RSS-24MCW-FR FCI-CONNECTOR | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

Features

  • Approvals include: - UL Standard 1971 - California State Fire Marshal (CSFM) - New York City (MEA) - Factory Mutual (FM)
  • ADA/NFPA/UFC/ANSI compliant.
  • Wall mounted models are available with field selectable multi-candela settings of 15, 30, 75, or 110 cd with high intensity models settable to 135 or 185 cd.
  • Ceiling mounted models are available with field select- able multi-candela settings of 15, 30, 75, or 95 cd with high intensity models set to 115 or 177 cd.
  • Single candela models provide 15/75 cd.
  • Strobes flash once per second over the regulated voltage range.
  • 12 & 24 VDC models with wide UL “regulated volt age range” using filtered DC or unfiltered FWR input volt age.
  • Synchronize with SM or DSM sychronization modules.
  • Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires. RSS Series RSS Series RSS Series Multi-Candela Indicator (bottom of lens) An ISO 9000-2000 Company

12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118

www.gamewell-fci.com 9020-0575 Rev. B page 2 of 4 General Notes

  • Strobes are designed to flash at one flash per second minimum over Regulated Voltage Range. Note that NFPA-72 (1999) specifies a flash rate of one to two flashes per second and ADA guidelines specify a flash rate of one to three flashes per second.
  • All candela ratings represent minimum effective strobe intensity based on UL Standard 1971.
  • Series RSS & RSSP Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%).
  • “Regulated Voltage Range” is the newest terminology used by UL to identify the voltage range. Prior to this, UL used the term “Listed Voltage Range”. Table 1: Average RMS Current* RSS/ RSSP 24VDC Models RSS/RSSP - Wall Mount RSS - Ceiling Mount 2415- 75W 24MCW 24MCWH 24MCC 24MCCH 1575 cd 15 cd 30 cd 75 cd 110 cd 135 cd 185 cd 15 cd 30 cd 75 cd 95 cd 115 cd 177 cd VDC 0.101 0.062 0.102 0.192 0.265 0.300 0.420 0.068 0.112 0.211 0.292 0.300 0.420 VDC 0.064 0.041 0.062 0.116 0.155 0.195 0.270 0.045 0.072 0.128 0.171 0.195 0.270 VDC 0.047 0.032 0.047 0.081 0.107 0.145 0.190 0.035 0.052 0.089 0.118 0.145 0.190 RSS/ RSSP VDC Models RSS/ RSSP Wall Mount 12157-

8 VDC

0.336 VDC 0.179 17.5 VDC 0.136 Table 2: Audible/Speakers for RSSP Strobe Plate Product Series Multitone Appliances AMT, MT Horns AH, NH, HS Motor Bells MB-G6/G10 Speakers ET-1010/1080, E70, ET70 Chimes CH70 SYNC Modules Model Number Order Code Input Voltage (VDC) Average Mean Current @ 24 VDC Mounting Options SM-12/24-R 6369 0.028 W DSM-12/24-R 6374 0.035 W * Average RMS Current is per UL average RMS method and Average Mean Current is per UL av- erage mean method. 12 volt models use Average Mean Current. For rated inrush and peak current across the UL Listed voltage range for both filtered DC and un- filtered Vrms (FWR), see installation instructions. SM Sync Module is rated for 3.0 amperes @ 24 VDC DSM Sync Module is rated for 3.0 amperes per circuit. The maximum number of interconnected DSM modules is 20.

