pro M compact ® Miniature circuit-breakers S 200/S 200 M Residual-current-operated circuit-breakers F 200 Cross wiring/accessories System pro M compact /L50557/L50557/L50557/L50557/L50557Technical data
pro M compact ® Standard Terms for Delivery and Sale For domestic business, the Standard Terms for Delivery of Products and Services of the Electrical Industry (ABB Form 2292) shall apply in connection with the Standard Sales Terms (ABB Form 2327) in their then applicable version. For foreign business, the Standard Terms for Delivery of Products and Services of the Electrical Industry (ABB Form 2293 German- English, or ABB Form 2294 German- French) shall apply in connection with the Standard Sales Terms (ABB-Form 2381 English) in their then applicable version. Warranty We assume warranty in accordance with the standard sales and delivery terms. Complaints shall be made in writing within eight days following receipt of the goods. Technical information and illustrations are not binding and subject to change without notice. Miniature circuit-breaker S 201
pro M compact ® Contents page The technology of S 200 The technology of F 200 The technology of busbars The program Miniature circuit-breakers Residual-current-operated circuit breaker Busbars Prior to connection of aluminium conductors (/L50871 4 mm ensure that their contact points are cleaned, brushed and coated with grease.
pro M compact ® Outstanding features
Applications
/L50098All round protection against contact with live parts in acordance with DIN VDE 106 part 100. /L50098Due to new design: Upper and lower shoulders reduced. More working space between component rows. Outgoing and incoming connection points easily accessible. /L50098New, failsafe, bi-directional cylinder lift terminal, ensuring a faster, totally error-free connection. As you tighten the screw, the terminal draws together to simultaneously close the front and rear wiring inputs. This creates a strong, contactassured connection between the wires and the device, in a single operation. Busbar is installed at the back terminals (A). Connection of conductors on the front terminals (B). Result: a clear view on all connection points. Never fumble for the right connection point again. Substantially improved cross-wiring safety. Tangible time-savings. /L50098Connection possible for single, multi and finely stranded conductors of 0.75 to 25 mm It is also possible to connect conductors with different cross section at the same time. /L50098New cross wiring busbars. Standard length sizes or meter length cutable. SK 0048 B 99 B A SK 0053 B 99 SK 0051 B 99 SK 0052 B 99
pro M compact ® Outstanding features /L50098New quick-fastening technique for easy disconnection of the device from the assembly. No time-consuming extra work: Cross-wiring remains with the assembly. To remove the device, just loosen the screw, lift the device and pull it out. If neccessary, all devices of the series connected to the new pro M compact cross-wiring rails may be exchanged easily and quickly, e.g. to implement the adaptation to the VDE standard 0100 part 410. Easy to add on MCB for extensions. /L50098New, integrated auxiliary contact, factory fitted, reduces space by 50 %. Cross wiring to customary compact busbar possible. /L50098Self-adhesive identification labels are provided for all devices, ensuring clear and accurate identification. Every detail of System pro M compact has now been optimised to meet the user’s requirements. Fuirthermore, System pro M compact offers you many different ways to label the switchgear cabinet and built-in consumer unit in a professional manner. Individual, effecient labeling of devices. /L50098Pad lock prevents unauthorized switching to ON or OFF. /L50098Complete range of tripping characteristics in B, C, D, K, Z. /L50098High rated switching capacity of 6 000 A (S 200) or 10 000 A (S 200 M). /L50098Current limitation is below the values prescribed by the VDE, therefore higher selectivity rating than energy limitation class 3. /L50098Disconnector abilities according to DIN VDE 0660 part 107, surge with- stand capability 6 kV (1.2/50). SK 0047 B 99SK 0045 B 99 SK 0050 B 99 SK 010 B 01
pro M compact ® Miniature circuit-breakers The offer at a glance
Description
The MCBs of the S 200/S 200 M series have a cur- rent-limiting effect. They have two different trip releases acting on the contact mechanism 1. the delayed thermal release providing overload protection 2. the electromagnetic instantaneous release with “hammer trip” solenoid providing fault current protection. They offer: /L50098high short-circuit capacity /L50098high selectivity for back-up fuse /L50098In case of short-circuit, low stress on the cable in the point of fault due to the high limitation of the let-through ƒi 2dt (current heating value). Task To protect against excessive temperature rises of electric items in the case of overcurrents caused by overload, short circuit of earth-fault current if assi- gned according to DIN VDE 0100 Part 430. Protec- tion against electric shock in the case of excessive touch voltage caused by insulation fault if assigned according to DIN VDE 0100 Part 410. Trip charcteristics SK 0126 Z 00 B SK 0128 Z 00C SK 0130 Z 98 IK · /L504962 = peak value of prospective short circuit current iD = max. let-through current of device S 200/S 200 M Un = system voltage UB = arc voltage of MCB tK = breaking time of MCB Oscillogram of rupturing process Trip charcteristics and rated current Independent of the type of characteristic, national codes of practice provide what highest rated current and/or performance characteristic can be assigned to the conductor cross section to be protected (e.g. DIN VDE 0100 Part 430). The following assignment rules apply: I b /L50872 In /L50872 Iz; I2 /L50872 1,45 · Iz Ib = operating current of the circuit to be expected In = rated current of the MCB of characteristics type B, C, D, K and Z Iz = permissible current loading of lines I2 = conventional tripping current B-, C- and D-type trip characteristics for line protection Tripping behaviour according to DIN VDE 0641 Part 11. assignments of MCBs to the permissible load of lines I z according to DIN VDE 0298 Part 4/11.98, as the second condition is already fulfilled (I 2 = 1.45 · I n). K-type trip characteristics Tripping behaviour according to DIN VDE 0660 Part 101 and IEC 947-2, rated current 0.5 ... 63 A, for circuits where current-consuming appartus cause functional current peaks and for the overcurrent protection of lines. Z-type trip characteristics Tripping behaviour according to DIN VDE 0660 Part 101 and IEC 947-2 transformers. SK 0142 Z 00K Z SK 0146 Z 00
pro M compact ® Miniature circuit-breakers S 200/S 200 M series Technical data Specifications: DIN VDE 0641 Part 11, IEC 60898, EN 60898, IEC 60947-2, UL 1077 No. of poles: 1, 2, 3, 4, 1 + NA, 3 + NA tripping charcteristics: B, C, D, K, Z rated voltage U n: 1-pole 230 V /L50513 multipole 400 V /L50513 max. operating voltage U Bmax:A C U n + 10 % DC 1-pole 60 V ... 2-pole 125 V ... min. operating voltage U Bmin : 12 V~, 12 V- energy limitation class: S 3 short circuit rupturing capacity: see page 9 frequency: 50 ...60 Hz insulation coordination: according to DIN VDE 0110 Part 1 and 2 - overvoltage category: III - pollution degree: 2 - surge voltage: 5 kV (1.2/50 µs) - impulse alternating voltage: 3 kV (50/60 Hz) housing: Insulating material rating I (CTI /L50871 600) according to DIN IEC 112/VDE 0303 Part 1, RAL 7035 operating lever: Insulating material rating II (400 /L50872 CTI /L50141 600) black, sealable degree of protection acc. to DIN VDE 0100: IP 20, in the consumer unit IP 40 dimensions: according to DIN 43880, size code 1 depth of device: 68 mm overall dimensions: see page 25 mounting position: optional fixing: snap-on to DIN rails EN 60 715, 35 mm or screw fixing by means of mounting plate (see accessories) connection: failsave bi-directional cylinder-lift terminal at top and bottom, shock-protected according to DIN VDE 0106 Part 100. Suitable for connection of single, multi or finely stranded conductors up to 25 mm 2 (if also connected to rails) tightening torque: 2.8 Nm mechanical service life: 20,000 operations service life at rated load In /L50141 32 A: 20,000 operations In /L50871 32 A: 10,000 operations climatic resistance acc. to DIN IEC 68 Part 2-30: constant climate 23/83, 40/93, 55/20 [°C/RH] alternating climate 25/95 - 40/93 [°C/RH] storage temperature: T max +70 °C/158 °F, Tmin -40 °C/-13 °F ambient temperature: T max +55 °C/158 °F, Tmin -25 °C/-13 °F shock resistance: 30 g, at least 2 impacts shock duration 13 ms weight: see selection tables Technical data of the integrated auxiliary contact contact: 1NO (1 make contact) 1NC (1 normally closed contact) contact load: AC 14 230 V 2 A DC 12 identical DC 13 DC 13 50 V 1 A min. operating voltage: 12 VAC/DC at 0.1 VA short-circuit withstand capacity: 230 V /L50513 1,000 A electrical service life: /L50140 4,000 operations safe disconnection of auxiliary circuit and main circuit according to VDE 0106 Part 101 connection capacity: 0.75 to 2.5 mm 2 (finely-stranded conductors to be fitted with a connector sleeve)
