Features
− Clear contact position indication in red/green (“real CPI”) − Unique, patented twin terminal with captive screws and an increased opening for cables up to max. 35 mm 2, finger-proof (IP20) − Busbar slot in the back for best visibility during installation − High performance at an increased rated voltage for marine and industrial applications: 10 kA/15 kA at U n = 440 V AC acc. to IEC/EN 60947-2 − Individual product identification code − Approved acc. to IEC/EN 60898-1, IEC/EN 60947-2 and UL 1077/CSA 22.2 No. 235 for global use 2CDC021038S0012
Miniature Circuit Breaker S 200/S 200 M Technical data S 200 S 200 M General Data Standards IEC/EN 60898-1, IEC/EN 60947-2 UL 1077 IEC/EN 60898-1, IEC/EN 60947-2 UL 1077, CSA 22.2 No. 235 Poles 1P , 2P , 3P , 4P , 1P+N, 3P+N Tripping Characteristics B, C, D, K, Z Rated current I n 0.5 up to 63 A Rated insulation voltage U i 250 V AC (phase to ground), 500 V AC (phase to phase) Rated frequency 50/60 Hz Overvoltage Category III Pollution Degree 3 IEC/EN 60898-1 Rated operational voltage U n 1P: 230/400 V AC; 1P+N: 230 V AC; 2P , 3P , 4P: 400 V AC; 3P+N: 400 V AC Power frequency recovery voltage U max 1P: 253 V AC; 1P+N: 253 V AC; 2P , 3P , 4P: 440 V AC; 3P+N: 440 V AC; 1P: 72 V DC; 2P: 125 V DC Min. operating voltage 12 V AC, 12 V DC Rated short-circuit capacity I cn 6 kA 10 kA Energy limiting class (B, C up to 40 A) 3 Rated impulse withstand voltage U imp (1.2/50 µs) 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m) Dielectric test voltage 2.0 kV (50/60 Hz, 1 min) Reference temperature for tripping characteristics B, C, D: 30 °C Electrical endurance In < 32 A: 20,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s - ON, 13 s - OFF In ≥ 32 A: 10,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s - ON, 28 s - OFF IEC/EN 60947-2 Rated operational voltage U e 1P: 230 V AC; 1P+N: 230 V AC; 2P , 3P , 4P: 440 V AC; 3P+N: 440 V AC Power frequency recovery voltage U max 1P: 253 V AC; 1P+N: 253 V AC; 2P , 3P ,4P: 462 V AC; 3P+N: 462 V AC; 1P: 72 V DC; 2P: 125 V DC Min. operating voltage 12 V AC, 12 V DC Rated ultimate short-circuit breaking capacity I cu 10 kA 15 kA Rated service short-circuit breaking capacity I cs 7.5 kA ≤ 40 A: 11.2 kA 50, 63 A: 7.5 kA Rated impulse withstand voltage U imp (1.2/50 µs) 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m) Dielectric test voltage 2.0 kV (50/60 Hz, 1 min) Reference temperature for tripping characteristics B, C, D: 55 °C; K, Z: 20 °C Electrical endurance In < 32 A: 20,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s - ON, 13 s - OFF In ≥ 32 A: 10,000 ops. (AC), 1,000 ops. (DC); one cycle 2 s - ON, 28 s - OFF Data acc. to UL/CSA Rated voltage 480Y / 277 V AC Rated interrupting capacity 6 kA Reference temperature for tripping characteristic B, C, D, K, Z: 25 °C Electrical endurance 6,000 ops. (AC), 6,000 ops. (DC); one cycle 1 s - ON, 9 s - OFF Mechanical data Housing Insulation group II, RAL 7035 Insulation group I, RAL 7035 Toggle Insulation group II, black, sealable Contact position indication Marking on toggle (I ON/0 OFF), Real CPI (red ON/green OFF) Protection degree acc. to EN 60529 IP20*, IP40 in enclosure with cover Mechanical endurance 20,000 ops. Shock resistance acc. to IEC/EN 60068-2-27 25 g, 3 shocks, 11 ms Vibration resistance acc. to IEC/EN 60068-2-6 5 g, 20 cycles at 5…150…5 Hz with load 0.8 I n Environmental conditions acc. to IEC/EN 60068-2-30 28 cycles with 55 °C/90-96 % and 25 °C/95-100 % Ambient temperature -25 ... +55 °C Storage temperature -40 ... +70 °C * Also fulfilling the requirements acc. to the protection degree IPXXB