www.gamewell-fci.com 9020-0575 Rev. B page 3 of 4 STROBE NAC CIRCUIT SM SERIES RSS/RSSP APPLIANCES SYNCHRONIZED WITH SM MODULE SINGLE CLASS "B" NAC CIRCUIT F A C P + STROBE - STROBE + AUDIBLE - AUDIBLE EOLR RSS RSS SERIES RSS/RSSP APPLIANCES NON-SYNCHRONIZED + - FROM PRECEDING APPLIANCE, SYNC MODULE, POWER SUPPLY OR FACP TO NEXT APPLIANCE OR EOLR SERIES RSS/RSSP APPLIANCES SYNCHRONIZED WITH MUTIPLE DSM MODULES STROBE NAC CIRCUIT RETURN + OUT 1 + IN 1 MINUS 1 + AUDIBLE - AUDIBLE MINUS 2 + IN 2 + OUT 2 F A C P STROBE NAC CIRCUIT SERIES RSS/RSSP APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS "A" NAC CIRCUIT F A C P STROBE NAC CIRCUIT OUT DSM + SYNC - SYNC DSM #1 DSM #2 DSM #3 - SYNC + SYNC STROBE NAC CIRCUIT STROBE NAC CIRCUIT DSM INTERCONNECTING WIRING SHOWN. MAXIUMUM OF TWENTY (20) MODULES WIRING DIAGRAMS + SYNC - SYNC - SYNC + SYNC STROBE/PLATE ASSEMBLY AUDIBLE & VISIBLE APPLIANCE OPERATE IN UNISON STROBE APPLIANCE STROBE/PLATE ASSEMBLY AUDIBLE & VISIBLE APPLIANCE OPERATE INDEPENDENTLY FROM PRECEDING APPLIANCE OR FACP STROBE FROM PRECEDING APPLIANCE, SYNC MODULE, POWER SUPPLY OR FACP + - TO NEXT STROBE OR EOLR TO NEXT APPLIANCE OR EOLR APPLIANCE RSS RSS RSS RSS RSS RSS RSS RSS RSS RSS RSS RSS TO NEXT APPLIANCE OR EOLR FROM PRECEDING APPLIANCE, SYNC MODULE, POWER SUPPLY OR FACP

www.gamewell-fci.com 9020-0575 Rev. B page 4 of 4 Architects and Engineers Specifications The visual notification appliances shall be Cooper-Wheelock Series RS strobe appliances or approved equals. The Series RSS shall be Listed under UL Standard 1971 (Emergency Devices for the Hearing Impaired) for Indoor Fire Protection Service. The strobe shall be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. The strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series RSS shall be of low current design. Where multi-candela appliances are specified, the strobe intensity shall have a minimum of four (4) field selectable settings and shall be rated per UL Standard 1971 at: 15, 30, 75, and 110 cd, or 135/185 cd for wall mount, or 15, 30, 75, and 95cd or 115/177 cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 cd UL Standard 1971 Listing with 75 cd on-axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compatible with Cooper-Wheelock’s SM and DSM Sync Modules. The strobes shall not drift out of synchronization at any time during operation. If the sync module fails to operate, (i.e. contacts remain closed), the strobe shall revert to a non-synchronized flash rate. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation. The Series RSS Strobe appliances shall incorporate a patented universal mounting plate that allows mounting on a single-gang, double-gang, 4-inch square, 100 mm European type backbox, or the SHBB surface backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided. An attaching cover plate shall be provided to give the appliance an attractive appearance. The appliance shall not have any mounting holes or screw heads visible when the installation is complete. The Series RSSP Multi-Candela or single candela Strobe Plate shall be mounted on either a standard 4-inch square backbox for flush mounting, or the Wheelock SBL2 backbox for surface mounting. All notification appliances shall be backward compatible. Specifications and Ordering Information Model Order Code Wall Mount Ceiling Mount Non- Sync Sync w/ SM or DSM Strobe Candela

24 VDC

# Model Color Red # Model Color White Square or Round UL MEA CSFM FM RSS-24MCW-FR 9400 X X X 15/30/75/110 X X Square X X X X RSS=241575W-FR 7471 X X X 15 (75 on Axis) X X Square X X X X RSS-121575W-FR 7476 X X X 15 (75 on Axis) X X Square X X X X RSS-24MCC-FW 3158 X X X 15/30/75/95 X X Square X RSS-24MCCR-FW 3159 X X X 15/30/75/95 X X Round X RSS-24MCCH-FW 3461 X X X X X Square X RSS-24MCCR-FW 3463 X X X X X Round x RSS-24MCWH-FR 3465 X X X X X Square X RSSP-24MCW-FR 9402 X X X 15/30/75/110 X X Square X X X X # Models are available in either red or white. * PENDING BFP X X X X RSSWP-2475W-FR 9013 X X X 75 @ -31°F X X Square X X X X RSSP-121575W-FR 7798 X X X 15 (75 on Axis) X X Square X X X X X RSSP-241575W-FR 7793 X X X 15 (75 on Axis) x Square X X X X X RSSP-24MCWH-FR 9482 X X X X X Square X