pro M compact ® Maximum permissible fault loop impedance Z S at U0 = 230 V/L50513/L50513/L50513/L50513/L50513 /L54706 to ensure compliance with the rupturing conditions prescribed in DIN VDE 0100 Part 410. The internal resistance of MCB is included. Note: Attention should be paid to the maximum voltage drop Miniature circuit-breakers S 200/S 200 M series Internal resistance and power loss of the miniature circuit-breakers Internal resistance per pole in m /L09202, power loss per pole in W type rated device series current B, C, D ➀➀➀➀➀ KZ In Am /L09202Wm /L09202Wm /L09202W S 200 and 0.5 5500 1.4 6340 1.6 10100 2.5 1 1440 1.4 1550 1.6 2270 2.3 S 200 M 1.6 630 1.6 695 1.8 1100 2.8 2 460 1.8 460 1.9 619 2.5 3 150 1.3 165 1.5 202 1.8 4 110 1.8 120 2.0 149 2.4 6 55 2.0 52 1.9 104 3.7 8 15 1.0 38 2.5 53.9 3.45 13 13.3 2.3 12.6 1. 26 – – ➀➀➀➀➀ Current intensities 0.5 – 4 apply exclusively to C-type trip characteristics. /L54706U0 = rated voltage against earthed conductor; for U 0 = 240 V/L50513 : ZS · 1.04; for U0 = 127 V/L50513/L52291 ZS · 0.55 The max. permissible lenght of cable at different voltage and cross sections on request. S 200 and S 200 M Bemessungs- BC D K Z /L09202/L09202 /L09202 /L09202 /L09202 0,5 46.0 33.0 38.3 153.3 1 23.0 16.5 19.2 76.7 2 11.5 8.2 9.6 38.3 3 7.7 5.5 6.4 25.6 4 5.8 4.1 4.8 19.2 13 3.5 1.7 1.2 – –
pro M compact ® Tripping characteristics thermal release /L54707 electromagnetic release /L54706 acc. to tripping characteristic current: tripping time currents: tripping time and rated current conventional conventional hold trip non-triping c. tripping c. current surges at least at DIN VDE B 6 to 63 A 1.13 · I n > 1 h 3 · I n > 0.1 s 0641/T 11 1.45 · I n < 1 h 5 · I n < 0.1 s C 0.5 to 63 A 1.13 · I n > 1 h 5 · I n > 0.1 s 1.45 · In < 1 h 10 · I n < 0.1 s D 0.5 to 63 A 1.13 · I n > 1 h 10 · I n > 0.1 s 1.45 · In < 1 h 20 · I n < 0.1 s DIN VDE 0660/9.82 K 0.5 to 63 A 1.05 · I n > 1 h 1.2 · In < 1 h not applicable DIN VDE 0660 1.05 · In > 2 h 8 · I n > 0.2 s 8/69 1.2 · In < 2 h /L54708 12 · In < 0.2 s Part 1/L54709 1.5 · In < 2 min. /L54708 DIN VDE 0660/9.82 Z 0.5 to 63 A 1.05 · I n > 1 h 1.2 · In < 1 h not applicable DIN VDE 0660 1.05 · I n > 2 h 2 · I n > 0.2 s 8/69 1.2 · I n < 2 h /L54708 3 · In < 0.2 s Part 1/L54709 1.5 · In < 2 min./L54708 /L54707The thermal releases are calibrated to a nominal reference ambient temperature; for Z and K, the value is 20 °C, for B and C = 30 °C. In the case of higher ambient temperatures, the current values fall by ca. 6% for each 10 K temperature rise. /L54708as from operating temperature (after I 1 > 1 h or, as applicable, 2 h ). /L54709The standard DIN VDE 0660/9.69 has expired in 1986, but is still referred to due to its complete statement of the tripping characteristics. /L54706The indicated tripping values of electromagnetic tripping devices apply to a frequency range of 16 2/3 ... 60 Hz. In the case of diverging frequencies or direct current, the values change by the factor indicated below Miniature circuit-breakers S 200/S 200 M series alternating current direct current
100 Hz 200 Hz 400 Hz
The thermal release operates independently of voltagest. operating sequence: B and C according to DIN VDE 0641, DIN VDE 0660 Part 101 I CS K and Z according to IEC 947Short circuit rupturing capacity and back-up series alternating current direct current Max. back-up trip characteristic 1phase 2/3phase 1pole /L54706 rated current 133 V /L50513 230 V /L50513 230 V /L50513 400 V /L50513 60 V ... main 133/230 V /L50513230/400 V /L50513 fuse circuit-br. A kA/cos ϕ kA/cos ϕ kA/cos ϕ kA/cos ϕ kA/T /L50872 ms gL /L54707 S 700 S 200-B 6 63 A 100 A S 200 M-B 10 ... 20
100 A 100 A
25 ... 32 100 A 100 A 40 10/0.5 10/0.5 125 A 100 A 50 ... 63 (S 200 M-B) (S 200 M-B)
160 A 100 A
S 200-C 0.5 ... 2 unlimited not required S 200 M-C 3 ... 4 20 A – S 200-D 6 40 A 100 A
63 A 100 A
10 ... 20 100 A 100 A ( S 200 M-C) (S 200 M-C)
125 A 100 A
50 ... 63 160 A 100 A S 200-K 0.5 ... 2 unlimited not required 3 20 A – 4 25 A – 6 ... 10 63 A 100 A 25 ... 32 100 A 100 A 40 125 A 100 A 50 ... 63 160 A 100 A S 200-Z 0.5 ... 2 unlimited not required 3 ... 4 20 A – 6 35 A 100 A 8 40 A 100 A 20 ... 25 80 A 100 A 32 ... 40 100 A 100 A 50 ... 63 125 A 100 A /L54706In symmetrically earthed direct current circuits, 2-pole devices (two poles connected in series) can be used up to 110 VDC. Any connection is possible, polarity does not need to be taken into account. /L54707Back-up protection is necessary only if the solid short-circuit current to be expected at the place of installation may exceed the switching capacity indicated.
pro M compact ® SK 0112 Z 99 SK 0113 Z 99 Miniature circuit-breakers S 200/S 200 M series /L50872 2 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 1 1.2 4 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 3 15 15 15 15 15 15 15 10 10 0.3 0.7 1.2 4.6 6 6 6 6 6 6 4 15 15 15 15 15 15 15 10 10 0.3 0.6 0.9 2.8 6 6 6 6 6 6 13 15 15 15 15 15 15 15 10 10 0.7 1.5 2.5 3.5 5 6 6 6 16 15 15 15 15 15 15 15 10 10 1.3 2 2.9 4.1 6 6 6 20 15 15 15 15 15 15 10 10 1.8 2.6 3.5 5 6 6 25 15 15 15 15 15 10 10 1.8 2.6 3.5 5 6 6 32 15 15 15 15 10 10 2.2 3 4 6 6 40 15 15 15 10 10 2.5 4 6 6 50/63 15 15 10 10 3.5 5 6 /L50872 2 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 0.3 1.2 4 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 3 10 10 10 10 10 10 10 10 10 0.3 0.7 1.2 4.6 6 6 6 6 6 6 4 10 10 10 10 10 10 10 10 10 0.3 0.6 0.9 2.8 6 6 6 6 6 6 6 1 0 1 01 01 01 01 01 01 01 0 0 . 7 1 . 7 3 5 . 96 6 6 6 8 1 0 1 01 01 01 01 01 01 01 0 1 . 3 2 . 2 3 . 66 6 6 6 10 10 10 10 10 10 10 10 10 10 1.7 2.5 4 6 6 6 16 10 10 10 10 10 10 10 10 10 2.2 3.1 4.6 6 6 20 10 10 10 10 10 10 10 10 3.1 4.6 6 6 25 10 10 10 15 10 10 10 2.6 3.5 6 6 32 10 10 10 10 10 10 3.5 6 6 40 10 10 10 10 10 5.5 6 50/63 10 10 10 10 6 /L50872 2 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 0.5 2 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 3 1 0 1 01 01 01 01 01 01 01 0 0 . 3 0 . 7 1 . 2 6 6 6 6 6 6 6 4 1 0 1 01 01 01 01 01 01 01 0 0 . 3 0 . 6 1 . 3 7 6 6 6 6 6 6 6 10 10 10 10 10 10 10 10 10 0.2 0.5 0.9 2.7 6 6 6 6 6 6 10 10 10 10 10 10 10 10 10 10 0.4 0.6 1.3 2.4 4 6 6 6 6 16 10 10 10 10 10 10 10 10 10 0.5 1.1 1.7 3 4.5 6 6 6 25 10 10 10 15 10 10 10 1.4 2 3 4 6 6 32 10 10 10 10 10 10 1.4 2 3 4 6 6 40 10 10 10 10 10 2 3 4 6 6 50/63 10 10 10 10 2.2 3.5 5.8 6 S 200 M-B, C Current values smaller than 6 A and 8 A, apply only to C characteristics. Short circuit selectivity: In the case of a short circuit, selectivity exists up to the values indicated. In 16 20 25 35 40 50 63 80 100 16 20 25 35 50 63 80 100 125 160A /L50872 2 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 1 1.2 4 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 /L5014015 3 10 10 10 10 10 10 10 8 8 0.3 0.7 1.2 4.6 6 6 6 6 6 6 4 10 10 10 10 10 10 10 8 8 0.3 0.6 0.9 2.8 6 6 6 6 6 6 13 10 10 10 10 10 10 10 8 8 0.7 1.5 2.5 3.5 5 6 6 6 16 10 10 10 10 10 10 10 8 8 1.3 2 2.9 4.1 6 6 6 20 10 10 10 10 10 10 8 8 1.8 2.6 3.5 5 6 6 25 10 10 10 10 10 8 8 1.8 2.6 3.5 5 6 6 32 10 10 10 10 8 8 2.2 3 4 6 6 40 10 10 10 8 8 2.5 4 6 6 6 50/63 10 10 8 8 3,5 5 6 series S 200-B, C, D Current values smaller than 6 A and 8 A, apply only to C and D characteristics. MCBs short circuit discrimination in kA to main circuit breaker S 700 S 200-K Selectivity values apply to Icu according to IEC 947-2. to fuse gL/gG (DIN VDE 0636; IEC 269/3) ** Limited or no selectivity at all possible in the overload range (thermal tripping) S 200 Z Selectivity values apply to Icu according to IEC 947-2. The above values require that, in the case of multi-phase installations, that the last cb be feed from above.
