RZUS-U9 MSYSTEM | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 10

Technical content

MODEL: RZUS-U9 RZUS-U9 SPECIFICATIONS ES-7622 Rev.10 Page 1/10 http://www.m-system.co.jp/ PC Recorders RZUS Series PC RECORDER (universal input, 12 points; isolated; bus-powered USB) Functions & Features

  • Industrial recorder on PC
  • 12-point universal inputs
  • Channel-to-channel isolation
  • Trigger input and alarm contact output
  • Filtering protection against 50/60 Hz noise
  • USB and RS-485 interface
  • No need of dedicated power source mm (inch) 175 (6.89) 128 (5.04) 56.5 (2.22) MODEL: RZUS-U9T/MSR

ORDERING INFORMATION

  • Code number: RZUS-U9T/MSR FIELD TERMINAL TYPE T: M3 screw terminals OPTIONS PC Recorder Software Package (must be specified) /MSR: With

RELATED PRODUCTS

  • Resistor module (model: REM3-250) Though the REM3 is designed to be mounted directly to this model, we recommend that it be attached to a separate terminal board in order to eliminate its heat conduction to affect the cold junction compensation and the overall measuring accuracy of this model.
  • RZXS configurator software (model: RZMSCFG) Downloadable at M-System’s web site. A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types. PACKAGE INCLUDES...
  • PC Recorder Software CD
  • USB cable (1 m or 3.3 ft) GENERAL SPECIFICATIONS Connection USB: USB type B connector, female RS-485: Euro type connector terminal (Applicable wire size: 0.2 – 2.5 mm2 (AWG24 – 12), stripped length 7 mm) I/O: M3 screw terminals (torque: 0.6N·m) Grounding: M4 screw terminal (torque: 1.2N·m) PC Configurator: Miniature jack, RS-232-C level Screw terminal: Nickel-plated steel Housing material: Flame-resistant resin (gray) Isolation: Input 1 to input 2 to input 3 to input 4 to input 5 to input 6 to input 7 to input 8 to input 9 to input 10 to input 11 to input 12 to trigger input to alarm output to USB or RS- 485 or configurator jack to ground Zero/span adjustments: Available with PC Configurator Software for all types of inputs. Burnout for T/C and RTD input: Upscale, Downscale or No burnout selectable Select ‘No Burnout’ to minimize the measuring errors caused by the sensor/wire resistance and the burnout sensing current. With RTD input, the signal may go transiently to the opposite direction from the burnout setting. With DC/potentiometer input, the burnout setting is ignored and the burnout sensing current is cancelled. In order to specify burnout actions to individual channels, use PC Configurator Software. Wire resistance compensation for RTD input: Field calibration for 3-wire (or 2-wire) RTD available with PC Configurator Software. Cold junction compensation (CJC) for T/C input: CJC can be enabled or disabled. Reference temperature is measured at the internal sensor by factory setting. In order to specify cold junction compensation to individual channels, use PC Configurator Software. Temperature measured at another channel of this model can be specified as the reference point by using PC Configurator Software. This is beneficial to reduce compensation wires’ cost when there are many temperature points in remote locations. Install a relaying terminal board near the sensors and use ordinary copper wires between the board and this model, and assign one channel to measure temperature at the terminal board as the reference. Operating mode setting: Rotary switch; burnout type, cold junction compensation, line noise frequency, software filter, A/D conversion mode, service channel numbers setting

