RSP-1000_V01 MEANWELL | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 8

Technical content

1000W Power Supply with Single Output RSP-1000 seri es File Name:RSP-1000-SPEC 2022-08-08      CNS14336-1 UL62368-1 GB4943.1 (except for 48V )TPTC004 IEC62368-1BS EN/EN62368-1 Bauar Sicherheit egel gema t gepruft od be www. ID 2000000000 tuv.com wac g o s User’s Manual IS 13252 THOMAS SAMUEL THOMAS SAMUEL

OUTPUT VOLTAGE ADJ. RANGE LINE REGULATION LOAD REGULATION SETUP, RISE TIME HOLD UP TIME (Typ.) VOLTAGE RANGE Note.4 FREQUENCY RANGE EFFICIENCY (Typ.)INPUT FUNCTION INRUSH CURRENT (Typ.) LEAKAGE CURRENT OVER TEMPERATURE WORKING TEMP. DC OK SIGNAL AUXILIARY POWER REMOTE ON-OFF CONTROL WORKING HUMIDITY STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION MTBF DIMENSIONOTHERS NOTE PACKING OVERLOAD OVER VOLTAGE AC CURRENT (Typ.) 300ms, 50ms at full load 16ms/230VAC 16ms/115VAC at full load 90 ~ 264VAC 127 ~ 370VDC 47 ~ 63Hz 12A/115VAC 6A/230VAC 25A/115VAC 40A/230VAC <2.0mA / 240VAC 105 ~ 125% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed Protection type : Shut down o/p voltage, re-power on to recover Shut down o/p voltage, recovers automatically after temperature goes down -20 ~ +60℃ (Refer to "Derating Curve") Power ON : short Power OFF : open. Please refer to the Function Manual. The TTL signal out, PSU turn on = 0 ~ 1V ; PSU turn off = 3.3 ~ 5.6V. Please refer to the Function Manual. 20 ~ 90% RH non-condensing -40 ~ +85℃, 10 ~ 95% RH non-condensing ±0.02%/℃ (0 ~ 50℃) 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes 939.4K hrs min. Telcordia SR-332 (Bellcore) ; 116.5K hrs min. MIL-HDBK-217F (25℃) 295*127*41mm (L*W*H) 1.95Kg; 6pcs/12.7Kg/1.15CUFT 150mVp-p 10 ~ 13.5V 150mVp-p 13.5 ~ 16.5V 150mVp-p 20 ~ 26.4V 150mVp-p 24 ~ 30V 150mVp-p 43 ~ 55V 12V 60A 0 ~ 60A 720W 15V 50A 0 ~ 50A 750W 24V 40A 0 ~ 40A 960W 27V 37A 0 ~ 37A 999W 48V 21A 0 ~ 21A 1008W RSP-1000-12 RSP-1000-15 RSP-1000-24 RSP-1000-27 RSP-1000-48 POWER FACTOR (Typ.) 0.95/230VAC 0.98/115VAC at full load SAFETY STANDARDS UL62368-1, CSA C22.2 , TUV BS EN/EN62368-1, CCC GB4943.1, BSMI CNS14336-1, AS/NZS62368.1 No. 62368-1 , IS13252(Part1)/IEC60950-1, EAC TP TC 004 approved RIPPLE & NOISE (max.) Note.2 VOLTAGE TOLERANCE Note.3 WITHSTAND VOLTAGE ISOLATION RESISTANCE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH ENVIRONMENT SAFETY & EMC (Note 5) PROTECTION 1000W Power Supply with Single Output RSP-1000 seri es File Name:RSP-1000-SPEC 2022-08-08 Parameter Parameter ESD Radiated EFT / Burst Surge Conducted Magnetic Field Voltage Dips and Interruptions Conducted Radiated Harmonic Current Voltage Flicker Standard Standard BS EN/EN55032 (CISPR32) BS EN/EN55032 (CISPR32) BS EN/EN61000-3-2 BS EN/EN61000-3-3 BS EN/EN61000-4-2 BS EN/EN61000-4-3 BS EN/EN61000-4-4 BS EN/EN61000-4-5 BS EN/EN61000-4-6 BS EN/EN61000-4-8 BS EN/EN61000-4-11 Test Level / Note Test Level / Note Level 3, 8KV air ; Level 2, 4KV contact Level 3 Level 3 Level 3 Level 4 >95% dip 0.5 periods, 30% dip 25 peniods, >95% interruptions 250 periods Class B Class A ----- ----- EMC IMMUNITY EMC EMISSION Adjustment of output voltage is allowable to 40 ~ 110% of nominal output voltage. Please refer to the Function Manual.OUTPUT VOLTAGE PROGRAMMABLE(PV) BS EN/EN55035, BS EN/EN61000-6-2, CCC GB17625.1, GB/T9254, BSMI CNS13438 CURRENT SHARING Up to 4000W or (3+1) units. Please refer to the Function Manual. REMOTE SENSE Compensate voltage drop on the load wiring up to 0.5V. Please refer to the Function Manual. Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line

