RENF22R2MMW SCHNEIDER | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 35
Technical content
Harmony, NFC modular timing relay, 8 A, 2 CO, 0.1 s…999 h, multifunction, 24...240 V AC/DC Product availability : Stock - Normally stocked in distribution facility Price* : 90.00 USD Main Range of Product Harmony Timer Relays Product or Component Type Multifunction relay Device short name RENF22 Supported OS Android Software Version V4.4 and above App for product Zelio NFC downloadable from Google Play store) Complementary Discrete output type Relay Nominal output current 8 A Contacts type and composition 2 C/O timed contact, cadmium free
1 C/O timed and instantaneous contact, cadmium free
Time delay type Power on-delay On-delay and off-delay Pulse delay Asymmetrical on-delay and off-delay Interval Off-delay Symmetrical flashing Safe-guard Star-delta Asymmetrical flashing Bistable Time delay range 0.1 s...999 h Product Compatibility NFC enabled mobile device [Us] rated supply voltage 24...240 V AC/DC Release input voltage <= 2.4 V Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications * Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price. Aug 25, 2021
Maximum RF power transmitted 0.0002 mW NFC operating frequency 13.56 MHz Supply frequency 50...60 Hz +/- 5 % Housing material Self-extinguishing Repeat accuracy +/- 0.2 % 10 s...999 h Temperature Drift +/- 0.05 %/°C Voltage drift +/- 0.2 %/V Setting accuracy of time delay +/- 1 % 1...999 h 77 °F (25 °C) Control signal pulse width 100 ms with load in parallel 60 ms no-load Insulation resistance 100 MOhm 500 V DC IEC 60664-1 Recovery time 120 ms on de-energisation Power consumption in VA 3 VA 240 V AC Power consumption in W 1.5 W 240 V DC
0.6 W 24 V DC
Switching capacity in VA 2000 VA Minimum switching current 10 mA 5 V Maximum switching current 8 A Maximum switching voltage 250 V Electrical durability 100000 cycles for resistive load, 8 A at 250 V, AC Mechanical durability 10000000 cycles Rated impulse withstand voltage 5 kV 1.2/50 µs IEC 60664-1 Power on delay 100 ms Creepage distance 4 kV/3 IEC 60664-1 Overvoltage category III IEC 60664-1 Safety reliability data MTTFd = 227.5 years 100 % duty cycle continuous operating condition at 30 °C Mounting position Any position Mounting support 35 mm DIN rail conforming to EN/IEC 60715 Status LED Un, green LED steady)power ON R1, amber LED steady)relay energised R2, amber LED steady)relay energised Pairing, green LED steady)communication status Un, green LED fast blinking)diagnosis mode R1, amber LED blinking)timing in progress R2, amber LED blinking)timing in progress Maximum communication distance 10 mm Response Time 2 s Maximum Width 0.89 in (22.5 mm) Net Weight 0.20 lb(US) (0.0904 kg) Environment Immunity to microbreaks 10 ms Dielectric strength 2.5 kV 1 mA/1 minute 50 Hz between relay output and power supply with basic insulation basic insulation Standards EN 61000-6-1 EN 61000-6-2 EN 61000-6-4 EN 61812-1 EN 61000-6-3 Directives 2014/35/EU - low voltage directive
2014/53/EU - radio equipment directive 2014/30/EU - electromagnetic compatibility Product Certifications CE CSA KC UL CCC EAC DNV-GL Ambient Air Temperature for Operation Ambient Air Temperature for Storage -40…158 °F (-40…70 °C) IP degree of protection Housing IP40 IEC 60529 IP40 front face: conforming to IEC 60529 Terminals IP20 IEC 60529 Pollution degree 3 IEC 60664-1 Vibration resistance 20 m/s² 10…150 Hz)IEC 60068-2-6 Shock resistance 15 gn not operating 11 ms IEC 60068-2-27 5 gn in operation 11 ms IEC 60068-2-27 Relative humidity 95 % 77…131 °F (25…55 °C) Electromagnetic compatibility Electrostatic discharge immunity test 6 kV contact discharge)level 3 EN/IEC 61000-4-2 Electrostatic discharge immunity test 8 kV air discharge)level 3 EN/IEC 61000-4-2 Fast transients immunity test 1 kV capacitive connecting clip)level 3 IEC 61000-4-4 Fast transients immunity test 2 kV direct contact)level 3 IEC 61000-4-4 Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5 Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5 Radiated radio-frequency electromagnetic field immunity test 10 V 0.15...80 MHz)level 3 IEC 61000-4-6 Electromagnetic field immunity test 10 V/m 80 MHz...1 GHz)level 3 IEC 61000-4-3 Immunity to microbreaks and voltage drops 30 % 500 ms) IEC 61000-4-11 Immunity to microbreaks and voltage drops 100 % 20 ms) IEC 61000-4-11 Radiated emissionclass B EN 55022 Conducted emissionclass A EN 55022 Electromagnetic field immunity test 3 V/m 1.4 GHz...2 GHz)level 2 IEC 61000-4-3 Electromagnetic field immunity test 1 V/m 2...2.7 GHz)level 1 IEC 61000-4-3 Ordering and shipping details Category 22376 - RELAYS-MEASUREMENT(RM4) Discount Schedule CP2 GTIN 03606480936203 Nbr. of units in pkg. 1 Package weight(Lbs) 3.66 oz (103.635 g) Returnability Yes Country of origin ID Packing Units Unit Type of Package 1 PCE Package 1 Height 0.94 in (2.4 cm) Package 1 width 3.17 in (8.05 cm) Package 1 Length 3.72 in (9.45 cm) Offer Sustainability Sustainable offer status Green Premium product California proposition 65 WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov REACh Regulation REACh Declaration EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration Mercury free Yes