MODEL: RZUS-U9 RZUS-U9 SPECIFICATIONS ES-7622 Rev.10 Page 2/10 http://www.m-system.co.jp/ available Line noise filter: NMNR ratio to the line frequency and its harmonic contents can be optimized. Factory set to 50/60 Hz mode for use with both frequencies. Select either frequency for the most effective result. Programmable first order lag filter: Time constant selectable with PC Configurator Software. The use of this filter is disabled at the factory shipment. With the large time constant setting, measured signals during the warm-up immediately after the power is turned on may affect the signals for a long time period. A/D conversion mode: Fast, Medium or Slow selectable with PC Configurator Software. With Slow setting, data fluctuations are minimized with limited sampling time (speed). With Fast setting, sampling time (speed) can be high though data fluctuations increase. Node address setting: Rotary switch; 1 – F (15 nodes) Indicator LEDs: Five (5) LEDs indicate the module’s operating conditions. Service channel numbers: 12 channels (ch.1 thr. 12) or 6 channels (ch.1 thr. 6) are selectable with PC Configurator Software. Factory set to 12 channels. COMMUNICATION Baud rate: 38.4 kbps Communication: Half-duplex, asynchronous, no procedure Protocol: Modbus RTU ■ RS-485 Standard: Conforms to TIA/EIA-485-A Transmission distance: 10 meters max. Transmission media: Shielded twisted-pair cable (CPEV-S 0.9 dia.) ■ USB Standard: Full Speed USB 2.0 (usable with USB 1.1 port) Transmission distance: 5 meters max. Transfer mode: Bulk transfer Power supply: Bus powered (high power device) INPUT SPECIFICATIONS ■ DC Voltage Input resistance: 900 kΩ min. Excluding the case in which, with range setting other than ±12 V, ±6 V or ±3 V, a voltage exceeding ±1.3 V is applied. Input range: ±60 mV, ±125 mV, ±250 mV, ±500 mV, ■ Thermocouple Input resistance: 900 kΩ minimum Input type: (PR), K (CA), E (CRC), J (IC), T (CC), B (RH), R, S, C (WRe 5-26), N, U, L, P (Platinel II) Burnout sensing Upscale: ≤ 130 nA Downscale: ≤ 220 nA No burnout: ≤ 10 nA Burnout sensing time K, E, J, N, L, P (upscale): ≤ 20 seconds Others: ≤ 10 seconds ■ RTD (3-wire) Excitation: 1.25 V / (1.25 kΩ + load resistance across the terminals A – C); 1.00 mA with 10 Ω across A – C; 0.55 mA with 1000 Ω across A – C Allowable leadwire resistance: 20 Ω per wire Input type: Pt 100 (JIS ’89), Pt 100 (JIS ’97, IEC), Pt 200, Pt 300, Pt 400, Pt 500, Pt 1000, Pt 50Ω (JIS ’81), JPt 100 (JIS ’89), Ni 100, Ni 120, Ni 508.4Ω, Ni-Fe 604, Cu 10 @ 25°C Burnout sensing Upscale or Downscale: ≤ 130 nA No burnout: ≤ 10 nA Burnout sensing time: ≤ 10 seconds ■ Potentiometer Excitation: 1.25 V / (1.31 kΩ + load resistance across the terminals A – C); 0.83 mA with 200 Ω across A – C; 0.20 mA with 5 kΩ across A – C Allowable leadwire resistance: 20 Ω per wire Total resistance: See Potentiometer Input Table of the "Input type, Range, Accuracy & Temperature Coefficient" section. ■ Trigger Input: Dry contact; detected ON at ≤ 0.8 V Voltage across the terminals: ≤ 2.5 V Current across the terminals: ≤ 4.0 mA ■ SAMPLING TIME LINE NOISE SERVICE A/D CONVERSION (Sec.) FILTER FREQ. CH. NO. MEDIUM SLOW FAST 50 Hz 12 ch 0.68 0.94 0.43 6 ch 0.38 0.53 0.26 50/60 Hz 12 ch 0.63 0.87 0.40 6 ch 0.35 0.49 0.24 60 Hz 12 ch 0.59 0.80 0.38 6 ch 0.33 0.45 0.22 Multplied by two (2) for RTD and potentiometer input. OUTPUT SPECIFICATIONS ■ Alarm Output: Photo MOSFET relay (no polarity); ≤ 50 Ω at ON, ≥ 1 MΩ at OFF; OFF when not powered Peak load voltage: 50 V max. Continuous load current: 50 mA max. Peak load current: 300 mA max. (≤ 0.1 sec.)