pro M compact ® Miniature circuit-breakers S 200/S 200 M series Tripping diagrams Reading example for tripping characte- ristic of the B-type trip characteristics (in connection with the table tripping characteristics on page 9, line B) a Thermal tripping characteristic: Conventional non-tripping current I1 = selected non-tripping current The MCB maintains the 1.13 times of the rated current for at least 60 minutes. Conventional tripping current I 2 = selected tripping current. The MCB switches off within 60 minutes when the 1.45 times of the rated current is reached. b Electromagnetic trip characteristic AC: The MCB maintains current rushes of the 3-fold of the rated current for more than 0.1 sec. (in this example up to ca. 4 sec.). The MCB switches off within less than 0.1 sec when the 5-times of the rated current is reached. SK 0038 Z 01 trip characteristic: C I n = 0.5 ... 63 A S 200/S 200 M MCBs SK 0128 Z 00 trip characteristic: D I n = 0.5 ... 63 A S 200 MCBs 2CDC 022 377 F0203 SK 0142 Z 00 trip characteristic: K In = 0.5 ... 63 A S 200 MCBs Note: Deviating ambient temperature values and interdependencies need to be taken into account SK 0146 Z 00 trip characteristic: Z I n = 0.5 ... 63 A S 200 MCBs trip characteristic: B I n = 6 ... 63 A S 200/S 200 M MCBs
pro M compact ® Pulse tripping of the MCBs S 200/S 200 M made by ABB-STOTZ-KONTAKT Miniature circuit-breakers S 200/S 200 M series Example: non-tripping current (electromagnetic release) S 201-B16 I hold = K x non-tripping current B-type characteristic = 3 x I n Ihold = 4.2 x 3 x 16 C-type characteristic = 5 x I n Ihold = 201.6 A D-type characteristic = 10 x I n K-type characteristic = 10 x I n Z-type characteristic = 2 x I n In the case of an impulse of 600 /L50528, S 201-B16 maintains up to a current of 201.6 A. 2CDC 022 131 F0203
pro M compact ® Miniature circuit-breakers S 200/S 200 M series Diagrams of let-through values I2 t at 230/400 VAC Miniature circuit-breakers S 200 B/C, D on request Miniature circuit-breakers S 200 K Miniature circuit-breakers S 200 Z Miniature circuit-breakers S 200 M B/C ➀ min. pre-arcing I 2t, e.g. In = 80 A gL ➁ max. let-through I 2t MCB e.g. B20 A G Fuse-MCB, selectivity with respect to the upstream fuse to the point of intersection of both curves ➀ and ➁. e.g. S 200-B20 to fuse 80 A: selectivity up to 3.5 kA min. G Let-through value I 2t reduced: 127 V/L50513 by factor 2.5
110 V/L50513 by factor 3
pro M compact ® Miniature circuit-breakers S 200/S 200 M series The influence of ambient temperature and interdependencies in the case of even loads on the load capability of MCBs Practical Note: This practical deduction, that is applicable for all types of characteristics, can be recommended for standard environments. Selection criteria for rated current of circuit-breakers according to EN 60898 and EN 60947-2. Choose the circuit-breaker that is appropriate for the lower of the rated value of the device or the permissible current loadin g. Now, the major factors having an influence on the circuit-breaker, must be taken into account: 1. ambient temperature with I B /L50872 0.9 x In at 40 °C ambient temperature 2. mutual influence with I B /L50872 0.75 x In in the case of more than one circuit-breaker being loaded evenly in parallel. The ensuing rated current of the circuit breaker is thus: In = 1.5 x rated current Example: operating currect 4 A, then the rated current of the circuit-breaker is: In = 1.5 x 4 A = 6 A The above takes into account all relevant factors and the circuit is protected at the lowest possible level. This practical note is based on the following: 1. Deviating ambient temperature: The thermal releases are adapted to a given reference ambient temperature. For the K- and Z-type characteristics, it is 20 °C, for B-, C- and D-type, it is 30 °C. For all other ambient temperatures, the current values indicated vary by ca. 6 % per 10 K temperature de/increase . For more precise calculations and very high/low ambient temperatures, the following tables apply: Max. operating current depending on the ambient temperature circuit-breaker in load circuit of characteristics type B, C and D B, C and D Ambient temperature T (°C) In (A) – 40 – 30 – 20 – 10 0 10 20 30 40 50 60 70 Max. operating current depending on the ambient temperature circuit-breaker in load circuit of characteristics type K and Z K and Z Ambient temperature T (°C) In (A) – 40 – 30 – 20 – 10 0 10 20 30 40 50 60 70 2. Interdependencies in the case of even loads A correction factor must be taken into account in the case butt-mounted devices and an evenly applied, high load: 2 and 3 circuit-breakers with factor 0.9 4 and 5 circuit-breakers with factor 0.8 6 and more circuit-breakers with factor 0.75 T he interdependency becomes irrelevant if FST … spacers or packing blocks (9mm width) are used. The influence of ambient temperature and interdependencies in the case of even loads on the load capability of MCBs Practical Note: This practical deduction, that is applicable for all types of characteristics, can be recommended for standard environments. Selection criteria for rated current of circuit-breakers according to EN 60898 and EN 60947-2. Choose the circuit-breaker that is appropriate for the lower of the rated value of the device or the permissible current loadin g. Now, the major factors having an influence on the circuit-breaker, must be taken into account: 1. ambient temperature with I B /L50872 0.9 x In at 40 °C ambient temperature 2. mutual influence with I B /L50872 0.75 x In in the case of more than one circuit-breaker being loaded evenly in parallel. The ensuing rated current of the circuit breaker is thus: In = 1.5 x rated current Example: operating currect 4 A, then the rated current of the circuit-breaker is: In = 1.5 x 4 A = 6 A The above takes into account all relevant factors and the circuit is protected at the lowest possible level. This practical note is based on the following: 1. Deviating ambient temperature: The thermal releases are adapted to a given reference ambient temperature. For the K- and Z-type characteristics, it is 20 °C, for B-, C- and D-type, it is 30 °C. For all other ambient temperatures, the current values indicated vary by ca. 6 % per 10 K temperature de/increase . For more precise calculations and very high/low ambient temperatures, the following tables apply: Max. operating current depending on the ambient temperature circuit-breaker in load circuit of characteristics type B, C and D B, C and D Ambient temperature T (°C) In (A) – 40 – 30 – 20 – 10 0 10 20 30 40 50 60 70 Max. operating current depending on the ambient temperature circuit-breaker in load circuit of characteristics type K and Z K and Z Ambient temperature T (°C) In (A) – 40 – 30 – 20 – 10 0 10 20 30 40 50 60 70
pro M compact ® Miniature circuit-breakers S 200/S 200 M series Use of S 200/S 200 M miniature circuit-breakers in direct current circuits 60 VDC/125 VDC In DC systems up to 60 VDC or, as the case may be, series connection up to 125 VDC, customary S 200/S 200 M series MCBs can be used. Polarity does not need to be taken into consideration, the outgoing circuit may be implemented from above or below the device. For higher direct voltage up to 440 VDC devices of the S 280 UC series must be used. Example for max. permissible voltages between conductors depending on the number of poles and type of connection. Fusing of lighting currents 1. Filament lamps and fluorescent lamps The following table indicates the maximum number of fluorescent lamps that can be protected with a single-pole miniature circui t-breaker. In the case of multipole MCBs, the value is reduced by 20 %. Tripping charcteristic type C allows for light currents up to the rated current of the MCB, for fusing of: filament lamps fluorescent lamps a) non-compensated b) shunt compensated (cos ϕ = 0.95) c) electronic load 2. High-pressure discharge lamps Starting current: ca. 1.7 x lamp current According to the type of lamp, line impedance and start-stop torque, the so-called rectifier effect may occur which superimpose s the starting current of the lamp for some half-waves. In the most unfavorable circumstances, inrush currents of 15 times of the lamp nominal current may ensue. To avoid nuisance tripping, MCBs with K-type characteristic should not carry loads higher than 0.6-fold of the lamp current. The load factor indicated refers to the least favorable case (proximity to transformer, low line impedances). Examples for different voltages between a conductor and earth where voltages between conductors are identical: ➀ electronic ballast: twin-lamp style, jointly switched number of lamps Characteristic/ non-compensated shunt compensated electronic ballast ➀ rated current conventional ballast conventional ballast 18/20 W 36/40 W 58/65 W 18/20 W 36/40 W 58/65 W 18/20 W 36/40 W 58/65 W 10 27 23 15 32 32 20 18 18 8 16 43 37 24 51 51 33 26 26 12 20 53 46 30 64 64 41 33 33 15 25 66 58 37 82 82 53 42 42 19 SK 0173 Z 99 SK 0174 Z 99
pro M compact ® Miniature circuit-breakers S 200/S 200 M series Installation and operation instructions Installation Can be installed in any mounting position due to snap-on fixing to DIN rails EN 60 715, 35 mm width. A If MCB S 200/S 200 M is installed without cross wiring, hinge the upper part into the DIN rail and push to let the lower part of the device snap into place (1). The device is released in the reverse order, after the quick fastener has been removed with a screw driver (2). B To release S 200 /S 200 M that are cross-wired with System pro M compact busbars, first remove the clamping screws Then, pull the lower part of the S 200/S 200 M forwards (1) and lift it straight up (1a) , then, the quick fastener (1b) will recede. C The busbar is deallocated and the S 200/S 200 M can be pulled out by lifting the device forwards (2). D The cross-wiring is re-inserted in the reverse order. First, open the clamping screws and pull out the quick fastener until it locks into place for the first time (3) . Then, take the S 200 /S 200 M and insert it with rear terminal side onto the pins of the System pro M compact busbar (4) , turn it into the direction of the DIN rail (4a) and shift it vertically downwards (4b) ,this way, the quick fasterner snaps back into place (4c). Attention: Do not forget to re-tighten the clamping screws. 2CDC 022 153 F0003 Operation MCBs are switched on by switching the operating lever into the upper position (with resepct to the text block of the nameplate) . If an MCB, after it has triggered, cannot be switched on again off-handedly, the triggering is probably caused by overload. If the MCB trips again immediately when trying to reclose (let a short period of time elapse), a complete short-circuit, or as the case may be, earth connection can be assumed. Do not try and continuously re-close an existing short circuit or earth fault. The MCB even trips under overload, or short-circuit or earth fault conditions, even if the operating lever is maintained in the ON position by force (trip-free mechanism). Cleaning the device MCBs soiled by installation work should be cleaned with a dry, or, if necessary, a damp and soapy cloth. Never use caustic agents or dissolvents. Maintenance STOTZ MCBs are maintenance-free. Opening the device will lead to a loss of warranty. Connection: For connection cross sections, see page 7. Feeder optional, top or bottom, terminal designation according to EN 50 005. For wiring diagrams, see picture to the right. C Removal when pro M compact cross wiring remains in place SK 0267 Z 98 SK 0266 Z 98 SK 0268 Z 98 SK 0269 Z 98 pro M compact busbar pro M compact busbar quick fastener D Insertion when pro M compact cross wiring remains in place A Assembly, disassembly without pro M compact cross wiring B Detaching when pro M compact cross wiring remains in place snap on release pro M compact busbar pin SK 0167 Z 99 pin
pro M compact ® Additional devices Mounting additional devices Additional devices are always fitted from the right hand side: – signal contact/auxiliary switch S2C-S/H6R for MCBs and RCCBS – auxiliary switch S2C-H6R for MCBs – shunt release S2C-A for MCB Supplementary devices 2CDC 092 154 F0003 S function signal contact H function auxiliary switch 1. Signal contact and auxiliary switches Retrofittable to the right side of circuit-breakers or shunt releases without extra installation devices.
