MCB distribution board 250A Edition 1
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Our electrical distribution solutions upgrade power in buildings to create safer, more energy efficient and more productive environments, enabling our customers and their customers to do more with less.
004 – 009 Introduction to Protecta Plus 010 – 021 Key modular components 022 – 047 Ordering codes 048 – 073 Technical information 074 – 075 Glossary TABLE OF CONTENTS
Main construction features
- Structure in epoxy coated metal sheets, 1 mm, textured finish
- Wall installation for indoor environments
- Degree of protection - IP43 with door, IP30 without door
- Mechanical resistance: IK07
- Busbar rating: 250A
- Number of ways: 4, 8, 12, 16, 20, 24
- Maximum ambient temperature +35 °C
- Compliance with IEC BS EN 61439 1-2
- Simple wiring of all cabinets, both horizontally and vertically
- Easy internal accessibility that facilitates all the wiring operations and maintenance
- Prepackaged standardized kits for specific applications (e.g. surge protection, metering) A comprehensive range The range consists of distribution boards for wall mounting in six heights from 590 mm to 1360 mm, 450 mm width and depth starting from 125 mm, ensuring the development of multiple solutions. Protecta Plus system is easy to design, quick to assemble and reliable to apply. Ease of wiring With the new mounting concept, Protecta Plus offers great levels of flexibility and accessibility for installation and wiring. The internal module can be easily removed allowing the wiring of different equipment outside the distribution board. This solution allows for an easier installation with more rapid production times. Maximum accessibility Thanks to the particularly large opening angle of the door, Protecta Plus offers the possibility to have optimal access to the distribution board, especially in case of maintenance. The perfectly reversible doors can be installed with right or left opening. Protecta Plus General features of the series With the new Protecta Plus system, ABB has developed a new and personalised series of MCB distribution boards which can be expanded over time. The wide internal accessibility ensures a quick and easy approach to the electrical components assembly. The neutral and earth bars positioned on the inner sides of the distribution board are completely isolated to ensure better safety for users. PROTECTA PLUS MCB DISTRIBUTION BOARD 250A
harnesses. A series of rational solutions developed to achieve a complete range of capabilities and functions with a single type of distribution board to meet different installation requirements, whilst simplifying the work of the installer. High output capacity Primary branch capacity up to 100A. Range depth: 125 mm; width: 450 mm; 6 heights: 590, 730, 870, 1050, 1220, 1360 mm. Ergonomics and design The design of this series is characterized by special features, such as rounded edges for a more efficient ergonomic look. Flexible mounting The PAN assembly system can easily be removed from the bottom distribution board of the framework, ensuring quick and simple installation. Complete protection Designed to ensure maximum protection and efficiency, through the prevision for the installation of surge protection devices and counters. 5PROTECTA PLUS – GENERAL FEATURES OF THE SERIES
Protecta Plus has been designed with a width of 450 mm, this combined with the reduced RCBO height of 115 mm gives the installer ample cable room either side of the board. Incoming shroud The shroud comes ready to accept a 125A 3P incoming devices. The easy break technology and clear indication on the rear allows the user to modify the shroud dependant upon requirements up to 250A 4P. One Solution All Protecta Plus boards come as standard with 250A main bars. This gives the user a full range from 125A 3P through to 250A 4P incoming options. 100A Outgoing ways The first two 3P outgoing ways are fitted with 3 mm branch copper to allow for 100A MCBs to be fitted. This allows for a maximum of 2 x 100A 3P or 6 x 100A 1P MCBs per board removing the need to move up to high performance boards or panel boards. Protecta Plus The details make the difference PROTECTA PLUS MCB DISTRIBUTION BOARD 250A
To aid installation and safety a custom MCB blank has been developed specifically for Protecta Plus. Padlocking facilities All outgoing devices on Protecta Plus can be padlocked in on/off position for increased safety. Clean earth Earth bars are fitted with removable links allowing the boards to be configured for 50/100% clean earth. Metering and surge protection Available in kit form to fit all Protecta Plus TPN boards. The boards have been designed to house these integrally. 7PROTECTA PLUS – THE DETAILS MAKE THE DIFFERENCE
The wide internal accessibility ensures a quick and easy approach to the electrical components assembly. PROTECTA PLUS MCB DISTRIBUTION BOARD 250A CMS Circuit monitoring systems (CMS) is a unique ultra-compact and high-performance multichannel measurement system for branch monitoring power
The wide internal accessibility ensures a quick and easy approach to the electrical components assembly.
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A IP20 finger safety. Easy identification of the product and highly resistant laser marking. Save your time all important data available right away. Easy product name, easy identification. Quick identification thanks to laser printed EAN marking. Contact position indication Captive screws don’t loose what’s important to you. Key modular components - MCB S 200 State-of-the-art safety Twin terminal for separate feeding of busbar and conductor.
Contact position indication All System pro M compact® MCBs are equipped with a con - tact position indication (CPI) on the toggle. You can easily identify, if the MCB is in the ON or OFF position – easy and safe maintenance work is possible. Locking device for MCBs and RCBOs Preventing unauthorised or dangerous operation of the operating lever. An adaptor makes it possible to block the operating lever whether switched ON or OFF. The lever is blocked with a padlock having a cross bar section of 3 mm or, as the case may be, 6 mm max. For multi-pole devices, one lock may be fitted per pole. IP 20 - finger safe terminals The System pro M compact® MCBs are equiped with 35 mm² + 10 mm² cylinder lift twin terminals, a well proven and reliable technology - designed for sopisticated industrial use. Approvals printed on the dome S 200 MCBs comply with IEC/EN 60898-1 and IEC/EN 60947-2 , as well as carrying the relevant approval marks for the markets they are designed for. Certification markings are printed on the dome of the MCB, making it possible to see the markings when mounted. 11KEY MODULAR COMPONENTS - MCB S 200 – STATE-OF-THE-ART SAFETY
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Key modular components - DSE201 M Compact design, enhanced protection Space for insulated screwdrivers Equipped with cage type terminals (16 mm² load side), with tightening torque of 1.2 Nm. Easy to install Fast installation is supported by the two flying leads for neutral cable and functional earth, each integrated in the device, which can be directly connected to the main neutral and earth bars. Earth fault indicator Blue window in the front of the device to detect any earth fault trip: the cause of trip of the device can be identified in a short time, reducing the downtime for maintenance. Anti-counterfeiting Equipped with an RFID tag containing a unique serial number assigned by ABB in accordance to ISO/IEC FCD 15693-3 standard in order to authenticate the product. Real contact position indicator below the toggle Directly linked to the moving contact of the device, the green/red window in the front of the device can identify the current position of the contacts (open/closed) independently on the toggle position. In control A test button allows the regular check of the functionality of the device: to be pushed every six months. Combination with auxiliary elements New platform suitable for quick installation in combination with the standard auxiliary elements that can be mounted with RCDs and MCBs. Reduced height Thanks to its reduced height, only 115 mm, DSE201 M makes for easier wiring operation inside the consumer unit or the distribution.
With its breaking capacity of 10/15kA in only one module width and 115 mm height, DSE201 M series is the perfect solution for a complete protection in commercial and industrial applications, where space optimization is required. 13KEY MODULAR COMPONENTS - DSE201 M - COMPACT DESIGN, ENHANCED PROTECTION Device status at a glance Earth fault indicator: blue window above the toggle to immediately detect and identify any earth fault trip, reducing downtime for maintenance. Contact position indicator (CPI): green/red window below the toggle to identify the real position of the contacts independently on the toggle position. Load side The load side terminal accepts cables, both rigid and flexible up to 16 mm2. Flying leads are straight instead of pigtail ones to reduce the space required for wiring operations. Double slot terminal Easy to install, , fail-safe line side, terminal to avoid improper connection. Two slots of different dimensions (35 mm2 and 10 mm2) available to allow the connection both with cables and busbars. Easy and flexible Double and bistable clips with a new design for a secure fixing in any type of consumer unit or distribution board. Easy removal from a cluster of RCBOs/MCBs supplied with busbars.
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Key modular components A complete range for your surge protection Standard pro M terminals Designed for a better coordination with the complete ABB System pro M compact® modular range. Auxiliary Contact Possibility to add an auxiliary contact on the OVR Plus range with the standard ABB option. Clear information On the front of the product indicating the technical characteristics of the OVR product. End-of-life indicator The end-of-life indicator of the SPD signals the status of the device. Turning from green to red when the SPD reaches the end of its life. The optional safety reserve system has a partial-release mechanism, which provides a pre-failure warning.
The pluggable feature of ABB OVR T1-T2, T2 and T2-T3 surge protective devices (SPDs) facilitates maintenance. Should one or more worn cartridges need to be replaced, the electrical circuit does not have to be isolated nor do the wires have to be removed. Active status indication The Furse ESP 415 CD40 offers three way LED status indication, showing full, reduced and no protection. It also notifies the user of loss of phase, loss of power and warning of excessive volts between N-E. KEY MODULAR COMPONENTS - OVR PLUS - A COMPLETE RANGE FOR YOUR SURGE PROTECTION Complete coordination The bi-directional cylindrical terminal block of the OVR Plus range allows a complete coordination with the ABB range with considerable time savings in wiring operations. All the devices allow connection through busbars, both from above and from below. Furse option for critical installations The Furse ESP 415 CD40 provides continuous operation of sensitive electronic systems in lightning intense environments, offering market-leading levels of protection, making it ideal for high-end applications, such as hospitals, data centres and automated process control systems. PLEASE SUPPLY IMAGE
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Requirements for a deliberate strategy to manage and control energy consumption are having an increasing impact on commercial buildings such as shopping centers, offices, hotels and airports. Electricity meters in commercial buildings are usually acquired by the property owner and read automatically via a facility or building management system. Just like for private property, modern sub-metering solutions can increase energy efficiency in commercial buildings and make considerable savings. MID approval facilitates problem-free cost distribution Meters that are MID approved have the advantage of a certified and verified metering accuracy. This is important if discussions on the fairness of the cost distribution arise. EQ meters can easily help distribute consumption costs between different tenants, e.g. stores and boutiques in shopping malls, businesses in office blocks, or different airlines and functions (baggage handling, for example) at airports. The fact that many commercial properties are not designed from the beginning for sub-metering presents no problem. EQ meters fit neatly wherever they are needed. Mandatory energy declarations Commercial properties must have an energy dec - laration that describes the building’s energy per - formance. Its aim is to reduce the climate effect and increase the efficient use of energy, i.e. bene - fits for both society and the building owner. Energy declarations require that the electrical consumption for lighting, elevators, heating and ventilation, etc., be accounted for separately. Data collected from individually-located meters (sub-metering) are extremely valuable in this respect. As well as being a legal requirement, it highlights ways to increase efficiency by locating unnecessary energy consumption. ISO 50001, L2 building regulations, BREEAM and others Whichever you aim for, analyzing energy consumption is an important early step and in the end also the best way to maintain an achieved level. EQ meters will provide accurate information regarding the electrical energy consumption. Max demand also cuts energy consumption* Measuring the highest average power during a set time interval results in the max demand value. Measuring max demand helps dimension a building’s electrical installations to its use.
01 Modern
cost distribution. Key modular components - Energy metering Advanced energy performance analysis
The EQ series are meters for single phase and three phase metering. The EQ series meters are mounted on a DIN rail and are suitable for installation in distribution boards and small enclosures such as consumer units. Inputs and outputs* The EQ series support two inputs and two outputs in a fixed configuration. Inputs can be used for counting pulses from e.g. a water meter, or reading status from external devices. Outputs can be used as pulse outputs or controlling external apparatus like a contactor or an alarm (connected via an external relay). Approvals* The EQ series meters are type approved according to IEC and they are both type approved and verified according to MID. MID is the Measuring Instruments Directive 2004/22/EC from the European Commission. MID type approval and verification is mandatory for meters in billing applications within EU and EEA. The type approval is according to standards that covers all relevant technical aspects of the meter. These include climate conditions, electromagnetic compatibility (EMC), electrical requirements, mechanical requirements and accuracy.
