RSI-95 GAMEWELL-FCI | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 2

Technical content

Features

 Compatible with the Gamewell-FCI 600 Series analog addressable fire alarm control panels.  Provides full solenoid supervision.  Transient voltage suppression.  Mounts in its own unique base.  Automatic bypass at system start-up.  2.0 A of DC power for solenoid.  Types of Suppressants: –N F P A 1 3 S p r i n k l e r . – NFPA 15 Water Spray. – NFPA 11 Low Expansion. – NFPA 16 Water Foam. – NFPA 17 Dry Chemical. – NFPA 2001 Clean Agent. NOTE: Releasing systems must be designed by properly qualified personnel. CS-2064ph1.wmf RSI-95 An ISO 9000-2000 Company SIGNALING S521

12 Clintonville Road, Northford, CT 06472-1610 USA  Tel: (203) 484-7161  Fax: (203) 484-7118

CS-2046 Rev. A page 2 of 2 www.gamewell-fci.com Installation Guideline (Continued) The addition of the trim ring (P/N 70839) allows flush instal- lation. The total voltage drop from the power supply to the end of the solenoid circuit shall not exceed two volts. The RSI-95 must have its address programmed before the sys- tem will operate correctly. Installation Connect the system wiring to the four-position terminal block L1, L2, P1, P2 per wiring diagram A-W532-1. Con- nect the solenoid device wiring to the four-position terminal block per wiring diagram A-W572. IMPORTANT! Maximum L1 – L2 loop resistance should not be more than 25 ohms. CAUTION: No wiring connections should be made while the system is powered. Specifications Temperature: 0°C to 49°C (32°F to 120°F) Humidity: 85%, non-condensing Power: 21 VDC from analog addressable module. +P and –P, or +24 and –24:

24 VDC from UL-Listed power

source. Normal Current: 6.5 mA Alarm Current: 6.5 mA + solenoid load Solenoid Circuit Rating:

2.0 A power-limited steady

Mounting: 4.0" (10.16 cm), 4.688" (11.908 cm), double-gang electrical box

Ordering Information

RSI-95 RSI-95 assembly consists of an RSM-95 analog addressable Releasing Service Module and integral SID Solenoid Interface Device. NOTE: RSM-95 and SID no longer available separately. 70839 Flush trim ring for RSM-95.