Harmony, Modular timing relay, 0.7 A, 1 CO, 1 s..100 h, on delay, solid state output, spring terminals, 24..240 V AC/DC Product availability : Non-Stock - Not normally stocked in distribution facility Price* : 47.67 USD Main Range of Product Harmony Timer Relays Product or Component Type Single function relay Discrete output type Solid state Maximum Width 0.69 in (17.5 mm) Component name RE17L Time delay type Power on-delay Time delay range 1...10 s 10...100 h 6...60 s 0.1...1 s 1...10 min 6...60 min 1...10 h Nominal output current 0.7 A Complementary Maximum Height 3.54 in (90 mm) Maximum Depth 2.83 in (72 mm) Control type Selector switch front panel [Us] rated supply voltage 24...240 V AC/DC 50/60 Hz Supply frequency 50...60 Hz +/- 5 % Control signal pulse width 0.05 s typical Insulation resistance 100 MOhm 500 V DC IEC 60664-1 [Uimp] rated impulse withstand voltage 5 kV 1.2/50 µs Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications * Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price. Aug 25, 2021

Dielectric strength 2.5 kV 1 mA/1 minute 50 Hz IEC 61812-1 Housing material Self-extinguishing Repeat accuracy +/- 0.5 % IEC 61812-1 Temperature Drift +/- 0.05 %/°C Voltage drift +/- 0.2 %/V Setting accuracy of time delay +/- 10 % of full scale 25 °C IEC 61812-1 Reset time 350 ms on de-energisation typical On-load factor 100 % Power consumption in VA 0…3 VA 240 V AC Maximum power consumption in W 1.5 W 240 V DC Breaking capacity 0.5 A AC/DC UL

0.7 A AC/DC 68 °F (20 °C)

Maximum output current 20 A Minimum switching current 10 mA Maximum leakage current 5 mA Maximum switching voltage 250 V AC/DC Maximum voltage drop <4 V 3-wire <8 V 2-wire Electrical durability 100000000 cycles Marking CE Creepage distance 4 kV/3 IEC 60664-1 Safety reliability data MTTFd = 353.8 years B10d = 320000 Mounting position Any position in relation to normal vertical mounting plane Mounting support 35 mm DIN rail conforming to EN/IEC 60715 Net Weight 0.11 lb(US) (0.05 kg) Time delay type A Functionality On-delay timing Compatibility code RE17 Environment Immunity to microbreaks 20 ms Derating factor 5 mA/°C Standards 2004/108/EC EN 61000-6-1 2006/95/EC EN 61000-6-3 EN 61000-6-2 IEC 61812-1 EN 61000-6-4 Product Certifications CSA CULus DNV-GL EAC Ambient Air Temperature for Storage -22…140 °F (-30…60 °C) Ambient Air Temperature for Operation IP degree of protection IP20 IEC 60529 terminal block) IP40 IEC 60529 housing) IP50 IEC 60529 front panel) Vibration resistance 20 m/s² 10…150 Hz)IEC 60068-2-6 Shock resistance 15 gn 11 ms IEC 60068-2-27 Relative Humidity 93 % without condensation IEC 60068-2-30

Electromagnetic compatibility Electrostatic discharge immunity test 6 kV in contact) level 3 IEC 61000-4-2 Electrostatic discharge immunity test 8 kV in air) level 3 IEC 61000-4-2 Susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz) level 3 IEC 61000-4-3 Electrical fast transient/burst immunity test 1 kV capacitive connecting clip) level 3 IEC 61000-4-4 Electrical fast transient/burst immunity test 2 kV direct) level 3 IEC 61000-4-4 1.2/50 µs shock waves immunity test 1 kV differential mode) level 3 IEC 61000-4-5 1.2/50 µs shock waves immunity test 2 kV common mode) level 3 IEC 61000-4-5 Conducted RF disturbances 10 V 0.15...80 MHz) level 3 IEC 61000-4-6 Voltage dips and interruptions immunity test 0 % 1 cycle) IEC 61000-4-11 Voltage dips and interruptions immunity test 70 % 25/30 cycles) IEC 61000-4-11 Conducted and radiated emissionsclass B EN 55022 Ordering and shipping details Category 22370 - RE, RM MISC TIMERS & COUNTERS Discount Schedule CP2 GTIN 03606489861520 Nbr. of units in pkg. 1 Package weight(Lbs) 2.22 oz (63 g) Returnability No Country of origin ID Packing Units Unit Type of Package 1 PCE Package 1 Height 1.06 in (2.7 cm) Package 1 width 3.15 in (8 cm) Package 1 Length 3.74 in (9.5 cm) Offer Sustainability Sustainable offer status Green Premium product California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov REACh Regulation REACh Declaration EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Function A : Power on Delay Relay

Description

The timing period T begins on energisation. After timing, the output(s) R close(s). The second output can be either timed or instantaneous. Function: 1 Output Function: 2 Outputs 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.)

R Relay or solid state output R1/R2 2 timed outputs R2 inst. The second output is instantaneous if the right position is selected T Timing period Ta - Adjustable On-delay Tr - Adjustable Off-delay U Supply