02 EQ series meters
- Dependant upon EQ Series metal selected The EQ series are suitable in applications where there is a need for reliable energy measurements and where space is limited. General features The EQ series meters are versatile meters for many applications and installations. Navigating the meter is easily done via the push-buttons below the display. To configure the meter settings, the set button must be accessed and this button is protected against unauthorized use when the transparent lid on the front of the meter is closed and sealed. The power consumption of the meter is very low, less than 0.8 VA. Communication* Data from the EQ series meters can be collected via pulse output or serial communication. The pulse output is a solid state relay that generates pulses proportionally to the measured energy. The meters can also be equipped with built-in serial communication interfaces for M-Bus or Modbus (RS-485). Instrumentation* The EQ series meters support reading of instrument values. A large number of electrical properties can be read. Depending on version of the meter the following data is available:
- Active power
- Apparent power
- Reactive power
- Current
- Voltage
- Frequency
- Power factor KEY MODULAR COMPONENTS - ENERGY METERING
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A
01 CMS-600
02 Connection
03 Double slot terminal
04 CMS sensors
Key modular components - CMS Circuit monitoring systems CMS bus interface A bus interface allows up to 96 sensors to be connected to the Control Unit. Control Units The Control Unit is a kind of computing and communication center that, depending on the equipment connected to it, evaluates the different data picked up by the sensors and makes it available via the built-in interfaces. Serial interfaces Depending on the unit, numerous interfaces and protocols are available to ensure smooth network implementation: RS485 (Modbus RTU), LAN (TCP/IP and Modbus TCP). Thanks to the built-in web server, an internet browser or a free Android or iOS app can be used to visualize the values measured. What’s more, the measured values can also be exported to CSV files.
The quality of a Circuit Monitoring System is dependent on the strengths of the individual components and how well they interact. ABB’s CMS sets the bar particularly high. Regardless of whether we’re talking compactness, technology, measurement results, user friendliness or flexibility, every component and every feature of this CMS has been fully optimized in terms of practicality and functionality. KEY MODULAR COMPONENTS - CMS - CIRCUIT MONITORING SYSTEMS Connection technology Connecting the sensors to the Control Unit is extremely simple and requires no special tools. All sensors are connected to the Control Unit by means of a flexible flat cable and insulation displacement connectors. The positioning of sensors is fully customizable so that they sit exactly where a measurement is required. Sensors The CMS sensors form the heart of the system and they can be mounted anywhere without any problem. Initializing the sensors is also child’s play, with the desired identifier being assigned to each individual sensor via the control unit in just a few simple steps. The entire configuration and commissioning procedure takes just a matter of minutes. All measurement functions are available immediately following initialization.
(issue commands) Actuators (command recipients) PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Key modular components - ABB i-bus® KNX Intelligent building solutions In many areas of our private and working lives, the increasing level of automation is a trend that confronts us on a daily basis without actually being noticed. Automation in buildings aims to combine individual room functions with one another and to simplify the implementation of individual customer preferences. KNX is the logical development for implementing traditional and new requirements in electrical building installations, replacing conventional installation techniques. The intelligent installation bus system efficiently performs the conventional functions and offers an additional broad range of expanded features, which could not be realized without a bus system.
01 The conventional
solution: Many separate cables, separate functionality, little flexibility
02 The intelligent
solution: KNX – a system, a standard, with many interoperable functions for maximum flexibility ABB offers consultants, system integrators and electrical installers a comprehensive product range with ABB i-bus® KNX, in order to meet the challenges posed to electrical building installations both today and in the future. Further information: http:/ /www.abb.com/knx Intelligent Building Solutions with ABB i-bus® KNX ensure:
- The right light in every situation by switching, dimming and controlling lights
- Visual protection and protection against sunlight by drive control of rolling shutters and blinds
- The right room temperature in every room by heating and cooling control
- The right air quality by controlling ventilation and climatization
- Automatic functions controlled by timer, movement, presence or meteorological data
- Security by monitoring operating conditions, signaling technical faults, recognizing hazards and triggering alarms
- Everything under control by visualization and manual operation
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Protecta Plus Order process Protecta Plus DB Vertical split-load board Horizintal split-load board Incoming kit Meter/surge kits (optional) Surge kits (optional) Surge kits (optional) MCB/RCBO/Blanks Accessories 2 x Distribution boards
ABB I-BUS® KNX In many areas of our private and working lives, the increasing level of automation is a trend that confronts us on a daily basis without actually being noticed. Protecta Plus Order Codes Protecta Plus Order Codes PROTECTA PLUS Protecta Plus gives UK installers and designers the flexibility to cover all applications through standard and customised kit packages. 2 x Distribution boards
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Pack contents: Horizontal split load kit
- 2 x MID, Modbus ( RS485 ) & Pulse Meters
- Associated CTs
- Incoming isolators
- Internal cables
- Requires 2 x MCB distribution board - Type B Please note as these kits allow for 4 to 24way boards cutting and crimping of cables is required. Pack contents: Standard distribution board
- 250A distribution bar
- RAL7035 textured finish
- Door closing latch Description Order codes Protecta Plus DB 4 Way 250A EPP-W304 Protecta Plus DB 8 Way 250A EPP-W308 Protecta Plus DB 12 Way 250A EPP-W312 Protecta Plus DB 16 Way 250A EPP-W316 Protecta Plus DB 20 Way 250A EPP-W320 Protecta Plus DB 24 Way 250A EPP-W324 MCB distribution board - Type B Description Order codes 125A 3P Horizontal split load kit - 2 x Meters EPP-HSL-1253P 125A 4P Horizontal split load kit - 2 x Meters EPP-HSL-1254P 160A 3P Horizontal split load kit - 2 x Meters EPP-HSL-1603P 160A 4P Horizontal split load kit - 2 x Meters EPP-HSL-1604P 250A 3P Horizontal split load kit - 2 x Meters EPP-HSL-2503P 250A 4P Horizontal split load kit - 2 x Meters EPP-HSL-2504P Horizontal split load kit Protecta Plus Order Codes
EPP-VSL1212-1253P 12+12 Way 125A 3P EPP-VSL168-2503P 16+8 Way 250A 3P Vertical DB CT ratios Dual 125 125+100 Dual 160 160+125 Dual 250 250+160 Tri 125 125+100+100 Tri 160 160+125+100 Tri 250 250+160+125 Order codes No. of outgoing Incomer rating (A) No. of poles EPP-VSL84 8+4 TPN -125 -160 -250 3 P
4 PEPP-VSL88 8+8 TPN
Vertical Split Load Boards - 42 variations are available Boards are supplied fully assembled and metering devices configured to C.T. ratio's MCB distribution board - Type B Protecta Plus Order Codes PROTECTA PLUS – ORDER CODES Pack contents: Vertical Split Load Boards
- 2/3 MID, Modbus ( RS485 ) & Pulse Meters
- Associated CTs
- Incoming terminals
- Internal cables Please note, no additional assembly is required. Units will be delivered with meters pre-configured to internal C.T sizing.
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Protecta Plus Order Codes Description Order codes 125A MID Approved c/w pulse output EPP-METMOD125A 125A MID Approved c/w pulse output & Modbus ( RS485 ) EPP-METMOD125B 125A MID Approved c/w pulse output, Modbus ( RS485 ) Imp / Exp EPP-METMOD125C 160A MID Approved c/w pulse output EPP-METMOD160A 160A MID Approved c/w pulse output & Modbus ( RS485 ) EPP-METMOD160B 160A MID Approved c/w pulse output, Modbus ( RS485 ) Imp / Exp EPP-METMOD160C 250A MID Approved c/w pulse output EPP-METMOD250A 250A MID Approved c/w pulse output & Modbus ( RS485 ) EPP-METMOD250B 250A MID Approved c/w pulse output, Modbus ( RS485 ) Imp / Exp EPP-METMOD250C Incoming metering Description Order codes 125A 3P Switch incoming connection kit EPP-1253P 125A 4P Switch incoming connection kit EPP-1254P 100A 4P RCD incoming connection kit 30mA Type AC - Left side neutral EPP-1004R 160A 3P Switch incoming connection kit EPP-1603P 160A 4P Switch incoming connection kit EPP-1604P 250A 3P Switch incoming connection kit EPP-2503P 250A 4P Switch incoming connection kit EPP-2504P Pack contents: Incoming kit
- Copper connection kit and fittings
- Incoming device
- Cover plate
- Instruction leaflet Incoming connection kit Pack contents: Incoming metering
- 1 x Meter
- 1 x C.T Block
- 1 x Wiring Loom & DIN support
- Instruction leaflet Please note as these kits allow for 4 to 24way boards cutting and crimping of cables is required.
125A AC1 rated 3P Contactor EPP-CON125 160A AC1 rated 3P Contactor EPP-CON160 250A AC1 rated 3P Contactor EPP-CON250 Protecta Plus Order Codes PROTECTA PLUS – ORDER CODES Description Order codes Type 2 surge protection - including 63A 3P MCB EPP-SOULE Type 2/3 surge protection - including 63A 3P MCB EPP-FURSE Surge protection Pack contents: Surge protection
- 1 x Surge unit
- 1 x MCB 3P
- 1 x Wiring Loom & DIN support
- Instruction leaflet Please note as these kits allow for 4 to 24way boards cutting and crimping of cables is required. Pack contents: Contactor control
- 3P contactor
- Control circuit & fuse protection
- Instruction leaflet Contactor Control
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Protecta Plus Order Codes Pack contents: Top extension boxes
- Fixings
- DIN rail / mounting plate
- RAL7035 textured finish Description Order codes Protecta Plus DB 4way 100A HSMS4C Protecta Plus DB 7way 100A HSMS7C Protecta Plus DB 11way 100A HSMS11C Protecta Plus DB 16way 100A HSMS16C Protecta Plus DB 20way 100A HSMS20C MCB Distribution board - Type A Pack contents: Type A distribution
- Supplied factory fitted with 100A switch disconnector
- RAL7035 textured finish Type No. of modules Dimensions (mm) Height (W x D) Order codes Hinged door with 1 DIN rail 16 200 450 x 130 EPP-R1016 Hinged door with 2 DIN rail 32 400 450 x 130 EPP-R2032 Plain extension box 200mm 200 450 x 130 EPP-EB20 Plain extension box 400mm 400 450 x 130 EPP-EB40 Extension boxes
PROTECTA PLUS – ORDER CODES Pack contents: Row type boards
- Fixings
- DIN rail / mounting plate
- RAL7035 textured finish Description Order codes Protecta Plus - Row Type N-Bar 9 EPP-N-09 Protecta Plus - Row Type N-Bar 13 EPP-N-13 Protecta Plus - Row Type N-Bar 17 EPP-N-17 Protecta Plus - Row Type N-Bar 21 EPP-N-21 Protecta Plus - Row Type E-Bar 9 EPP-PE-09 Protecta Plus - Row Type E-Bar 13 EPP-PE-13 Protecta Plus - Row Type E-Bar 17 EPP-PE-17 Protecta Plus - Row Type E-Bar 21 EPP-PE-21 Additional N/PE for side extension boxes No. of modules No. of rows Sided width Dimension Height Order codes 36 2 4way DB 590 EPP-R2036 54 3 8way DB 730 EPP-R3054 72 4 12way DB 870 EPP-R4072 90 5 16way DB 1050 EPP-R5090 108 6 20way DB 1220 EPP-R6108 126 7 24way DB 1360 EPP-R7126 Row type extension boxes Description Order codes Protecta Plus - Top Shroud EPP-TC Protecta Plus Mains TS - 4 Way EPP-MTCO4 Protecta Plus Mains TS - 8 Way EPP-MTCO8 Protecta Plus Mains TS - 12 Way EPP-MTC12 Protecta Plus Mains TS - 16 Way EPP-MTC16 Protecta Plus Mains TS - 20 Way EPP-MTC20 Protecta Plus Mains TS - 20 Way EPP-MTC24 Terminal cover
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A No. of ways Order codes
4 EPP KIT-LAB04W
8 EPP KIT-LAB08W
12 EPP KIT-LAB12W
16 EPP KIT-LAB16W
20 EPP KIT-LAB20W
24 EPP KIT-LAB24W
Labels for outgoing circuits Description Order codes MCB Blank RAL7035 Grey EPP-BP1 MCB Blank RAL9004 Black EPP-BP1B Lock And Key EPP-LK KEY Side By Side Connection Kit EPP-KIT JOIN Padlock Adaptor SA 1 Padlock C/W 2 X Keys SA 2 125A Single Phase Kit EPP-KIT-1251P* 250A Single Phase Kit EPP-KIT-2501P** Trunking adaptor plate EPP-TRADT Protecta Plus - Glandplate Plain EPP-GP-B Protecta Plus - Glandplate K Os EPP-GP KO
19 Modules 30 mm Busbar PS1/19/30
Protecta Plus Trans Door - 4 ways / 2 rows EPP-TD-04 Protecta Plus Trans Door - 8 ways / 3 rows EPP-TD-08 Protecta Plus Trans Door - 12 ways / 4 rows EPP-TD-12 Protecta Plus Trans Door - 16 ways / 4 rows EPP-TD-16 Protecta Plus Trans Door - 20 ways / 5 rows EPP-TD-20 Protecta Plus Trans Door - 24 ways / 6 rows EPP-TD-24 Protecta Plus Solid Door - 4 ways / 2 rows EPP-ST-04 Protecta Plus Solid Door - 8 ways / 3 rows EPP-ST-08 Protecta Plus Solid Door - 12 ways / 4 rows EPP-ST-12 Protecta Plus Solid Door - 16 ways / 4 rows EPP-ST-16 Protecta Plus Solid Door - 20 ways / 5 rows EPP-ST-20 Protecta Plus Solid Door - 24 ways / 6 rows EPP-ST-24 Replacement doors Accessories * Requires kit EPP-1254P ** Required kit EPP-2504P
MBCS – ORDER CODES PROTECTA PLUS ABB has developed a new and personalised series of MCB distribution boards which can be expanded over time.
