MODEL: R80 R80 SPECIFICATIONS ES-7021 Rev.0 Page 1/6 http://www.m-system.co.jp/ Remote I/O R80 Series R80 SERIES GENERAL SPECIFICATIONS Functions & Features
- Remote I/O modules which interchange analog or digital I/O signals with the fieldbus
- Space-saving Typical Applications
- Remote I/O for DCS and PLC
- Personal computer I/O
ORDERING INFORMATION
Refer to the specifications of the respective modules for details. POWER/NETWORK MODULE: R80[1]-R Refer to the specifications for the respective models. [1] MODULE TYPE NECT1: EtherCAT POWER INPUT DC power R: 24 V DC (Operational voltage range: ±10 %; ripple 10 %p-p max.) I/O MODULE: R80[1] Refer to the specifications for the respective models. [1] MODULE TYPE
- Discrete Input DAT8A: Discrete input (NPN), 8 points (Tension clamp terminal block)
- Discrete Output DCT8A: Transistor output (NPN), 8 points (Tension clamp terminal block) Since internal power supply source and internal communication bus are performed through the connector of each module, installation base is unnecessary. FUNCTIONS & FEATURES The R80 Series Remote I/O is composed of power/network modules and I/O modules. ■ I/O MODULE Performs data conversion of field inputs; Data conversion of data received through the internal bus into outputs. ■ POWER/NETWORK MODULE The power/network module supplies the I/O modules with required internal electrical power source. The power/network module changes the receiving data from internal bus into output signal and vice versa, acts as a gateway between transmission line and internal bus. ■ HOT INSERTION/REMOVAL OF I/O MODULES Since internal power supply and internal bus are performed through the connector of each module, it cannot be replaced with the power on. ■ DIELECTRIC STRENGTH As dielectric strength differs depending on each module, refer to each specification sheet.
RELATED PRODUCTS
- PC configurator software (model: R80CFG) Downloadable at M-System’s web site. For connecting to PC, use commercially available Mini-B type USB cable. (provided by user) GENERAL SPECIFICATIONS Power input:
- R80NECT1-R 24 V DC ±10 %; ripple 10 %p-p max. Power consumption
- DC: Approx. 12 W 24 V DC (@ output current 1.6 A) Internal power
- DC: 5 V DC
- Operational current: 1.6 A Excitation supply output
- DC: 24 V DC ±10 %
- Operational current: 10 A (Power output current consumption must be under rated current) Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: DIN rail (35 mm wide) Connection
- Power/network module
MODEL: R80 R80 SPECIFICATIONS ES-7021 Rev.0 Page 2/6 http://www.m-system.co.jp/
- Power supply, exc. supply: Tension clamp terminal block (Front twin connection) Applicable wire size: 0.2 to 2.5 mm2, stripped length 10 mm
- EtherCAT: RJ-45 connector
- I/O module: Tension clamp terminal block Applicable wire size: 0.2 to 1.5 mm2, stripped length 10 mm Housing material: Flame-resistant resin (black) Max. number of I/O modules: 16 (module address: 0 to 15) Internal communication bus: Transmission cycle approx. 65 μsec. + 65 μsec. x No. of Modules ■ Weight R80NECT1: 210 g (0.46 lb) R80DAT8A: 80 g (0.18 lb) R80DCT8A: 80 g (0.18 lb) Protective cover: 15 g (0.03 lb) CURRENT CONSUMPTION The I/O modules operate by the DC voltage (5 V DC) supplied from the power/network module. Arrange these modules in order that the total current consumed by these modules can be within the supply current capacity. If the current consumption exceeds the limit, change the combination of I/O modules or reduce the no. of modules mounted. Even if total consumption current of the I/O modules is less than the supply current capacity, the total install number of the modules is max. 16. ■ Max. current consumption R80DAT8A: 100 mA R80DCT8A: 120 mA USING EXCITATION SUPPLY Some I/O modules use excitation supply, on the other hand some I/O modules do not. When excitation supply is cut off during power supply is on, operation is as the table shown below. MODEL EXC. SUPPL Y OPERATION AT ONL Y EXC. SUPPL Y CUTOFF R80DAT8A √ Input is turned OFF . R80DCT8A √ Output is turned OFF . ‘√’: Excitation supply is used. ‘–’: Excitation supply is not used. BASIC CONFIGURATION The number of I/O modules that can be mounted changes depending on the power/network module. Refer to the specifications of each power/network module for details. Althoug the module address can be arbitrarily set regardless of its mounting position, to avoid overlapped and unused addresses, set them consecutively starting at 0. Only for rightmost module, set termination resistor to enable. Protective cover is included in the package of power/network module. I/O MODULES POWER/NETWORK MODULE PROTECTIVE COVER HOW TO MOUNT THE MODULE ON DIN RAIL ■
- Power/Network Module Position the upper hook at the rear on the DIN rail and push in the lower. When removing the module, push down the DIN rail adaptor utilizing a flat-blade screwdriver and pull. Hook DIN Rail Adaptor
MODEL: R80 R80 SPECIFICATIONS ES-7021 Rev.0 Page 3/6 http://www.m-system.co.jp/
- I/O Module A B Confirm that the locking clamps of the I/O module are set. Insert the module in parallel to the next one while aligning the grooves of both modules (A & B in the above figure). Maintain it perpendicularly to the rail. More I/O modules can be added in the same manner.
- Protective Cover Hook Groove When removing the cover, pull it out while squeezing the hooks inward. The protective cover is to be attached over the connected I/O module at the right end. Align the hooks on the cover with the grooves of the module and slide it straight until the hooks are latched.
MODEL: R80 R80 SPECIFICATIONS ES-7021 Rev.0 Page 4/6 http://www.m-system.co.jp/ ■ HOW TO UNMOUNT THE MODULE FROM DIN RAIL
- Release the locking clamps and pull out straight the module.
- Removing an intermediate module Note 1: Be careful not to hurt your hand by pointed edges of the internal bus connector. Note 2: I/O modules cannot hold tightly on the DIN rail by themselves without power/network module. Secure them to the position if necessary by using DIN rail end plates.
MODEL: R80 R80 SPECIFICATIONS ES-7021 Rev.0 Page 5/6 http://www.m-system.co.jp/ MOUNTING REQUIREMENTS unit: mm (inch) 115 (4.53) 50 (1 .97) 12 × No. of modules 6.5 (.26) 12 (.47) 55 (2.17) [4 (.16)] DIN RAIL (35 mm wide) 73 (2.87) ʷ ■ MOUNTING DIRECTION Up Down Flat surface mounting ■ MOUNTING TO PANEL Leave enough space between the modules and the mounting panel. 35 (1 .38) 20 (.79) 20 (.79) 35 (1 .38)
MODEL: R80 R80 SPECIFICATIONS ES-7021 Rev.0 Page 6/6 http://www.m-system.co.jp/ SYSTEM CONFIGURATION EXAMPLES R80DAT8A EtherCAT R80DCT8A Power supply
24 V DC
5 V DC
■ POWER/NETWORK MODULE: EXAMPLE OF R80NECT1 Specifications are subject to change without notice.