10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Static Characteristics LOAD (%)LOAD (%) INPUT VOLTAGE (VAC) 60Hz 90 95 100 115 264 100 Block Diagram PFC fosc : 110KHz PWM fosc : 90KHz PFC FILTER RECTIFIERS AUX POWER(5V/0.5A) PFC CONTROL O.L.P. AUX GND SHARE CURRENT CURRENT V_TRIM DC OK SHARE O.V.P. REMOTE ON-OFF RECTIFIERS CONTROL ON/OFF FAN LIMITING ACTIVE CURRENT INRUSH CONTROL I/P -V +VRECTIFIERS FILTERSWITCHING POWERRECTIFIERS FILTER EMI PWM CIRCUIT DETECTION POWER AUX 1000W Power Supply with Single Output RSP-1000 seri es File Name:RSP-1000-SPEC 2022-08-08 Efficiency vs Load (48V Model) ※ The curve above is measured at 230VAC. MODEL 12V 720W 648W 750W 675W 960W 864W 999W 899.1W 1008W 907.2W 60A 54A 50A 45A 40A 36A 37A 33.3A 21A 18.9A 100~264VAC 90VAC 15V 24V 27V 48VINPUT EFFICIENCY (%) LOAD Derating Curve AMBIENT TEMPERATURE (℃) 100 -20 0 10 20 30 40 50 60 70 (HORIZONTAL)

1000W Power Supply with Single Output RSP-1 00 0 s e ri es File Name:RSP-1000-SPEC 2022-08-08 1.Remote Sense ※ The Remote Sense compensates voltage drop on the load wiring up to 0.5V ◎ The +S signal should be connected to the positive terminal of the load whereas -S signal to the negative terminal. ◎ This configuration is based on the assumption the Output Voltage Programming is not activated and power supply is ON. TB1-V+V CN50 1 11 2 12 PIN8 Vco PIN10 Vca PIN6 REMOTE ON-OFF LOAD +V PIN1 +S PIN2 -S Sense lines should be twisted in pairs to minimize noise pick-up. Fig 1.1 Between Remote ON-OFF (pin6) and -S(pin2) Switch Short Switch Open ON Power Supply Status OFF 2.Remote ON-OFF Control When multiple power supplies need to turn ON/OFF simultaneously by Remote ON-OFF control, -S & -V, as well as +S & +V, on each power supply ◎ should be connected. TB1-V+V CN50 Fig 2.1 Fig 3.1 LOAD 1 11 2 12 Switch PIN2 -S PIN6 REMOTE ON-OFF PIN10 Vca PIN8 Vco 3.DC_OK signal ※ "DC_OK" is an open collector signal. It indicates the output status of the power supply. It can operate in two ways : One is sinking current from external TTL signal ; the other is sending out a TTL voltage signal. Sinking current from external TTL signal: The maximum sink current is 10mA and the maximum external voltage is 5.6V.◎ ◎ Sending out TTL voltage signal : Between DC- OK(pin5) and GND(pin11&12) 0 ~ 1V 3.3 ~ 5.6V Output Status ON OFF TB1-V+V CN50 1 11 2 12 PIN2 -S PIN5 DC_OK PIN12 GND PIN6 REMOTE ON-OFF PIN10 Vca PIN8 Vco ※ The power supply can be turned ON-OFF indivicluaaly or along with other units by using the “Remote ON-OFF” function. The power supply is shipped, by factory default, with Remote ON-OFF(pin6) and -S(pin2) shorted by connector.◎

1000W Power Supply with Single Output RSP-1 00 0 series TB1 TB1 CN50 CN50 1 11 2 12 1 11 2 12 PIN10 Vca PIN10 Vca PIN9 Vci PIN9 Vci PIN4 AUX PIN4 AUX PIN6 REMOTE ON-OFF PIN6 REMOTE ON-OFF PIN1 +S PIN1 +S PIN3 AUXG PIN3 AUXG PIN2 -S PIN2 -S Fig 4.2 Fig 4.3 (2)Applying EXTERANL RESISTANCE as shown in Fig4.2 & Fig 4.3 (A) Output voltage goes down EXTERNAL RESISTANCE (Ω) 390 560 820 1K2 2K2 4K7 open R1, 1/8W(Typ.) 100 Vout Non-Linear OUTPUT VOLTAGE (%) ◎ +S & +V and -S & -V also need to be connected on CN50. ◎ +S & +V and -S & -V also need to be connected on CN50. (B)Output voltage goes up EXTERNAL RESISTANCE (Ω) open 18K 7K5 R2, 1/8W(Typ.) 110 Vout OVP 120%(Typ.) Non-Linear 105 100 OUTPUT VOLTAGE (%) ※ Caution: By factory default, the Output Voltage Programming is not activated, and Vco (pin8) and Vca(pin10) are shorted by connector. Whenever this function is not needed to activate, as assumed in other sections’ diagrams, please keep Vco(pin8) and Vca(pin10) shorted ; other wise, the power supply will have no output. EXTERNAL VOLTAGE (VDC) 1 2 3 4 5 6 Vci(Referenced to -S) 100 120 Vout OVP 120%(Typ.) Non-Linear80 OUTPUT VOLTAGE (%) (1)Applying EXTERNAL VOLTAGE between "Vci"(pin9) and "-S"(pin2) as shown in Fig4.1 ※ In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 40~110% of the nominal voltage by applying ◎ +S & +V and -S & -V also need to be connected on CN50 either an EXTERNAL VOLTAGE or an EXTERNAL RESISTANCE. 4. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim) TB1-V+V CN50 1 11 2 12 EXTERNAL VOLTAGE (DC) PIN9 Vci PIN6 REMOTE ON-OFF PIN1 +S PIN2 -S Fig 4.1 AUXG AUXG AUX AUX DC_OK REMOTE ON-OFF REMOTE ON-OFF DC_OK CS CS CN50 CN50 Vco Vco Vci Vci Vca Vca GND GND GND GND LOAD LOAD External Voltage LOAD AUXG AUX DC_OK ON/OFF CS CN50 Vco Vci Vca GND GND File Name:RSP-1000-SPEC 2022-08-08