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A MCB - S 200 M series Order codes S 200 series M C Rated current in A Rated current in kA Order codes IEC/EN 60898-1 IEC/EN 60947-2 1 Pole 3 Pole 6 10kA/15kA S201M-C6 S203M-C6 10 10kA/15kA S201M-C10 S203M-C10 13 10kA/15kA S201M-C13 S203M-C13 16 10kA/15kA S201M-C16 S203M-C16 20 10kA/15kA S201M-C20 S203M-C20 25 10kA/15kA S201M-C25 S203M-C25 32 10kA/15kA S201M-C32 S203M-C32 40 10kA/15kA S201M-C40 S203M-C40 50 10kA/15kA S201M-C50 S203M-C50 63 10kA/15kA S201M-C63 S202M-C63 80A 6kA S201-C80 S203-C80 100A 6kA S201-C100 S203-C100 S 200 series M B Rated current in A Rated current in kA Order codes IEC/EN 60898-1 IEC/EN 60947-2 1 Pole 3 Pole 6 10kA/15kA S201M-B6 S203M-B6 10 10kA/15kA S201M-B10 S203M-B10 13 10kA/15kA S201M-B13 S203M-B13 16 10kA/15kA S201M-B16 S203M-B16 20 10kA/15kA S201M-B20 S203M-B20 25 10kA/15kA S201M-B25 S203M-B25 32 10kA/15kA S201M-B32 S203M-B32 40 10kA/15kA S201M-B40 S203M-B40 50 10kA/15kA S201M-B50 S203M-B50 63 10kA/15kA S201M-B63 S202M-B63 80A 6kA S201-B80 S203-B80 100A 6kA S201-B100 S203-B100 S 200 series M D Rated current in A Rated current in kA Order codes IEC/EN 60898-1 IEC/EN 60947-2 1 Pole 3 Pole 6 10kA/15kA S201M-D6 S203M-D6 10 10kA/15kA S201M-D10 S203M-D10 13 10kA/15kA S201M-D13 S203M-D13 16 10kA/15kA S201M-D16 S203M-D16 20 10kA/15kA S201M-D20 S203M-D20 25 10kA/15kA S201M-D25 S203M-D25 32 10kA/15kA S201M-D32 S203M-D32 40 10kA/15kA S201M-D40 S203M-D40 50 10kA/15kA S201M-D50 S203M-D50 63 10kA/15kA S201M-D63 S202M-D63 Please see glossary for complete MCB offering.
MCB - S 200 SERIES - ORDER CODES S 200 series P C S 200 series P B Rated current in A Rated current in kA Order codes IEC/EN 60898-1 1 Pole 3 Pole 6 25kA S201P-B6 S203P-B6 10 25kA S201P-B10 S203P-B10 13 25kA S201P-B13 S203P-B13 16 25kA S201P-B16 S203P-B16 20 25kA S201P-B20 S203P-B20 25 25kA S201P-B25 S203P-B25 32 15kA S201P-B32 S203P-B32 40 15kA S201P-B40 S203P-B40 50 15kA S201P-B50 S203P-B50 63 15kA S201P-B63 S203P-B63 Rated current in A Rated current in kA Order codes IEC/EN 60898-1 1 Pole 3 Pole 6 25kA S201P-C6 S203P-C6 10 25kA S201P-C10 S203P-C10 13 25kA S201P-C13 S203P-C13 16 25kA S201P-C16 S203P-C16 20 25kA S201P-C20 S203P-C20 25 25kA S201P-C25 S203P-C25 32 15kA S201P-C32 S203P-C32 40 15kA S201P-C40 S203P-C40 50 15kA S201P-C50 S203P-C50 63 15kA S201P-C63 S203P-C63 S 200 series P D Rated current in A Rated current in kA Order codes IEC/EN 60898-1 1 Pole 3 Pole 6 25kA S201P-D6 S203P-D6 10 25kA S201P-D10 S203P-D10 13 25kA S201P-D13 S203P-D13 16 25kA S201P-D16 S203P-D16 20 25kA S201P-D20 S203P-D20 25 25kA S201P-D25 S203P-D25 32 15kA S201P-D32 S203P-D32 40 15kA S201P-D40 S203P-D40 50 15kA S201P-D50 S203P-D50 63 15kA S201P-D63 S203P-D63 Please see glossary for complete MCB offering.
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A RCBO DSE201 M - Type A Order codes Rated residual current IΔn [mA] Rated current in A Rated current in kA Order codes B Characteristic C Characteristic 10 6 10kA/15kA DSE201 M B6 A10 DSE201 M C6 A10 10 10kA/15kA DSE201 M B10 A10 DSE201 M C10 A10 16 10kA/15kA DSE201 M B16 A10 DSE201 M C16 A10 20 10kA/15kA DSE201 M B20 A10 DSE201 M C20 A10 25 10kA/15kA DSE201 M B25 A10 DSE201 M C25 A10 32 10kA/15kA DSE201 M B32 A10 DSE201 M C32 A10 40 10kA/15kA DSE201 M B40 A10 DSE201 M C40 A10 50 10kA DSE201 M B50 A10 DSE201 M C50 A10 30 6 10kA/15kA DSE201 M B6 A30 DSE201 M C6 A30 10 10kA/15kA DSE201 M B10 A30 DSE201 M C10 A30 16 10kA/15kA DSE201 M B16 A30 DSE201 M C16 A30 20 10kA/15kA DSE201 M B20 A30 DSE201 M C20 A30 25 10kA/15kA DSE201 M B25 A30 DSE201 M C25 A30 32 10kA/15kA DSE201 M B32 A30 DSE201 M C32 A30 40 10kA/15kA DSE201 M B40 A30 DSE201 M C40 A30 50 10kA DSE201 M B50 A30 DSE201 M C50 A30 100 6 10kA/15kA DSE201 M C6 A100 10 10kA/15kA DSE201 M C10 A100 16 10kA/15kA DSE201 M C16 A100 20 10kA/15kA DSE201 M C20 A100 25 10kA/15kA DSE201 M C25 A100 32 10kA/15kA DSE201 M C32 A100 40 10kA/15kA DSE201 M C40 A100 50 10kA DSE201 M C50 A100 300 6 10kA/15kA DSE201 M C6 A300 10 10kA/15kA DSE201 M C10 A300 16 10kA/15kA DSE201 M C16 A300 20 10kA/15kA DSE201 M C20 A300 25 10kA/15kA DSE201 M C25 A300 32 10kA/15kA DSE201 M C32 A300 40 10kA/15kA DSE201 M C40 A300 50 10kA DSE201 M C50 A300 DSE201 M - Type A
RCBO DSE201 M - TYPE AC – ORDER CODES Rated residual current IΔn [mA] Rated current in A Rated current in kA Order codes B Characteristic C Characteristic 10 6 10kA/15kA DSE201 M B6 AC10 DSE201 M C6 AC10 10 10kA/15kA DSE201 M B10 AC10 DSE201 M C10 AC10 16 10kA/15kA DSE201 M B16 AC10 DSE201 M C16 AC10 20 10kA/15kA DSE201 M B20 AC10 DSE201 M C20 AC10 25 10kA/15kA DSE201 M B25 AC10 DSE201 M C25 AC10 32 10kA/15kA DSE201 M B32 AC10 DSE201 M C32 AC10 40 10kA/15kA DSE201 M B40 AC10 DSE201 M C40 AC10 50 10kA DSE201 M B50 AC10 DSE201 M C50 AC10 30 6 10kA/15kA DSE201 M B6 AC30 DSE201 M C6 AC30 10 10kA/15kA DSE201 M B10 AC30 DSE201 M C10 AC30 16 10kA/15kA DSE201 M B16 AC30 DSE201 M C16 AC30 20 10kA/15kA DSE201 M B20 AC30 DSE201 M C20 AC30 25 10kA/15kA DSE201 M B25 AC30 DSE201 M C25 AC30 32 10kA/15kA DSE201 M B32 AC30 DSE201 M C32 AC30 40 10kA/15kA DSE201 M B40 AC30 DSE201 M C40 AC30 50 10kA DSE201 M B50 AC30 DSE201 M C50 AC30 100 6 10kA/15kA DSE201 M C6 AC100 10 10kA/15kA DSE201 M C10 AC100 16 10kA/15kA DSE201 M C16 AC100 20 10kA/15kA DSE201 M C20 AC100 25 10kA/15kA DSE201 M C25 AC100 32 10kA/15kA DSE201 M C32 AC100 40 10kA/15kA DSE201 M C40 AC100 50 10kA DSE201 M C50 AC100 300 6 10kA/15kA DSE201 M C6 AC300 10 10kA/15kA DSE201 M C10 AC300 16 10kA/15kA DSE201 M C16 AC300 20 10kA/15kA DSE201 M C20 AC300 25 10kA/15kA DSE201 M C25 AC300 32 10kA/15kA DSE201 M C32 AC300 40 10kA/15kA DSE201 M C40 AC300 50 10kA DSE201 M C50 AC300 DSE201 M - Type AC DSE201 M - Type A
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A RCCB F 200 series AC type Order Codes Number of poles Rated residual current IΔn [mA] Rated current in A Order codes 2 10 16 F202 AC-16/0.01 25 F202 AC-25/0.01 30 25 F202 AC-25/0.03 40 F202 AC-40/0.03 63 F202 AC-63/0.03 80 F202 AC-80/0.03 100 F202 AC-100/0.03 100 25 F202 AC-25/0.1 40 F202 AC-40/0.1 63 F202 AC-63/0.1 80 F202 AC-80/0.1 100 F202 AC-100/0.1 300 25 F202 AC-25/0.3 40 F202 AC-40/0.3 63 F202 AC-63/0.3 80 F202 AC-80/0.3 100 F202 AC-100/0.3 500 25 F202 AC-25/0.5 40 F202 AC-40/0.5 63 F202 AC-63/0.5 80 F202 AC-80/0.5 100 F202 AC-100/0.5 F 200 AC type - F202
37RCCB F 200 SERIES – ORDER CODES F 200 AC type - F202 Number of poles Rated residual current IΔn [mA] Rated current in A Order codes 4 30 25 F204 AC-25/0.03 40 F204 AC-40/0.03 63 F204 AC-63/0.03 80 F204 AC-80/0.03 100 F204 AC-100/0.03 100 25 F204 AC-25/0.1 40 F204 AC-40/0.1 63 F204 AC-63/0.1 80 F204 AC-80/0.1 100 F204 AC-100/0.1 300 25 F204 AC-25/0.3 40 F204 AC-40/0.3 63 F204 AC-63/0.3 80 F204 AC-80/0.3 100 F204 AC-100/0.3 500 25 F204 AC-25/0.5 40 F204 AC-40/0.5 63 F204 AC-63/0.5 80 F204 AC-80/0.5 100 F204 AC-100/0.5 F 200 AC type - F204 RCCB F 200 series AC type Order Codes
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Metering EQ series Order codes 80A TPN 7mod Description Order codes Pulse output A43 111 - 100 Pulse output, RS-485 A43 112 - 100 Pulse output, M-Bus A43 113 - 100 2 output, 2 input, RS-485 A43 312 - 100 2 output, 2 input, M-Bus A43 313 - 100 A series - A43 80A SPN 4mod Description Order codes Pulse output A41 111 - 100 Pulse output, RS-485 A41 112 - 100 Pulse output, M-Bus A41 113 - 100 2 output, 2 input, RS-485 A41 312 - 100 2 output, 2 input. M-Bus A41 313 - 100 A series - A41 65A SPN 2mod Description Order codes Pulse output B21 111 - 100 Pulse output, RS-485 B21 112 - 100 Pulse output, M-Bus B21 113 - 100 2 output, 2 input, RS-485 B21 312 - 100 2 output, 2 input, M-Bus B21 313 - 100 B series - B21 65A TPN 4mod Description Order codes Pulse output B23 111 - 100 Pulse output, RS-485 B23 112 - 100 Pulse output, M-Bus B23 113 - 100 2 output, 2 input, RS-485 B23 312 - 100 2 output, 2 input, M-Bus B23 313 - 100 B series - B23
39CIRCUIT MONITORING STYSTEM - CMS - ORDER CODES Description 0rder codes 8 0 A CMS-120DR 4 0 A CMS-121DR 2 0 A CMS-122DR Open core sensors Open-core sensors 18 mm for DIN rail mounting (universally usable) Description 0rder codes Control Unit CMS-600 CMS-600 Control Unit CMS-700 CMS-700 Control Units Accessories Description 0rder Codes Cable 5m C M S - 8 0 2 Sensor connectors ( 35pcs ) CMS-820 Circuit Monitoring System - CMS Order Codes ABB's circuit monitoring system (CMS) is a unique ultra-compact and high-performance multi-channel measurement system for branch monitoring. The system consists of a control unit and sensors with different measurement ranges and mounting possibilities. Description 0rder codes 8 0 A CMS-120PS 4 0 A CMS-121PS 2 0 A CMS-122PS Open core sensors Open-core sensors 18 mm for Pro M & SMISSLINE installation devices with twin terminals For more detailed information see p66.
