEC Single Pole 240/415 VAC, 60 VDC 240/415 VAC, 60 VDC 240/415 VAC, 60 VDC 240/415 VAC, 60 VDC IEC Multi-Pole 415 VAC, 110 VDC 415 VAC, 110 VDC 415 VAC, 110 VDC 415 VAC, 110 VDC Production Category: IP20 IP20 IP20 IP20 Mounting Position: Vertical / horizontal Vertical / horizontal Vertical / horizontal Vertical / horizontal Standard Mounting: 35mm DIN rail 35mm DIN rail 35mm DIN rail 35mm DIN rail Main and Shunt Trip Terminals: Tool # 2 Posidrive # 2 Posidrive # 2 Posidrive # 2 Posidrive Accessory Terminals Tool # 1 Posidrive # 1 Posidrive # 1 Posidrive # 1 Posidrive Service Life at Rated Load: No Load 20,000 operations Full Load 10,000 operations No Load 20,000 operations Full Load 10,000 operations No Load 20,000 operations Full Load 10,000 operations No Load 20,000 operations Full Load 10,000 operations Ambient Temperatures: Storage Temperatures: Shock Resistance: 30g minimum of 2 impacts, shock duration of 13 ms 30g minimum of 2 impacts, shock duration of 13 ms 30g minimum of 2 impacts, shock duration of 13 ms 30g minimum of 2 impacts, shock duration of 13 ms Vibration Resistance: 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz Disconnecting Neutral Rating: 6 kA switching 6 kA switching 6 kA switching — Technical data S200-P-B; S200P-C; S200P-D; S200P-K

15.94 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage Miniature circuit breakersTechnical data 15 15 Technical data S200P-Z; S200PR-K; S280UC-K; S280C-Z Item S200P-Z S200PR-K S280UC-K S280UC-Z Approvals: UL 1077 489 1077 1077 VDE 0660 0660 0660 0660 IEC 898, 60947-2 60947-2 898, 60947-2 898, 60947-2 Number of Poles: 1,2,3,4 1,2,3,4 1,2,3 1,2,3 Tripping Characteristic: Z K K Z Rated Currents: 0.5 to 63A 0.2 to 63A 0.2 to 63A 0.5 to 63A Minimum Operating Voltage: 12 V 12 VAC 12 V 12 V UL/CSA Rated Voltage Single pole Multi pole Single pole Multi pole Single pole Multi pole & Interrupting Capacity: Frequency: 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 120VAC 10 kA — 10 kA 10 kA 10 kA 10 kA —

240 VAC 10 kA 10 kA 10 kA 10 kA 6 kA 10 kA 10 kA

277 VAC 10 kA — 10 kA 10 kA 6 kA 10 kA —

277/480 VAC — — 10 kA — 4.5 kA for 0.2-40 A 5 kA for 50-63 A — 4.5 kA for 0.2-40 A 5 kA for 50-63 A 60VDC 15 kA 15 kA — 10 kA 10 kA 10 kA 10 kA 125VDC 15 kA 15 kA — 10 kA — 10 kA 10 kA 250VDC — — — 4.5 kA 4.5 kA 4.5 kA 4.5 kA 500VDC — — — — 4.5 kA — 4.5 kA IEC Rated Voltage Frequency: 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz Rated Voltage IEC Single Pole 240/415 VAC, 220 VDC 240 VAC 240/415VAC, 220VDC 240/415VAC, 220VDC IEC Multi-Pole 415 VAC, 440 VDC 400 VAC 415VAC, 440VDC 415VAC, 440VDC Production Category: IP20 IP20 IP20 IP20 Mounting Position: Vertical / horizontal Any Vertical / horizontal Vertical / horizontal Standard Mounting: 35mm DIN rail 35mm DIN rail 35mm DIN rail 35mm DIN rail Main and Shunt Trip Terminals: 0.2 - 40A 18-2 AWG for 50 A & above 18-4 AWG/.82-21.2 mm² for 0.5 - 40A 18-2 AWG for 50 A & above Tool # 2 Posidrive # 2 Posidrive # 2 Posidrive # 2 Posidrive Accessory Terminals Tool # 1 Posidrive # 1 Posidrive # 1 Posidrive # 1 Posidrive Service Life at Rated Load: No Load 20,000 operations Full Load 10,000 operations 6000 operations (AC), 1 cycle (1s-ON, 9s-OFF) No Load 20,000 operations Full Load 10,000 operations No Load 20,000 operations Full Load 10,000 operations Ambient Temperatures: Storage Temperatures: Shock Resistance: 30g minimum of 2 impacts, shock duration of 13 ms 25gminimum of 2 impacts, shock duration of 13 ms 30g minimum of 2 impacts, shock duration of 13 ms 30g minimum of 2 impacts, shock duration of 13 ms Vibration Resistance: 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5-150, 5Hz with load 0.8in 5g, 20 cycles, 5 Hz, 150 Hz 5g, 20 cycles, 5 Hz, 150 Hz Disconnecting Neutral Rating: — — — —

Low Voltage Products & Systems 15.95 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Miniaturecircuit breakers Technical data Technical data S800U-K, Z; S800S-B, S800S-C, S800S-D Item S800U-K, Z S800S-B S800S-C S800S-D Approvals: UL 489, E312425 — — — VDE — — — — IEC 60947-2 60947-2 60947-2 60947-2 Number of Poles: 1,2,3,4 1,2,3,4 1,2,3,4 1,2,3,4 Tripping Characteristic: K B C D Rated Currents: 10 to 100A 10 to 125A 10 to 125A 10 to 125A Minimum Operating Voltage: — 400/690VAC 400/690VAC 400/690VAC UL/CSA Rated Voltage & Interrupting Capacity: Frequency: 50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz 120VAC — — — — 240 VAC 50 kA multi, 30 kA single 50 kA multi, 30 kA single; IEC 50 kA multi, 30 kA single; IEC 50 kA multi, 30 kA single; IEC