5.Current Sharing with Remote Sense +S+S+S+S -S-S-S-S AUXGAUXGAUXGAUXG AUXAUXAUXAUX DC_OKDC_OKDC_OKDC_OK ON/OFFON/OFFON/OFFON/OFF CSCSCSCS VcoVcoVcoVco VciVciVciVci VcaVcaVcaVca GNDGNDGNDGND GNDGNDGNDGND PSU PSU PSU PSU -V Sense lines should be twisted in pairs LOAD 1111 11111111 CN50CN50CN50CN50 Fig 5.1 CS(pin7) +S(pin1) -S(pin2) 2222 12121212 TB1 TB1 TB1 TB1-V -V -V -V+V +V +V +VCN50 CN50 CN50 CN50 1 11 2 12 1 11 2 12 1 11 2 12 1 11 2 12 1000W Power Supply with Single Output RSP-1000 seri es File Name:RSP-1000-SPEC 2022-08-08 ※ Difference of output voltages among parallel units should be less than 0.2V. RSP-1000 has the built-in active current sharing function and can be connected in parallel, up to 4 units, to provide higher output power as exhibited below : ※ The total output current must not exceed the value determined by the following equation: ※ When the total output current is less than 5% of the total rated current, or say (5% of Rated current per unit)×(Number of unit) the current shared among units may not be fully balanced. Maximum output current at parallel operation=(Rated current per unit)×(Number of unit)×0.9 +S,-S and CS are connected mutually in parallel.◎ ※The power supplies should be paralleled using short and large diameter wiring and then connected to the load.

Mounting Surface Chassis of RSP-1000 1000W Power Supply with Single Output RSP-1000 seri es File Name:RSP-1000-SPEC 2022-08-08 Mechanical Specification Case No. 952B Unit:mm TB1 -V 20.5 Air flow direction 127 18.5 3-M4 L=4 2-M5 277.7 25.4 7.8 21 34.5 295 277.7 25.47.86 20.5 CN50 SVR51 3-M4 L=6 3-M4 L=6 Pin No. Function Description 11,12 5V-AUX DC_OK CS Vco Vca GND G-AUX Remote ON-OFF Vci Auxiliary voltage output, 4.6~5.25V, referenced to pin 3(G-AUX). The maximum load current is 0.5A. This output has the built-in oring diodes and is not controlled by the "remote ON/OFF control". Open collector signal, referenced to pin11,12(GND). Low when PSU turns on. The maximum sink current is 10mA and the maximum external voltage is 5.6V. Current sharing signal. When units are connected in parallel, the CS pins of the units should be connected to allow current balance between units. Short connecting between Vco (pin8) and Vca (pin10) if output voltage programming function is not activated. Connect to external resistor (1/8W) for output voltage programming. These pins connect to the negative terminal (-V). Return for DC_OK Signal output. Turns the output on and off by electrical or dry contact between pin 6 (Remote ON-OFF) and pin 2 (-S). Short: Power ON, Open: Power OFF. Connect to external DC voltage source for output voltage programming, referenced to pin 2 (-S). Negative sensing for remote sense. Positive sensing for remote sense. Auxiliary voltage output ground. The signal return is isolated from the output terminals (+V & -V). ※Control Pin No. Assignment : HRS DF11-12DP-2DS or equivalent(CN50) Mating Housing Terminal HRS DF11-12DS or equivalent HRS DF11-**SC or equivalent ※ Mounting Instruction Hole No. Recommended Screw Size MAX. Penetration Depth L Recommended mounting torque 6mm 4mm 7~11Kgf-cm 7~11Kgf-cm

Please refer to : http://www.meanwell.com/manual.html ※DC Output Terminal Pin No. Assignment Assignment Diagram Maximum mounting torque 10Kgf-cm+V, -V 1000W Power Supply with Single Output RSP-1000 seri es File Name:RSP-1000-SPEC 2022-08-08 ※AC Input Terminal Pin No. Assignment Pin No. Assignment Diagram Maximum mounting torque 18Kgf-cm AC/N AC/L FG