1.1 Universal signal contact/ auxiliary switch type S2C-S/H6R
S2 – serial code: S 2 C - S/H 6 R R = right side-mounted 6 = change over H = auxiliary switch S = signal contact C = compatible to pro M compact S2C-S/H6R is a universal device complementing the range of pro M compact, which is supplied to offer signal contact functionali ty, or the auxiliary switch can be activated, all you need is a screwdriver. The universal switch can be with MCBs and RCCBs. Up to three S2C-H6R can be mounted (one signal contact max. fitted to MCB or RCCB). Both the switchgear and the S2C-S/H6R must be in the ON end position to ensure that the coupling is correct. Function of the signal contact S Signal is transmitted only if caused by fault-tripping of the circuit-breaker, but not if the switch has been switched on or of f manually. Press the orange reset button to acknowledge the has-tripped signal. Function of the auxiliary switch H The switch always indicates the switching position of the MCB, irrespective of whether the switching position is attributable t o manual operation or fault tripping. Functionality selection To select either the signal contact function S or the auxiliary switch H, use a screwdriver and adjust to position S, or as the case may be, H at the side of the device. SK 0170 Z 02 to MCBs and RCCBs only to MCBs to shunt releases
pro M compact ® Supplementary devices Installation: 1. Mounting one S2C-S/H6R → RCCB or MCB must be in the ON position → remove coupling cover on the right side of the MCB/RCCB → signal contact/auxiliary switch in ON position → if fitted to MCB, remove bottom (RCD), if fitted to RCCB middle (MCB) coupling pin → plug devices together. SK 0287 Z 02 SK 0288 Z 02 2. Mounting more than one S2C-S/H6R Up to three S2C-H6R can be mounted. Note: one signal contact max. fitted at first to MCB or RCCB If fitted to an MCB, remove the bottom coupling pin (RCD), if fitted to an RCCB, remove the middle coupling pin (MCB), switch a ll signal contact/ auxiliary switches to the end position ON, plug them together and carry through a function control test. SK 0285 Z 02 Function control test: After all signal contacts/auxiliary switches or auxiliary switches have been mounted, use the upper coupling pin to switch on t he devices (ON position). If the lower (for RCD) or, as the case may be, the middle (for MCB) coupling pin is operated, all devices must t rip. Now combination with MCB/RCCB: RCCB or MCB must be in the ON position → remove coupling cover on the right side of the MCB/RCCB → signal contact/auxiliary switch in ON position → if fitted to MCB, remove bottom (RCD), if fitted to RCCB middle (MCB) coupling pin → plug devices together. SK 0240 Z 02 Test functions of the signal contact in ON and OFF position after hand operation SK 0241 Z 02 Test functions of the auxiliary switch in ON position SK 0242 Z 02 in ON position after tripping SK 0243 Z 02 in OFF position
pro M compact ® Supplementary devices Technical Data Signal contact/auxiliary switch S2C-S/H6R and auxiliary switch S2C – H6R according to EN 62019 rated current I th: 10 A min. rated voltage U Bmin: 24 V ~, 24 V ... min. rated operational current: 5 VA /L54706 short-circuit withstand capacity: 230 V~ 1000 A with S 201 K 4 insulation coordination: according to DIN VDE 0110 Parts 1 and 2 – overvoltage category: III – surge voltage: 4 kV (1.2/50 µs) – pollution degree: 2 tightening torque: 1.2 Nm max. contact stability in vibration test at 24 VAC/DC, 5 mA automatic reclosing < 10 ms mech. service life: 10 000 operations /L54706The minimum rated operational current value applies in the case of operation and environmental conditions according to EN 60 204-1/1998 and EN 60 439-1/2000 if installed indoors and in clean ambient air: 24 VAC/DC, 5 mA (AC-12, DC-12)
1.2 Auxiliary switch type S2C-H6R
The simple auxiliary switch without test functionality is appropriate for applications where it is only necessary to indicate t he contact position of the circuit-breaker. Up to three S2C-H6R can be butt-mounted, including combinations with the signal contact/auxiliary switch SC2-S/H6R. Installation and technical data the same as for signal contact/auxiliary switch SC2-S/H6R, see preceding page and above. Installation and technical data the same as for signal contact/auxiliary switch SC2-S/H6R, see preceding page and above. 2. Shunt trip S2C-A For distance tripping of the MCB. The shunt release has a relay coil with an integrated contact which disconnects the coil and the coil voltage if the MCB trips, this prevents the flow of current in the case of sustained coil voltage. Technical data type: S2C - A1 S2C - A2 AC 14 DC 12 DC 13 Ue 400 V 230 V Ie 1 A 2 A Ue 220 V 110 V Ie 1 A 1.5 A Ue 60 V 24 V Ue 1.5 A 4 A STOTZ-Shunt trip with automatic disconnecting within 10 milliseconds U B = Un + 10 – 30 % UB IBmax UB IBmax S2C-A1 12 VDC 2.2 A S2C-A2 110 VDC 0.35 A 12 VAC 2.5 A 110 VAC 0.5 A 24 VDC 4.5 A 220 VDC 1.1 A 24 VAC 5 A 230 VAC 1.0 A 60 VDC 14 A 415 VAC 2.7 A 60 VAC 8.8 A U B = operating voltage I Bmax = operating current
pro M compact ® Residual-current-operated circuit breaker F 200 series Residual-current protective devices have a balance or, as the case may be, differential current transformer as measuring device that is connected with permanent magnet trip via the secondary winding. Residual-current protective devices cover a.c. fault current an d pulsating d.c. fault current and are insensitive to current rushes up to 250 A, selective and short-time delayed tripping types up to 3,000 A). Pulse shape 8/20 according to DIN VDE 0432 Part 2. STOTZ residual-current protective devices are surge-proof and thus insensitive to transient leakage current to earth, as may oc cur e.g. when switching fluorescent lamps, X-ray apparatus, IT systems and also thyristor control. (The value of the surge strength is i ndicated in the technical data information regarding the switching variants). Protection through RCD of types AC, A and B according to IEC 755 Selective RCCB F 200S Is installed centrally and operates on a time-selective basis with respect to more sensitive downstream residual-current device s. The result is a high degree of service security, as in the case of a fault, only the circuit affected will be switched off. Due to their surge strength of up to 5,000 A/3,000 A, nuisance tripping of STOTZ main RCCBs caused by remote strike is ruled ou t. They are therefore the perfect choice for the connection of freezers and agricultural applications (e.g. fans in intensive live stock husbandry) according to DIN VDE 0100 Part 705. Short-time delayed RCCBs F 200 R are RCCBs with high surge strength needed where apparatus causes high leakage currents when switched on or off (e.g. lighting c ircuits with ballast, long lines). Application To obtain a better level of security in all wiring systems, as well as in supply areas with respect to which codes of practice recommend or require the use of residual-current protective devices. Tasks Protection against electric shock Measures for the protection against electric shock as provided for in DIN VDE 0100 Part 410. These measures are: /L50540Protection from indirect touch – as fault protection through disconnection of circuit in the case of excessive touch voltage ca used by short circuit to exposed conductive part. /L50540Protection from direct touch – as additional protection through disconnection when conductive parts are touched. Dangerous leak age current is switched off within the shortest possible time if the rated residual current of the circuit-breakers is I ∆n /L50872 30 mA, in the case of people protector FS 201 I ∆n /L50872 10 mA. /L50540Protection against fire – protection against fire ignited by electricity if the nominal residual current of the circuit-breaker is I∆n /L50872 300 mA. form of residual current sinusoidal a.c. pulsating d.c. smooth d.c. correct functioning of RCD /L50540 a.c.- sensitive type AC pulsating current-sensitive type A d.c.-sensitive type B /L50540 F 200 AC /L50540 F 200 /L50540 /L50540 /L50540 /L50540 suddenly applied slowly rising suddenly applied with/without superimosed smooth d.c. of 6 mA slowly rising
