MODEL: R7G R7G SPECIFICATIONS ES-7817 Rev.3 Page 1/6 http://www.m-system.co.jp/ Remote I/O R7 Series GATEWAY MODULE MODEL: R7G-SC-S[1]-R[2]

ORDERING INFORMATION

  • Code number: R7G-SC-S[1]-R[2] Specify a code from below for each [1] and [2]. (e.g. R7G-SC-SHL-R/Q)
  • Specify the specification for option code /Q (e.g. /C01) Module type of network 1 S: Slave Type of network 1 C: CC-Link Module type of network 2 S: Slave [1] Type of network 2 HL: HLS (Hi-speedLink System) Full-duplex HL1: HLS (Hi-speedLink System) Half-duplex POWER INPUT DC Power R: 24 V DC [2] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating FUNCTIONS & FEATURES The Gateway Module for CC-Link and HLS (Hi-speedLink System) connects discrete I/O between the networks each other. The module hands over 32 point inputs of CC-Link to 32 point outputs of HLS or 32 point inputs of HLS to 32 point outputs of CC-Link. CAUTION In this module, the transmission between CC-Link and HLS is not synchronized. Therefore, if one of the networks read the transmitted data before completion of its update by the other network, the data may be uncertain as 16-bit data. If the correct 16-bit data is necessary, arrange the host application program. Refer to the instruction manual. GENERAL SPECIFICATIONS Connection
  • Power supply, CC-Link: Screwless spring terminal Applicable wire size: 0.2 - 1.25 mm2 Stripped length: 10 mm Recommended solderless terminal AI0,25-10YE 0.25 mm2 (Phoenix Contact) AI0,34-10TQ 0.34 mm2 (Phoenix Contact) AI0,5-10WH 0.5 mm2 (Phoenix Contact) AI0,75-10GY 0.75 mm2 (Phoenix Contact) A1-10 1.0 mm2 (Phoenix Contact) A1,5-10 1.5 mm2 (Phoenix Contact)
  • HLS: RJ-45 Connectors Recommended cable connector: TM21P-88P (Hirose Electric) (not included in the package) Isolation: CC-Link or FG to HLS to power Station address setting: Rotary switch (For the detail refer to the instruction manual.) Transfer rate
  • CC-Link Rotary switch
  • HLS DIP switch (For the detail refer to the instruction manual.) Power LED: Green LED turns on when the power is supplied. Status indicator LED
  • CC-Link: Red LEDs indicate communication status.
  • HLS: Green LEDs indicate communication status. COMMUNICATION ■ HLS COMMUNICATION Network: Full-duplex or half-duplex Transmission distance:
  • 12 Mbps: 100 meters (328 ft)
  • 6 Mbps: 200 meters (656 ft)

MODEL: R7G R7G SPECIFICATIONS ES-7817 Rev.3 Page 2/6 http://www.m-system.co.jp/ Network cable:

  • Full-duplex communication: ZHY262PS, ZHT262PS
  • Half-duplex communication: ZHY221PS (Shinko Seisen Industry Co., Ltd.) Data allocation: 2 Terminating resistor: Built-in (Selected with the DIP SW; factory setting: disabled) ■ CC-LINK COMMUNICATION CC-LinkVer.1.10 Network cable: CC-Link cable designated by Mitsubishi Electric Station Type: Remote I/O Data allocation: 2 (1 station x 2) Terminating resistor: Built-in (Selected with the DIP SW; factory setting: disabled) INSTALLATION Power input
  • DC: Operational voltage range 24 V DC ±10 %; ripple 10 %p-p max., approx. 1.8 W Operating temperature: -10 to +55°C (14 to 131°F) Storage temperature: -20 to +65°C (-4 to +149°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: DIN rail Weight: 150 g (0.33 lb) PERFORMANCE Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @1 minute (CC-Link or FG to HLS to power) EXTERNAL VIEW X10 X1 STATION ADD. PWR RUN1 RUN2 6M 12M H C HLS RUN1 ERR1 SD1 RD1 RUN2 ERR2 SD2 RD2X10 X1 STATION ADD. B.RATE CC-Link TERM TERM ON OFF ON OFF Operating Mode Setting DIP SW (SW1) CC-Link Baud Rate Setting Rotary SW CC-Link Station Address Setting Rotary SW CC-Link Terminating Resistor SW CC-Link Status Indicator LED CC-Link Terminals Power Supply Terminals HLS RJ-45 Connectors HLS Terminating Resistor SW HLS Station Address Setting Rotay SW HLS Status Indicator LED

MODEL: R7G R7G SPECIFICATIONS ES-7817 Rev.3 Page 3/6 http://www.m-system.co.jp/ CONNECTION DIAGRAMS 1. NC 2. NC 3. TXD+ 4. TXD– 5. RXD+ 6. RXD– 7. NC 8. SLD1

