MODEL: R9MWTU R9MWTU SPECIFICATIONS ES-6221 Rev.11 Page 1/7 https://www.m-system.co.jp/ Remote I/O R9 Series MULTI POWER MONITORING UNIT (Clamp-on current sensor CLSE, Modbus) Functions & Features

  • Multi Power Monitoring Unit for Modbus.
  • By using clamp-on current sensors, there is no need of current transformers.
  • Up to 8 circuits can be measured. (Common voltage measurement)
  • Current sensors are easy to install in existing systems. Wide input range of 5 to 600 A is availabe.
  • All measured values, counter values, display mode, setting data are stored in the non-volatile memory when power is off.
  • By using SD card, data logging of current and power etc. with calendar is available. 125 (4.92) mm (inch) 140 (5.51) 80 (3.15) MODEL: R9MWTU–2001–AD4[1]

ORDERING INFORMATION

  • Code number: R9MWTU-2001-AD4[1] Specify a code from below for [1]. (e.g. R9MWTU-2001-AD4/Q)
  • Specify the specification for option code /Q (e.g. /C01/SET) CONFIGURATION 2: Single-phase/2-wire, 3-phase/3-wire, single-phase/3-wire; 8 circuits CONNECTION 0: Terminal block I/O 0: Without EXTENSION UNIT 1: With connection (Extension unit does not conform to EU directive) AUXILIARY POWER SUPPLY AD4: universal 100 – 240 V AC (Operational range 85 – 264 V, 50 / 60 Hz) / 110 – 240 V DC (Operational range 99 – 264 V, ripple 10 %p-p max) [1] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating EX-FACTORY SETTING /SET: Preset according to the Ordering Information Sheet (No. ESU-6221)

RELATED PRODUCTS

  • Discrete I/O extension unit (model: R9WTU-ED)
  • Multi power monitoring extension unit (model: R9WTU-EP)
  • PC configurator software (model: PMCFG) Software downloadable at M-System’s web site. A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
  • Clamp-on current sensor (model: CLSE) The clamp-on current sensors, not included in this product package, must be ordered separately. Required number depends upon the system configuration.
  • SD card A SD card is required to store data in the unit. Use the specified model number of memory card. Available for purchase from M-System. Consult M-System. - Hagiwara Solutions NSD6-004GH(B21SEI (NSD6-004GH(A00SDI, NSDA-004GT, NSDA-004GL ... discontinued) - Apacer Technology AP-ISD04GIS4B-3T (AP-ISD04GIS4B-T ... discontinued) GENERAL SPECIFICATIONS Construction: Stand-alone Degree of protection: IP20 Connection

MODEL: R9MWTU R9MWTU SPECIFICATIONS ES-6221 Rev.11 Page 2/7 https://www.m-system.co.jp/ Auxiliary power or voltage input: M3.5 screw terminals (torque 0.8 N·m) Current input: M3 screw terminals (torque 0.5 N·m) Modbus: M3 screw terminals (torque 0.5 N·m) Solderless terminal: Refer to the drawing at the end of the section. Recommended manufacturer: Japan Solderless Terminal MFG.Co.Ltd, Nichifu Co.,ltd Applicable wire size M3 screw terminal: 0.25 to 1.65 mm2 (AWG 22 to 16) M3.5 screw terminal: 1.04 to 2.63 mm2 (AWG 16 to 14) Configuration: Single-phase/2-wire, single-phase/3-wire, 3- phase/3-wire Screw terminal: Nickel-plated steel Housing material: Flame-resistant resin (black) Isolation: Sensor core to sensor output or current input or voltage input to Modbus to auxiliary power to FE1 ■ Measured variables Voltage: R – N, S – N, T – N, R – S, S – T, T – R Current: R, S, T, N Active / reactive / apparent power: R, S, T, Σ Power factor: R, S, T, Σ Frequency Active energy: Incoming Reactive energy: Incoming lag Active / reactive / apparent power intervals (demand) Average (demand) current: R, S, T, N Harmonic contents: Σ Voltage: R - N, S - N, T - N, R - S, S - T, T - R Current: R, S, T, N Max. and min. values Calendar log (inserting SD card): Voltage, Current, power, electric energy, power factor Operating mode setting: Connection, clamp-on sensor selection Status indicators: Power, SD Card ■Recommended solderless terminal size - M3 6 (.24) max 3.3 (.13) max mm (inch) ■Recommended solderless terminal size - M3.5 (.2 ) max 3. (.1 ) max mm (inch) MODBUS COMMUNICATION Communication: Half-duplex, asynchronous, no procedure Standard: Conforms to TIA/EIA-485-A Transmission distance: 500 meters max. Transmission media: Shielded twisted-pair cable (CPEV-S 0.9 dia.) Protocol: Modbus - RTU (default) or Modbus - ASCII Max. number of nodes: 31 (excluding master) Node address setting: 1 - 99 (with rotary switch) (factory default setting: 00) Baud rate setting: With rotary switch 38.4 kbps (default), 19.2 kbps, 9600 bps, 4800 bps Status indicator LED: Run, RD, SD, ERR Terminating resistor: Built-in (Selected with the DIP SW; factory setting: disabled) INPUT SPECIFICATIONS Frequency: 50 / 60 Hz (45 – 65 Hz)