277 VAC — — — —

60VDC — — — — 125VDC — — — — 250VDC — — — — 500VDC — — — — IEC Rated Voltage Frequency: — 50/60 Hz 50/60 Hz 50/60 Hz Rated Voltage IEC Single Pole — 690 VAC 690 VAC 690 VAC IEC Multi-Pole — — — — Production Category: IP20 IP20 IP20 IP20 Depth of Unit Per DIN 43880: — — — — Mounting Position: Vertical / horizontal Vertical / horizontal Vertical / horizontal Vertical / horizontal Standard Mounting: 35mm DIN rail 35mm DIN rail 35mm DIN rail 35mm DIN rail Main and Shunt Trip Terminals: Torque 35 in-lbs. / 4 Nm 35 in-lbs. / 4 Nm 35 in-lbs. / 4 Nm 35 in-lbs. / 4 Nm Tool — — — — Accessory Terminals Torque 35 in-lbs./4 Nm 35 in-lbs./4 Nm 35 in-lbs./4 Nm 35 in-lbs./4 Nm Tool — — — — Service Life at Rated Load: 6,000 operations 6,000 operations 6,000 operations 6,000 operations Ambient Temperatures: Storage Temperatures: Shock Resistance: — — — — Vibration Resistance: — — — — Disconnecting Neutral Rating: — — — —

15.96 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage Miniature circuit breakersTechnical data 15 15 Technical data S800S-K Item S800S-K Approvals: UL — CSA — VDE — IEC 60947-2 Number of Poles: 1,2,3,4 Tripping Characteristic: K Rated Currents: 10 to 125A Minimum Operating Voltage: 400/690 VAC UL/CSA Rated Voltage & Interrupting Capacity: Frequency: 50/60 Hz 120VAC —

240 VAC 50 kA multi; 30 kA single; IEC

277 VAC —

277/480 VAC — 60VDC — 125VDC — 250VDC — 500VDC — IEC Rated Voltage Frequency: 50/60 Hz Rated Voltage IEC Single Pole 690 VAC IEC Multi-Pole — Production Category: IP20 Depth of Unit Per DIN 43880: — Mounting Position: Vertical / horizontal Standard Mounting: 35mm DIN rail Main and Shunt Trip Terminals: Wire Size 1... 25 Torque 35 in-lbs. / 4 Nm Tool — Accessory Terminals Wire Size 1... 35 Torque 35 in-lbs./4 Nm Tool — Service Life at Rated Load: 6,000 operations Ambient Temperatures: Minimum -25ºC... -13ºF Maximum 60ºC... 140ºF Storage Temperatures: Minimum -40ºC... -40ºF Maximum 70ºC... 158ºF Shock Resistance: — Vibration Resistance: — Disconnecting Neutral Rating: —

Low Voltage Products & Systems 15.97 ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage 1SXU000023C0202 Rev. A Miniaturecircuit breakers Technical data Technical data S500-K, Z; S500UC-B, K Approvals: UL CSA VDE No. of poles: Tripping characteristic: Rated currents: Rated voltage: UL single pole UL multi pole IEC multi pole Rated interrupting capacity: Frequency: Mounting position: Standard mounting: Terminals: Service life at rated load: Approvals: UL 1077 CSA C22.2 - No. 235 VDE 0641/6.78 IEC — No. of poles: 1,2,3, +N, +NA Tripping characteristic: K Rated currents: 0.1 to 45A Rated voltage: UL/CSA single pole 277VAC UL/CSA multi pole 600YVAC IEC single pole 690VAC Rated interrupting capacity: Single pole 0.15-25A – 30KA/240VAC 14KA/277VAC 26-45A – 18KA/240VAC 14KA/277VAC Multi-pole 0.15-45A – 14KA/480VAC 6KA/600VAC Frequency: 50/60Hz Mounting position: Vertical / horizontal Standard mounting: 35mm DIN rail Terminals: 16-4AWG / 1-25mm Service life at rated load: 20,000 operations Calibration temperature: 40°C Item S500-K, Z Item S500UC-B, K 1077 C22.2 0660 1,2,3, 4 B, K B: 6 to 63A K: 0.15 to 45A 277VAC/250VDC 600VAC/600VDC 690VAC/750VDC B single pole: 6 – 25A 18KA/240VAC 14KA/277VAC 30KA/250VDC 32 – 63A 30KA/240VAC 14KA/277VAC 30KA/250VDC B two-pole: 6 – 63A 14KA/480VAC 6KA/600VAC 30KA/500VDC B three-pole: 6 – 63A 14KA/480VAC 6KA/600VAC 30KA/600VDC K single pole: 0.15 – 25A 30KA/240VAC 14KA/277VAC 30KA/250VDC 32 – 45A 18KA/240VAC 14KA/277VAC 30KA/250VDC K two-pole: 0.15 – 45A 14KA/480VAC 6KA/600VAC 30KA/500VDC K three-pole: 0.5 – 45A 14KA/480VAC 6KA/600VAC 30KA/600VDC 50/60Hz Vertical / horizontal 35mm DIN-rail 16-4AWG / 1-25mm 20,000 operations

15.98 Low Voltage Products & Systems

1SXU000023C0202 Rev. A ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage Miniature circuit breakersTechnical data 15 15 Notes