MODEL: RZUS-U9 RZUS-U9 SPECIFICATIONS ES-7622 Rev.10 Page 3/10 http://www.m-system.co.jp/ INSTALLATION Power input Normal operating mode: Approx. 0.2 A Suspend mode: ≤ 0.5 mA The USB high power port must be capable of 300 mA power consumption. When connecting the RZUS to a USB hub, choose the self-powered configuration. Laptop PC’s supply current may be limited by its battery power. Confirm the USB port’s current capacity in advance. Operating temperature: 0 to 60°C (32 to 140°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 520 g (1.15 lb) PERFORMANCE Accuracy: See "Input type, Range, Accuracy & Temperature Coefficient" section. Cold junction compensation error: (°C) ≤ ±[0.6 +|Ambient Temp. – 25|× 0.04] (in stable ambient temperature; e.g. ±1.0°C at 15°C and 35°C) Applicable with balanced terminal temperature. Error will increase by imbalances caused by direct mounting of the REM3 to the terminals. Temp. coefficient: See "Input type, Range, Accuracy & Temperature Coefficient" section. Response time (Assuming the fastest reading on Modbus)

  • DC of ±1000 mV or narrower ranges or T/C: ≤ [Sampling Time + 0.3 sec.] (0 – 90 %)
  • DC of ±3 V or wider ranges: ≤ [Sampling Time + 0.5 sec.] (0 – 90 %)
  • RTD or potentiometer: ≤ [Sampling Time + 0.3 sec.] (0 – 90 %) Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 500 Vpeak @ 1 minute Peak value including both AC and DC (e.g. 354 V AC with 0 V DC). (input 1 to input 2 to input 3 to input 4 to input 5 to input 6 to input 7 to input 8 to input 9 to input 10 to input 11 to input 12 to trigger input to alarm output to USB or RS-485 or configurator jack to ground) Line noise normal mode rejection: ≥ 100 dB Magnitude of the effects of normal mode 50/60 Hz noise, with the most appropriate line noise filter frequency setting. Each input circuit has a CR filter of sufficient large time constant so that there will be little effect of line noise such as 500 mV AC superposed on a thermocouple or ±60 mV input. Common mode noise rejection Magnitude of the effects of voltages applied across the terminal C and the ground terminal when there is no potential difference among all the C terminals. DC: N/A AC, ±3 V, ±6 V, ±12 V: Approx. 86 dB AC, other ranges: Approx. 120 dB Common mode noise rejection between channels: Magnitude of the effects of DC/50/60 Hz voltages applied across the terminals C of the present and the last scanned channels. (Data are scanned from ch 1 to ch 12 in turn and back to ch 1 again.) DC, ±3 V, ±6 V, ±12 V: Approx. 100 dB DC, other ranges: Approx. 120 dB AC, ±3 V, ±6 V, ±12 V: Approx. 86 dB AC, other ranges: Approx. 106 dB High common mode noise between channels may compromise the accuracies in low millivolts measuring including thermocouple input. We recommend that C terminals of each channel be cross- wired and then connected to the ground terminal to ensure the measurement of the highest accuracy. If such configuration is not possible, take special consideration to minimize the channel-to-channel common mode noise and the potential against the ground terminal. The potential of the open terminal C against the ground terminal equals to that of the last scanned channel. If ch 2 and ch 3 are not connected, the accuracy of ch 4 measurement is affected by potential difference between the C terminals of ch 1 and ch 4. STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive EN 50581

