RCI-11-000-A E-T-A | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 7

Technical content

INTELLIGENT POWER DISTRIBUTION SYSTEMS RCI11 RCI11 The RCI11 Remote Control Interface allows remote control and monitoring of the system and its connected loads, reducing main- tenance costs and providing maximum transparency. It helps in- tegrate the ControlPlex® Rack system into the network surroun- dings and into the centralised corporate management system. The RCI11 provides access to all installed ESX300-S circuit protectors via the internal bus system and can enquire or store individual m e- asuring data, status conditions and fault indications and forward them to the superordinate control unit or execute com m ands from the control unit for controlling purposes. The RCI11 Remote Con- trol Interface can be extended during operation “Hot Plug & Play“. INTELLIGENT POWER DISTRIBUTION SYSTEMS RCI11 TYPICAL FEATURES YOUR BENEFITS

  • Rated voltage DC 20...75 V
  • Integrated web server
  • Integrated BUS interface
  • External terminal, RJ45 socket
  • Limited maintenance time on site due to manual remote control and monitoring of loads
  • Remote power reset of the application in the event of a fault
  • Increased system availability through param eter-dependent / auto- matic switching of loads
  • Easy integration into an existing centralised management system thanks to SNMP and Modbus TCP/IP or remote control and moni- toring via web browser surface.
  • Early detection of errors by continuous recording of measuring da- ta
  • Energy data collection for each connected load TYPICAL APPLICATIONS COMPLIANCE Telecommunications and datacom, energy providers, industrial swit- ching and control systems, rail engineering, infrastructure WEB LINKS Further information, Instruction manual, Open Source licenses, Inter- national approvals, Technical basics, REACH , RoHS , Contact global.e-t-a.com 1225

INTELLIGENT POWER DISTRIBUTION SYSTEMS RCI11 GENERAL INFORMATION FURTHER INFORMATION Instruction manual https://www.e-t-a.com/datei/17796 TECHNICAL DATA (T u = +25 °C, Ub = DC 48 V) ELECTRICAL DATA Rated voltage range DC 20...75 V (Power-D-Box ® CP - input voltage) Dielectric strength DC 100 V for 1 ms Power consumption I Typ. 25 mA at DC 48 V operating voltage Power consumption Typ. 3 W (max. power consumption 5 W) External connection 10 / 100 Mbit/s, 10 Base-T Ethernet, RJ45-connection sleeve for standard network cable of cate- gory Cat-5, type "Shielded Twisted Pair" LED for operating condition signallingMulticoloured (red, green, blue)

  • Status LEDs Insulation co-ordination (IEC 60934)1000 V (according to EN 60934 – table 20 rated voltage > 50. ≤ 125 V) MECHANICAL DATA Mounting position Vertical, cooling Convection cooling Mass Approx. 100 g PROTOCOLS HTTP / HTTPS (Hypertext Transfer Protocol) Integrated web server Tested browsers Google Chrome: v115.0.5790.110 Firefox: v116.0.3 Edge: 115.0.1901.203 SNMP v1, v2c, v3 protocol Protocol for integration into a management system SNMP-MIB (Management Information Base) File: CP-RCIxx_SNMP-MIB_Vxx.mib Modbus TCP/IP Protocol for integration into a management system SSH v2 (Secure Shell) System configuration and safety settings Recommended SSH v2 terminal pro- gramme LePuttyc 1997-2006 Simon Tathman NTP (Network Time Protocol) Automatic time synchronisation via an NTP server IP protocol (internet protocol) IPv4 and IPv6 address formats are supported DHCP server (Dynamic Host Config. Protocol) Is supported, allows automatic assignment of network parameters, e.g. the IP address SYSTEM DATA Processor RM Cortex-A53, 64 Bit, 1.2GHz OS Linux Kernel 4.14 Volatile 1GB-LPDDR2-SDRAM-memory Non-Volatile 8GB-eMMC-Flash 8MB NOR-Flash 1MB MRAM AMBIENT CONDITIONS Ambient temperature -20...+60 °C (without condensation, cf. EN 60204-1) Storage temperature -30...+70 °C global.e-t-a.com 1225

INTELLIGENT POWER DISTRIBUTION SYSTEMS RCI11 Damp heat Test according to IEC 60068-2-78, 3K6 climate class according to EN 60721 96 hours at 95 % relative humidity, 40 °C Vibration Test according to IEC 60068-2-6, test Fc 3 g Actuating area IP code (standard) IP 20 (w hen rack is fully populated and SU B-D connectors are plugged in) Terminal area IP code (standard) IP00 ESD 4 kV / air 8 kV EMC requirements (EMC directive, CE logo) emitted interference EN 61000-6-3 EMC requirements (EMC directive, CE logo) resistance to disturbances EN 61000-6-2 FURTHER INFORMATION OPERATING CONDITIONS: LED STATUS INDICATION Momentary switch Status LED colour Status LED Importance Description - G reen ON Normal operation Continuously ON when booting is com- pleted and the RCI11 is operating faultless- ly. Network connection can be established af- ter another 10 sec. Pushed down for 35 sec G reen Blinking Reset IP address to factory settings By pushing the reset button for 35 seconds, the IP settings can be reset to factory set- tings. For visual con- trol that the reset but- ton has been pushed down long enough, the green LED w ill blink for 5 seconds (see /f_ig. 1). - Red ON Internal failure RCI11Serious internal fault in the RCI11 module. The module is no lon- ger operational. The RCI11 module should be replaced. - Red ON Serious internal failure BUS (EL-BUS) ELBus® Failure Impai- red communication to the ESX300-S cir- cuit protectors and the RCI11 module. - Blue ON Ethernet link availableIf a network connec- tion is established in operation (layer 1), the LED will be lighted blue for some 10 se- conds. - Blue ON Reset IP address to factory settings The blue LED will be lighted for 10 seconds when the IP address has successfully be- en reset to factory set- tings, see /f_ig. 1 Auto- matic booting will fol- low, this can last up to 60 seconds. - - OFF Booting The RCI11 module is booting. Booting can take up to 60 seconds. - - OFF No supply voltage No supply voltage or w rong polarity. global.e-t-a.com 1225