pro M compact ® Residual-current-operated circuit-breakers F 200 series/FS 201 Technical data F 200 F 200 R F 204 S FS 201 short time delayed selective RCBO specifications: DIN VDE 0664 Part 11, EN 61008-2-1 DIN VDE 0664 Part 21 and EN 61009/IEC 61009 No. of poles: 2-pole 2-pole 2-pole 4-pole 4-pole 4-pole 4-pole tripping characteristics: – B and C acc. to DIN VDE 0641 and EN 60898; K acc. to DIN VDE 0660 and EN 60947 rated current I n: 16, 25, 40, 63 A 25, 40, 63 A 25, 40, 63 A 40 A, 63 A 6 to 32 (40) A rated residual current I /L50876n: 10, 30, 300 30, 100 30 mA 300 mA 10 mA, 30 mA, 300 mA and 500 mA and 300 mA tripping time at 1 · I /L50876n: /L50872 300 ms /L50872 300 ms 120 … 300 ms 150 ... 500 ms /L50872 300 ms at 2 · I/L50876n: 50 … 150 ms 60 ... 200 ms at 5 · I/L50876n: /L50872 40 ms /L50872 40 ms 40 ... 150 ms /L50872 40 ms at 500 A: 20 … 40 ms 40 ... 150 ms tripping time at 1 · 1,4 I /L50876n: /L50872 300 ms /L50872 300 ms /L50872 300 ms /L50872 300 ms at 5 · 1,4 I /L50876n: /L50872 40 ms /L50872 40 ms /L50872 50 ... 150 ms /L50872 40 ms rated switching capacity: – – 6 kA, ϕ 0,7 surge strength (impulse waveshape 8/20): 250 A 3000 A 5000 A 250 A short-circuit withstand capacity: 10.000 A, in connection with an upstream 10.000 A, in connection fuse gL 100 A or the STOTZ selective with an upstream fuse main circuit-breaker S 700-E 100 A gL 100 A or the selective main circuit-breaker S 700-E 100 A rated voltage U n: 2-pole: 230 V ~ 4-pole: 230/400 V ~ 230/400 V ~ 2-pole: 230 V ~ max. operating voltage U Bmax:U n + 10 % operative range of test equipment U T: 100 V ~ to 264 V ~ 100 V ~ to 264 V ~ 100 V ~ to 264 V ~ insulation coordination according to DIN VDE 0110 Part 1 and 2 – overvoltage category: III, disconnector abilities – pollution degree: 2 – surge voltage U imp (1,2/50): 4 kV – power-frequency withstand voltage (50/60 Hz): 2.5 kV frequency: 50/60 Hz 50/60 Hz housing: moulding grey moulding grey operating lever/test button: blue black/blue degree of protection: IP 20; in the distribution board IP 40; in moulded-plastic casing IP 55 (see accessories) dimensions: see dimension drawings connection cross section: 1 to 16 mm 2 for finely-stranded to massive conductors 1 to 16 mm 2 for In to 40 A, 1 to 25 mm 2 for In 63 A service life: > 5.000 switches climatic resistance according to DIN IEC 68 Part 2-30: damp heat: 28 cycl. 55/95 … 100 (°/RH) (RH = rel. humidity) damp heat, cyclic (55 °C/28 cycles) alterning climate: 25/95 - 40/93 (°C/RH) constant climate: 23/83, 40/93, ambient temperature: T max. + 55 °C T min. – 25 °C vibration resistance according to: DIN VDE 0664 Part 1/10.85 and EN 61008 DIN VDE 0664 Part 2/10.85 and EN 61009 terminals: bi-directional cylinder-lift terminal trip-free mechanism: yes connection: individually or collectively via a busbar supplementary devices: type S2C-S/HR s. pagee 17 in preparation F 200 AC
pro M compact ® Residual-current-operated circuit-breakers F 200 series/FS 201 Installation and operation instructions Installation Can be installed in any mounting position due to snap-on fixing to DIN rails EN 50 022, 35 mm width. A If RCD F 200/FS 201 is installed without cross-wiring , hinge the upper part into the DIN rail and push to let the lower part of the device snap into place (1). The device is released in the reverse order, after the quick fastener has been removed with a screw driver (2). B To release RCD F 200/FS 201 that are cross-wired with System pro M compact busbars, first remove the clamping screws. Then, pull the lower part of the F 200/FS 201 forwards (1) and lift it straight up (1a), then, the quick fastener will recede (1b). C The busbar is deallocated and the RCD F 200/FS 201 can be pulled out by lifting the device forwards (2). D The cross-wiring is re-inserted in the reverse order. First, open the clamping screws and pull out the quick fastener until it locks into place for the first time (3). Then, take the RCD F 200/FS 201 and insert it with the rear terminal side onto the pins of the System pro M compact busbar (4), turn it into the direction of the DIN rail (4a) and shift it vertically downwards (4b), to let the quick fastener snap back into place (4c). Attention: Do not forget to re-tighten the clamping screws. Connection Feeder optional, top or bottom. Ensure that conductors are con- nected correctly and firmly. If the 4-pole RCCB is operated as a 2-pole RCCB, use terminals 5 and 7 or, as the case may be, 6 and 8 to make sure that the test button function of the RCCB is working. In the case of a three-phase system with U n = 127/230 V (without neutral N), terminals 4 and 8 must be bridged. Operation F 200/FS 201 is switched ON or OFF with the blue operating lever. SK 0012 Z 96 SK 0272 Z 98 2CDC 032 138 F0203 C Removal when pro M compact cross wiring remains in place SK 0267 Z 98 SK 0266 Z 98 SK 0268 Z 98 SK 0269 Z 98 pro M compact busbar pro M compact busbar quick fastener D Insertion when pro M compact cross wiring remains in place A Assembly, disassembly without pro M compact cross wiring B Detaching when pro M compact cross wiring remains in place snap on release pro M compact busbar pin SK 0167 Z 99 pin Operating test To test proper functioning, press the blue test button when the device is switched ON, the RCCB must trip immediately (the knob jumps into the „0“ switching position). It is necessary to test the RCD halfyearly, if no other regional or user specified additional test are required.
pro M compact ® Residual-current-operated circuit-breakers F 200 series/FS 201 Test of protective measure Except for the operating test, the effectiveness of the protection provided within the installation must be tested according to the applicable codes of practice. For RCD protection, the maximum permissible earthing resistance values are as follows: max. max. earthing resistance touch at nominal residual current voltage UL 10 mA 30 mA 100 mA 300 mA 500 mA
25 V 2500 /L09202833 /L09202250 /L09202 83 /L09202 50 /L09202
50 V 5000 /L092021666 /L09202500 /L09202166 /L09202100 /L09202
The high-quality STOTZ residual-current-operated circuit-breakers are thorougly adjusted and tested in our works. Where damage occurs (caused e.g. by transport, storage, etc.) no repair work must be undertaken. If the device responds immediately after putting the RCCB into operation, check the downstream active circuit and any connected current- consuming apparatus for earth fault current. Remove insulation faults or connections between the neutral conductor and the prot ective conductor existing in load circuit. Where the RCCB does not trip in the first operating test after pressing the test button, ch eck first wheth- er the test circuit is connected correctly. Where none of the above causes apply, or should the operating test be completed unsuccessfully, the RCCB must be replaced. Opening the device will lead to a loss of warranty. TN-S system (protective multiple earthing) separate neutral and protective conductors throughout the network TN-C-S system neutral and protective conductor (PEN) combined in one part of the network. TT system IT system The residual-current-operated circuit-breaker trips if a double fault occurs, as e.g. is indicated as fault 1 and fault 2 above Examples for the protection against electric shock I„ insulation“ C„ combined“ PE and N (PEN) S„ separated“ PE and N „…“ terms used in international IEC standard SK 0005 Z 97SK 0017 Z 95 SK 0040 Z 94 SK 0038 Z 94 /L54706only indicated by line isolation monitor Explanation of type codes L1, L2, L3 „ line“ phase conductor PE „ protection earth“ N„ neutral“ PEN PE and N combined T„ terre“ direct bond to earth
pro M compact ® Load capability depending on the feed point bar cross section 10 mm 2 16 mm2 /L54706/L54706/L54706/L54706/L54706max. busbar current I S/phase 63 A 80 A /L54707/L54707/L54707/L54707/L54707max. current in branch I E/phase 100 A 130 A* * If the device is fed via the device terminal, ensure that - irrespective of the current carrying capacity (I S) of the busbar - the following values are not exceeded: For devices up to and including 40 A I n max. 110 A and for 50/63 A I n max. 140 A. The newly developed pro M compact cross wiring busbar system includes everything that is needed for secure and economic connections of distribution build-in devices of the series S 200 and F 200. The optimised quick fastener of the S 200 series, F 200 , when used together with the System pro M compact cross wiring busbars, makes removing and inserting devices a quick and easy job, and the cross wiring of other devices remains in place, at that. Busbars are supplied ready-to-use and in standard lengths, time-consuming cutting to length or end caps are no longer required. MCBs and RCCBs of the customary System pro M technology can also be easily cross-wired with the new System pro M compact busbars. Technical data specifications: VDE 0660 Part 500, DIN EN 60439-1: 1994 test surge voltage: (1,2/50) 6,2 kV busbar material: SF-Cu F 24 short-circuit withstand capacity:25 kA insulating profile material: plastic, temperature resistant /L50871 90 °C climatic resistance: constant climate L23/83; 40/92 flame-retardant, self-extinguishing 55/20 according to DIN 50 015 dioxine- and halogene-free humid heat, 28 cycles (/L50871 IEC 68 Part 2 - 30) busbar cross section: 10 mm 2 insulation coordination: acc. to VDE 0110 Part 1 April 1997 (IEC 664) max. operating voltage: 440 V - overvoltage category: III rated surge voltage: 4 kV - pollution degree: 2 /L54706/L54706/L54706/L54706/L54706incoming supply /L54707/L54707/L54707/L54707/L54707incoming supply at the beginning of the within the busbar busbar or centre-fed If the device is centre-fed (see picture to the right), ensure that the combined outgoing currents a 1 ...an per branch do not exceed the max. busbar current IS/phase referred to above. SK 0063 Z 91 SK 0062 Z 91 Busbars for series S 200, S 200 M, F 200, FS 201
pro M compact ® Miniature circuit-breakers S 200/S 200 M Residual-current-operated circuit breakers F 200/FS 201 Dimensions Dimensions measurements in mm F 202, F 204, F 204 S SK 0111 Z 99 S 201 H, S 202 H, S 203 H, S 204 H S 201, S 202, S 203, S 204 SK 0058 Z 01 SK 0136 Z 01 1-pole 2-pole 3-pole 4-pole 1 + NA 3 + NA 1-pole 2-pole 3-pole 4-pole 2-pole 4-pole SK 0046 Z 02 Supplementary devices FS 201 SK 0047 Z 02 S2C-S/H 6 R S2C-A... S2C-H 6 R S2C-UA...
