RPS-200 MEANWELL | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 6

Technical content

‧Extremely low leakage current File Name:RPS-200-SPEC 2016-11-09 Type 200W Reliable Green Medical Power Supply μ File Name:RPS-200-SPEC 2017-10-23

VOLTAGE ADJ. RANGE LOAD REGULATION SETUP, RISE TIME HOLD UP TIME (Typ.) VOLTAGE RANGE Note.4 FREQUENCY RANGE POWER FACTOR EFFICIENCY (Typ.)INPUT FUNCTION INRUSH CURRENT (Typ.) ISOLATION RESISTANCE WORKING HUMIDITY WORKING TEMP. FAN SUPPLY OVER TEMPERATURE STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION MTBF DIMENSION (L*W*H) OTHERS NOTE PACKING OVERLOAD OVER VOLTAGE AC CURRENT (Typ.) 700ms, 30ms/230VAC 700ms, 30ms/115VAC at full load 16ms/230VAC 16ms/115VAC at full load 80 ~ 264VAC 113 ~ 370VDC 47 ~ 63Hz PF>0.94/230VAC PF>0.98/115VAC at full load 93.5% 93% 94% 16.5 ~ 19.5V 94% 26.4 ~ 31.2V 95% 29.7 ~ 35V 52.8 ~ 62.4V 2A/115VAC 1A/230VAC COLD START 30A/115VAC 60A/230VAC 110 ~ 140% rated output power 13.2 ~ 15.6V Protection type : Hiccup mode, recovers automatically after fault condition is removed 20 ~ 90% RH non-condensing -30 ~ +70℃ (Refer to "Derating Curve") 12V@0.5A for driving a fan ; tolerance +15% ~ -15% -40 ~ +85℃, 10 ~ 95% RH non-condensing ±0.03%/℃ (0 ~ 50℃) 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes 500.2Khrs min. MIL-HDBK-217F (25℃) ±1.0% ±0.5% ±1.0% ±0.5% ±1.0% ±0.5% ±0.5% ±1.0% ±1.0% ±0.5% 100mVp-p 100mVp-p 120mVp-p 120mVp-p 120mVp-p 15V 24V 27V 48V 16.7A 11.7A 13.4A 9.4A 8.4A 5.9A 7.5A 5.3A 4.2A 200.4W 140.4W 141W 201W 141.6W 201.6W 143.1W 202.5W 144W 201.6W RPS-200-12□ RPS-200-15□ RPS-200-24□ RPS-200-27□ RPS-200-48□ SAFETY STANDARDS RIPPLE & NOISE (max.) Note.2 VOLTAGE TOLERANCE Note.3 ENVIRONMENT SAFETY & EMC (Note 7) PROTECTION Primary-Secondary: 2xMOPP, Primary-Earth:1xMOPP, Secondary-Earth:1xMOPP IEC60601-1, TUV EN60601-1, UL ANSI / AAMI ES60601-1 (3.1 version), CAN/CSA-C22.2 No. 60601-1:14 - Edition 3 approved; Design refer to EN60335-1 12V LEAKAGE CURRENT(max.)Note.5 Earth leakage current < 130 A/264VAC , Touch current < 40 A/264VAC WITHSTAND VOLTAGE ISOLATION RESISTANCE I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC I/P-O/P, I/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH Protection type : Shut down o/p voltage, re-power on to recover Protection type : Shut down o/p voltage, re-power on to recover Parameter Parameter ESD Standard Standard EN55011 (CISPR11) EN55011 (CISPR11) EN61000-3-2 EN61000-3-3 EN61000-4-2 EN61000-4-3 EN61000-4-4 EN61000-4-5 EN61000-4-6 EN61000-4-8 EN61000-4-11 Test Level / Note Test Level / Note Class B Class B Class A ----- EMC IMMUNITY EMC EMISSION EN60601-1-2 100% dip 1 periods, 30% dip 25 periods, 100% interruptions 250 periods OPERATING ALTITUDE Note.6 4000 meters 200W Reliable Green Medical Power Supply μ μ μ μ RF field susceptibility EFT bursts Surge susceptibility Conducted susceptibility Magnetic field immunity Voltage dip, interruption Conducted emission Radiated emission Harmonic current Voltage flicker Level 4, 15KV air ; Level 4, 8KV contact Level 4, 4KV/Line-FG ; 2KV/Line-Line Level 4, 30A/m Level 3, 10V Level 3, 2KV File Name:RPS-200-SPEC 2017-10-23 Level 3, 10V/m( 80MHz~2.7GHz ) Table 9, 9~28V/m( 385MHz~5.78GHz )

