time delay relay 6 functions - 0.05..1 s - 24 V AC DC - 1OC Discontinued Commercial status Discontinued on: 01 June 2016 End-of-service on: 01 June 2016 Main Range of product Zelio Time Product or component type Industrial timing relay Component name RE7 Time delay type Di D W C A H Time delay range 0.05 s...300 h Complementary Discrete output type Relay Contacts material 90/10 silver nickel contacts Width pitch dimension 22.5 mm [Us] rated supply voltage 110...240 V AC 50/60 Hz
24 V AC/DC 50/60 Hz
42...48 V AC/DC 50/60 Hz Connections - terminals Screw terminals, 2 x 1.5 mm² flexible with cable end Screw terminals, 2 x 2.5 mm² flexible without cable end Tightening torque 0.6…1.1 N.m Setting accuracy of time delay +/- 10 % of full scale Repeat accuracy +/- 0.2 % Temperature drift < 0.07 %/°C Voltage drift < 0.2 %/V Minimum pulse duration 20 ms Reset time 50 ms Maximum switching voltage 250 V AC/DC Mechanical durability 20000000 cycles [Ith] conventional free air thermal current 8 A Maximum [Ie] rated operational current 2 A DC-13 24 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
0.1 A DC-13 250 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications Mar 4, 2021
0.2 A DC-13 115 V at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
3 A AC-15 at 70 °C conforming to IEC 60947-5-1/1991/VDE 0660
Minimum switching capacity at 12 V 10 mA Input voltage < 60 V X1Z2 terminal(s) < 60 V Y1Z2 terminal(s) Maximum switching current 1 mA (X1Z2) 1 mA (Y1Z2) Input compatibility 3/4 wires sensors PNP/NPN without internal load <50 m X1Z2 terminal(s) 3/4 wires sensors PNP/NPN without internal load <50 m Y1Z2 terminal(s) Potentiometer characteristic Linear 47 kOhm (+/- 20 %), 0.2 W, cable length <25 m Z1Z2 terminal(s) Marking CE Overvoltage category III conforming to IEC 60664-1 [Ui] rated insulation voltage 250 V between contact circuit and control inputs IEC certified
250 V between contact circuit and power supply IEC certified
300 V between contact circuit and control inputs CSA certified
300 V between contact circuit and power supply CSA certified
Supply disconnection value > 0.1 Uc Operating position Any position without derating Surge withstand 2 kV conforming to IEC 61000-4-5 level 3 Power consumption in VA 0.7 VA at 24 V
1.6 VA at 48 V
1.8 VA at 110 V
8.5 VA at 240 V
Maximum power consumption in W 0.5 W at 24 V
1.2 W at 48 V
Terminal description (Y1)UNUSED (15-16-18)OC (Z1)UNUSED (Z2)UNUSED (B1-A2)CO ALT (X1)UNUSED Height 78 mm Width 22.5 mm Depth 80 mm Net weight 0.15 kg Environment Immunity to microbreaks 3 ms Standards EN/IEC 61812-1 Product certifications CSA GL UL Ambient air temperature for storage -40…85 °C Ambient air temperature for operation -20…60 °C Relative humidity 15…85 % 3K3 conforming to IEC 60721-3-3 Vibration resistance 0.35 mm (f= 10…55 Hz) conforming to IEC 60068-2-6 Shock resistance 15 gn for 11 ms conforming to IEC 60068-2-27 IP degree of protection IP20 (terminals) IP50 (housing) Pollution degree 3 conforming to IEC 60664-1 Dielectric strength 2.5 kV Non-dissipating shock wave 4.8 kV Resistance to electrostatic discharge 6 kV in contact conforming to IEC 61000-4-2 level 3 8 kV in air conforming to IEC 61000-4-2 level 3 Resistance to electromagnetic fields 10 V/m conforming to IEC 61000-4-3 level 3 Resistance to fast transients 2 kV conforming to IEC 61000-4-4 level 3 Disturbance radiated/conducted CISPR 11 group 1 - class A CISPR 22 - class A
Package 1 Weight 0.131 kg Package 1 Height 0.270 dm Package 1 width 0.820 dm Package 1 Length 0.870 dm Contractual warranty Warranty 18 months
Width 22.5 mm Rail Mounting Screw Fixing
Recommended Application Wiring Diagram Start on Energisation
1 Supply
2 12…48 V 3 24 V
Recommended Application Wiring Diagram Start by External Control 2 12…48 V 3 24 V
Recommended Application Wiring Diagram External Control of Partial Stop 2 12…48 V 3 24 V
Connection of Potentiometer
UNEXPECTED EQUIPMENT OPERATION No galvanic isolation between supply terminals and control inputs. Failure to follow these instructions can result in death, serious injury, or equipment damage.
A.C. Load Curve 1 Electrical durability of contacts on resistive loading millions of operating cycles X Current broken in A Y Millions of operating cycles A.C. Load Curve 2 Reduction factor k for inductive loads (applies to values taken from durability curve 1). X Power factor on breaking (cos ϕ) Y Reduction factor k Example: An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current consumption equal to 0.1 A and cos ϕ reduction coefficient k to this number of cycles as indicated by curve 2. For cos ϕ = 0.3: k = 0.6 The electrical durability therefore becomes:1.5 106 operating cycles x 0.6 = 900 000 operating cycles. D. C. Load Limit Curve
1 L/R = 20 ms
2 L/R with load protection diode
3 Resistive load
Function A : Power on Delay Relay
Description
The timing period T begins on energisation. After timing, the output(s) R close(s). The second output can be either timed or instantaneous. Function: 1 Output Function: 2 Outputs 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Function C : Off-Delay Relay with Control Signal After power-up and closing of the control contact C, the output R closes. When control contact C re-opens, timing T starts. At the end of the timing period, the output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous. Function: 1 Output Function: 2 Outputs 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Function D : Symmetrical Flasher Relay (Starting Pulse Off) Repetitive cycle with two timing periods T of equal duration, with output(s) R changing state at the end of each timing period T. The second output can be either timed or instantaneous. Function: 1 Output Function: 2 Outputs 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Function Di : Symmetrical Flasher Relay (Starting Pulse On) Repetitive cycle with two timing periods T of equal duration, with output(s) R changing state at the end of each timing period T. The second output can be either timed or instantaneous. Function: 1 Output Function: 2 Outputs 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Function H : Interval Relay On energisation of the relay, timing period T starts and the output(s) R close(s). At the end of the timing period T, the output(s) R revert(s) to its/ their initial state. The second output can be either timed or instantaneous. Function: 1 Output Function: 2 Outputs 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)
Function W : Interval Relay with Control Signal Off After power-up and opening of the control contact, the output(s) close(s) for a timing period T. At the end of this timing period the output(s) revert(s) to its/their initial state. The second output can be either timed or instantaneous. Function: 1 Output Function: 2 Outputs 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.).
R Relay or solid state output R1/R2 2 timed outputs R2 inst. The second output is instantaneous if the right position is selected T Timing period Ta - Adjustable On-delay Tr - Adjustable Off-delay U Supply RE7ML11BU is replaced by: Relay Output RE22R1MYMR Modular timing relay, 8 A, 0.05 s…300 h, 1 CO, multi-function, 24...240 V AC/DC Qty 1 Reason for Substitution: End of life | Substitution date: 18 August 2016