pro M compact ® Accessories Dimensions Terminal covers measurements in mm Enclosure of moulded-plastic Flush frame type S 500 - ME 1 S 500 - ME 2 S 500 - ME 3 dim. L 38 mm 88 mm 184 mm max. No. of modules (1 module = 17.5 mm) for 2 Module for 5 Module for 10 Module Mounting rails SK 0136 Z 96 name A A1 DSW 17.5 15 DSW 2 35 20 DSW 3 52.5 37.5 DSW 4 70 55 DSW 6 105 90 PCD 2 N PCD 4 N PCD 6 N SK 0137 Z 96 PCD 8 N SK 0138 Z 96 QES 4/3 N QES 6/3 N SK 0078 Z98 SK 0079 Z98 SK 0131 Z 94 /L54706In the case of DSW 1, the drill holes are vertical SK 0150 Z 93
pro M compact ® Busbars Dimensions Dimensions measurements in mm 2CDC 062 145 F0203 2CDC 062 139 F0203 PS 1/2 PS 3/6 PS 1/6 PS 1/9 PS 1/12 2CDC 062 140 F0203 2CDC 062 141 F0203 2CDC 062 142 F0203 2CDC 062 146 F02032CDC 062 255 F02032CDC 062 148 F0203 PS 3/9 PS 3/12 PS 3/12 FI PS 3/60 2CDC 062 263 F0203 2CDC 062 149 F0203 auxiliary contact bridge HKB
pro M compact ® Busbars Dimensions Dimensions measurements in mm 2CDC 062 261 F0203 PS 3/48 H 2CDC 062 260 F0203 PS 3/39 H 2CDC 062 253 F0203 PS 2/58 2CDC 062 251 F0203 PS 2/12 2CDC 062 252 F0203 PS 2/48 2CDC 062 143 F0203 PS 3/12 E 463 2CDC 062 267 F0203 PS 4/58 N 2CDC 062 269 F0203 PS 4/60 2CDC 062 265 F0203 PS 4/12 PS 3/12 FI H 2CDC 062 148 F0203
pro M compact ® No. of rated order details bbn price price w'ght pack. poles current 40 16779 1 piece group 1 pc. unit In A type code order code EAN € kg pc. 0.5 S 201-D 0.5 2CDS 251 001 R0981 52993 8 0.125 10/40
1 S 201-D 1 2CDS 251 001 R0011 52994 5
1.6 S 201-D 1.6 2CDS 251 001 R0971 52995 2
2 S 201-D 2 2CDS 251 001 R0021 52996 9
3 S 201-D 3 2CDS 251 001 R0031 52997 6
4 S 201-D 4 2CDS 251 001 R0041 52998 3
6 S 201-D 6 2CDS 251 001 R0061 52999 0
8 S 201-D 8 2CDS 251 001 R0081 53000 2
10 S 201-D 10 2CDS 251 001 R0101 53001 9
13 S 201-D 13 2CDS 251 001 R0131 53002 6
16 S 201-D 16 2CDS 251 001 R0161 53003 3
20 /L54706S 201-D 20 2CDS 251 001 R0201 53004 0
25 S 201-D 25 2CDS 251 001 R0251 53005 7
32 /L54707S 201-D 32 2CDS 251 001 R0321 53006 4 40 /L54708S 201-D 40 2CDS 251 001 R0401 53007 1
50 S 201-D 50 2CDS 251 001 R0501 55199 1
63 S 201-D 63 2CDS 251 001 R0631 55200 4
0.5 S 202-D 0.5 2CDS 252 001 R0981 53048 4 0.250 5/20
1 S 202-D 1 2CDS 252 001 R0011 53049 1
1.6 S 202-D 1.6 2CDS 252 001 R0971 53050 7
2 S 202-D 2 2CDS 252 001 R0021 53051 4
3 S 202-D 3 2CDS 252 001 R0031 53052 1
4 S 202-D 4 2CDS 252 001 R0041 53053 8
6 S 202-D 6 2CDS 252 001 R0061 53054 5
8 S 202-D 8 2CDS 252 001 R0081 53055 2
10 S 202-D 10 2CDS 252 001 R0101 53058 3
13 S 202-D 13 2CDS 252 001 R0131 53060 6
16 S 202-D 16 2CDS 252 001 R0161 53061 3
20 S 202-D 20 2CDS 252 001 R0201 53063 7
25 S 202-D 25 2CDS 252 001 R0251 53064 4
32 S 202-D 32 2CDS 252 001 R0321 53065 1
40 S 202-D 40 2CDS 252 001 R0401 53066 8
50 S 202-D 50 2CDS 252 001 R0501 55203 5
63 S 202-D 63 2CDS 252 001 R0631 55204 2
0.5 S 203-D 0.5 2CDS 253 001 R0981 53081 1 0.375 3/12
1 S 203-D 1 2CDS 253 001 R0011 53082 8
1.6 S 203-D 1.6 2CDS 253 001 R0971 53083 5
2 S 203-D 2 2CDS 253 001 R0021 53084 2
3 S 203-D 3 2CDS 253 001 R0031 53085 9
4 S 203-D 4 2CDS 253 001 R0041 53086 6
6 S 203-D 6 2CDS 253 001 R0061 53088 0
8 S 203-D 8 2CDS 253 001 R0081 53089 7
10 S 203-D 10 2CDS 253 001 R0101 53090 3
13 S 203-D 13 2CDS 253 001 R0131 53091 0
16 S 203-D 16 2CDS 253 001 R0161 53092 7
20 /L54706S 203-D 20 2CDS 253 001 R0201 53093 4
25 S 203-D 25 2CDS 253 001 R0251 53094 1
32 /L54707S 203-D 32 2CDS 253 001 R0321 53095 8 40 /L54708S 203-D 40 2CDS 253 001 R0401 53096 5
50 S 203-D 50 2CDS 253 001 R0501 55205 9
63 S 203-D 63 2CDS 253 001 R0631 55206 6
0.5 S 204-D 0.5 2CDS 254 001 R0981 53112 2 0.500 2
1 S 204-D 1 2CDS 254 001 R0011 53113 9
1.6 S 204-D 1.6 2CDS 254 001 R0971 53114 6
2 S 204-D 2 2CDS 254 001 R0021 53115 3
3 S 204-D 3 2CDS 254 001 R0031 53116 0
4 S 204-D 4 2CDS 254 001 R0041 53117 7
6 S 204-D 6 2CDS 254 001 R0061 53118 4
8 S 204-D 8 2CDS 254 001 R0081 53119 1
10 S 204-D 10 2CDS 254 001 R0101 53120 7
13 S 204-D 13 2CDS 254 001 R0131 53121 4
16 S 204-D 16 2CDS 254 001 R0161 53122 1
20 S 204-D 20 2CDS 254 001 R0201 53123 8
25 S 204-D 25 2CDS 254 001 R0251 53129 0
32 S 204-D 32 2CDS 254 001 R0321 53130 6
40 S 204-D 40 2CDS 254 001 R0401 53131 3
50 S 204-D 50 2CDS 254 001 R0501 55209 7
63 S 204-D 63 2CDS 254 001 R0631 55210 3
D SK 018 B 01 Selection table Miniature circuit-breakers S 200 series S 200-D SK 019 B 01SK 020 B 019SK 030 B 01 /L54706suitable for flow-type heaters 12 kW /L54708suitable for flow-type heaters 21, 24 and 27 kW /L54707suitable for flow-type heaters 18 kW /L54709UBmax 125 V ... with 2 poles connected in series UBmax
440 V /L50513
60 V ... UBmax 125 V ... /L54709 UBmax 125 V ... /L54709 6000
pro M compact ® B Selection table No. of rated order details bbn price price w'ght pack. poles current 40 16779 1 piece group 1 pc. unit In A type code order code EAN € kg pc. 6 S 201 M-B 6 2CDS 271 001 R0065 54942 4 0.125 10/40
10 S 201 M-B 10 2CDS 271 001 R0105 54943 1
13 S 201 M-B 13 2CDS 271 001 R0135 54944 8
16 S 201 M-B 16 2CDS 271 001 R0165 54945 5
20 /L54706S 201 M-B 20 2CDS 271 001 R0205 54946 2
25 S 201 M-B 25 2CDS 271 001 R0255 54947 9
32 /L54707S 201 M-B 32 2CDS 271 001 R0325 54948 6 40 /L54708S 201 M-B 40 2CDS 271 001 R0405 54949 3
50 S 201 M-B 50 2CDS 271 001 R0505 54381 1
63 S 201 M-B 63 2CDS 271 001 R0635 54382 8
6 S 202 M-B 6 2CDS 272 001 R0065 54958 5 0.250 5/20
10 S 202 M-B 10 2CDS 272 001 R0105 54959 2
13 S 202 M-B 13 2CDS 272 001 R0135 54960 8
16 S 202 M-B 16 2CDS 272 001 R0165 54961 5
20 S 202 M-B 20 2CDS 272 001 R0205 54962 2
25 S 202 M-B 25 2CDS 272 001 R0255 54963 9
32 S 202 M-B 32 2CDS 272 001 R0325 54964 6
40 S 202 M-B 40 2CDS 272 001 R0405 54965 3
50 S 202 M-B 50 2CDS 272 001 R0505 54385 9
63 S 202 M-B 63 2CDS 272 001 R0635 54386 6
6 S 203 M-B 6 2CDS 273 001 R0065 54966 0 0.375 3/12
10 S 203 M-B 10 2CDS 273 001 R0105 54967 7
13 S 203 M-B 13 2CDS 273 001 R0135 54968 4
16 S 203 M-B 16 2CDS 273 001 R0165 54969 1
20 /L54706S 203 M-B 20 2CDS 273 001 R0205 54970 7
25 S 203 M-B 25 2CDS 273 001 R0255 54971 4
