RE17RMJU SCHNEIDER | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 17

Technical content

Harmony, Modular timing relay, 8 A, 1 CO, 0,1 s..100 h, multifunction, 12 V AC/DC Product availability : Non-Stock - Not normally stocked in distribution facility Price* : 75.00 USD Main Range of Product Harmony Timer Relays Product or Component Type Multifunction relay Discrete output type Relay Maximum Width 0.69 in (17.5 mm) Device short name RE17R Time delay type Power on-delay On-delay and off-delay Interval Off-delay Symmetrical flashing Time delay range 1...10 s 6...60 s 10...100 h 1...10 min 1...10 h 0.1...1 s 6...60 min Nominal output current 8 A Complementary Contacts type and composition 1 C/O Contacts material Cadmium free Maximum Height 3.54 in (90 mm) Maximum Depth 2.83 in (72 mm) Control type Selector switch front panel [Us] rated supply voltage 12 V AC/DC 50/60 Hz Supply frequency 50...60 Hz +/- 5 % Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications * Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price. Aug 25, 2021

Release of input voltage 5 V Housing material Self-extinguishing Repeat accuracy +/- 0.5 % IEC 61812-1 Temperature Drift +/- 0.05 %/°C Voltage drift +/- 0.2 %/V Setting accuracy of time delay +/- 10 % of full scale 25 °C IEC 61812-1 Control signal pulse width 100 ms with load in parallel typical 30 ms typical Insulation resistance 100 MOhm 500 V DC IEC 60664-1 Reset time 120 ms on de-energisation typical On-load factor 100 % Power consumption in VA 0…0.7 VA 12 V AC Maximum power consumption in W 0.5 W 12 V DC Minimum switching current 10 mA 5 V DC Maximum switching current 8 A AC/DC Maximum switching voltage 250 V AC Breaking capacity 2000 VA Operating frequency 10 Hz Electrical durability 100000 cycles resistive 8 A 250 V AC Mechanical durability 10000000 cycles Dielectric strength 2.5 kV 1 mA/1 minute 50 Hz IEC 61812-1 [Uimp] rated impulse withstand voltage 5 kV 1.2/50 µs Power on delay 100 ms Marking CE Creepage distance 4 kV/3 IEC 60664-1 Safety reliability data MTTFd = 296.8 years B10d = 270000 Mounting position Any position in relation to normal vertical mounting plane Mounting support 35 mm DIN rail conforming to EN/IEC 60715 Local signalling LED indicator on steady: relay energised, no timing in progress LED indicator 80 % ON and 20 % OFF flashing: timing in progress LED indicator 5 % ON and 95 % OFF pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) Net Weight 0.15 lb(US) (0.07 kg) Time delay type A, Ac, At, B, Bw, C, D, Di, H, Ht Functionality Multifunction Compatibility code RE17 Environment Immunity to microbreaks 20 ms Standards 2006/95/EC 2004/108/EC EN 61000-6-4 EN 61000-6-1 EN 61000-6-3 IEC 61812-1 EN 61000-6-2 Product Certifications CSA GL CULus Ambient Air Temperature for Storage -22…140 °F (-30…60 °C)

Ambient Air Temperature for Operation IP degree of protection IP20 IEC 60529 terminal block) IP40 IEC 60529 housing) IP50 IEC 60529 front panel) Vibration resistance 20 m/s² 10…150 Hz)IEC 60068-2-6 Shock resistance 15 gn 11 ms IEC 60068-2-27 Relative Humidity 93 % without condensation IEC 60068-2-30 Electromagnetic compatibility Electrostatic discharge immunity test 6 kV in contact) level 3 IEC 61000-4-2 Electrostatic discharge immunity test 8 kV in air) level 3 IEC 61000-4-2 Susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz) level 3 IEC 61000-4-3 Electrical fast transient/burst immunity test 1 kV capacitive connecting clip) level 3 IEC 61000-4-4 Electrical fast transient/burst immunity test 2 kV direct) level 3 IEC 61000-4-4 1.2/50 µs shock waves immunity test 1 kV differential mode) level 3 IEC 61000-4-5 1.2/50 µs shock waves immunity test 2 kV common mode) level 3 IEC 61000-4-5 Conducted RF disturbances 10 V 0.15...80 MHz) level 3 IEC 61000-4-6 Voltage dips and interruptions immunity test 0 % 1 cycle) IEC 61000-4-11 Voltage dips and interruptions immunity test 70 % 25/30 cycles) IEC 61000-4-11 Conducted and radiated emissionsclass B EN 55022 Ordering and shipping details Category 22370 - RE, RM MISC TIMERS & COUNTERS Discount Schedule CP2 GTIN 03606480552748 Nbr. of units in pkg. 1 Package weight(Lbs) 2.68 oz (76 g) Returnability No Country of origin ID Packing Units Unit Type of Package 1 PCE Package 1 Height 1.06 in (2.7 cm) Package 1 width 3.11 in (7.9 cm) Package 1 Length 3.74 in (9.5 cm) Unit Type of Package 2 S02 Number of Units in Package 2 40 Package 2 Weight 7.66 lb(US) (3.475 kg) Package 2 Height 5.91 in (15 cm) Package 2 width 11.81 in (30 cm) Package 2 Length 15.75 in (40 cm) Offer Sustainability Sustainable offer status Green Premium product California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov REACh Regulation REACh Declaration EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information