  • HLS Full-duplex communication
  • Power supply • CC-Link
  • HLS Full-duplex communication No connection No connection Network (Slave, transmission +) Network (Slave, transmission –) Network (Master, transmission+) Network (Master, transmission–) No connection Shield TXD– TXD+ RXD– RXD+ SLD1 RXD– RXD+ TXD– TXD+ RXD– RXD+ TXD– TXD+ SLD1 SLD1 Master Module Slave Module Slave Module Terminating Resistor Terminating Resistor Terminating Resistor Terminating Resistor 1. NC 2. NC 3. TR+ 4. TR– 5. NC 6. NC 7. NC 8. SLD1 Half-duplex communication Half-duplex communication No connection No connection Network (+) Network (–) No connection No connection No connection Shield TR+ TR– SLD1 TR+ TR– SLD1 TR+ TR– SLD1 Master Module Slave Module Slave Module Terminating Resistor Terminating Resistor 12345678 12345678 1. +24V 2. 0V 3. FG Power Supply (24V DC) Power Supply (0V) FG 1. DA 2. DB 3. DG 4. SLD 5. FG blue white yellow Shield FG DA DB DG SLD FG Master Module DA DB DG SLD FG Remote Module DA DB DG SLD FG Remote Module Terminating Resistor blue white yellow Terminating Resistor ■ Master Module wirng
  • CC-Link 1 2 3 1 2 3 4 5 ■ POWER SUPPLY AND TRANSMISSION WIRING

MODEL: R7G R7G SPECIFICATIONS ES-7817 Rev.3 Page 4/6 http://www.m-system.co.jp/ INDICATOR LED RUNx ERRx SDx *1 RDx STATUS *2 ON BL BL ON Communicates normally with occasional CRC errors due to noise interference. ON BL BL ON Communicates normally but the Baud Rate and/or Station Address switches failed. ERRx LED blinks approximately in 0.5 seconds intervals. ON BL BL OFF ---- ON BL OFF ON CRC error found in the received data. Unable to respond. ON BL OFF OFF ---- ON OFF BL ON Normal communication ON OFF BL OFF ---- ON OFF OFF ON Unable to receive data addressed to the station. ON OFF OFF OFF ---- OFF BL BL ON Performs the interval-timed responses but CRC error found in receiving the refresh data. OFF BL BL OFF ---- OFF BL OFF ON CRC error found in the data addressed to the station. OFF BL OFF OFF ---- OFF OFF BL ON Link is not started. OFF OFF BL OFF ---- OFF OFF OFF ON No data addressed to the station. Or unable to receive data addressed to the station due to noise interference. (Missing parts of the data sent from the master) OFF OFF OFF OFF Unable to receive data due to wire breakdown OFF ON OFF OFF/ON Faulty Baud Rate and/or Station Address setting OFF OFF OFF OFF Power input removed. Or power supply failure. OFF = OFF, ON = ON, BL = Blinking *1. SDx LEDs may look not blinking but ON with high baud rate and fewer connected modules. *2. LEDs indicated with “----” in STATUS rarely occurs in normal operation. (LED failure or the like as possible cause). ■ CC-Link STATUS INDICATOR LED DATA ALLOCATION 0 1 2 3 4 5 6 7 8 9 A B C D E F 0 1 2 3 4 5 6 7 8 9 A B C D E F RX(n+1) RX(n+0) CH1 CH2 CH1 CH2RX(n+2) RX(n+3) Interval-timed Response(X) CC-Link Do HLS Unused Unused 0 1 2 3 4 5 6 7 8 9 A B C D E F 0 1 2 3 4 5 6 7 8 9 A B C D E F RY(n+1) RY(n+0) n: CC-Link station address selected with rotary SW. m: HLS module address selected with rotary SW. CH1 CH2 CH1 CH2 RY(n+2) RY(n+3) Refresh Data(Y) Di Unused Unused {(100+2m) +1}H {(100+2m) +0}H

MODEL: R7G R7G SPECIFICATIONS ES-7817 Rev.3 Page 5/6 http://www.m-system.co.jp/ I/O DATA DESCRIPTIONS 015 Input 0 (Output 0) Input 1 (Output 1) Input 2 (Output 2) Input 3 (Output 3) Input 15 (Output 15) 0: OFF 1: ON Input 7 (Output 7) Input 8 (Output 8) DIMENSIONS unit: mm (inch) 115 (4.53) 30 (1.18) DIN RAIL 35mm wide 53 (2.09)18 (0.71) [5 (.20)]

MODEL: R7G R7G SPECIFICATIONS ES-7817 Rev.3 Page 6/6 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Control circuit CC-Link comm. circuit HLS comm. circuit DA DB DG SLD FG TXD–(TR–) RXD+ RXD– NC NC TXD+(TR+) NC SLD1 CC-Link comm.(IN) HLS comm. (IN) TXD–(TR–) RXD+ RXD– NC NC TXD+(TR+) NC SLD1 HLS comm. (OUT) DA DB DG SLD FG CC-Link comm.(OUT) 24V DC FG POWER (IN) 24V DC FG POWER (OUT) Isolation SYSTEM CONFIGURATION EXAMPLES Gateway module Model: R7G CC-Link I/O module Model:R7C HLS I/O module Model: R7HL CC-Link Master CC-LinkHLS HLS Master Specifications are subject to change without notice.