  • Voltage Input Rated voltage
  • Between lines: 400 V AC
  • Line-neutral (phase voltage): 230 V (single-phase / 2-wire and 3-wire) Input burden: ≤ ULN2 / 300 kΩ / phase Overload capacity: 200 % of rating for 10 sec., 120 % continuous Selectable primary voltage range: 50 – 400 000 V
  • Current Input CLSE-R5: 0 – 5 A AC CLSE-05: 0 – 50 A AC CLSE-10: 0 – 100 A AC CLSE-20: 0 – 200 A AC CLSE-40: 0 – 400 A AC CLSE-60: 0 – 600 A AC Overload capacity: 120 % continous, 500 % for 10 sec. Note: Use for the circuit not exceed 480 V Selectable primary current range: 1 – 20 000 A (Using CLSE- R5 the unit is configurable only with configurator software.) Operational range Current: 0 – 120 % of the rating Voltage: 10 – 120 % of the rating Apparent power: ≤ 120 % of the rating Active/reactive power: ±120 % of the rating Frequency: 45 – 65 Hz Power factor: ±1 INSTALLATION Auxiliary power supply
  • AC: < 7 VA
  • DC: < 1.2 W Operating temperature: -10 to +55°C (14 to 131°F)

MODEL: R9MWTU R9MWTU SPECIFICATIONS ES-6221 Rev.11 Page 3/7 https://www.m-system.co.jp/ Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Surface or DIN rail Weight: 500 g (1.1 lb) PERFORMANCE Accuracy (at 10 - 35°C or 50 - 95°F, 45 – 65 Hz)*1 Add the accuracy of the current sensor for overall values. Voltage: ±0.5 % of the rating*2 Current: ±0.5 % of the rating*2 Power: ±0.5 % of the rating*2 Power factor: ±1.5 % Frequency: ±0.1 % of the rating*2 Energy: ±1 % Harmonic contents: ±2 % of the rating*2 *1. Sensor error margin not included *2. The described accuracy levels are ensured at the input 1% or more for neutral current in a 1-phase/3-wire circuit and phase-S current in an unbalanced 3-phase/3-wire circuit. Data update period: Harmonic contents and frequency: ≤ 1 sec. Other: ≤ 500 msec. Calendar clock: (with battery backup) Accuracy: Monthly deviation 3 minutes at 25°C Back up period: Approx. 2 years at 25°C without power With the power on, no battery drain Battery: Primary lithium battery (non-removable) Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @ 1 minute (current input or voltage input to Modbus to auxiliary power or FE1) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1,EN 61010-2-201 Measurement Category II (input) Installation Category II (auxiliary power) Pollution Degree 2 Input to Modbus: Reinforced insulation (400 V) Input or Modbus to auxiliary power: Reinforced insulation (300 V) RoHS Directive