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A These devices are specifically made for commanding loads and signalling electrical conditions in any low-voltage distribution board. The functions of these devices are particularly switching, pushing and signalling electrical conditions in any installations (low-voltage area) Main poles Number of modules Control coil voltage 40-50 Hz DC Order codes 2 N.O. 2 24 V 24 V ESB 24-20* 4 N.O. 2 12 V 12 V ESB 24-40*
24 V 24 V ESB 24-40*
4 N.C. 2 12 V 12 V ESB 24-04*
24 V 24 V ESB 24-04*
2 N.O. 2 N.C. 2 12 V 12 V ESB 24-22*
24 V 24 V ESB 24-22*
2 12 V 12 V ESB 24-31* 3 N.O. 1 N.C. 24 V 24 V ESB 24-31* 2 12 V 12 V ESB 24-13* 4 N.O. 3 N.C. 24 V 24 V ESB 24-13* ESB 24 ESB installation contactors Order Codes * Ensure voltage is selected
4 N.O. 3 12 V 12 V ESB 40-40*
24 V 24 V ESB 40-40*
2 N.C. 3 24 V 24 V ESB 40-22*
230 V 230 V ESB 40-22*
1 N.C. 3 24 V 24 V ESB 40-31*
230 V 230 V ESB 40-31*
3 N.O. 3 24 V 24 V ESB 40-30*
230 V 230 V ESB 40-30*
2 N.O. 3 24 V 24 V ESB 40-20*
230 V 230 V ESB 40-20*
4 N.O. 3 12 V 12 V ESB 63-40*
24 V 24 V ESB 63-40*
1 N.C. 3 110 V 110 V ESB 63-31*
230 V 230 V ESB 63-31*
3 N.O. 3 230 V 230 V ESB 63-30*
400 V 400 V ESB 63-30*
2 N.O. 3 24 V 24 V ESB 63-20*
230 V 230 V ESB 63-20*
1 N.O. 1 N.C. 3 230 V 230 V ESB 63-11* ESB 40 ESB 63 ESB 24 ESB installation contactors Order Codes ESB INSTALLATION CONTACTORS – ORDER CODES * Ensure voltage is selected * Ensure voltage is selected
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Channels no. Type Order codes D1 D1 Plus 1 D1 2CSM258763R0621
1 D1 PLUS 2CSM257583R0621
1 D1 SYNCHRO 2CSM257493R0621
2 D2 2CSM256313R0621
2 D2 PLUS 2CSM277583R0621
2 D2 SYNCHRO 2CSM277363R0621
Programming key D KEY 2CSM277143R0621 Programming software D SW 2CSM299973R0621 DCF77 antenna D DCF77 2CSM299983R0621 GPS antenna D GPS 2CSM299993R0621 D Line weekly digital time switches The unique design, with white backlit LCD display, and extreme ease of use with two lines of text menu and only four buttons, make D Line ideal to automate the installation functions. Thanks to the innovative management of time vacation, the D Line digital time switches allow the exclusion of the normal weekly program in one or more periods of several years or between two different years. The range includes 1 and 2 channel versions, equipped with large capacity internal battery to maintain operation without power supply and permanent memory EEPROM, to avoid the risk of program loss and to maintain the date and time settings in the event of power failure, irrespective of its duration. The “Plus” version can transfer different types of program by using a D KEY to be quickly copied in using no digital time switches, avoiding the errors due to future modification. The “SYNCHRO” version can be coupled to the D DCF77 antenna, that allows an automatic synchronization of the digital time switch with the Frankfurt DCF77 time signal, or can be coupled to the D GPS antenna to allows synchronization received from the Global Positioning System. The D Line is particularly useful in environments and situations where user management is required with a time schedule flexible enough to predict or exclude activities according to time and day of week or month. D Line switches Accessories D Line digital time switches Order Codes Please see page 70 for explanation of types
Programming key D KEY 2CSM277143R0621 Programming software D SW 2CSM299973R0621 DCF77 antenna D DCF77 2CSM299983R0621 GPS antenna D GPS 2CSM299993R0621 Accessories D/T LINE DIGITAL TIME SWITCHES – ORDER CODES Brightness range lux Order codesType 2:200 T1 2CSM295563R1341 2:15000 T1 PLUS 2CSM295793R1341 Brightness range lux Order codesType External sensor LS-D 2CSM295723R1341 T Line modular twilight switches Order Codes T Line modular twilight switches These twilight switches allow to switch ON and switch OFF lighting devices according to a scheduled level of the ambient light. They are used in combination with an external sensor to detect if the ambient light is higher or lower than the set level. A switching delay prevents them from operating unnecessarily when the light intensity suddenly changes (e.g. lightning, moving vehicles, etc.). The T1 twilight switch in 1 channel is preset at 10 lux. Accessories for T Line modular twilight switches The external sensor is supplied in the same package of the switch, but it’s also available separately as spare part. The upper part of the external case (with screw locking), is made up of from factory and is equipped with 2 signalling LEDs that indicate the setpoint value and display the status of the contact . The operating instructions are printed on the side of the product. T1 PLUS switches feature a setpoint that can be adjusted for 4 different scale values (2:40, 20:200, 200:2000, 2000:15000).This makes them ideal for daytime applications where the lux values are very high. With a 10 lux preset factory setting, they are equipped with 2 signalling LEDs that indicate the setpoint value and display the status of the contact. thermoplastic materials and bears up against ultraviolet rays to guarantee a homogeneous diffusion of the daylight internally. LS-D is also equipped with a cable gland. 01 T1
02 T1 PLUS
03 LS-D
T Line modular twilight switches Accessories
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Colour Modules Order codes M1363 Grey 3 M1363 Grey with light 3 M1363-L British standard modular sockets Modular sockets Order Codes Number of poles Rated current In Modules Order codes E92 1 32 1 E 91/32 1 32 1 E 91/32s 3 32 3 E 93/32 E94 3 32 3 E 93/32s E 90 fuse switch disconnectors Order Codes E 90 series fuse switch disconnectors are designed for switching circuits under load, providing protection against short circuits and overloads. The case is made of self-extinguishing thermoplastic material resistant to high temperatures (all materials are UL listed) while the contact clips are in silver plated copper. E 90 fuse switch disconnectors can be sealed or padlocked to ensure operator safety during maintenance. Versions with blown fuse indicator allow to check whether the fuse is still working correctly or not. For easy and quick installation E 90 range is totally compatible with connecting bars, terminals and caps of S 200 MCBs. Thanks to cURus approval, they can be installed in UL certified machines. E 90 fuse switch disconnectors for 10.3 x 38 mm fuses (AC-22B) E94 Fuses not included
The CMS system allows users to measure AC and DC currents for up to 64 individual lines. Data can be remotely monitored via desktop or mobile device app. Colour Modules Order codes M1363 Grey 3 M1363 Grey with light 3 M1363-L
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A
Description
Standards/requirements IEC BS EN 61439-1&2, ed.2 (2011-08) Rated current Maximum load 250A at ambient temperature +35° Rated operational voltage (Ue) 415 V AC Rated frequency 50/60 Hz Rated insulation voltage (Ui) 690 V Rated conditional short circuit current (Icc) 35 kA Neutral size 2 Brass bar each size (7*10) mm Earth size 2 Brass bars each size (7*10) mm Degree of protection With Door IP 43 Pan Assembly IP 20 Mechanical impact strength Cabinet enclosures IK 07 Housing and door material Material Type Cold rolled sheet steel 1 mm Color RAL 7035 Coating Type (Powder or) Electrostatic powder coating, textured finish Door opening angle 180° Position of knockouts Top and bottom Type of Door Closure Latch (Optional Lock) Incoming cable connections* 125A >50 mm 160A >70 mm 250A >95 mm Protecta Plus Technical specifications Technical features *For requirements above stated figures seek advise from technical services
EPP-W304 590 450 125 358 500 EPP-R2036 590 450 125 358 500 EPP-W308 730 450 125 358 640 EPP-R3054 730 450 125 358 640 EPP-W312 870 450 125 358 780 EPP-R4072 870 450 125 358 780 EPP-W316 1,050 450 125 358 960 EPP-R5090 1,050 450 125 358 960 EPP-W320 1,220 450 125 358 1,130 EPP-R6108 1,220 450 125 358 1,130 EPP-W324 1,360 450 125 358 1,270 EPP-R7126 1,360 450 125 358 1,270 Type B Distribution boards Height mm Width mm Depth mm mm mm EPP-EB20 200 450 125 358 110 EPP-EB40 400 450 125 358 310 EPP-RW1016 200 450 125 358 110 EPP-RW2032 400 450 125 358 310 EPP-CON 500 450 125 358 410 Extension boxes
01 Type B
02 Extension
PROTECTA PLUS – DIMENSIONS
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Height mm 125/160A Height mm 250A Width mm Depth mm EPP-HSL 2x4way 990 1,190 900 125 EPP-HSL 2x8way 1,130 1,330 900 125 EPP-HSL 2x12way 1,270 1,470 900 125 EPP-HSL 2x16way 1,450 1,650 900 125 EPP-HSL 2x20way 1,620 1,820 900 125 EPP-HSL 2x24way 1,760 1,960 900 125 01 / 02 Horizontal split-load boards Protecta Plus Dimensions
01 Horizontal
03 Type A
Isolator Direct Connection kit Meter & C.T EPP-HSL kits are aligned from the base of the DB. SLP-HSL assemblies are aligned from the top od the DB. SLP-HSL are complete assemblies designed for projects. 1SKC802015C0205 Consumer Units Dimensional details (continued) Housemaster compact sheet steal consumer unit surface mounted 256 256 110 110 C 142 A (mm)No. of Modules Type Code B (mm) 155 210 263 368 440 HSMS 04C HSRC 04C HSMS 07C HSRC 07C HSMS 11C HSRC 11C HSSL 4+4C HSMS 16C HSRC 16C HSSL 6+6C HSMS 20C HSRC 20C HSSL 8+8C 152 207 257 365 437 C (mm) 133 187 292 360 Comby steel flap consumer unit flush mounted A (mm)No. of Modules Type Code B (mm) 203 257 262 434 ECS 107 DF ECS 110 DF ECS 116 DF ECS 120 DF 229 283 386 460 C (mm) 133 187 292 366 256 142 110 C 250 276 Housemaster compact plastic consumer unit surface mounted A (mm)No. of Modules Type Code B (mm) 100 140 210 280 350 HMMS 04C HMRC 04C HMMS 07C HMRC 07C HMMS 11C HMRC 11C HMSL 4+4C HMMS 16C HMRC 16C HMSL 6+6C HMMS 20C HMRC 20C HMSL 8+8C 190 230 300 370 440 A B 123 122 226 Number of modules A mm B mm C mm HSMS 04C 4way 152 155 77 HSMS 07C 7way 207 210 133 HSMS 11C 11way 257 263 187 HSMS 16C 16way 265 368 292 HSMS 20C 20way 437 440 360
03 Housemaster compact sheet steal consumer unit (surface mounted)
EPP-VSL 8+4 1,090 450 125 358 1,000 EPP-VSL 8+8 1,270 450 125 358 1,180 EPP-VSL 12+8 1,440 450 125 358 1,350 EPP-VSL 12+12* 1,580 450 125 358 1,490 EPP-VSL 16+8* 1,580 450 125 358 1,490 EPP-VSL 8+4+4* 1,380 450 125 358 1,290 EPP-VSL 12+4+4* 1,690 450 125 358 1,600 Vertical split-load boards Protecta Plus Dimensions
01 Vertical
02 Metering layout
Meter & C.T PROTECTA PLUS – DIMENSIONS 01 / 02 Horizontal split-load boards * Please ensure RCBO lead lengths are considered.