MODEL: RZUS-U9 RZUS-U9 SPECIFICATIONS ES-7622 Rev.10 Page 4/10 http://www.m-system.co.jp/ INPUT TYPE, RANGE, ACCURACY & TEMPERATURE COEFFICIENT Applicable with the common mode voltage 0 V between C terminals of all channels and between C terminal of each channel and the ground terminal. The effects by the following factors are excluded: Fast A/D conversion mode; temperature drift with the REM3 directly mounted to the I/O terminals; wire resistance; burnout sensing current with upscale/downscale settings. DC Voltage Input INPUT RANGE ACCURACY (mV) ±60mV ±0.05 ±125mV ±0.07 ±250mV ±0.13 ±500mV ±0.25 ±1000mV ±0.5 ±3V ±2.5 ±6V ±5 ±12V ±10 Thermocouple Input, Celsius T/C USABLE CONFORMANCE ACCURACY RANGE (°C) RANGE (°C) (°C) (PR) 0 to 1770 400 to 1770 ±4.6 K (CA) -270 to +1370 0 to 1370 ±1.5 E (CRC) -270 to +1000 0 to 1000 ±0.8 J (IC) -210 to +1200 0 to 1200 ±1.0 T (CC) -270 to +400 0 to 400 ±1.3 B (RH) 100 to 1820 700 to 1820 ±7.2 R -50 to +1760 400 to 1760 ±4.8 S -50 to +1760 400 to 1760 ±5.3 C (WRe 5-26) 0 to 2320 0 to 2320 ±4.9 N -270 to +1300 0 to 1300 ±1.9 U -200 to +600 0 to 600 ±1.3 L -200 to +900 0 to 900 ±1.0 P (Platinel II) 0 to 1395 0 to 1395 ±1.7 Note 1: Measuring accuracy at 50µV emf. Note 2: CJC error is not included. Thermocouple Input, Fahrenheit T/C USABLE CONFORMANCE ACCURACY RANGE (°F) RANGE (°F) (°F) (PR) 32 to 3218 752 to 3218 ±8.28 K (CA) -454 to +2498 32 to 2498 ±2.7 E (CRC) -454 to +1832 32 to 1832 ±1.44 J (IC) -346 to +2192 32 to 2192 ±1.8 T (CC) -454 to +752 32 to 752 ±2.34 B (RH) 212 to 3308 1292 to 3308 ±13.0 R -58 to +3200 752 to 3200 ±8.64 S -58 to +3200 752 to 3200 ±9.54 C (WRe 5-26) 32 to 4208 32 to 4208 ±8.82 N -454 to +2372 32 to 2372 ±3.42 U -328 to +1112 32 to 1112 ±2.34 L -328 to +1652 32 to 1652 ±1.8 P (Platinel II) 32 to 2543 32 to 2543 ±3.06

MODEL: RZUS-U9 RZUS-U9 SPECIFICATIONS ES-7622 Rev.10 Page 5/10 http://www.m-system.co.jp/ RTD Input, Celsius RTD USABLE RANGE (°C) ACCURACY at < 0°C at ≥ 0°C Pt 100 (JIS ’97, IEC) -200 to +850 ±0.4°C ±[0.4°C + Measured Value × 0.1%] (±1.3°C at 850°C) Pt 200 -200 to +850 ±0.3°C ±[0.3°C + Measured Value × 0.17%] (±1.8°C at 850°C) Pt 300 -200 to +850 ±[0.4°C + Measured Value × 0.08%] ±[0.4°C + Measured Value × 0.21%] (±2.2°C at 850°C) Pt 400 -200 to +850 ±[0.4°C + Measured Value × 0.11%] ±[0.4°C + Measured Value × 0.21%] (±2.2°C at 850°C) Pt 500 -200 to +850 ±[0.4°C + Measured Value × 0.13%] ±[0.4°C + Measured Value × 0.26%] (±2.6°C at 850°C) Pt 1000 -200 to +850 ±[0.4°C + Measured Value × 0.15%] ±[0.4°C + Measured Value × 0.4%] (±3.8°C at 850°C) Pt 100 (JIS ’89) -200 to +660 ±0.4°C ±[0.4°C + Measured Value × 0.1%] (±1.1°C at 650°C) JPt 100 (JIS ’89) -200 to +510 ±0.4°C ±[0.4°C + Measured Value × 0.1%] (±0.91°C at 510°C) Pt 50Ω (JIS ’81) -200 to +649 ±0.5°C at < 160°C, ±[0.4°C + Measured Val ue × 0.1%] at ≥ 160°C (±1.049°C at 649°C) Ni 100 -80 to +260 ±0.3°C Ni 120 -80 to +260 ±0.3°C Cu 10 @ 25°C -50 to +250 ±1.2°C (only after the field calibrations) RTD Input, Fahrenheit RTD USABLE RANGE (°F) ACCURACY at < 32°F at ≥ 32°F Pt 100 (JIS ’97, IEC) -328 to +1562 ±0.72°F ±[0.4°C + Measured Value × 0.1%] (±1.3°C at 850°C) Pt 200 -328 to +1562 ±0.54°F ±[0.3°C + Measured Value × 0.17%] (±1.8°C at 850°C) Pt 300 -328 to +1562 ±[0.72°F + Measured Value × 0.08%] ±[0.4°C + Measured Value × 0.21%] (±2.2°C at 850°C) Pt 400 -328 to +1562 ±[0.72°F + Measured Value × 0.11%] ±[0.4°C + Measured Value × 0.21%] (±2.2°C at 850°C) Pt 500 -328 to +1562 ±[0.72°F + Measured Value × 0.13%] ±[0.4°C + Measured Value × 0.26%] (±2.6°C at 850°C) Pt 1000 -328 to +1562 ±[0.72°F + Measured Value × 0.15%] ±[0.4°C + Measured Value × 0.4%] (±3.8°C at 850°C) Pt 100 (JIS ’89) -328 to +1220 ±0.72°F ±[0.4°C + Measured Value × 0.1%] (±1.1°C at 650°C) JPt 100 (JIS ’89) -328 to +950 ±0.72°F ±[0.4°C + Measured Value × 0.1%] (±0.91°C at 510°C) Pt 50Ω (JIS ’81) -328 to +1200 ±0.9°F at < 320°F, ±[0.72°F + Measured Value × 0.1%] at ≥ 320°F (±1.888°F at 1200°F) Ni 100 -112 to +500 ±0.54°F Ni 120 -112 to +500 ±0.54°F Cu 10 @ 25°C -58 to +482 ±2.16°F (only after the field calibrations) Note 1: The lower the temperature range, the better the accuracy is for Pt 300 , Pt 400, Pt 500, Pt 1000 and Ni 508.4Ω. ‘Measured Value’ in the equations is not an absolute value. Include the minu s sign when calculating accuracies. Note 2: For Cu 10 @ 25°C, be sure to perform the field calibrations of wire imbalance and zero/span by using the PC Configurat or Software.