32 /L54707S 203 M-B 32 2CDS 273 001 R0325 54972 1 40 /L54708S 203 M-B 40 2CDS 273 001 R0405 54973 8
50 S 203 M-B 50 2CDS 273 001 R0505 54387 3
63 S 203 M-B 63 2CDS 273 001 R0635 54388 0
6 S 204 M-B 6 2CDS 274 001 R0065 54982 0 0.500 2
10 S 204 M-B 10 2CDS 274 001 R0105 54983 7
13 S 204 M-B 13 2CDS 274 001 R0135 54984 4
16 S 204 M-B 16 2CDS 274 001 R0165 54985 1
20 S 204 M-B 20 2CDS 274 001 R0205 54986 8
25 S 204 M-B 25 2CDS 274 001 R0255 54987 5
32 S 204 M-B 32 2CDS 274 001 R0325 54988 2
40 S 204 M-B 40 2CDS 274 001 R0405 54989 9
50 S 204 M-B 50 2CDS 274 001 R0505 54391 0
63 S 204 M-B 63 2CDS 274 001 R0635 54392 7
Miniature circuit-breakers S 200 series M 10000 S 200 M-B SK 032 B 02 UBmax 60 V ... UBmax 125 V ... /L54709 UBmax 125 V ... /L54709 UBmax /L54706suitable for flow-type heaters 12 kW /L54708suitable for flow-type heaters 21, 24 and 27 kW /L54707suitable for flow-type heaters 18 kW /L54709UBmax 125 V ... with 2 poles connected in series
pro M compact ® No. of rated order details bbn price price w'ght pack. poles current 40 16779 1 piece group 1 pc. unit In A type code order code EAN € kg pc. With disconnecting neutral NA 6 S 201 M-B 6 NA 2CDS 271 103 R0065 54950 9 0.250 50/40
10 S 201 M-B 10 NA 2CDS 271 103 R0105 54951 6
13 S 201 M-B 13 NA 2CDS 271 103 R0135 54952 3
16 S 201 M-B 16 NA 2CDS 271 103 R0165 54953 0
20 /L54706S 201 M-B 20 NA 2CDS 271 103 R0205 54954 7
25 S 201 M-B 25 NA 2CDS 271 103 R0255 54955 4
32 /L54707S 201 M-B 32 NA 2CDS 271 103 R0325 54956 1 40 /L54708S 201 M-B 40 NA 2CDS 271 103 R0405 54957 8
50 S 201 M-B 50 NA 2CDS 271 103 R0505 54383 5
63 S 201 M-B 63 NA 2CDS 271 103 R0635 54384 2
6 S 203 M-B 6 NA 2CDS 273 103 R0065 54974 5 0.500 2/20
10 S 203 M-B 10 NA 2CDS 273 103 R0105 54975 2
13 S 203 M-B 13 NA 2CDS 273 103 R0135 54976 9
16 S 203 M-B 16 NA 2CDS 273 103 R0165 54977 6
20 /L54706S 203 M-B 20 NA 2CDS 273 103 R0205 54978 3
25 S 203 M-B 25 NA 2CDS 273 103 R0255 54979 0
32 /L54707S 203 M-B 32 NA 2CDS 273 103 R0325 54980 6 40 /L54708S 203 M-B 40 NA 2CDS 273 103 R0405 54981 3
50 S 203 M-B 50 NA 2CDS 273 103 R0505 54389 7
63 S 203 M-B 63 NA 2CDS 273 103 R0635 54390 3 0.580 Miniature circuit-breakers S 200 series M B Selection table NA NA S 200 M-B SK 032 B 02 UBmax 60 V ... UBmax /L54706suitable for flow-type heaters 12 kW /L54708suitable for flow-type heaters 21, 24 and 27 kW /L54707suitable for flow-type heaters 18 kW 10000
pro M compact ® No. of rated order details bbn price price w'ght pack. poles current 40 16779 1 piece group 1 pc. unit In A type code order code EAN € kg pc. 0.5 S 201 M-C 0.5 2CDS 271 001 R0984 54990 5 0.125 10/40
1 S 201 M-C 1 2CDS 271 001 R0014 54992 9
1.6 S 201 M-C 1.6 2CDS 271 001 R0974 54991 2
2 S 201 M-C 2 2CDS 271 001 R0024 54993 6
3 S 201 M-C 3 2CDS 271 001 R0034 54994 3
4 S 201 M-C 4 2CDS 271 001 R0044 54995 0
6 S 201 M-C 6 2CDS 271 001 R0064 54996 7
8 S 201 M-C 8 2CDS 271 001 R0084 54997 4
10 S 201 M-C 10 2CDS 271 001 R0104 54998 1
13 S 201 M-C 13 2CDS 271 001 R0134 54999 8
16 S 201 M-C 16 2CDS 271 001 R0164 55000 0
20 /L54706S 201 M-C 20 2CDS 271 001 R0204 55001 7
25 S 201 M-C 25 2CDS 271 001 R0254 55002 4
32 /L54707S 201 M-C 32 2CDS 271 001 R0324 55003 1 40 /L54708S 201 M-C 40 2CDS 271 001 R0404 55004 8
50 S 201 M-C 50 2CDS 271 001 R0504 54393 4
63 S 201 M-C 63 2CDS 271 001 R0634 54394 1
0.5 S 202 M-C 0.5 2CDS 272 001 R0984 55020 8 0.250 5/20
1 S 202 M-C 1 2CDS 272 001 R0014 55022 2
1.6 S 202 M-C 1.6 2CDS 272 001 R0974 55021 5
2 S 202 M-C 2 2CDS 272 001 R0024 55023 9
3 S 202 M-C 3 2CDS 272 001 R0034 55024 6
4 S 202 M-C 4 2CDS 272 001 R0044 55025 3
6 S 202 M-C 6 2CDS 272 001 R0064 55026 0
8 S 202 M-C 8 2CDS 272 001 R0084 55027 7
10 S 202 M-C 10 2CDS 272 001 R0104 55028 4
13 S 202 M-C 13 2CDS 272 001 R0134 55029 1
16 S 202 M-C 16 2CDS 272 001 R0164 55030 7
20 S 202 M-C 20 2CDS 272 001 R0204 55031 4
25 S 202 M-C 25 2CDS 272 001 R0254 55032 1
32 S 202 M-C 32 2CDS 272 001 R0324 55033 8
40 S 202 M-C 40 2CDS 272 001 R0404 55034 5
50 S 202 M-C 50 2CDS 272 001 R0504 54397 2
63 S 202 M-C 63 2CDS 272 001 R0634 54398 9
0.5 S 203 M-C 0.5 2CDS 273 001 R0984 55035 2 0.375 3/12
1 S 203 M-C 1 2CDS 273 001 R0014 55037 6
1.6 S 203 M-C 1.6 2CDS 273 001 R0974 55036 9
2 S 203 M-C 2 2CDS 273 001 R0024 55038 3
3 S 203 M-C 3 2CDS 273 001 R0034 55039 0
4 S 203 M-C 4 2CDS 273 001 R0044 55040 6
6 S 203 M-C 6 2CDS 273 001 R0064 55041 3
8 S 203 M-C 8 2CDS 273 001 R0084 55042 0
10 S 203 M-C 10 2CDS 273 001 R0104 55043 7
13 S 203 M-C 13 2CDS 273 001 R0134 55044 4
16 S 203 M-C 16 2CDS 273 001 R0164 55045 1
20 /L54706S 203 M-C 20 2CDS 273 001 R0204 55046 8
25 S 203 M-C 25 2CDS 273 001 R0254 55047 5
32 /L54707S 203 M-C 32 2CDS 273 001 R0324 55048 2 40 /L54708S 203 M-C 40 2CDS 273 001 R0404 55049 9
50 S 203 M-C 50 2CDS 273 001 R0504 54399 6
63 S 203 M-C 63 2CDS 273 001 R0634 54400 9
0.5 S 204 M-C 0.5 2CDS 274 001 R0984 55065 9 0.500 2
1 S 204 M-C 1 2CDS 274 001 R0014 55067 3
1.6 S 204 M-C 1.6 2CDS 274 001 R0974 55066 6
2 S 204 M-C 2 2CDS 274 001 R0024 55068 0
3 S 204 M-C 3 2CDS 274 001 R0034 55069 7
4 S 204 M-C 4 2CDS 274 001 R0044 55070 3
6 S 204 M-C 6 2CDS 274 001 R0064 55071 0
8 S 204 M-C 8 2CDS 274 001 R0084 55072 7
10 S 204 M-C 10 2CDS 274 001 R0104 55073 4
13 S 204 M-C 13 2CDS 274 001 R0134 55074 1
16 S 204 M-C 16 2CDS 274 001 R0164 55075 8
20 S 204 M-C 20 2CDS 274 001 R0204 55076 5
25 S 204 M-C 25 2CDS 274 001 R0254 55077 2
32 S 204 M-C 32 2CDS 274 001 R0324 55078 9
40 S 204 M-C 40 2CDS 274 001 R0404 55079 6
50 S 204 M-C 50 2CDS 274 001 R0504 54403 0
63 S 204 M-C 63 2CDS 274 001 R0634 54404 7
C Selection table Miniature circuit-breakers S 200 series M S 200 M-C SK 045 B 02 SK 044 B 02 SK 046 B 02 /L54706suitable for flow-type heaters 12 kW /L54708suitable for flow-type heaters 21, 24 and 27 kW /L54707suitable for flow-type heaters 18 kW /L54709UBmax 125 V ... with 2 poles connected in series UBmax 60 V ... UBmax 125 V ... /L54709 UBmax 125 V ... /L54709 UBmax
pro M compact ® No. of rated order details bbn price price w'ght pack. poles current 40 16779 1 piece group 1 pc. unit In A type code order code EAN € kg pc. With disconnecting neutral NA 0.5 S 201 M-C 0.5 NA 2CDS 271 103 R0984 55005 5 0.250 5