MODEL: R9MWTU R9MWTU SPECIFICATIONS ES-6221 Rev.11 Page 4/7 https://www.m-system.co.jp/ EXTERNAL VIEW Terminal Block, Current Input 2 SD Card Slot PC Configurator Connection Jack Status Indicator LED Terminal Block, Current Input 1 FRONT VIEW Operating Mode Setting DIP SW (SW1) Terminal Block, Voltage Input / Auxiliary Power Supply T1 3K T2 3L 17 18 8 9 1K 3K 1L 3L 15 16 6 7 1K 3K 1L 3L 13 14 4 5 1K 3K 1L 3L 11 12 2 3 18ch 7ch 8ch 6ch 7ch 5ch 6ch 5ch 8ch 7ch 8ch 6ch 7ch 5ch 6ch 5ch NC 1L NC 1K 2 1 11 10 3L 1L 3K 1K 4 3 13 12 3L 1L 3K 1K 6 5 15 14 3L 1L 3K 1K 8 7 17 16 U(+) V(-) P2 P3 2 1 6 5 FE1 N 7 1ch 2ch 1ch 3ch 2ch 4ch 3ch 4ch 1ch 2ch 1ch 3ch 2ch 4ch 3ch 4ch DB SLD DG NC NC 2 3 5 6 FE DA Term on Modbus Terminals Node Address Setting Rotary SW Baud Rate Setting Rotary SW Terminating Resistor SW TERMINAL CONNECTIONS Use the model CLSE clamp sensor for current inputs. The figure below shows only one circuit. A maximum of eight (8) current sensor inputs can be connected (Ch. 1 through Ch. 8). Grounding is not required for low voltage circuits. N 1K 1L 3K 3L source load N u v v u U V V U k l K L k l K L N 1K 1L 3K 3L source load N k l K L k l K L 1K 1L source load u v v u U V V U k l K L 1K 1L source load k l K L N 1K 1L source load N k l K L u v U V N 1K 1L source load N k l K L System / Application Single-phase / 2-wire Three-phase / 3-wire balanced load Single-phase / 3-wire 1K 1L 3K 3L source load u v v u U V V U k l K L k l K L 1K 1L 3K 3L source load k l K L k l K L Three-phase / 3-wire unbalanced load Terminal System / Application Terminal P1 P2 P3 P1 P2 P3 P1 P2 P3 P1 P2 P1 P3 P1 P3

MODEL: R9MWTU R9MWTU SPECIFICATIONS ES-6221 Rev.11 Page 5/7 https://www.m-system.co.jp/ COMMUNICATION CABLE CONNECTIONS Tx+/Rx+ SG Rx+ Rx − Host PC DA DB DG SLD FE Remote Unit DA DB DG SLD FE Remote Unit TERMINATOR TERMINATOR Be sure to connect the terminating resistor across DA and DB at both ends of communication line. When this unit is located at an end, turn the terminating resistor SW ON. The Host PC can be located at not only both ends but also any node of the of communication line. ■ MASTER CONNECTION Tx −/Rx− TERMINAL ASSIGNMENTS 14 13 1K 3K 3 2 1 12 11 10 1L 3L 1L 1K 3K 18 17 T1 3K 7 6 16 15 6ch 6ch7ch 5ch 5ch8ch 7ch8ch 6ch 6ch7ch 5ch 5ch8ch 7ch8ch 1L 3L 1K 3K 1K No. ID FUNCTION No. ID FUNCTION 1 5ch 1L Ch.5, Current input 1L 10 5ch 1K Ch.5, Current input 1K 2 5ch 3L Ch.5, Current input 3L 11 5ch 3K Ch.5, Current input 3K 3 6ch 1L Ch.6, Current input 1L 12 6ch 1K Ch.6, Current input 1K 4 6ch 3L Ch.6, Current input 3L 13 6ch 3K Ch.6, Current input 3K 5 7ch 1L Ch.7, Current input 1L 14 7ch 1K Ch.7, Current input 1K 6 7ch 3L Ch.7, Current input 3L 15 7ch 3K Ch.7, Current input 3K 7 8ch 1L Ch.8, Current input 1L 16 8ch 1K Ch.8, Current input 1K 8 8ch 3L Ch.8, Current input 3L 17 8ch 3K Ch.8, Current input 3K