MODEL: RZUS-U9 RZUS-U9 SPECIFICATIONS ES-7622 Rev.10 Page 6/10 http://www.m-system.co.jp/ Potentiometer Input TOTAL RESISTANCE ACCURACY Up to 200Ω ±0.12% at 200Ω Up to 500Ω ±0.14% at 500Ω Up to 5kΩ ±0.14% at 1kΩ ±0.10% at 2kΩ or 5kΩ Temperature Coefficient INPUT TYPE TEMPERATURE COEFFICIENT DC Voltage ±[Nominal Input Range × 0.015%]/°C or ±[Nominal Input Range × 0 .008%]/°F (e.g. ±0.018mV/°C with ±60mV range) Thermocouple ±[Accuracy / 3] °C/°C or ±[Accuracy / 3] °F/°F (e.g. ±0.27° C/°C with E thermocouple) RTD at < 0°C or 32°F at ≥ 0°C or 32°F Pt 100 (JIS ’97, IEC) ±0.041°C/°C ±0.041°F/°F ±[0.041°C + Measured Value × 0.026%]/°C ±[0.041°F + Measured Value × 0.026%]/°F Pt 200 ±0.044°C/°C ±0.044°F/°F ±[0.044°C + Measured Value × 0.033%]/°C ±[0.044°F + Measured Value × 0.033%]/°F Pt 300 ±0.047°C/°C ±0.047°F/°F ±[0.047°C + Measured Value × 0.04%]/°C ±[0.047°F + Measured Value × 0.04%]/°F Pt 400 ±0.05°C/°C ±0.05°F/°F ±[0.05°C + Measured Value × 0.052%]/°C ±[0.05°F + Measured Value × 0.052%]/°F Pt 500 ±0.053°C/°C ±0.053°F/°F ±[0.053°C + Measured Value × 0.053%]/°C ±[0.053°F + Measured Value × 0.053%]/°F Pt 1000 ±[0.068°C + Measured Value × 0.025%]/°C ±[0.068°F + Measured Value × 0.025%]/°F ±[0.068°C + Measured Value × 0.087%]/°C ±[0.068°F + Measured Value × 0.087%]/°F Pt 100 (JIS ’89) ±0.041°C/°C ±0.041°F/°F ±[0.041°C + Measured Value × 0.024%]/°C ±[0.041°F + Measured Value × 0.024%]/°F JPt 100 (JIS ’89) ±0.041°C/°C ±0.041°F/°F ±[0.041°C + Measured Value × 0.023%]/°C ±[0.041°F + Measured Value × 0.023%]/°F Pt 50Ω (JIS ’81) ±0.039°C/°C ±0.039°F/°F ±[0.039°C + Measured Value × 0.021%]/°C ±[0.039°F + Measured Value × 0.021%]/°F Ni 100 ±0.028°C/°C ±0.028°F/°F ±[0.028°C + Measured Value × 0.01%]/°C ±[0.028°F + Measured Value × 0.01%]/°F Ni 120 ±0.028°C/°C ±0.028°F/°F ±[0.028°C + Measured Value × 0.01%]/°C ±[0.028°F + Measured Value × 0.01%]/°F ±0.046°F/°F ±[0.046°C + Measured Value × 0.018%]/°C ±[0.046°F + Measured Value × 0.018%]/°F Ni-Fe 604 Potentiometer ±0.005%/°C or ±0.003%/°F PC RECORDER SOFTWARE PC Recorder Software Package (model: MSRPAC-2010) is included with purchases of the RZUS modules. Refer to the MSRPAC-2010 data sheet for the contents of the package and the requirements for the PC to be prepared by the user. The RZUS is usable with the following programs included in the MSRPAC-2010: MSR128, MSR128LS and MSR-128LV. The MSRPAC-2010 CD includes the driver to interface with these programs and the PC Configurator Software via USB. The PC Configurator Software can be connected either via USB or via Special Configurator Cable.