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Rated operational voltage (U n) The rated voltage of a circuit-breaker is the value of voltage, assigned by the manufacturer, to which its performance (particularly the short- circuit performance) is referred. The same circuit-breaker may be assigned a number of rated voltages and associated rated short-circuit capacities. The voltage which appears across the terminals of a pole of a circuit-breaker after the breaking of the current. The value of the power frequency recovery voltage shall be equal to 110% of the rated voltage of the circuit-breaker under test. IEC/EN 60947-2 This part of the IEC/EN 60947 applies to circuit- breakers, the main contacts of which are intended to be connected to circuits, the rated voltage of which does not exceed 1,000 V AC or 1,500 V DC It applies whatever the rated currents, the method of construction or the proposed applications of the circuit-breakers may be. The circuit-breakers are designed for use by instructed people. Rated ultimate short-circuit breaking capacity Icu The rated ultimate short-circuit breaking capacity of a circuit-breaker is the value of ultimate short- circuit breaking capacity assigned to that circuit- breaker by the manufacturer for the corresponding rated operational voltage. It is expressed as the value of the prospective breaking current, in kA (r.m.s. value of the AC component in the case of AC). The sequence of operations shall be: O – t – CO Rated service short-circuit breaking capacity Ics The rated service short-circuit breaking capacity of a circuitbreaker is the value of service short- circuit breaking capacity assigned to that circuit- breaker by the manufacturer for the corresponding rated operational voltage. It is expressed as a value of prospective breaking current, in kA, corresponding to one of the specified percentages of the rated ultimate MCBs technical details Definitions according to standards for miniature circuit breakers Rated insulation voltage (U i) according IEC/EN 60664-1: Root mean square (R.M.S.) withstand voltage value assigned by the manufacturer to the equipment or to a part of it, characterizing the specified (long-term) withstand capability of its insulation. The rated insulation voltage is not necessarily equal to the rated voltage of the equipment which is primarily related to functional performance. IEC/EN 60898-1 Miniature Circuit Breakers according IEC/EN 60898-1 are intended for the protection against over-currents of wiring installations in buildings and similar applications; they are designed for use by uninstructed people and for not being maintained. This part of IEC/EN 60898 applies for a.c. air- break circuit-breakers for operation at 50 Hz or
60 Hz, having a rated voltage not exceeding 440 V
(between phases), a rated current not exceeding
125 A and a rated short-circuit capacity not
exceeding 25,000 A. As far as possible, it is in line with the requirements contained in IEC/EN 60947-2. Rated short-circuit capacity (Icn) The rated short-circuit capacity of a circuit- breaker is the value of the ultimate short-circuit breaking capacity assigned to that circuit- breaker by the manufacturer. The sequence of operations shall be: O – t – CO Service short-circuit capacity (Ics) A circuit-breaker having a given rated short- circuit capacity has a corresponding fixed service short-circuit capacity (Ics). This is therefore generally not indicated.
ARTICLE OR CHAPTER TITLE 51 shortcircuit breaking capacity and rounded up to the nearest whole number. It may be expressed as a percentage of Icu (for example Ics = 25% Icu). The sequence of operations shall be: O – t – CO – t – CO The following symbols are used for defining the sequence of operatons: O represents an opening operation. CO represents a closing operation followed by an automatic opening. t represents the time interval between two short-circuit operations.
01 The rated insulation
Rated operational voltage (U e) The rated operational voltage of an equipment is a value of voltage which, combined with a rated operational current, determines the application of the equipment and to which the relevant tests and the utilization categories are referred. For single-pole equipment it is generally stated as the voltage across the pole. For multi pole equipment it is generally stated as the voltage between phases. Equipment may be assigned a number of combinations of rated operational voltage and associated making and breaking capacities for different duties and utilization categories.
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Characteristic K IEC-EN60947-2 2CSC400400F0202 2CSC400400F0202Multiples of rated current 2CSC400401F0202 2CSC400400F020 2 Seconds Multiples of rated current Minutes Tripping curve from cold state Seconds Multiples of rated current Minutes Tripping curve from cold state Seconds Multiples of rated current Minutes Tripping curve from cold state Seconds Minutes Tripping curve from cold state Seconds Multiples of rated current 2CSC400400F020 2 Characteristic B IEC-EN60898 Characteristic C IEC-EN60898 Characteristic Z IEC-EN60947-2 Characteristic D IEC-EN60898 MCBs technical details Definitions according to standards for miniature circuit breakers 2CSC400400F020 2 2CSC400400F020 2 Multiples of rated current 2CSC400401F0202 2CSC400400F0202 Seconds Multiples of rated current Minutes Tripping curve from cold state Seconds Multiples of rated current Minutes Tripping curve from cold state Seconds Multiples of rated current Minutes Tripping curve from cold state Seconds Minutes Tripping curve from cold state Seconds Multiples of rated current 2CSC400400F0202
Characteristic C IEC-EN60898 Characteristic Z IEC-EN60947-2 Characteristic D IEC-EN60898 ABB ABB continually develops smart solutions for controlling and monitoring the flow of electricity, as well as improving energy efficiency in buildings and critical power applications.