1 S 201 M-C 1 NA 2CDS 271 103 R0014 55007 9
1.6 S 201 M-C 1.6 NA 2CDS 271 103 R0974 55006 2
2 S 201 M-C 2 NA 2CDS 271 103 R0024 55008 6
3 S 201 M-C 3 NA 2CDS 271 103 R0034 55009 3
4 S 201 M-C 4 NA 2CDS 271 103 R0044 55010 9
6 S 201 M-C 6 NA 2CDS 271 103 R0064 55011 6
8 S 201 M-C 8 NA 2CDS 271 103 R0084 55012 3
10 S 201 M-C 10 NA 2CDS 271 103 R0104 55013 0
13 S 201 M-C 13 NA 2CDS 271 103 R0134 55014 7
16 S 201 M-C 16 NA 2CDS 271 103 R0164 55015 4
20 /L54706S 201 M-C 20 NA 2CDS 271 103 R0204 55016 1
25 S 201 M-C 25 NA 2CDS 271 103 R0254 55017 8
32 /L54707S 201 M-C 32 NA 2CDS 271 103 R0324 55018 5 40 /L54708S 201 M-C 40 NA 2CDS 271 103 R0404 55019 2 50 S 201 M-C 50 NA 2CDS 271 103 R0504 54395 8 0.290
63 S 201 M-C 63 NA 2CDS 271 103 R0634 54396 5
0.5 S 203 M-C 0.5 NA 2CDS 273 103 R0984 55051 2 0.500 2
1 S 203 M-C 1 NA 2CDS 273 103 R0014 55052 9
1.6 S 203 M-C 1.6 NA 2CDS 273 103 R0974 55050 5
2 S 203 M-C 2 NA 2CDS 273 103 R0024 55053 6
3 S 203 M-C 3 NA 2CDS 273 103 R0034 55054 3
4 S 203 M-C 4 NA 2CDS 273 103 R0044 55055 0
6 S 203 M-C 6 NA 2CDS 273 103 R0064 55056 7
8 S 203 M-C 8 NA 2CDS 273 103 R0084 55057 4
10 S 203 M-C 10 NA 2CDS 273 103 R0104 55058 1
13 S 203 M-C 13 NA 2CDS 273 103 R0134 55059 8
16 S 203 M-C 16 NA 2CDS 273 103 R0164 55060 4
20 /L54706S 203 M-C 20 NA 2CDS 273 103 R0204 55061 1
25 S 203 M-C 25 NA 2CDS 273 103 R0254 55062 8
32 /L54707S 203 M-C 32 NA 2CDS 273 103 R0324 55063 5 40 /L54708S 203 M-C 40 NA 2CDS 273 103 R0404 55064 2 50 S 203 M-C 50 NA 2CDS 273 103 R0504 54401 6 0.580
63 S 203 M-C 63 NA 2CDS 273 103 R0634 54402 3
Miniature circuit-breakers S 200 series M C Selection table NA NA S 200 M-C SK 032 B 02 UBmax 60 V ... UBmax /L54706suitable for flow-type heaters 12 kW /L54708suitable for flow-type heaters 21, 24 and 27 kW /L54707suitable for flow-type heaters 18 kW 10000 Attention: S 200 M, B and C with integrated auxiliary contact on request. Description order details bbn price price w'ght pack. 40 16779 1 piece group 1 pc. unit type code order code EAN € kg pc. Signalcontact/Auxiliary switch (universal) Retrofittable to the right side of MCB’s, RCB’s and Shunt trip’s 1 change over S 2C-S/H6R 2CDS 200 922 R0001 56381 9 0.04 1 Auxiliary contact Retrofittable to the right side of MCB’s 1 change over S 2C-H6R 2CDS 200 912 R0001 56382 6 0.04 1 Shunt trip AC/DC 12 … 60 V S 2C-A1 2CDS 200 909 R0001 57099 2 0.15 1 AC 110 … 415 V und DC 110 … 250 V S 2C-A2 2CDS 200 909 R0002 57100 5 Undervoltage release (in preparation) DC 12 V S 2C-UA 12 2CDS 200 911 R0001 57101 2 0.09 1 AC/DC 24 V S 2C-UA 24 2CDS 200 911 R0002 57102 9 AC/DC 48 V S 2C-UA 48 2CDS 200 911 R0003 57103 6 AC/DC 110 V S 2C-UA 110 2CDS 200 911 R0004 57104 3 AC/DC 220 V S 2C-UA 220 2CDS 200 911 R0005 57105 0 AC 380 V S 2C-UA 380 2CDS 200 911 R0006 57106 7 System pro M compact ® Supplementary devices MCB’s Range S 200/S 200 M SK 011 B 02 SK 209 B 02 SC-S/H6R S 2C-A
pro M compact ® Areas of application DIN VDE… Required F 200 F 200 F 172 F220 sensitivity F 660 F 690 FS 200 F 804 InmA F 670 In apartments /L5087232 A Socket-outlets up to 20 A Outdoor lightning installations 0100 – 739 10…30 0100 – 470 10…30 0100 – 714 10…30 F 200 F 172 F 660 FS 200 F 670 Fire protection in high-risk or high-danger areas 0100 – 482 10 u. 30 F 200 F 200 F 172 F 660 F 690 FS 200 F 670 Rooms with bath tub or shower Swimming pools 0100 – 701 10…30 0100 – 702 10…30 F 200 F 172 F 660 FS 200 F 670 Construction sites Socket-outlet circuits up to 32 A and other socket-outlet circuits 0100 – 704 10…30 BG F&E /L50872300…500 /L54706 F 200 F 200 F 172 F 220 F 660 F 690 FS 200 F 804 F 670 Type B Agricultural and horticultural properties, General socket-outlet circuits /L50872300…500 /L54706 0100 – 705 10…30 F 200 F 200 F 172 F 660 F 690 FS 200 F 670 F 270 P 270 Feed points for caravans Camp sites 0100 – 708 10…30 F 200 F 172 F 660 FS 200 F 670 Berths Socket-outlets 0100 – 721 10…30 F 200 F 172 F 660 FS 200 F 670 Temporary buildings, carny carriages and caravans, Feed points 0100 – 722 30 and 300 Medical rooms Group 1 Group 2 a Group 2 b at I n /L50872 32 A 0100 – 710 10…30 10…30 /L50872 300 F 200 F 200 F 172 F 220 F 660 F 690 FS 200 F 804 F 670 Type B Equipment of power installations with electronic items I /L50876b type A, test for type B 0160 DIN EN /L50872 4kVA 10…30 50 178 > 4kVA 300 Photovoltaics 0100 – 712 E /L50872 30 EnBW F 220 F 802 Type B /L54706 /L54706 /L54706 /L54706 /L54706 Operating areas subject to fire hazards… VdS 2033: 2002 – 02 /L50872 /L50872 /L50872 /L50872 /L50872 300 mA S F 200 F 200 F 172 F 660 F 690 FS 200 F 670 F 200 F 200 F 172 F 220 F 660 F 690 FS 200 F 804 F 670 Type B RCCBs and RCBOs and their fields of applications
pro M compact ® ABB STOTZ-KONTAKT GmbH P.O. Box 10 16 80, 69006 Heidelberg, Germany Eppelheimer Straße 82, 69123 Heidelberg, Germany Telephone: +49 (0) 62 21 701- 0 Fax: +49 (0) 62 21 701-723 www.abb.de/stotz-kontakt Pub. No. 2CDC 002 001 D0203 Approvals and certifications by classification societies MCB’s and RCB’s Type Approvals Ship classification associatons Sign of comformity BD 6 /L54706/L54706 Code SEV DEMKO NEMKO SEMKO EL. CSA KEMA ÖVE CEBEC UTE VDE BV GL LRS DNV Inspect. Valid for CH DK N S SF CDN USA NL A B F D F D GB N 277/480 V~ S 200, B, C 1 – 4 pole /L52408/L52408/L52408/L52408/L52408 /L50237/L52408/L52408/L52408/L52408/L50237/L52408/L52408/L52408/L52408 S 200 M 1 – 4 pole /L52408/L52408/L52408/L52408/L50237 /L52408/L52408/L52408/L52408/L50237/L52408/L52408/L52408/L52408 F 200 - 16/25/ 40 – 0.01/ 0.03/0.1/ /L50237 0.3/0.5 F 200 A, AC, S 2/4 pole /L50237/L50237/L50237/L50237/L50237 /L52408/L50237/L52408/L52408/L5023716…63 A 0.01…0.5 A FS 201 B 6…40/0,03 A /L50237/L50237/L50237/L50237/L50237 /L52408/L50237/L52408/L52408/L50237 C 16/0,03 /L50237approved /L52408submitted for aproval/planed to be submitted /L50773Approved variants on request /L50263Approval not required /L54706Back-up protection usually required. For details contact your importer and/or inspector.