Miniature Circuit Breaker S 200/S 200 M Technical data and tripping characteristics S 200 S 200 M Installation Terminal Failsafe bi-directional cylinder-lift terminal Cross-section of conductors (top/bottom) 35 mm 2 / 35 mm 2 18 – 4 AWG Cross-section of busbars (top/bottom) 10 mm 2 / 10 mm 2 18 – 8 AWG Torque 2.8 Nm 25 in-Ibs. Screwdriver No. 2 Pozidrive Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip Mounting position any Supply optional Dimensions and weight Mounting dimensions acc. to DIN 43880 Mounting dimension 1 Pole dimensions (H x D x W) 85 x 69 x 17.5 Pole weight approx. 125 g Combination with auxiliary elements Auxiliary contact Yes Signal/auxiliary contact Yes Shunt trip Yes Undervoltage release Yes Motor Operating Device Yes Tripping characteristics Acc. to Tripping characte- ristics Rated current Thermal release 1) Electromagnetic release 2) In Currents: conventional non-tripping current I conventional tripping current I Tripping time Range of instantaneous tripping Tripping time IEC/EN 60898-1 B 6 to 63 A 1.13 · I n 1.45 · I n > 1 h < 1 h 3 · I n 5 · I n < 0.1 s C 0.5 to 63 A 1.13 · I n 1.45 · I n > 1 h < 1 h 5 · I n 10 · I n < 0.1 s D 0.5 to 63 A 1.13 · I n 1.45 · I n > 1 h < 1 h 10 · I n 20 · I n < 0.1 s IEC/EN 60947-2 K 0.5 to 63 A 1.05 · I n 1.2 · I n > 1 h < 1 h not applicable 1.05 · I n 1.2 · I n > 2 h < 1 h 10 · I n 14 · I n > 0.2 s < 0.2 s Z 0.5 to 63 A 1.05 · I n 1.2 · I n > 1 h < 1 h not applicable 1.05 · I n 1.2 · I n > 2 h < 1 h 2 · I n 3 · I n > 0.2 s < 0.2 s 1) The thermal releases are calibrated to a nominal reference ambient temperature; for B, C, D the reference value is 30 °C, for K and Z the reference value is 20 °C. In the case of higher ambient temperatures, the current values fall by approx. 6 % for each 10 K temperature rise. 2) The indicated tripping values of electromagnetic tripping devices apply to a frequency of 50/60 Hz. The thermal release operates independent of frequency. 3) As from operating temperature (after I 1 > 1h or, as applicable, 2h)
Miniature Circuit Breaker S 200/S 200 M 2CDC022060F0211 Z characteristic Tripping characteristics 2CDC022006F0211 2CDC022008F0211 B characteristic C characteristic 2CDC022010F0211 K characteristic D characteristic 2CDC022108F0209
Miniature Circuit Breaker S 200/S 200 M For installations of miniature circuit breakers at other temperatures than the reference value and installations of several minia- ture circuit breakers directly side by side, derating factors have to be considered. Deviating ambient temperature The rated value of the current of a miniature circuit breaker refers to a reference ambient temperature of 30 °C for circuit breakers with the characteristics B, C and D and 20 °C for circuit breakers with the characteristics K and Z. The following table contains the derating of the load capability at ambient temperatures from -40 °C to 70 °C for the characteristics B, C, D, K and Z. Derating Tripping Rated Maximum operating current at ambient temperature T charac- current teristics In A - 40 °C - 30 °C - 20 °C - 10 °C 0 °C 10 °C 20 °C 30 °C 40 °C 50 °C 60 °C 70 °C Influence of adjacent devices If several miniature circuit breakers are installed directly side by side with high load on all poles, a correction factor has to be applied to the rated current (see table). If distance pieces are used, the factor is not to be considered. No. of adjacent devices Factor F 1 1 2, 3 0.9 4, 5 0.8 ≥ 6 0.75 Example S201-C16 at T = 40 °C Conditions of use Values to use Calculation Result Load at ambient temperature 40 °C with 8 adjacent devices I n (40 °C), Factor F 15.1 A x 0.75 In = 11.33 A
Miniature Circuit Breaker S 200/S 200 M Accessory overview Dimensional drawing 2CDC022007F0010 Accessories and dimensional drawing H Auxiliary contact S2C-H6R (change-over contact) H-R Auxiliary contact S2C-H6-...R S/H Signal/Auxiliary contact S2C-S/H6R S/H (H) Signal/Auxiliary contact used as auxiliary contact S2C-S/H6R ST Shunt trip S2C-A... UR Undervoltage release S2C-UA OR Overvoltage release S2C-OVP 2CDC092002F0212 H-L Auxiliary contact S2C-H...L H-BF Auxiliary contact for bottom fitting S2C-H01 (1 per pole) S2C-H10 BP Mechanical tripping device S2C-BP NT Neutral disconnector S2C-Nt MOD-S* Motor operating device S2C-CM DDA 200 RCD-block DDA 20... * In case of using S 200/S 200 M coupled with DDA 200, MOD-S does not operate in case of earth-leakage fault.
Eppelheimer Straße 82
69123 Heidelberg, Germany
Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-Mail: info.desto@de.abb.com You can find the address of your local sales organization on the ABB home page http://www.abb.com/contacts -> Low Voltage Products and Systems Contact us Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB AG. Copyright© 2012 ABB All rights reserved Brochure number 2CDC002157D0201pdf (04/12-pdf)