RE8RA41FUTQ SCHNEIDER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 6

Technical content

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. 7/9/2011 Product data sheet Characteristics RE8RA41FUTQ industrial timing relay - 20..1800 s - type C - 110..240 V AC - 1 C/O Main Range of product Zelio Time Product or component type Optimum industrial timing relay Component name RE8 Time delay type C Time delay range 20...1800 s [Us] rated supply voltage 110...240 V AC, 50/60 Hz Sale per indivisible quantity Complementary Discrete output type Relay Contacts material 90/10 silver nickel contacts Width pitch dimension 22.5 mm Connections - terminals Screw terminals 2 x 1.5 mm², flexible cablewith cable end Screw terminals 2 x 2.5 mm², flexible cablewithout cable end Setting accuracy of time delay +/- 20 % of full scale Repeat accuracy < 1 % Voltage drift < 2.5 %/V Temperature drift < 0.2 %/°C Minimum pulse duration 26 ms Reset time 50 ms Maximum switching voltage 250 V Mechanical durability 20000000 cycles [Ith] conventional free air thermal current 8 A [Ie] rated operational current <= 2 A at 24 V, DC-13 for 70 °C conforming to IEC 60947-5-1/1991 <= 2 A at 24 V, DC-13 for 70 °C conforming to VDE 0660 <= 3 A at 24 V, AC-15 for 70 °C conforming to IEC 60947-5-1/1991 <= 3 A at 24 V, AC-15 for 70 °C conforming to VDE 0660 <= 0.1 A at 250 V, DC-13 for 70 °C conforming to IEC 60947-5-1/1991 <= 0.1 A at 250 V, DC-13 for 70 °C conforming to VDE 0660 <= 0.2 A at 115 V, DC-13 for 70 °C conforming to IEC 60947-5-1/1991 <= 0.2 A at 115 V, DC-13 for 70 °C conforming to VDE 0660 Minimum switching capacity 10 mA at 12 V Input voltage 110...240 V (Y1) Maximum switching current 10 mA (Y1) Input compatibility 2-wire sensors DC with leakage current < 1 mA, cable length: <= 50 m (Y1) Marking CE Overvoltage category III conforming to IEC 60664-1 [Ui] rated insulation voltage 250 V conforming to IEC

300 V conforming to CSA

Supply disconnection value > 0.1 Uc Operating position Any position without derating factor Surge withstand 2 kV conforming to IEC 61000-4-5 level 3 Power consumption in VA 1.8 VA at 110 V

8.5 VA at 240 V

Terminal description (15-16-18)OC_ON (A1-A2)CO (Y1)UNUSED Height 78 mm Width 22.5 mm Depth 80 mm Product weight 0.11 kg Environment Immunity to microbreaks 3 ms Standards EN/IEC 61812-1 Product certifications CSA GL UL Ambient air temperature for storage -40...85 °C Ambient air temperature for operation -20...60 °C Relative humidity 15...85 % 3K3 conforming to IEC 60721-3-3 Vibration resistance 0.35 mm 10...55 Hz conforming to IEC 60068-2-6 Shock resistance 15 gn (duration = 11 ms conforming to IEC 60068-2-27 IP degree of protection IP20 (terminals) IP50 (casing) Pollution degree 3 conforming to IEC 60664-1 Dielectric test voltage 2.5 kV Non-dissipating shock wave 4.8 kV Resistance to electrostatic discharge 6 kV in contact conforming to IEC 61000-4-2 level 3 8 kV in air conforming to IEC 61000-4-2 level 3 Resistance to electromagnetic fields 10 V/m conforming to IEC 61000-4-3 level 3 Resistance to fast transients 2 kV conforming to IEC 61000-4-4 level 3 Disturbance radiated/conducted CISPR11 group 1- class A CISPR22 - class A RoHS EUR status Compliant RoHS EUR conformity date 0626

Function C: Timing After Opening of Control Contact

Description

After power-up and closing of the control contact C, the output R closes. When control contact C re-opens, timing T starts. At the end of the timing period, the output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous. Function: 1 Output Function: 2 Outputs 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.) Legend Relay de-energised Relay energised Output open Output closed C Control contact G Gate R Relay or solid state output R1/ 2 timed outputs inst. The second output is instantaneous if the right position is selected T Timing period Ta Adjustable On-delay Tr Adjustable Off-delay U Supply

Width 22.5 mm Rail Mounting Screw Fixing

Recommended Application Wiring Diagram Control of Several Relays Control of several relays with a single external control contact The external control contact C may be an electronic control device, for example a true-wire sensor. In this case A1-A2= 24 Vdc and the control device can only control-up to a maximum of 4 relays. Connection of a 2-Wire Sensor Leakage current (open state) if < 1 mA.

A.C. Load Curve 1 Electrical durability of contacts on resistive loading millions of operating cycles X Current broken in A Y Millions of operating cycles A.C. Load Curve 2 Reduction factor k for inductive loads (applies to values taken from durability curve 1). X Power factor on breaking (cos ϕ) Y Reduction factor k Example: An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current consumption equal to 0.1 A and cos apply a reduction coefficient k to this number of cycles as indicated by curve 2. For cos ϕ = 0.3: k = 0.6 The electrical durability therefore becomes:1.5 106 operating cycles x 0.6 = 900 000 operating cycles. D. C. Load Limit Curve X Current in A Y Voltage in V

1 L/R = 20 ms

2 L/R with load protection diode

3 Resistive load