MODEL: RZUS-U9 RZUS-U9 SPECIFICATIONS ES-7622 Rev.10 Page 7/10 http://www.m-system.co.jp/ EXTERNAL VIEW T1 T2 T3 T4 1A 1B 1C 3A 3B 3C 5A 5B 5C 7A 7B 7C 9A 9B 9C 11A 11B ALM ALM –11C 2A 2B 2C 4A 4B 4C 6A 6B 6C 8A 8B 8C 10A 10B 10C 12A 12B 12C TRG TRG RUN Indicator LED COMM Indicator LED ERR Indicator LED TRIG Indicator LED ALM Indicator LED RS-485 Connector Configurator Jack /PEF Address Setting Rotary SW Operating Mode Setting Rotary SW Ground Terminal USB B Connector ■ TOP VIEW ■ REAR VIEW ■ INDICATOR LED RUN : Green LED blinks when the internal microprocessor is operating normally. COMM : Communication LED. Amber LED turns on when the RZUS is receiving normal data query frames from Modbus and sending responses out. ERR : Error LED. Red LED turns on with internal errors and blinks when the RZUS is receiving abnormal data query frames from Modbus. TRG : Trigger LED. Amber LED turns on when the trigger contact input turns on. ALM : Alarm LED. Amber LED turns on when the alarm contact output turns on. ■ USB INTERFACE 2 1 3 4 ID PIN NO. EXPLANATION OF FUNCTION VBUS 1 USB Bus Power D – 2 Differential Signal Line D + 3 Differential Signal Line GND 4 Shield

MODEL: RZUS-U9 RZUS-U9 SPECIFICATIONS ES-7622 Rev.10 Page 8/10 http://www.m-system.co.jp/ CONNECTION DIAGRAM RS-485 Connector USB CONNECTOR GND Term. Resist. Network Interface Shielded Twisted-pair Cable To Other I/O Modules To PC Jumper JACK CONFIGURATOR INPUT 2 INPUT 1 Analog Input Circuit 1 Analog Input Circuit 2 INPUT 4 INPUT 3 Analog Input Circuit 3 Analog Input Circuit 4 INPUT 6 INPUT 5 Analog Input Circuit 5 Analog Input Circuit 6 INPUT 8 INPUT 7 Analog Input Circuit 7 Analog Input Circuit 8 INPUT 10 INPUT 9 10A 10B 10C Analog Input Circuit 9 Analog Input Circuit 10 INPUT 12 11A 11B 11C INPUT 11 12A 12B 12C Analog Input Circuit 11 Analog Input Circuit 12 TRIGGER INPUT ALM ALM ALARM OUTPUT TRG+ TRG– Isolated Alarm Output Isolated Trigger Input Photo MOSFET Multiplexer Floating A/D Converter and Terminal Temperature Sensor Micro Processor Based Controller C B A ext. wire – C B A C B A C B A ext. wire + – B A A B B max. min. ■ DC INPUT ■ T/C INPUT