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A MCB S 200 Series technical features General data Specifications S 200 M S 200P Standards IEC/EN 60898-1, IEC/EN 60947-2 IEC/EN 60898-1, IEC/EN 60947-2 UL 1077, CSA 22.2 No. 235 UL 1077, CSA 22.2 No. 235 Poles – 1P, 2P, 3P, 4P, 1P+N, 3P+N Tripping characteristics – B, C, D, K, Z B, C, D, K, Z Rated current I n A 0.5...63A – Rated current f Hz 50/60Hz 50/60Hz Rated insulation voltage U i acc. to IEC/EN 60664-1 – 440V AC (phase to phase) 250 V AC (phase to ground),
500 V AC (phase to phase)
Overvoltage category – III – Pollution degree – 3 2 Data acc. to IEC/EN 60898-1 (except S200M UC data acc. to IEC/EN60898-2) Rated operational voltage Un V 1P: 230/400V AC; 1P+N: 230V AC ; 2... 4P: 400V AC; 3P+N: 400V 1P: 230V AC, 220V DC 2P: 400V AC, 440V DC 3...4P: 400V AC* Max. power frequency recovery voltage (U max) V 1P: 253V AC; 1P+N: 253V AC; 2P: 440V AC; 3...4P: 440V AC; 3P+N: 440V AC 1P: 230V AC, 220V DC 2P: 400V AC, 440V DC 3...4P: 400V AC* Min. operating voltage V 12V AC - 12V DC – Rated short-circuit capacity I cn kA 10kA ≤ 25A: 25kA > 25A: 15kA Energy limiting class (B, C up to 40 A) – 3 3 Rated impulse withstand voltage Uimp. (1.2/50μs) kV – – Dielectric test voltage kV 2kV (50/60Hz, 1 min.) 2kV (50/60Hz, 1 min.) Reference temperature for tripping characteristics oC B, C, D: 30°C 30°C Electrical endurance ops. In < 32A: 20,000 ops (AC), In ≥ 32A: 10,000 ops. (AC); 1,000 ops. (DC); Data acc. to IEC/EN 60947-2 Rated operational voltage Ue V 1P: 230V AC; 1P+N: 230V AC; 2...4P: 400V AC; 3P+N: 400V AC Max. power frequency recovery voltage (U max) V 1P: 253V AC; 1P+N: 253V AC; 2P...4P: 440V AC; 3P+N: 440V AC; 1P: 72V DC; 2P: 125V DC Min. operating voltage V 12V AC - 12V DC 12 V AC - 12V DC Rated ultimate short-circuit breaking capacity Icu kA 15kA ≤ 25A: 25kA ≥ 32A: 15kA Rated service short-circuit breaking capacity Ics kA ≤ 40A: 11.2kA 50, 63A: 7.5kA ≤ 25A: 12.5kA ≤ 32…40A: 11.2kA 50, 63A: 7.5kA Rated impulse withstand voltage U imp. (1.2/50μs) kV 4kV (test voltage 6.2kV at sea level, 5kV at 2,000m) – Dielectric test voltage kV 2kV (50/60Hz, 1 min.) – Reference temperature for tripping characteristics °C B, C, D: 55°C; K, Z: 20°C B, C: 55°C; K, Z: 20°C Electrical endurance ops. In < 32A: 20,000 ops (AC), In ≥ 32A: 10,000 ops. (AC); 1,000 ops. (DC); (1 cycle 2s - ON, 13s - OFF, In ≤ 32A), (1 cyle 2s - ON, 28s - OFF, In > 32A) In < 32A: 20,000 ops (AC), In ≥ 32A: 10,000 ops. (AC); 1,000 ops. (DC); (1 cycle 2s - ON, 13s - OFF, In ≤ 32A), (1 cyle 2s - ON, 28s - OFF, In ≥ 32A) Note: * Only acc. to IEC/EN 60898-1 r switching Technical features
55MCB - TECHNICAL FEATURES MCB S 200 80A-100A series technical features General Data S 200 80A-100A Standards IEC/EN 60898-1, IEC/EN 60947-2 Poles 1P, 2P, 3P, 4P, 1P+N, 3P+N Tripping characteristics B, C Rated current I n 80 A, 100 A Rated frequency f 50/60 Hz Rated insulation voltage Ui acc. to IEC/EN 60664-1 (VDE 0110-1) 440 V AC Overvoltage category III Pollution degree 2 IEC/EN 60898-1 (VDE 0641-11) Rated operational voltage U n 1P: 230/400 V AC; 1P+N: 230 V AC; 2P, 3P, 4P, 3P+N: 400 V AC Max. power frequency recovery voltage U max 1P: 253/440 V AC; 1P+N: 253 V AC; 2P, 3P, 4P, 3P+N: 440 V AC Min. operating voltage 12 V AC Rated short-circuit capacity I cn 6 kA Rated impulse withstand voltage U imp (1.2/50µs) 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m) Dielectrical test voltage 2 kV (50/60 Hz, 1 min.) Reference temperature for tripping characteristics B, C: 30 °C Electrical endurance 10,000 ops. (AC); one cycle 2 s - ON, 28 s - OFF IEC/EN 60947-2 (VDE 0660-101) Rated operational voltage U e 1P, 1P+N: 230 V AC; 2P, 3P, 4P, 3P+N: 400 V AC Max. power frequency recovery voltage U max 1P, 1P+N: 253 V AC; 2P, 3P, 4P, 3P+N: 440 V AC Min. operating voltage 12 V AC Rated ultimate short-circuit breaking capacity I cu 6 kA Rated service short-circuit breaking capacity I cs 6 kA Rated impulse withstand voltage U imp (1.2/50 µs) 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m) Dielectrical test voltage 2 kV (50/60 Hz, 1 min.) Reference temperature for tripping characteristics B, C: 55 °C Electrical endurance 10,000 ops. (AC); one cycle 2 s - ON, 28 s - OFF Mechanical data Housing Insulation group I, RAL 7035 Toggle Insulation group II, black, sealable Contact position indication Real CPI (red ON/green OFF) Protection degree acc. to DIN EN 60529 IP20 (1), IP40 in enclosure with cover Mechanical endurance 20,000 ops. Shock resistance acc. to DIN EN 60068-2-27 25 g, 2 shocks, 13 ms Vibration resistance acc. to DIN EN 60068-2-6 5 g, 20 cycles at 5…150…5 Hz at 0.8 I n Environmental conditions (Damp heat cyclic) acc. to DIN EN 60068-2-30 28 cycles with 55 °C/90-96 % and 25 °C/95-100 % Ambient temperature -25 ... +55 °C Storage temperature -40 ... +70 °C Technical features
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A MCB S200 80A-100A series technical features and tripping characteristics Installation features Tripping characteristics Installation S 200 80A-100A Terminal Failsafe bi-directional cache clamp Cross-section of conductors (top/bottom) solid, stranded: 50 mm 2 / 50 mm 2 flexible: 50 mm 2 / 50 mm 2 Cross-section of busbars (top/bottom) 16 mm2 / 16 mm 2 Torque 3.0 Nm Screwdriver Nr. 2 Pozidriv Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip Mounting position any Supply any Dimensions and weight Mounting dimensions acc. to DIN 43880 Mounting dimension 1 Pole dimensions (H x T x B) mm 88.8 x 69 x 17.5 Pole weight approx. 126 g Combination with auxiliary elements Auxiliary contact Yes Signal/auxiliary contact Yes Shunt trip Yes Unervoltage release Yes Motor Operating Device Yes Data acc. to Tripping characteristics Rated current I n Thermal release (¹) Electromagnetic release (²) Currents: conventional non-tripping current Conventional tripping current I2 Tripping time Range of instantaneous tripping Tripping time DIN EN 60898-1 B 80 up to 100 A 1.13 · In 1.45 · In > 2 h < 2 h 3 · In 5 · In 0.1 ... 90 s < 0.1 s (VDE 0641-11) C 80 up to 100 A 1.13 · In 1.45 · In > 2 h < 2 h 5 · I n 10 · I n 0.1 ... 30 s < 0.1 s (¹) The thermal releases are calibrated to a nominal reference ambient temperature; for B and C the reference value is 30 °C. In the case of higher ambient temperatures, the current values fall by approx. 6 % for each 10 K temperature rise. (²) The indicated tripping values of electromagnetic tripping devices apply to a frequency of 50/60 Hz. The thermal release operates independent of frequency.
57RCBO DSE201 M - TECHNICAL FEATURES RCBO DSE201 M Technical features Technical features Electrical features Standards IEC 61009-1; IEC 61009-2-2; AS/NZS 61009 Type (wave form of the earth leakage sensed) AC, A Number of poles 1P+N Rated current I n A 6≤ In ≤ 50 Rated sensitivity I Δn mA 10, 30, 100, 300 Rated voltage U e V 230-240 Insulation voltage U i V 500 V AC Overvoltage category III Pollution degree 2 Max. operating voltage V 264 Min. operating voltage for protection against IΔn residual sinusoidal alternating currents V 85 Min. operating voltage of circuit test V 195 Rated frequency Hz 50/60 Rated breaking capacity acc. to IEC 61009 ultimate I cn A 10000 Rated breaking capacity acc. to IEC 60947-2 ultimate I cn kA 15 (for 6A≤ In ≤ 40A) kA 10 (for In = 50A) service I cs kA 7.5 Rated residual breaking capacity I Δm kA 10 Rated impulse withstand voltage (1.2/50) U imp kV 4 kV (test voltage 6.2kV at sea level, 5kV at 2000m) Thermomagnetic release - characteristic B: 3 I n ≤ I m ≤ 5 I n C: 5 I n ≤ I m ≤ 10 I n Surge current resistance (wave 8/20) A 250 Mechanical data Housing insulation group II, RAL 7035 Toggle insulation group IIIA, black, sealable in ON-OFF positions Contact position indication CPI on toggle (I ON / 0 OFF) Electrical life operations 10000 Mechanical life operations 20000 Protection degree housing IP4X terminals IP2X Shock resistance acc. to IEC/EN 60068-2-27 30g - 2 shocks - 13ms Vibration resistance acc. to IEC/EN 60068-2-6 0.35mm or 5g - 20 cycles at 5…150…5 Hz without load Environmental conditions (damp heat) acc. to IEC/EN 60068-2-30 °C/RH 28 cycles with 55°C/90-96% and 25°C/95-100% Reference temperature for setting of thermal element °C 30 Ambient temperature (with daily average ≤ +35 °C) °C -25…+55 Storage temperature °C - 40…+70
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A RCBO DSE201 M Technical features and dimentions Installation features Installation Terminal type top (load side) failsafe cage (shock protected) bottom (line side) failsafe bi-directional cylinder-lift terminal (shock protected) Terminal size for cables load side (top) mm² 16 line side (bottom) mm² 25 Terminal size for busbars load side (top) only for wire connection line side (bottom) mm² 10 (Standard ABB busbar / distribution board system) Tightening torque top (load side) Nm 1.2 bottom (line side) Nm 2.8 Neutral load cable Type low smoke halogen free Lenght mm 750 Section mm² 2.5 mm² up to 20 A; 4 mm² up to 50 A Color blue Functional earth cable Type low smoke halogen free Lenght mm 750 Section mm² 0.75 Color white Mounting on DIN rail EN 60715 (35 mm) by means of fast clip device in consumer unit Type A according to IEC 61439-1&3, BS EN 61439-1&3, in distribution board Type B according to IEC 61439-1&3, BS EN 61439-1&3. Supply from bottom terminal Dimensions and weight Dimensions (H x D x W) mm 100 x 68.9 x 17.6 Weight g 180 Combination with auxiliary elements Auxiliary contact Signal contact / auxiliary switch yes Shunt trip yes Undervoltage release yes Overvoltage release yes Auxiliary contact for MCBs bottom fitting yes yes Signal contact / auxiliary switch yes Shunt trip yes Undervoltage release yes Overvoltage release yes Auxiliary contact for MCBs bottom fitting yes 01 50A version is 115 mm height