INTELLIGENT POWER DISTRIBUTION SYSTEMS RCI11 Pushed down for 3 sec - OFF W arm boot The system can be re- set by pushing the re- set button for 3 se- conds (warm boot) - - OFF RCI11 module defec- tive Serious internal fault in the RCI11 module. LED remains dark af- ter booting (max. 60 sec). The RCI11 mo- dule must be replaced. ORDERING NUMBER CODE R C I A

1 TYPE NUMBER

RCI Remote Control Interface

2 VERSION

11 Standard, pluggable (front plate, w ithout enclosure)

3 INTERNAL INTERFACES

0 With EL-BUS interface (standard)

4 VOLTAGE RANGE (SUPPLY)

0 DC 20...75 V

5 EXTERNAL INTERFACES

0 Ethernet with RJ45 connection

6 SOFTWARE PROTOCOLS

A IP v4, IP v6, SN M P v1, v2c, v3, http, https, SSH v2, M odbus-TCP , LD A P ,N TP COMPLIANCE CE according to EMC directive (EN 61000-6-3 & EN 61000-3-2) Compliance accord- ing to EN60950-1 / UL60950-1 global.e-t-a.com 1225

INTELLIGENT POWER DISTRIBUTION SYSTEMS RCI11 DIMENSIONS DIMENSIONS SCHEMATIC DIAGRAMS PIN ASSIGNMENT OF 20-POLE PCB CONNECTOR global.e-t-a.com 1225

INTELLIGENT POWER DISTRIBUTION SYSTEMS RCI11 APPLICATION EXAMPLES FRONT RCI11 FUNCTIONAL DIAGRAMS FIG. 1: FUNCTION IP-RESET BY PRESSING THE RESET BUTTON WITH LED ACCESSORIES OPTIONAL ACCESSORIES FROM CP P ow er-D -Box® for Con- trolPlex® Rack The Power-D-Box ® CP is a modular power distribution system. Depending on the respective application, the compact 2 HU enclosure can accommo- date these system components: ESX300-S, RSI10, RCI11 oder EAI300. User friendliness is of top priority in the event of a system extension with the sys- tem live w ithout causing dow ntim es. A ll sub-assem blies are hot-sw appable without affecting neighbouring components. Depending on the application, term ination can be placed both on the front or on the rear. M ajor applicati- on areas of the ControlPlex® Rack system are com m unication technolo- gy equipment both in the negative (DC -48 V or DC -60 V) and in the positive voltage range (D C 24 V, 48 V, 60 V). global.e-t-a.com 1225

INTELLIGENT POWER DISTRIBUTION SYSTEMS RCI11 FURTHER PRODUCTS

RELATED PRODUCTS

ESX300-S minus The hot pluggable ESX300-S minus electronic circuit protector ensures re- liable overcurrent protection by means of electronic current limitation and load disconnection. It reliably prevents the destruction of electronic sub-as- semblies or load lines in power supply systems in a voltage range of DC -48 V and D C -60 V. Thanks to a selective load disconnection, a voltage dip is prevented in the event of a failure and other faultless devices in the circuit re- main working. The integral bus interface can transmit the recorded measuring values and status messages to the RCI11 control interface, where they can be used to automatically trigger actions or for data collection and monitoring. ESX300-S plus The hot pluggable ESX300-S plus electronic circuit protector ensures reliable overcurrent protection by means of electronic current limitation and load dis- connection. It reliably prevents the destruction of electronic sub-assem blies or load lines in pow er supply system s in D C +24 V, D C +48 V and D C +60 V voltage ranges. Thanks to its selective load disconnection, a voltage dip is prevented in the event of a failure and fault-free devices can be further ope- rated. The integral bus interface can transmit the recorded measuring values and status messages to the RCI11 control interface, where they can be used to automatically trigger actions or for data collection and monitoring. EAI300 Combined with the RCI11, the EAI300 External Alarm Interface allows record- ing of external sensor data and alarm signalling in the management system. It includes e.g. additional monitoring and indication of door contacts or tempe- rature sensors in the technical room . This provides high system transparency and fast intervention in the event of alarms. Thanks to programmable logical links, operating conditions of the ESX300-S can be linked to external encoder signals that enable automatic switching operations. Instead of the ESX300-S electronic circuit protector, the EAI300 can be easily plugged into an empty slot of the ControlPlex® Rack system without shutting down the connected loads. This allows connection of external signalling devices in the control ca- binets without requiring additional space. RSI10 The RSI10 Remote Signalling Interface ensures reliable and early detection of critical system conditions. It can communicate with all circuit protectors in- stalled in the ControlPlex® Rack via internal BUS connection. When one of the circuit protectors is disconnected from the related load due to an over- current etc., the R SI10 w ill externally indicate this status via a potential-free group signal, e.g. to a m onitoring system . It is the perfect w ay to m inim ise downtimes and reduce operational and maintenance costs. All information and data given on our products are accurate and reliable to the best of our knowledge, but E-T-A does not accept any responsibility for the use in applications which are not in accordance with the present specification. E-T-A reserves the right to change specifications at any time in the interest of technical improvement. Dimensions are subject to change without notice. Please enquire for the latest dimensional drawing with tolerances if required. All dimensions, data, pictures and descriptions are for information only and are not binding. Amendments, errors and omissions excepted. Ordering part numbers may differ from the device marking. global.e-t-a.com 1225