RoHS exemption information Yes China RoHS Regulation China RoHS declaration Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information
Function A: Power On-Delay Relay
Description
On energisation of power supply, the timing period T starts. After timing, the output(s) R close(s).The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function At: Power On-Delay Relay with Pause / Summation Control Signal On energisation of power supply, the timing period T starts.Timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R close(s).The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output T = t1 + t2 +…
Function Ac: On-Delay and Off-Delay Relay with Control Signal After energisation of power supply and energization of Y1 causes the timing period T to start. At the end of this timing period, the output(s) R close(s). When deenergization of Y1, the timing T starts. At the end of this timing period T,the output(s) R revert(s) to its/their initial position. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function Ad : Pulse Delayed Relay with Control Signal After energisation of power supply, pulsing or maintaining of energization of Y1 starts the timing T. At the end of this timing period T, the output(s) R close(s). The output(s) R reverts to its initial position the next time Y1 is energized in pulsation or permanent energized manner. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function Ah : Pulse Delayed Relay (Single Cycle) with Control Signal After energisation of power supply, pulsing or maintaining of energization of Y1 starts the timing T. A single flashing cycle then starts with 2 timing periods T of equal duration (start with output(s) R in initial position). Output(s) R closes at the end of the first timing period T and reverts to its initial position at the end of the second timing period T. Re-energizing of Y1, either in pulsation or permanent energized manner, will re-start the single flashing cycle again. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function Ak: Asymmetrical On-Delay and Off-Delay Relay With Control Signal After energisation of power supply and energization of Y1, timing starts for a period Ta. At the end of this timing period Ta, the output(s) R closes. Deenergization of Y1 causes a second timing period Tr to start. At the end of this timing period Tr, the output(s) R reverts to its initial state. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function B: Single Interval Relay with Control Signal After energisation of power supply, pulsing or maintaining of energization of Y1 starts the timing T. The output(s) R close(s) for the duration of the timing period T then revert(s) to its/their initial state. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function Bw : Double Interval Relay with Control Signal After energisation of power supply, transition of Y1 (either from energization to deenergization or vice-versa) will cause the output(s) R close(s) for the duration of the timing period T then revert(s) to its/their initial state. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function C: Off-Delay Relay with Control Signal After energisation of power supply and energization of Y1 causes output(s) R close(s). When Y1 deenergizes, timing T starts.At the end of this timing period T,the output(s) R revert(s) to its/their initial position.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function D: Symmetrical Flashing Relay (Starting Pulse-Off) On energisation of power supply, output(s) R starts at its/their initial state for timing duration T then change(s) to output(s) R close(s) for the same timing duration T.This cycle is repeated indefinitely until power supply removal. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function Di: Symmetrical Flashing Relay (Starting Pulse-On) On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration T then revert(s) to its/their initial state for the same timing duration T.This cycle is repeated indefintely until power supply removal.