Width 17.5 mm

1) Contact Y1:

  • Control for functions B, C, Ac, Bw, Ad, Ah, N, O, W, T, Tt.
  • Partial stop for functions At, Ht and Pt.
  • Function D if Di selected.
  • Not used for functions A, H and P.

Function A : Power on Delay Relay

Description

The timing period T begins on energisation. After timing, the output(s) R close(s). The second output can be either timed or instantaneous. Function: 1 Output Function: 2 Outputs 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)

Function Ac: On-Delay & Off-Delay with Control Signal After energisation of power supply and energization of Y1 causes the timing period T to start. At the end of this timing period, the output(s) R close(s). When deenergization of Y1, the timing T starts. At the end of this timing period T,the output(s) R revert(s) to its/their initial position. The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 1 Output Function: 2 Outputs

Function At : Power on Delay Relay (Summation) with Control Signal After power-up, the first opening of control contact C starts the timing. Timing can be interrupted each time control contact closes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output relay closes. Function: 1 Output T = t1 + t2 +...

Function B : Interval Relay with Control Signal After power-up, pulsing or maintaining control contact C starts the timing T. The output R closes for the duration of the timing period T then reverts to its initial state. Function: 1 Output

Function Bw : Double Interval Relay with Control Signal On closing and opening of control contact C, the output R closes for the duration of the timing period T. Function: 1 Output

Function C : Off-Delay Relay with Control Signal After power-up and closing of the control contact C, the output R closes. When control contact C re-opens, timing T starts. At the end of the timing period, the output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous. Function: 1 Output Function: 2 Outputs 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)

Function D: Symmetrical Flashing Relay (Starting Pulse Off) On energisation of power supply, output(s) R starts at its/their initial state for timing duration T then change(s) to output(s) R close(s) for the same timing duration T.This cycle is repeated indefintely until power supply removal.Specially for RE17*, RE22R2AMU, RE22R2MMW, RE22R2MMU, RE22R2MJU,this D function can only be initiated by energizing Y1 permanently.The second output (R2) can be either timed (when set to "TIMED") or instantaneous (when set to "INST"). Function: 1 Output Function: 2 Outputs Function: 1 Output with Retrigger / Restart Control Function: 2 Output with Retrigger / Restart Control

Function Di : Symmetrical Flasher Relay (Starting Pulse On) Repetitive cycle with two timing periods T of equal duration, with output(s) R changing state at the end of each timing period T. The second output can be either timed or instantaneous. Function: 1 Output Function: 2 Outputs 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)

Function H : Interval Relay On energisation of the relay, timing period T starts and the output(s) R close(s). At the end of the timing period T, the output(s) R revert(s) to its/ their initial state. The second output can be either timed or instantaneous. Function: 1 Output Function: 2 Outputs 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)

Function Ht: Interval Relay & With Pause / Summation Control On energisation of power supply, output(s) R close(s) and timing period T starts. The timing can be interrupted / paused each time X1 energizes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output(s) R revert(s) to its/their initial state Reenergization of X1 will also cause output(s) R close(s) if the time has elapsed and restart the same operation as described at the beginning. Except for RE17*, RE22R2MMW, RENF22R2MMW, RE22R2MMU and RE22R2MJU, timing can be interrupted / paused each time Y1 energizes. The second output (R2) can be either timed (when set to “TIMED” or instantaneous (when set to “INST”). Function: 1 Output T = t1 + t2 +... Function: 2 Outputs T = t1 + t2 +... Function: 1 Output with Retrigger / Restart Control T = t1 + t2 +... Function: 2 Outputs with Retrigger / Restart Control T = t1 + t2 +...

R Relay or solid state output R1/R2 2 timed outputs R2 inst. The second output is instantaneous if the right position is selected T Timing period Ta - Adjustable On-delay Tr - Adjustable Off-delay U Supply