  • Upscale / No Burnout ■ T/C INPUT
  • Downscale Burnout ■ RTD INPUT ■ POTENTIOMETER INPUT *1 Input Connection Examples *2 When the device is located at the end of a transmission line via twisted-pair cable, (when there is no cross-wiring), close across the terminal T2 – T3 with the attached jumper pin (or with a leadwire). When the device is not at the end, remove the jumper pin. In order to prevent instability in measured values caused by noise entering through the I/O terminals or RS-485 connector, to protect the unit from malfunction and failure, to protect the operator from electrical shock, grounding the RZUS-U9’s GND terminal to a most stable earth point in the environment is recommended. If the PC is equipped with an earth terminal, grounding it to the same point is also recommended. Be careful to eliminate noise as much as possible by e.g. using shielded cables. Ground the signal shield to a most stable earth point in the environment. Separate USB and RS-485 cables as far from power supply or other field wiring which may be a noise source. Certain types of PC, susceptible to noise interference through USB cable, easily freeze. The smaller is common mode voltage (DC and AC) between C terminals and between C and GND, the better is measuring accuracy. Connecting between C terminals and if possible to GND will yield the best accuracy. Resistor modules (model: REM3-250) can be connected to 1A through 12C terminals to convert current inputs into voltage. However, it is not recommended when TC inputs are mixed because the heat developed on and around the REM3 affects the cold junction compensation performance. We recommend that REM3 be connected on a separate terminal board. When the internal temperature sensors are used for CJC, temperature imbalance around the terminal block affects greatly the CJC accuracy. In order to minimize such imbalance, do not use wires of large diameter which has large heat dissipation. Be sure to close the terminal cover. Do not expose the module directly in the line of wind from a cooling fan. Two-wire RTD can be used by closing across B and C terminals. Be sure to compensate wire resistance by PC Configurator Software. Note 1: Note 2: Note 3: Note 4: Note 5: Note 6: Note 7:

MODEL: RZUS-U9 RZUS-U9 SPECIFICATIONS ES-7622 Rev.10 Page 9/10 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 1A 1B 1C 3A 3B 3C 5A 5B 5C 7A 7B 7C 9A 9B 9C 11A 11B ALM ALM –11C 2A 2B 2C 4A 4B 4C 6A 6B 6C 8A 8B 8C 10A 10B 10C 12A 12B 12C TRG TRG T1 T2 T3 T4 175 (6.89) 56.5 (2.22) 117 (4.61) [6 (.24)] 165 (6.50) 6.2 (.24) FOR WALL MOUNT. 40–M3 I/O TERMINALS 3–5 (.20) dia. MTG HOLES DIN RAIL 35 mm wide When the module is mounted on a DIN rail attached on the wall surface in vertical direction, use of a attachment plate to prevent the module from sliding down is recommended. 15.5 (.61) 3 (.12) 15.2 (.60) 7.5 (.30) 11.4 (.45) 10.7 (.42) (.47) 50.8 (2) (.47) ■ USB CABLE SYSTEM CONFIGURATION EXAMPLES USB Cable RS-485 (Max. total cable length 10 meters) PC Recorder (model: RZMS-U9) PC Recorder (model: RZUS-U9) PC Recorder (model: R1M-A1) USB Cable PC Recorder (model: R1M-D1) PC Recorder (model: R1M-GH) PC Recorder (model: R1MS-GH3) PC Recorder (model: RZUS-U9) Non-isolated between USB and RS-485. RS-485 cable length is limited within 10 meters.

MODEL: RZUS-U9 RZUS-U9 SPECIFICATIONS ES-7622 Rev.10 Page 10/10 http://www.m-system.co.jp/ Specifications are subject to change without notice.