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function Dt: Symmetrical Flashing Relay (Starting Pulse-Off) With Pause / Summation Control Signal On energisation of power supply, output(s) R starts at its/their initial state for timing duration T and the timing can be interrupted / paused each time Y1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, then changes to output(s) R close(s).The output(s) R close state will remain for the same timing duration T and the timing can be interrupted / paused each time Y1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R revert(s) to its/their initial state.This cycle is repeated indefintely until power supply removal.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output T = t1 + t2 +… T = t'1 + t'2 +…
Function Dit: Symmetrical Flashing Relay (Starting Pulse-On) With Pause / Summation Control Signal On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration T and the timing can be interrupted / paused each time Y1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, then revert(s) to its/their initial state.The output(s) R at initial state will remain for the same timing duration T and the timing can be interrupted / paused each time Y1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R change(s) to close state.This cycle is repeated indefinitely until power supply removal.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output T = t1 + t2 +… T = t'1 + t'2 +…
Function H: Interval Relay On energisation of power supply, output(s) R close(s) and timing period T starts.At the end of the timing period T, the output(s) R revert(s) to its/ their initial state.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function Ht: Interval Relay With Pause / Summation Control Signal On energisation of power supply, output(s) R close(s) and timing period T starts.The timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R revert(s) to its/their initial state. The second output (R2) can be either timed (when set to "TIMED" or instantaneous (when set to "INST"). Function: 2 Output T = t1 + t2 +…
Function L: Asymmetrical Flashing Relay (Starting Pulse-Off) On energisation of power supply, output(s) R starts at its/their initial state for timing duration Tr then change(s) to output(s) R close(s) for the another timing duration Ta. This cycle is repeated indefinitely until power supply removal. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function Li: Asymmetrical Flashing Relay (Starting Pulse-On) On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration Ta then change(s) to its/their initial state for timing duration Tr. This cycle is repeated indefinitely until power supply removal. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function Lt: Asymmetrical Flashing Relay (Starting Pulse-Off) With Pause / Summation Control Signal On energisation of power supply, output(s) R starts at its/their initial state for timing duration Tr and the timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value Tr, then changes to output(s) R close(s). The output(s) R close state will remain for the same timing duration Ta and the timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value Ta, the output(s) R revert(s) to its/their initial state. This cycle is repeated indefinitely until power supply removal. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output Tr = t1 + t2 +… Ta = t'1 + t'2 +…
Function Lit: Asymmetrical Flashing Relay (Starting Pulse-On) With Pause / Summation Control Signal On energisation of power supply, output(s) R starts at output(s) R close(s) for timing duration Ta and the timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value Ta, the output(s) R revert(s) to its/their initial state. The output(s) R at initial state will remain for timing duration Tr the timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value Tr, then changes to output(s) R close(s) This cycle is repeated indefinitely until power supply removal. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output Ta = t1 + t2 +… Tr = t'1 + t'2 +…