Features Specifications F 200AC Electrical features Standards IEC/EN 61008-1; IEC/EN 61008-2-1, UL 1053 ( ¹) Type (wave form of the earth leakage – AC Poles – 2P, 4P (for 125 A only 4P) Rated current I n A 16, 25, 40, 63, 80, 100, 125 Rated sensitivity IΔ n A 50/60Hz Rated voltage U e V 230/400 - 240/415 V 480Y/277 (up to 100 A Insulation voltage U i – V 500 Max. operating voltage of circuit test V 110 (185 for 125 A); 195 for F 200 left neutral 170 (150 for 125 A); 300 for F 200 left neutral for IDn = 30 mA ( ⁵) V 277 (up to 100 A); 480 for F 200 left neutral (⁴ Min. operating voltage of circuit test V 110 (185 for 125 A); 195 for F 200 left neutral 170 (150 for 125 A); 300 for F 200 left neutral for IDn = 30 mA ( ⁵) Rated frequency Hz 50…60 Rated conditional short-circuit current Inc=IΔ (³) kA 277 (up to 100 A); 480 for F 200 left neutral (⁴ Rated residual breaking capacity IΔm=Im kA 1 (1.25 for 125 A) Rated impulse withstand voltage (1.2/50) Uimp kV 4 Dielectric test voltage at ind. freq. for 1 min. kV 2.5 Overvoltage category – III, disconnector abilities Surge current resistance (wave 8/20) A 250 Mechanical features Toggle – Blue sealable in ON-OFF position Contact position indicator (CPI) – Yes Electrical life – – 10000 (2000 for 125 A) Mechanical life – – 20000 (5000 for 125 A) Protection degree Housing IP4X Terminals IP2X Environmental conditions (damp heat) acc. to IEC/EN 60068-2- 30 °C/RH 28 cycles with 55°C/90-96% and 25°C/95 Ambient temperature (with daily average ≤ +35 °C) °C -25…+55 (-25...+40 for 125A) Storage temperature – °C - 4 0…+70 Installation Terminal type Failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected) (cage for In > 63A) ( 2) Terminal size top/bottom for cable mm2 25/25 (35/35 single slot terminal for In > 63A) UL/CSA AWG 18-4 (up to 63A) Terminal size top/bottom for busbar IEC mm2 10/10 (not for In = 80-100A) UL/CSA AWG 18-8 (up to 63A) Tightening torque Nm 2.8 (3 for In = 125A) UL/CSA in-lbs. 25 (up to 63A) Tool – Nr. 2 Pozidriv Mounting – On DIN rail EN 60715 (35mm) by means of fast clip device Connection – From top and bottom Withdrawal from busbar – It is possible without using any tools only from the bottom (not for 125A) Dimensions and weight Dimensions (H x D x W) mm 85 x 69 x 35 Weight g 200 Combination with auxiliary elements Combinable with: Auxiliary contact Yes (no for 125A) Signal contact/auxiliary switch Yes Shunt trip Yes (no for 125A) undervoltage release Yes (no for 125A) Technical features (¹) Ground-fault sensing and relaying equipment-component (up to 63 A). (²) Prior to connection of aluminium conductors (≥ 4 mm²) ensure that their contact points are cleaned, brushed and coated with grease. (³) For S700-E/K 100A, S750-E 63A, S750DR-E/K 63A and other SCPD coordination values see Chapter 3 of Solutions for electrical distribution in buildings – technical details. (⁴) F200 left neutral has not the UL certification and the UL mark. (5) Only for versions with marking according to EN 61008-1; EN 61008-2-1. RCCB F 200 SERIES - TECHNICAL FEATURES
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A EQ Meter - A series Technical features Technical features A41 A43 Voltage/current inputs Nominal voltage 230 V AC 3x230/400 V AC Power dissipation voltage circuits 0.8 VA (0.8 W) total Power dissipation current circuits 0.007 VA (0.007 W) at 230 V AC and I b 0.007 VA (0.007 W) per phase at 230 V AC and I b Base current I b 5 A 5 A Rated current I n - - Reference current I ref 5 A 5 A Transitional current I tr 0.5 A 0.5 A Maximum current I max 80 A 80 A Minimum current I min 0.25 A 0.25 A Starting current I st < 20 mA < 20 mA Terminal wire area 1 - 25 mm 2 1 - 25 mm 2 Recommended tightening torque 3 Nm 3 Nm Communication Terminal wire area 0.5 - 1 mm 2 0.5 - 1 mm 2 Recommended tightening torque 0.25 Nm Transformer ratios Configurable voltage ratio (VT) - - Configurable current ratio (CT) - - Pulse indicator (LED) Pulse frequency 1000 imp/kWh 1000 imp/kWh Pulse length 40 ms 40 ms General data Frequency 50 or 60 Hz ± 5% Active energy 1% 1%, 2% Display of energy Pixel oriented Environmental Operating temperature -40°C - +70°C Storage temperature -40°C - +85°C Humidity 75% yearly average, 95% on 30 days/year Resistance to fire and heat Terminal 960°C, cover 650°C (IEC 60695-2-1) Resistance to water and dust IP20 on terminal block without protective enclosure and IP51 in protective enclosure, according to IEC 60529. Mechanical environment Class M2 in accordance with the Measuring Instrument Directive (MID). (2004/22/EC). Electromagnetic environment Class E2 in accordance with the Measuring Instrument Directive (MID), (2004/22/EC). Outputs Current 2 - 100 mA Voltage 5 - 240 V AC/DC. For meters with only 1 output, 5 - 40 V DC. Pulse output frequency Programmable: 1 - 999999 imp/kWh Pulse length Programmable: 10 - 990 ms Terminal wire area 0.5 - 1 mm Recommended tightening torque 0.25 Nm Inputs Voltage 0 - 240 V AC/DC OFF 0 - 12 V AC/DC ON 57-240 V AC/24 - 240 V DC Min. pulse length 30 ms Terminal wire area 0.5 - 1 mm 2 Recommended tightening torque 0.25 Nm EMC compatibility Impulse voltage test 6 kV 1.2/50 µs (IEC 60060-1) Surge voltage test 4 kV 1.2/50 µs (IEC 61000-4-5) Fast transient burst test 4 kV (IEC 61000-4-4) Immunity to electromagnetic HF-fields 80 MHz - 2 GHz at 10 V/m (IEC 61000-4-3) Immunity to conducted disturbance 150 kHz - 80 MHz, (IEC 61000-4-6) Immunity to disturbance with harmonics 2kHz - 150kHz Radio frequency emission EN 55022, class B (CISPR22) Electrostatic discharge 15 kV (IEC 61000-4-2) Standards IEC 62052-11, IEC 62053-21 class 1 & 2, IEC 62053-22 class 0,5 S, IEC 62053-23 class 2, IEC 62054-21, GB/T 17215.211-2006, GB/T 17215.321-2008 class 1 & 2, GB/T 17215.322-2008 class 0,5 S, GB 4208-2008, EN 50470-1, EN 50470-3 category A, B & C Mechanical Material Polycarbonate in transparent front glass, bottom case, upper case and terminal cover, Glass reinforced polycarbonate in terminal block. Dimensions Width 70 mm 123 mm Height 97 mm 97 mm Depth 65 mm 65 mm DIN modules 4 7 *) Only A44 552 - 110 and A44 553 - 110
61EQ METER - A/B SERIES - TECHNICAL FEATURES EQ Meter - B series Technical features Technical features B21 B23 B24 Voltage/current inputs Nominal voltage 230 V AC 3 x 230/400 V AC Voltage range 220-240 V AC (-20% - +15%) 3 x 220-240 V AC (-20% - +15%) Power dissipation voltage circuits 0.9 VA (0,4 W) total 1.6 VA (0.7 W) total Power dissipation current circuits 0.014 VA (0.014 W) at 230 V AC and I b 0.007 VA (0.007 W) per phase at 230 V AC and I b Base current I b 5 A - Rated current I n - 1 A Reference current I ref 5 A - Transitional current I tr 0.5 A 0.05 A Maximum current I max 65 A 6 A Minimum current I min 0.25 A 0.02 A Starting current I st < 20 mA < 1 mA Terminal wire area 1 - 25 mm 2 0.5 - 10 mm 2 Recommended tightening torque 3 Nm 1.5 Nm Communication Terminal wire area 0.5 - 1 mm Recommended tightening torque 0.25 Nm Transformer ratios Configurable current ratio (CT) - 1/9 - 9999/1 Pulse indicator (LED) Pulse frequency 1000 imp/kWh 1000 imp/kWh 5000 imp/kWh Pulse length 40 ms 40 ms 40 ms General data Frequency 50 or 60 Hz ± 5% Accuracy Class B (Cl. 1) and Reactive Cl. 2 B (Cl. 1) and Reactive Cl. 2 B (Cl. 1) or C (Cl. 0,5 S) and Reactive Cl. 2 Active energy 1% 1% 0.5%, 1% Display of energy 6 digit LCD 7 digit LCD Environmental Operating temperature -40°C - +70°C Storage temperature -40°C - +85°C Humidity 75% yearly average, 95% on 30 days/year Resistance to fire and heat Terminal 960 °C, cover 650°C (IEC 60695-2-1) Resistance to water and dust IP20 on terminal block without protective enclosure and IP51 in protective enclosure, according to IEC 60529. Mechanical environment Class M2 in accordance with the Measuring Instrument Directive (MID), (2004/22/EC). Electromagnetic environment Class E2 in accordance with the Measuring Instrument Directive (MID), (2004/22/EC). Outputs Current 2 - 100 mA Voltage 5 - 240 V AC/DC. For meters with only 1 output 5 - 40 V DC. Pulse output frequency Programmable: 1 - 999999 imp/kWh Pulse length Programmable: 10 - 990 ms Terminal wire area 0.5 - 1 mm Recommended tightening torque 0.25 Nm Inputs Voltage 0 - 240 V AC/DC OFF 0 - 12 V AC/DC ON 57 - 240 V AC/24 - 240 V DC Min. pulse length 30 ms Terminal wire area 0.5 - 1 mm Recommended tightening torque 0.25 Nm EMC compatibility Impulse voltage test 6 kV 1.2/50μs (IEC 60060-1) Surge voltage test 4 kV 1.2/50μs (IEC 61000-4-5) Fast transient burst test 4kV (IEC 61000-4-4) Immunity to electromagnetic HF-fields 80 MHz - 2 GHz (IEC 61000-4-6) Immunity to conducted disturbance 150kHz - 80MHz (IEC 61000-4-6) Immunity to disturbance with har - monics 2kHz - 150kHz Radio frequency emission EN 55022, class B (CISPR22) Electrostatic discharge 15 kV (IEC 61000-4-2) Standards IEC 62052-11, IEC 62053-21 class 1 & 2, IEC 62053-22 class 0,5 S, IEC 62053-23 class 2, IEC 62054-21, GB/T 17215.211-2006, GB/T 17215.312-2008 class 1 & 2, GB/T 17215.322-2008 class 0,5 S, GB 4208-2008, EN 50470-1, EN 50470-3 category A, B & C Mechanical Material Polycarbonate in transparent front glass. Glass reinforced polycarbonate in bottom case and upper case. Polycarbonate in terminal cover. Dimensions Width 35 mm 70 mm Height 97 mm 97 mm Depth 65 mm 65 mm DIN modules 2 4
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A EQ Meter - A series Wiring diagram Terminal block A41 (A) 3 4 L N 1 6 Terminal block A43 (A) 3 wire connection, 2 elements 3 4 6 7 9 1 1210 3 4 6 7 9 N 1 1210 4 wire connection, 3 elements OK SET
01 Terminal block A41
02 Terminal block A43
03 Terminal block A44
(A) (A) (A) (B)(B)(B) (C)(C)(C)
63EQ METER - A/B SERIES - WIRING DIAGRAM EQ Meter - B series Wiring diagram Terminal block A41 (A) Terminal block B21 Terminal block B23 Terminal block A43 (A) Terminal block B24
01 Terminal block B21
02 Terminal block B23
03 Terminal block B24
L N 3 wire connection, 2 elements 3 4 6 7 9 1 11 3 4 6 7 9 N 1 11 4 wire connection, 3 elements 3 wire connection, 2 elements 3 5 7 8 9 1 2 11 P1 P1 P1 P2 S1 S2 3 4 5 6 7 8 9 N 1 2 11 P1 P1 P1 P1 P2 S1 S2 4 wire connection, 3 elements Phase in Phase out Neutral 1 4 7 3 6 9 Phase in Phase out Neutral 1 4 7 3 6 9 2 5 8 Current in Voltage Current out Neutral 1 5 (A & B ) 1 11 4 7 9 6 3 11 8 7 5 4 2 1 9 6 3
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A EQ Meter - A/B series Inputs/ouputs and communication Inputs / outputs (B) Communication (C) C RS-485 A B 37 36 35 M-Bus 37 36 2 outputs, 2 inputs C Inp3 Inp4Out1 Out2 13 15 16 17 18
4 Configurable inputs/outputs
External power supply needed 5-240 VAC/VDC... External power supply needed 5-40VDC...
Inputs / outputs (B) Communication (C) ABB With a broad range of market- leading products and solutions, a global sales network and customised support, ABB provides flexibility that improves energy performance, whatever the requirements.