9 T2 Unused 18 T1 Unused

No. ID FUNCTION No. ID FUNCTION

1 NC Unused 10 NC Unused

2 1ch 1L Ch.1, Current input 1L 11 1ch 1K Ch.1, Current input 1K 3 1ch 3L Ch.1, Current input 3L 12 1ch 3K Ch.1, Current input 3K 4 2ch 1L Ch.2, Current input 1L 13 2ch 1K Ch.2, Current input 1K 5 2ch 3L Ch.2, Current input 3L 14 2ch 3K Ch.2, Current input 3K 6 3ch 1L Ch.3, Current input 1L 15 3ch 1K Ch.3, Current input 1K 7 3ch 3L Ch.3, Current input 3L 16 3ch 3K Ch.3, Current input 3K 8 4ch 1L Ch.4, Current input 1L 17 4ch 1K Ch.4, Current input 1K 9 4ch 3L Ch.4, Current input 3L 18 4ch 3K Ch.4, Current input 3K 5 6 3L 1L 16 17 18 7 8 9 3K 1K 3K 3L 1L 1 2 NC NC 1L 12 13 3 4 3ch 3ch2ch 4ch 4ch1ch 2ch1ch 3ch 3ch2ch 4ch 4ch1ch 2ch1ch 3K 1K 3L 1L 3L

  • Current Input 2 U(+) 2 3 V(−) FE1 N No. ID FUNCTION

1 U(+) Auxiliary power (+)

2 V(−) Auxiliary power (−)

3 FE1 Power ground

4 P1 Voltage input P1

5 P2 Voltage input P2

6 P3 Voltage input P3

7 N Voltage input N

  • Auxiliary Power Supply, Voltage Input • Current Input 1 NC FE NC 2 1 DG SLD DB DA No. ID FUNCTION

1 DB DB

2 SLD Shield

3 FE Modbus ground

4 DA DA

5 DG DG

6 NC Unused

7 NC Unused

  • Modbus

MODEL: R9MWTU R9MWTU SPECIFICATIONS ES-6221 Rev.11 Page 6/7 https://www.m-system.co.jp/ EXTERNAL DIMENSIONS unit: mm [inch] 6 (.24) 43−M3 SCREW TERMINAL 126 (4.96) 122 (DIN RAIL MOUNT) 115 (4.53) 140 (5.51) DIN RAIL 35 mm wide [4 (.16)] 6.5 (.25) 80 (3.15) 75 (2.95) 125 (4.92) 7.3 (.29) 7−M3.5 SCREW TERMINALS 4 − 4.5 (.18) dia. MTG HOLE MOUNTING REQUIREMENTS unit: mm [inch] Pitch 130 (5.12) min. 126 (4.96) 75 (2.95) 4–M4 ■ SINGLE MOUNTING ■ BASIC + EXTENSION UNIT Pitch 223 (8.78) min. 126 (4.96)

MODEL: R9MWTU R9MWTU SPECIFICATIONS ES-6221 Rev.11 Page 7/7 https://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Note: In order to improve EMC performance, bond the FE1 terminal to ground. Caution: FE1 terminal is NOT a protective conductor terminal. To other Modbus devices 4P1 N 111K 123K Uʢʴʣ Vʢʵʣ FE1 3 DA DB DG SLD FE ݯ VOLTAGE AUX. POWER SUPPLY VOLTAGE INPUT CURRENT INPUT 1 Ch. 1 CURRENT Ch. 2 CURRENT Ch. 3 CURRENT Ch. 4 CURRENT Ch. 5 CURRENT Ch. 6 CURRENT Ch. 7 CURRENT Ch. 8 CURRENT CURRENT INPUT 2 AUXILIARY POWER SUPPLY EXTENSION CONNECTOR COMMUNICATION Control Circuit Comm. Circuit Isolation NC NC 1NC NC Specifications are subject to change without notice.