Function N : Safe-Guard Relay After energisation of power supply and on energization of Y1 cause the output(s) R close(s) and starts the timing T. If the duration interval between 2 consecutive energization of Y1 is greater than the pre-set value T, the output(s) R close(s) at the end of the timing period. If the duration interval between 2 consecutive energization of Y1 is less than the pre-set value T, the output(s) R remain(s) closed and timing restarted base on the last energization of Y1. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function O : Delayed Safe-Guard Relay On energisation of power supply, the timing T starts. At the end of this timing period, the output(s) R close(s). On energization of Y1, the output(s) R revert(s) to its/their initial state and the timing T restarts. If the duration interval between 2 consecutive energization of Y1 is greater than the pre-set value T, the output(s) R close(s) at the end of the timing period. If the duration interval between 2 consecutive energization of Y1 is less than the pre-set value T, the output(s) R remain(s) at its/their initial state and timing restarted base on the last energization of Y1. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function P : Pulse Delayed Relay with Fixed Pulse Length On energisation of power supply, the timing T starts. At the end of this period, the output(s) R close(s) for a fixed time P then revert(s) to its/their initial state. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output P = 500ms
Function Pt : Pulse Delayed Relay With Fixed Pulse Length and Pause / Summation Control Signal On energisation of power supply, the timing T starts. The timing can be interrupted / paused each time Y1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R close(s) for a fixed time P then revert(s) to its/their initial state. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output T = t1 + t2 + … P = 500ms
Function Qt: Star-Delta Relay (2 CO Outputs with Split Common) On energisation of power supply, the output R3 & R4 initializes at its initial state such that energizes STAR CONTACTOR + MAIN CONTACTOR and the timing T starts (STAR connection time duration starts).At the end of the timing period T, the output R3 closes such that deenergizes STAR CONTACTOR and causes t transition time starts.At the end of the transition time, the output R4 closes such that energizes DELTA CONTACTOR. Diagnostic feature not available. Function: 2 Output T = 50, 60... ms
Function Qtt: Star-Delta Relay (2 CO Outputs With Split Common) with Pause / Summation Control Signal On energisation of power supply, the output R3 & R4 initializes at its initial state such that energizes STAR CONTACTOR + MAIN CONTACTOR and the timing T starts (STAR connection time duration starts).During STAR connection time, the timing can be interrupted / paused each time Y1 energizes.When the cumulative total of time periods elapsed reaches the pre-set value T, the output R3 closes such that deenergizes STAR CONTACTOR and causes t transition time starts.At the end of the transition time, the output R4 closes such that energizes DELTA CONTACTOR. Diagnostic feature not available. Function: 2 Output T = t1 + t2 +... t = 50, 60 ... ms
Function TL : Bistable Relay with Control Signal On After energisation of power supply and on energization of Y1 cause the output(s) R close(s). The subsequent on energization of Y1 cause the output(s) R revert(s) to its/their initial state. This cycle is repeated indefinitely until power supply removal. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function Tt : Retriggerable Bistable Relay with Control Signal On After energisation of power supply and on energization of Y1 cause the output(s) R close(s) and starts the timing T. If the duration interval between 2 consecutive energization of Y1 is greater than the pre-set value T, the output(s) R will toggle from its/their present status the end of the timing period. If the duration interval between 2 consecutive energization of Y1 is less than the pre-set value T, the output(s) R toggle from its/their present status as soon as Y1 energizes without completing T duration. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output
Function W: Interval Relay with Control Signal Off After energisation of power supply and on energization of Y1 following by denergization of Y1, the output(s) R close(s) and starts the timing T.At the end of the timing period, the output(s) R revert(s) to its/their initial state.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 2 Output Legend Relay de-energised Relay energised Output open Output closed U - Supply R1/R2 - 2 timed outputs Ta - Adjustable On-delay Tr - Adjustable Off-delay Y1 - Retrigger / Restart control R2 inst. - The second output is instantaneous if the right position is selected T - Timing period R4 - Delta contact output t - Delay to switch ON Delta contact output R3 - Star-Delta contact output