Output Derating VS Input VoltageDerating Curve fosc : 65KHz CIRCUIT DETECTION EMI FILTER POWER SWITCHING FILTER FILTER RECTIFIERS RECTIFIERS +12V FAN supply I/P FG CONTROL O.V.P. EMI FILTER RECTIFIER INPUT VOLTAGE (VAC) 60Hz 80 11590 130120 160140 200180 240220 264 LOAD (%) 100 AMBIENT TEMPERATURE (℃) LOAD (%) -30 0 2010 30 40 45 100 6050 70 (HORIZONTAL) With 10CFM Fan for RPS-200(-C) With 10CFM Fan for RPS-200(-C) Convection for RPS-200 24~48V Convection V~48Vfor RPS-200-C 12 & RPS-200 12V~15V RPS-200 seri es200W Reliable Green Medical Power Supply File Name:RPS-200-SPEC 2017-10-23

50.8 44.45 3.175 4-ψ3.3 612 CN101 LEDSVR1 3.175 95.25 101.6 CN2 293 max. FS1 CN1 T4A/250VFS2 F4A/250V FAN 10CFM direction Air flow 50mm ※Note RPS-200 seri es Top View Side View 200W Reliable Green Medical Power Supply RPS-200 (PCB Type) File Name:RPS-200-SPEC 2017-10-23

Case No.245A Unit:mm FAN 10CFM direction Air flow 50mm 30.8 100 103.4 1.7 2-M3 L=2 2-M3 L=4 2-R1.75 12.7 78 24.2 55 CN1 612 CN101 CN2 RPS-200 seri es Side ViewTop View Bottom View Side View Side View Side View 200W Reliable Green Medical Power Supply RPS-200-C (Enclosed Type) File Name:RPS-200-SPEC 2017-10-23

AC Input Connector (CN1) : JST B3P-VH or equivalent Pin No. Assignment AC/L No Pin AC/N Mating Housing JST VHR JST SVH-21T-P1.1 or equivalent or equivalent Terminal DC Output Connector (CN2) : JST B6P-VH or equivalent Pin No. 1,2,3 4,5,6 Assignment Mating Housing JST VHR or equivalent Terminal JST SVH-21T-P1.1 or equivalent Mating Housing JST PHR-2 or equivalent Terminal JST SPH-002T-P0.5S or equivalent FAN Connector(CN101) : or equivalentJST B2B-PH-K-S Pin No. Assignment +12V DC COM ※Note : 1. The FAN supply is designed to serve as the source of the additive external fan for the cooling of the power supply, enabling the full load delivery and assuring the best life span of the product. Please do not use this FAN supply to drive other devices. 2.The PCB type(Blank type)model delivers EMI Class B for both conducted emission and radiated emission for the power supply, when configured into either Class Ⅰ(with FG) 3.The enclosed type(-C type) model is not suitable for the configuration within a Class system but Ⅱ(no FG) is suggested to used within a Class Ⅰ(with FG) system. RPS-200 seri es Installation Manual Please refer to : http://www.meanwell.com/manual.html 200W Reliable Green Medical Power Supply File Name:RPS-200-SPEC 2017-10-23