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Control Unit CMS-700 Supply voltage [V AC] 80 – 277 (L1-N, +5%) Frequency [Hz] 50 / 60 Power input (L1-N) [W] 5 ... 40 (dep. on number of sensors) Power input, current transformer, secondary side [VA] Current circuit <2 (per phase) Voltage measurement range [V AC] 80 – 277 (L1, L2, L3-N) Measurement range, current transformer, [A] nominal: 5, max.: 6 Harmonic component [Hz] up to 2000 Data rate of Modbus RTU [Baud] RS485 2-wire, 2400 ... 115 200 Refresh time ≤1 sec with max. 96 sensors LAN [Mbit/s] 100 Mounting method 35 mm DIN rail (DIN 50022) Degree of protection IP20 Dimensions [mm] 160.0 x 87.0 x 64.9 (9 WM) Operating temperature [°C] − 25 ... +60 Bearing temperature [°C] − 40 ... +85 Standards IEC61010-1 UL 508/ CSA C22.2 No. 14 Main circuit accuracy Voltage ± 1 % Current ± 1 % Harmonic component 1 % Active power ± 2 % Apparent power ± 2 % Reactive power ± 2 % Power factor ± 0 . 2 % Control Unit CMS-600 – «Modbus RTU»Unit 600 Supply voltage [V DC] 24 (± 10 %) Power input [W] 4 – 24 (dep. on number of sensors) Interface RS485 2-wire Protocol Modbus RTU Data rate [Baud] 24 0 0 . . . 115 2 0 0 Refresh time ≤1 sec with max. 64 sensors Insulation strength [V AC] 400 Mounting method 35 mm DIN rail (DIN 50022) or SMISSLINE TP plug base Dimensions [mm] 71.8 x 87.0 x 64.9 (4 WM) Operating temperature [°C] − 2 5 . . . +70 Bearing temperature [°C] − 4 0 . . . + 8 5 Standards IEC 61010-1 UL 508/ CSA C22.2 No. 14 Control unit CMS 600 Control unit CMS 700 Circuit Monitoring System - CMS Technical features
Sensor type CMS-120xx CMS-121xx CMS-122xx CMS 120PS Measurement range [A] 80 40 20 Measuring method TRMS, AC 50 / 60 Hz, DC Peak factor, distorted waveform ≤ 1.5 ≤ 3 ≤ 6 AC accuracy (TA = + 25 °C)* ≤ ± 1 % AC temperature coefficient* ≤ ± 0.04 % CMS 120DR DC accuracy (TA = + 25 °C)* ≤ ± 1.2 % ≤ ± 1.4 % ≤ ± 1.8 % DC temperature coefficient* ≤ ± 0.14 % ≤ ± 0.24 % ≤ ± 0.44 % Resolution [A] 0.01 Sampling rate, internal [Hz] 5000 Response time (±1 %) [sec] typ. 0.34 Conductor penetration [mm] 9,6 Insulation strength 6 9 0 A C /15 0 0 D C Dimensions CMS-120PS Serie [mm] 17.4 x 41.0 x 26.5 CMS-120CA Serie [mm] 17.4 x 41.0 x 29.0 CMS-120DR Serie [mm] 17.4 x 51.5 x 43.2 Standards IEC 61010-1 | UL508 / CSA C22.2 No 14 Open-core sensors 18 mm Circuit Monitoring System - CMS Technical features *All accuracy specifications refer to the relevant full scale value and apply to 25 °C. In the case of open-core sensors, the position of the cable influences the precision. CIRCUIT MONITORING SYSTEM - CMS - TECHNICAL FEATURES
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A ESB installation contactors Technical features ESB installation contactors technical features Main Pole - Utilization Characteristics according to IEC Contactor types: AC operated ESB20/EN20 AC/DC operated ESB24/ EN24 ESB40/ EN40 ESB63 Rated operational voltage Ue max. V 250 400 Rated frequency limits Hz 50/60 DC or 50/60 Hz Utilization category AC-1 / AC-7a for air temperature close to contactor < 55 °C Max. rated operational current Ie AC-1 / AC-7a (NO) A 20 24 40 63 (NC) A 20 24 30 30 Rated operational power AC-1/ AC-7a 230 V - 1 phase (NO) kW 4 5.5 9.2 14.5
400 V - 3 phases (NO) kW - 16 26 41
230 V - 1 phase (NC) kW 4 5.3 8.8 6.9
400 V - 3 phases (NC) kW - 16 26 26
Utilization category AC-3 / AC-7b for air temperature close to con - tactor < 55 °C Max. rated operational current Ie AC-3/AC-7b
230 V - 1 phase A 9 9 22 30
400 V - 3 phases A - 9 22 30
Rated operational power AC-3/ AC-7b 230 V - 1 phase kW 1.1 1.3 3.7 5
400 V - 3 phases kW - 4 11 15
Rated making capacity AC-3/AC-7b 10 x Ie / AC-3 Rated breaking capacity AC-3/AC-7b 8 x Ie / AC-3 Short-circuit protection for contactors gG type fuse A 20 35 63 80 Rated short-time withstand cur - rent Icw at 40 °C ambient temp., in free air, from a cold state 10 s A 72 72 176 240 Heat dissipation per pole Ie / AC-1/AC-7a W 1 3 4 6 Max. electrical switching fre - quency – for AC-1 / AC-7a cycles/h 300 – for AC-3 / AC-7b cycles/h 600 Electrical durability – for AC-1 / AC-7a cycles 150000 150000 150000 150000 – for AC-3 / AC-7b cycles 150000 500000 170000 240000 Mechanical durability – millions of operating cycles 1.000.000
69ESB INSTALLATION CONTACTORS - TECHNICAL FEATURES ESB installation contactors Technical features ESB installation contactors technical features Main Pole - Utilization Characteristics according to IEC Contactor types: AC operated ESB20/EN20 AC/DC operated ESB24/EN24 ESB40/EN40 ESB63 Coil operating limits acc. to IEC 60947- 4-1 Frequency range Hz 50/60 50/60 or DC Coil consumption Average pull-in value VA / W 8 / 5 4 / 4 5 / 5 65 / 65 Average holding value VA / W 3.2 / 1.2 4 / 4 5 / 5 4.2 / 4.2 Main Pole - Utilization Characteristics according to IEC Contactor types: AC operated ESB20/EN20 AC/DC operated ESB24/EN24 ESB40/EN40 ESB63 Main pole terminals Degree of protection acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529 Protection against direct contact in acc. with EN 50274 All terminals IP20 EH04... Auxiliary Contact Block - Utilization Characteristics according to IEC Contactor types: AC operated ESB20 AC/DC operated ESB24 ESB40 ESB63 Rated operational voltage Ue max. V - 500 Conventional free air thermal current Ith q < 40 °C A - 6 Rated frequency limits Hz - 50/60 Rated operational current Ie / AC-15 acc. to IEC 60947-5-1
240 V 50/60 Hz A - 4
415 V 50/60 Hz A - 3
500 V 50/60 Hz A - 2
Making capacity acc. to IEC 60947-5-1 - 11 x Ie AC-15 Breaking capacity acc. to IEC 60947-5-1 - 11 x Ie AC-15 Short-circuit protection gI type fuse A - 10 Minimum switching capacity with failure rate acc. to IEC 60947-5-4 V/mA - 17 / 5 Heat dissipation per pole at 6 A W - 0.1
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A D Line digital time switches Technical features D Line technical features General data D1 D1 PLUS SYNCHRO D2 D2 PLUS D2 SYNCHRO Rated voltage [V] 230 AC ± 10% Rated pulsating voltage [kV] 4 Contact type Contact relay in free exchange from potential Programming key External input DCF77 antenna GPS antenna Programming software
250 V contact capacity
Ohm loads [A] 16 16 Inductive loads [A] 10 2 Rated frequency [ H z ] 50-60 Time base quartz Minimum switching [sec.] 1 Max programs per cycle [n°] 64 (can be coupled in day blocks) Running reserve [year] 6 from the first start-up (lithium battery) External input [n°] 1 - 2 - Activity suspension From 1 day to 12 months Operating precision [sec./ day] ± 0.5 Max. dissipated power [VA] 6.5 7.8 Max. switch power [VA] 3500 Incandescent lamps [W] 3000 Non-rephased fluorescent lamps [W] 1100 Fluorescent tube lamps rephased in parallel [W] 900 Fluorescent tube lamps with electronic reactor [W] 7 ÷ 23 (max. 23 lamp.) Fluorescent tube lamps rephased in series [W] 1100 Protection degree [IP] 20 Max. terminal cross-section [mm²] 6 Terminals In positive safety with captive screw Tightening torque [Nm] 0.5 Installation type DIN rail Operating temperature [°C] -5 … +55 Storage temperature [°C] -10 … +65 Modules [n°] 2 Reference standards EN 60730-1; EN 60730-2-7
71T LINE TWILIGHT SWITCHES - TECHNICAL FEATURES T Line twilight switches Technical features T1 technical features General data T1 T1 PLUS Rated supply voltage [V] 110 ÷ 230 AC Contact type 1NO Switching capacity resistive load cosj 1 [A] 16 inductive load cosj 0.6 [A] 3 incandescent lamps cosj 1 max 3600 W fluorescent lamps cosj0.8 max 3600 W fluorescent - duo./electronic lamps cosj0.9 max 300 W Rated frequency [Hz] 50-60 Switching delay Brightness range [lx] 2:200 2:40 20:200 200:2000 2000:15000 Protection degree twilight switch IP20 IP20 sensor IP65 IP65 Operating temperature twilight switch [°C] -25…+55 sensor [°C] -40...+70 Storage temperature twilight switch [°C] -40...+70 sensor [°C] -50...+80 Power consumption [VA] 4.5 Max. commutable power [W] 3500 Max. terminal cross-section [mm²] 2.5 Terminals loss-proof screw Tightening torque terminals [Nm] 0.5 sensor screw [Nm] 0.4 Mounting on DIN rail Switching status indication/ brightness range red Led / green Led Max wiring length [m] 100 Modules 1 Reference standards EN 60669-1; EN 60669-2-1; EN 60730-1
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Example of installation As shown in the diagrams, one of the possible applications is the installation of a T1 twilight switch in the lighting system of a commercial establishment. When the external light falls below a certain level (e.g. when the shop is closed), the twilight switch switches on the window lights and the sign. The lights can be switched off late evening to reduce power consumption thanks to the AT1 switch timer which keeps the circuit open until the next morning. When the external light returns to above the threshold value, the twilight switch relay returns to the open position. T1 & T1 PLUS twilight switch Control and automation technical features Operating principle The diagram shows an example of the installation of the T1 twilight switch in the lighting system of a commercial establishment. When the external light falls below a certain level (e.g. during the evening when the shop is closed), the device switches on the window lights and the shop sign. The lights can be switched off late evening to reduce power consumption thanks to the AT1 switch timer. Application environments The installation of the T1 twilight switch with an AT electromechanical timer is particularly useful in settings and situations where energy saving is a prime concern (shops, office corridors and public passageways, car parks, parks, etc.).
01 Daytime
02 Evening operation
03 Late evening mode
N L N T11 AUXILIARY AT1 LIGHTING AUXILIARY L1 N sensor AT1
73T1 & T1 PLUS TWILIGHT SWITCH CONTROL AND AUTOMATION - TECHNICAL FEATURES Example of installation As shown in the diagrams, one of the possible options is to install a T1 PLUS twilight switch in the lighting system of a greenhouse. When the external light exceeds a certain level (for example during peak hours in the early afternoon) the twilight switch activates the roller blinds, protecting the plants in the greenhouse against burning by the strong sunlight. When the external light returns to below the threshold value, the twilight switch relay opens the blinds to allow the sunlight to pass through. Operating principle The diagram shows an example of the installation of the T1 PLUS twilight switch in the lighting system of a greenhouse. When the external light exceeds a certain level (e.g. during the warmest hours of the day, i.e. early afternoon), the device activates the shading system, e.g. roller blinds. Thanks to the option to advance or delay the activation-deactivation time, the T1 PLUS can also maintain the roller blinds closed in the case of passing clouds. Application environments The installation of the T1 PLUS twilight switch is particularly useful in settings and situations where lighting control is required for locations where there are consistently high brightness values, thus guaranteeing substantial savings in energy consumption (greenhouses, arcades, photovoltaic plants, etc.).
04 Required light levels
05 Excessive light levels
N L N T1 PLUS T1 PLUS AUXILIARY LIGHTING AUXILIARY L1 N T1 PLUS sensor
PROTECTA PLUS MCB DISTRIBUTION BOARD 250A Additional information We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatso - ever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustra - tions contained therein. Any reproduc - tion, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB AG. Glossary Detailed product information MDRC Products ( MCB etc ) Brochure title Link Order code Solutions for electrical installation in buildings (Catalogue) 2017 http:/ /search-ext.abb.com/library/Download.aspx?DocumentID=9AKK10 6930A8017&LanguageCode=en&DocumentPartId=&Action=Launch 2CHC 000 001 C0201 - 03/2017 ( 9AKK106930A8017 ) Solutions for electrical installation in buildings (Technical details) 2017 http:/ /search-ext.abb.com/library/Download.aspx?DocumentID=9AKK10 6930A8027&LanguageCode=en&DocumentPartId=&Action=Launch 2CHC 000 001 C0201 - 03/2017 ( 9AKK106930A8027 )
Electrification Products Division Tower Court Foleshill Enterprise Park Courtaulds Way Coventry CV6 5NX Tel: +44 (0) 333 999 9900 E-Mail: LV.Enquiries@gb.abb.com Twitter: @ABBUKEP new.abb.com/uk/protecta-plus 9AKK107045A1604 REV B 02.10.2017 © Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice.