MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 1/31 http://www.m-system.co.jp/ Remote I/O R7 Series ETHERNET I/O MODULE (Modbus/TCP)

ORDERING INFORMATION

  • Basic module: R7E-[1]-R[2] Specify a code from below for each of [1] and [2]. (e.g. R7E-DC16A-R/Q)
  • Specify the specification for option code /Q (e.g. /C01/SET)
  • Extension module: R7E-[1][2] Specify a code from below for each of [1] and [2]. (e.g. R7E-EC16B/Q)
  • Specify the specification for option code /Q (e.g. /C01) BASIC MODULE: R7E–[1]–R[2] [1] I/O TYPE DA16: Discrete input, 16 points DC16A: NPN transistor output, 16 points DC16B: PNP transistor output, 16 points SV4: DC voltage/current input (10 V/20 mA), 4 points TS4: Thermocouple input, 4 points RS4: RTD input, 4 points MS4: Potentiometer input, 4 points CT4E: AC current input, 4 points, clamp-on current sensor CLSE use PA8: Totalized pulse input, 8 points, (CE not available) YV2: DC voltage output, 2 points YS2: DC current output, 2 points POWER INPUT DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [2] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating EX-FACTORY SETTING /SET: Preset according to the Ordering Information Sheet (No. ESU-7807-x) EXTENSION MODULE: R7E–[1][2] [1] I/O TYPE EA8: Discrete input, 8 points EA16: Discrete input, 16 points EC8A: NPN transistor output, 8 points EC16A: NPN transistor output, 16 points EC8B: PNP transistor output, 8 points EC16B: PNP transistor output, 16 points [2] OPTIONS blank: none /Q: Option other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating FUNCTIONS & FEATURES The R7E interfaces analog and discrete I/O signals with a PLC or PC via Ethernet Modbus/TCP nerwork. A ‘basic’ module can be attached with an ‘extension’ module. By combining two modules, single station can handle mixed analog and discrete signals, 32-point discrete inputs, 32-point discrete outputs, 16-point discrete I/Os and other combinations of signals. Input sensor type (thermocouple, RTD) and range can be selected with the front DIP switches for all channels. In order to set different selections for individual channels, the PC Configurator Software (model: R7CON) is used.

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 2/31 http://www.m-system.co.jp/

RELATED PRODUCTS

  • PC configurator software (model: R7CON) Downloadable at M-System’s web site. A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
  • Clamp-on current sensor (model: CLSE) For R7E-CT4E, the clamp-on current sensors must be ordered separately. Required number depends upon the channel number. Note: PC Configurator Software is required to set IP address. GENERAL SPECIFICATIONS
  • Common Specifications Power input: 24 V DC ±10 %; ripple 10 %p-p max. Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @1 minute (between isolated circuits) Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Storage temperature: -20 to +65°C (-4 to +149°F) Mounting: DIN rail (35 mm wide) Connection Ethernet: RJ-45 connector Power & I/O: M3 separable screw terminals (torque 0.5 N·m) Screw terminal material: Nickel-plated steel Solderless terminal: Refer to the drawing at the end of the section. Recommended manufacturer: Japan Solderless Terminal MFG.Co.Ltd, Nichifu Co.,ltd Applicable wire size: 0.25 to 1.65 mm2 (AWG22 to 16) Housing material: Flame-resistant resin (gray) Status indicator LEDs: PWR, RUN ■ Current Consumption & Weight R7E-DA16: Approx. 74 mA, 200 g (7.0 oz) R7E-DC16A: Approx. 86 mA, 200 g (7.0 oz) R7E-DC16B: Approx. 86 mA, 200 g (7.0 oz) R7E-SV4: Approx. 97 mA, 200 g (7.0 oz) R7E-TS4: Approx. 97 mA, 200 g (7.0 oz) R7E-RS4: Approx. 97 mA, 200 g (7.0 oz) R7E-MS4: Approx. 97 mA, 200 g (7.0 oz) R7E-CT4E: Approx. 90 mA, 200 g (7.0 oz) R7E-PA8: Approx. 80 mA, 200 g (7.0 oz) R7E-YV2: Approx. 115 mA, 180 g (6.3 oz) R7E-YS2: Approx. 161 mA, 180 g (6.3 oz) R7E-EA8: Approx. 10 mA, 90 g (3.2 oz) R7E-EA16: Approx. 20 mA, 150 g (5.3 oz) R7E-EC8A: Approx. 10 mA, 90 g (3.2 oz) R7E-EC16A: Approx. 20 mA, 150 g (5.3 oz) R7E-EC8B: Approx. 10 mA, 90 g (3.2 oz) R7E-EC16B: Approx. 20 mA, 150 g (5.3 oz) ■ Recommended solderless terminal 6 (.24) max 3.3 (.13) max mm (inch) ETHERNET COMMUNICATION Physical layer standard: IEEE 802.3u Data link layer: 10BASE-T / 100BASE-TX Baud rate: 10 / 100 Mbps, Auto Negotiation Protocol: Modbus/TCP Data: RTU (binary) Max. number of socket connections: Two (2) Transmission media: 10BASE-T (STP cable, category 5) 100BASE-TX (STP cable, category 5e) Max. segment length: 100 meters IP address: 192.168.0.1 (factory setting); Selectable with PC Configurator Software (model: R7CON) Port No.: 502 Ethernet indicator LED: LINK, LINK100, COL STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive EN 50581

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 3/31 http://www.m-system.co.jp/ EXTERNAL VIEW ■ BASIC MODULE Status Indicator LED Operating Mode Setting DIP SW (SW1) PC Configurator Jack Discrete I/O Status Indicator LED*1 Power Supply Terminals I/O Terminals*2 *1. Not available with analog I/O modules. *2. 10 screw terminals for analog output modules. CNFG. 1 2 3 4 5 6 7 8 0 1 2 3 4 5 6 7 8 9 A B C D E F 10 11 12 13 2 3 41 15 16 17 18 7 8 96 RJ-45 Connector LINK COL RUN LINK100 PWR 4 5 6 7 1 2 3

  • SIDE VIEW • FRONT VIEW ■ EXTENSION MODULE 0 1 2 3 4 5 6 7 Discrete I/O Status Indicator LED I/O Terminals 7 86 9 10 2 31 4 5
  • DISCRETE, 8 POINTS

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 4/31 http://www.m-system.co.jp/ 0 1 2 3 4 5 6 7 8 9 A B C D E F 10 11 12 13 2 3 41 15 16 17 18 7 8 96 Discrete I/O Status Indicator LED I/O Terminals

  • DISCRETE, 16 POINTS ■ DISCRETE I/O & TOTALIZED PULSE INPUT STATUS INDICATOR LED Discrete I/O modules, including those for extensions, have LED indicators showing I/O signal status. Totalized pulse modules have LED indicators showing input signal status. ON : LED ON OFF : LED OF CONNECTION DIAGRAMS ID NO. FUNCTION, NOTES I POWER SUPPLY TERMINAL ASSIGNMENT NC NC FG NC NC +24 V 0 V ---- ---- FG ---- ---- Power input (24 V DC) Power input (0 V) NC NC +24 V NC NC FG

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 5/31 http://www.m-system.co.jp/ MODBUS FUNCTION CODES & SUPPORTED CODES ■ Data & Control Functions CODE NAME

01 Read Coil Status X Digital output from the slave (read/write)

02 Read Input Status X Status of digital inputs to the slave (read only)

03 Read Holding Registers X General purpose register within the slave (read/write)

04 Read Input Registers X Collected data from the /f_i eld by the slave (read only)

05 Force Single Coil X Digital output from the slave (read/write)

06 Preset Single Register X General purpose register within the slave (read/write)

07 Read Exception Status

08 Diagnostics X

09 Program 484

10 Poll 484

11 Fetch Comm. Event Counter X Fetch a status word and an event counter 12 Fetch Comm. Event Log X A status word, an event counter, a message count and a /f_i eld of event bytes

13 Program Controller

14 Poll Controller

15 Force Multiple Coils X Digital output from the slave (read/write)

16 Preset Multiple Registers X General purpose register within the slave (read/write)

17 Report Slave ID X Slave type / ‘RUN’ status

18 Program 884/M84

19 Reset Comm. Link

20 Read General Reference

21 Write General Reference

22 Mask Write 4X Register

23 Read/Write 4X Register

24 Read FIFO Queue

˙ Exception Code CODE NAME

01 Illegal Function X Function code is not allowable for the slave

02 Illegal Data Address X Address is not available within the slave

03 Illegal Data Value X Data is not valid for the function

04 Slave Device Failure

05 Acknowledge

06 Slave Device Busy

07 Negative Acknowledge

08 Memory Parity Error

˙ Diagnostic Subfunctions CODE NAME

00 Return Query Data X Loop back test

01 Restart Comm. Option

02 Return Diagnostic Register

03 Change Input Delimiter Character

04 Force Slave to Listen Only Mode

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 6/31 http://www.m-system.co.jp/ MODBUS I/O ASSIGNMENT 015 Input 0 (Burnout, input range error) Input 1 (Burnout, input range error) Input 2 (Burnout, input range error) Unused Input 3 (Burnout, input range error) Input 0 (ADC error) Input 1 (ADC error) Input 2 (ADC error) Input 3 (ADC error) Unused Burnout, input range error (≤-15%, ≥+115%) 0 : Normal 1 : Error ADC error (no response from ADC) 0 : Normal 1 : Error ■ STATUS Analog input modules (models: R7E-SV4, R7E-TS4, R7E-RS4, R7E-MS4, R7E-CT4E) can show input status of each channel. Analog output modules (models: R7E-YS2, R7E-YV2) discrete I/O modules (models: R7E-DA16, R7E-DC16A, R7E-DC16B) and totalized pulse input (model: R7E-PA8) show ‘0’ at the same address. ADDRESS DATA TYPE DATA Coil (0X) 1 – 16 Digital Output (discrete output of the basic module) 17 – 32 Digital Output (discrete output of the extension module) Inputs (1X) 1 – 16 Digital Input (discrete input of the basic module) 17 – 32 Digital Input (discrete input of the extension module) 33 – 48 Reserved (unused) 49 – 64 Module Status 65 – 80 Reserved (unused) Input Registers (3X) 1 – 4 I Analog Input 5 – 16 ---- Reserved (unused) 17 – 24 F Analog Input 25 – 48 ---- Reserved (unused) Holding Registers (4X) 1 – 2 I Analog Output 3 – 16 ---- Reserved (unused) 17 – 20 F Analog Output 21 – 48 ---- Reserved (unused) F : Floating Note: DO NOT access addresses other than mentioned above. Such access may cause problems such as inadequate operation.

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 7/31 http://www.m-system.co.jp/ DATA CONVERSION I 0 – 100% DATA CONVERSION Analog input data is converted into digital representations of 0 – 100% proportional to each scaled range. The converted % values are multiplied by 100 and expressed in 16 bits. Overrange input is possible from -15 to +115% of the nominal range. When the signal exceeds the limit, the data is fixed at -15% or +115% respectively. Negative value is represented in 2ʼs complements.

  • Input Range 0 – 5 V DC ≤ -0.75 V 0 V 5 V ≥ 5.75 V Input Value -15% 100% 115% Input % -1500 10000 11500 Converted Data, Decimal FA24 2710 2CEC Converted Data, Hex Analog output is converted in the reverse order of the input data. The output range 0 – 5 V DC is expressed as 10000 at 11500 (2CEC) 10000 (2710) -0.75 -1500 (FA24) 5.0 5.750 (V) I ENGINEERING UNIT CONVERSION Engineering unit value °C or K is multiplied by 10 and expressed in 16 bits. °F data is represented in engineering unit value, without multiplication. Engineering unit value A is multiplied by 100 or 1000, expressed in 16 bits. Negative value is represented in 2ʼs complements.
  • Input TYPE K Thermocouple ≤ -272°C -150°C 1370°C ≥ 1472°C Input Value -2720 -1500 13700 14720 Converted Data, Decimal F560 FA24 3584 3980 Converted Data, Hex 14720 (3980) 13700 (3584) -272 -150 -1500 (FA24) -2720 (F560) 1370 1472 (°C) ■ COUNT VALUE The count value is 32-bit data. It is divided in 2 words of 16 bits represented with 2 addresses.The lower address is allocated in the upper word (MSB) and the upper address in the lower word (LSB). The count value is 0 - 4 294 967 295. The maximum count value available is 1 000 - 4 294 967 295. In case of overflow, the vaule is reset to 0 or 1 (configurable) from which the count will restart. The preset of the count value is also available. Use the R7CON or IPTU1$1-$ for the configuration.

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 8/31 http://www.m-system.co.jp/ EXTENSION MODULE A ‘basic’ module can be attached with one ‘extension’ module. The extension module is powered from the basic module. By combining two modules, single station can handle mixed analog and discrete signals, 32-point discrete inputs, 32-point discrete outputs, 16-point discrete I/Os and other combinations of signals. ■ OUTPUT AT THE LOSS OF COMMUNICATION The extension module is set to ‘Hold Output’ by factory default setting. The PC Configurator software is used to change the setting to ‘Reset Output.’ CONNECTING THE EXTENSION MODULE 1) Remove the extension connector cover located at the side of the basic module. 2) Connect the extension module. 3) Mount the combined module on a DIN rail. EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) ■ BASIC MODULE 4 5 6 7 1 2 3 10 11 12 13 2 3 41 15 16 17 18 7 8 96 (.28)

  • R7E-TS4 30 (1.18) 65 (2.56) [5 (.20)] (.12) 5.5 (.22) DIN RAIL 35mm wide 54 (2.13)17 (.66) 115 (4.53) RJ-45 CONNECTOR 7–M3 SCREW TERMINALS for POWER 18–M3 SCREW TERMINALS for I/O 6 (.24) 6 (.24) DIN RAIL 35mm wide 54 (2.13)17 (.66)

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 9/31 http://www.m-system.co.jp/ ■ BASIC MODULE, ANALOG OUTPUT 2 3 41 5 107 8 964 5 6 7 1 2 3 7–M3 SCREW TERMINALS for POWER 10–M3 SCREW TERMINALS for OUTPUT DIN RAIL 35mm wide 54 (2.13)17 (.66) 6 (.24) 6 (.24) 115 (4.53) 65 (2.56) (.12) ■ EXTENSION MODULE, 8 POINTS 11.5 (.45) 7 86 9 10 2 31 4 5 65 (2.56) 3 (.12) 5.5 (.22) DIN RAIL 35mm wide 54 (2.13)17 (.66) 10–M3 SCREW TERMINALS for I/O 6 (.24) ■ EXTENSION MODULE, 16 POINTS 11.5 (.45) 10 11 12 13 2 3 41 15 16 17 18 7 8 96 94 (3.70) DIN RAIL 35mm wide 54 (2.13)17 (.66) 18–M3 SCREW TERMINALS for I/O 6 (.24)

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 10/31 http://www.m-system.co.jp/ DISCRETE INPUT MODULE, 16 points MODEL: R7E-DA16 SPECIFICATIONS Common: Positive or negative common (NPN/PNP) per 16 points Number of I/O: Input, 16 points Maximum inputs applicable at once: No limit (at 24 V DC) Input status indicator: LED turns ON with contact ON Isolation: Input to Ethernet to FG to power input Rated input voltage: 24 V DC ±10 %; ripple 5 %p-p max. ON voltage / current: ≥ 15 V DC (input – COM) / ≥ 3.5 mA OFF voltage / current: ≤ 5 V DC (input – COM) / ≤ 1 mA Input current: ≤ 5.5 mA per point at 24 V DC Input resistance: Approx. 4.4 kΩ ON delay: ≤ 2.0 msec. OFF delay: ≤ 2.0 msec. OPERATING MODE SETTING (*) Factory setting Caution ! - SW1-3 through 1-8 are unused. Be sure to turn off unused ones.

  • Extension (SW1-1, 1-2) SW1-1 SW1-2 Extension OFF OFF No extension ( ON OFF Discrete input, 8 or 16 points OFF ON Discrete output, 8 or 16 points TERMINAL ASSIGNMENTS NC COM XB XA XD XC XE XF NO. ID FUNCTION NO. ID FUNCTION

1 COM Common 10 NC No Connection

2 X0 Input 0 11 X1 Input 1

3 X2 Input 2 12 X3 Input 3

4 X4 Input 4 13 X5 Input 5

5 X6 Input 6 14 X7 Input 7

6 X8 Input 8 15 X9 Input 9

7 XA Input 10 16 XB Input 11

8 XC Input 12 17 XD Input 13

9 XE Input 14 18 XF Input 15

Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. Input Circuit Control Circuit ■ Input Circuit 24V DC FG XB 15 X9 XF XD 14 X7 13 X5 12 X3 11 X1 9XE 8XC 7XA 6X8 5X6 4X4 3X2 2X0 COM ■ Input Connection Examples 2X0 COM 18 XF PNP Connection 2X0 COM 18 XF NPN Connection Isolation Modbus/ TCP RJ-45 CONNECTOR EXTENSION CONNECTOR 1COM X0 2 18 XF Control Circuit – + – +

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 11/31 http://www.m-system.co.jp/ NPN TRANSISTOR OUTPUT MODULE, 16 points MODEL: R7E-DC16A SPECIFICATIONS Common: Negative common (NPN) per 16 points Number of I/O: Output, 16 points Maximum outputs applicable at once: No limit (at 24 V DC) Output status indicator: LED turns ON with contact ON Isolation: Output to Ethernet to FG to power input Rated load voltage: 24 V DC ±10 % Rated output current: 0.25 A per point, 2.0 A per common Residual voltage: ≤ 1.2 V Leakage current: ≤ 0.1 mA ON delay: ≤ 0.5 msec. OFF delay: ≤ 1.5 msec. (When driving an inductive load, connect a diode in parallel with the load.) OPERATING MODE SETTING (*) Factory setting Caution ! - SW1-3, 1-5 through 1-8 are unused. Be sure to turn off unused ones. SW1-4 Output at the loss of communication OFF Reset the output (turned off) ON Hold the output ( (maintains the last data received normally)

  • Output at the Loss of Communication (SW1-4)
  • Extension (SW1-1, 1-2) SW1-1 SW1-2 Extension OFF OFF No extension ( ON OFF Discrete input, 8 or 16 points OFF ON Discrete output, 8 or 16 points TERMINAL ASSIGNMENTS +24V YB YA YD YC YE YF NO. ID FUNCTION NO. ID FUNCTION 1 0 V 0 V (common) 10 +24 V 24 V DC

2 Y0 Output 0 11 Y1 Output 1

3 Y2 Output 2 12 Y3 Output 3

4 Y4 Output 4 13 Y5 Output 5

5 Y6 Output 6 14 Y7 Output 7

6 Y8 Output 8 15 Y9 Output 9

7 YA Output 10 16 YB Output 11

8 YC Output 12 17 YD Output 13

9 YE Output 14 18 YF Output 15

Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. 10V +24V 2Y0 18 YF Output Circuit Control Circuit ■ Output Circuit YD 16 YB YF 15 Y9 14 Y7 13 Y5 12 Y3 11 Y1 9 YE 8 YC 7 YA 6 Y8 5 Y6 4 Y4 3 Y2 +24V ■ Output Connection Example 24VDC FG Isolation Modbus/ TCP RJ-45 CONNECTOR EXTENSION CONNECTOR +24V10 18 YF 1 0V Control Circuit

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 12/31 http://www.m-system.co.jp/ PNP TRANSISTOR OUTPUT MODULE, 16 points MODEL: R7E-DC16B SPECIFICATIONS Common: Positive common (PNP) per 16 points Number of I/O: Output, 16 points Maximum outputs applicable at once: No limit (at 24 V DC) Output status indicator: LED turns ON with contact ON Isolation: Output to Ethernet to FG to power input Rated load voltage: 24 V DC ±10 % Rated output current: 0.25 A per point, 2.0 A per common Residual voltage: ≤ 1.2 V Leakage current: ≤ 0.1 mA ON delay: ≤ 0.5 msec. OFF delay: ≤ 1.5 msec. (When driving an inductive load, connect a diode in parallel with the load.) OPERATING MODE SETTING (*) Factory setting Caution ! - SW1-3, 1-5 through 1-8 are unused. Be sure to turn off unused ones. SW1-4 Output at the loss of communication OFF Reset the output (turned off) ON Hold the output ( (maintains the last data received normally)

  • Output at the Loss of Communication (SW1-4)
  • Extension (SW1-1, 1-2) SW1-1 SW1-2 Extension OFF OFF No extension ( ON OFF Discrete input, 8 or 16 points OFF ON Discrete output, 8 or 16 points TERMINAL ASSIGNMENTS +24V YB YA YD YC YE YF NO. ID FUNCTION NO. ID FUNCTION 1 0 V 0 V 10 +24 V 24 V DC (common)

Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. +24V10 18 YF 1 0V Control Circuit Output Circuit Control Circuit ■ Output Circuit YD 16 YB YF 15 Y9 14 Y7 13 Y5 12 Y3 11 Y1 9 YE 8 YC 7 YA 6 Y8 5 Y6 4 Y4 3 Y2 +24V ■ Output Connection Example 24V DC FG Isolation Modbus/ TCP RJ-45 CONNECTOR EXTENSION CONNECTOR 2Y0 +24V 18 YF

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 13/31 http://www.m-system.co.jp/ DC VOLTAGE/CURRENT INPUT MODULE, 4 points MODEL: R7E-SV4 SPECIFICATIONS Isolation: Input 0 to input 1 to input 2 to input 3 to Ethernet to FG to power input Converted data range: 0 – 10000 of the input range

  • Input range Wide span voltage: -10 – +10 V DC, -5 – +5 V DC, 0 – 10 V DC, 0 – 5 V DC, 1 – 5 V DC Narrow span voltage: -1 – +1 V DC, 0 – 1 V DC, -0.5 – +0.5 V DC Current range: -20 – +20 mA DC, 0 – 20 mA DC, 4 – 20 mA DC
  • Input resistance Wide span voltage: ≥ 1 MΩ Narrow span voltage: ≥ 100 kΩ Current range: 70 Ω Conversion rate / conversion accuracy: 80 msec./±0.1 % Response time: Conversion rate × 2 + 50 msec. (0 – 90 %) Temperature coefficient: ±0.015 %/°C (±0.008 %/°F) OPERATING MODE SETTING (*) Factory setting
  • Input Range (SW1-5, 1-6, 1-7 , 1-8) SW1-5 SW1-6 SW1-7 SW1-8 Input range OFF OFF OFF OFF -10 – +10 V DC ( *) ON OFF OFF OFF -5 – +5 V DC OFF ON OFF OFF -1 – +1 V DC ON ON OFF OFF 0 – 10 V DC OFF OFF ON OFF 0 – 5 V DC ON OFF ON OFF 1 – 5 V DC OFF ON ON OFF 0 – 1V DC ON ON ON OFF -0.5 – +0.5 V DC ON OFF OFF ON -20 – +20 mA DC OFF ON OFF ON 4 – 20 mA DC ON ON OFF ON 0 – 20 mA DC ON ON ON ON PC Configurator setting
  • Conversion Rate / Accuracy (SW1-3, 1-4) SW1-3 SW1-4 Conversion rate / Accuracy OFF OFF 80 msec. / ±0.1% ( ON OFF 40 msec. / ±0.2% OFF ON 20 msec. / ±0.4% ON ON 10 msec. / ±0.8%
  • Extension (SW1-1, 1-2) SW1-1 SW1-2 Extension OFF OFF No extension ( ON OFF Discrete input, 8 or 16 points OFF ON Discrete output, 8 or 16 points TERMINAL ASSIGNMENTS VL0 VL1 VH0 COM0 VH1 COM1 NC NC VL2 VH2 COM2 VL3 VH3 COM3 NO. ID FUNCTION NO. ID FUNCTION 1 VH0 Wide span volt. 0 10 VL0 Narrow span volt. 0

2 COM0 Common 0 11 I0 Current range 0

3 VH1 Wide span volt. 1 12 VL1 Narrow span volt. 1

4 COM1 Common 1 13 I1 Current range 1

5 NC No connection 14 NC No connection

6 VH2 Wide span volt. 2 15 VL2 Narrow span volt. 2

7 COM2 Common 2 16 I2 Current range 2

8 VH3 Wide span volt. 3 17 VL3 Narrow span volt. 3

9 COM3 Common 3 18 I3 Current range 3

Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. Input Circuit Control Circuit 1VH0 ■ Input Connection Examples VHn VLn In – COMn

10 VL0

12 VL1

15 VL2

17 VL3

– COMn NARROW SPAN VOLTAGE VHn VLn In – COMn Be sure to close across VLn and In terminals for a current input. CURRENT RANGE 24V DC FG Isolation Modbus/ TCP RJ-45 CONNECTOR EXTENSION CONNECTOR

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 14/31 http://www.m-system.co.jp/ THERMOCOUPLE INPUT MODULE, 4 points MODEL: R7E-TS4 SPECIFICATIONS Isolation: Input 0 to input 1 to input 2 to input 3 to Ethernet to FG to power input Converted data range: Engineering unit value (°C, K) × 10 (integer); No multiplication for °F Linearization: Standard Thermocouple: K, E, J, T, B, R, S, C, N, U, L, P, PR Cold junction compensation: CJC sensor attached to the input terminals Input resistance: ≥ 30 kΩ Burnout sensing: ≤ 0.1 μA Conversion accuracy: ±1°C (±1.8°F); ±2.0°C (±3.6°F) for B, R, S, C, PR Conversion rate: 250 msec. or 1 sec. Response time: Conversion rate × 2 + 50 msec. (0 – 90 %) Temperature coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span CJC error: ±1.0°C at 25°C ±10°C ±1.5°C (±2.7°F) for R, S, PR T/C BURNOUT INDICATION (°C) K (CA) -272 +1472 -150 to +1370 E (CRC) -272 +1120 -170 to +1000 J (IC) -260 +1300 -180 to +1200 T (CC) -272 + 500 -170 to + 400 B (RH) 24 1920 1000 to 1760 R -100 +1860 380 to 1760 S -100 +1860 400 to 1760 C (WRe 5-26) -52 +2416 100 to 2315 N -272 +1400 -130 to +1300 U -252 + 700 -200 to +600 L -252 +1000 -200 to +900 P (Platinel II) -52 +1496 0 to 1395 (PR) -52 +1860 300 to 1760 Downscale Upscale CONFORMANCE RANGE (°C) K (CA) -458 +2682 -238 to +2498 E (CRC) -458 +2048 -274 to +1832 J (IC) -436 +2372 -292 to +2192 T (CC) -458 +932 -274 to +752 B (RH) 75 3488 1832 to 3200 R -148 +3380 716 to 3200 S -148 +3380 752 to 3200 C (WRe 5-26) -62 +4381 212 to 4199 N -458 +2552 -202 to +2372 U -422 +1292 -328 to +1112 L -422 +1832 -328 to +1652 P (Platinel II) -62 +2725 32 to 2543 (PR) -62 +3380 572 to 3200 CONFORMANCE RANGE (°F) Downscale Upscale BURNOUT INDICATION (°F) T/C OPERATING MODE SETTING (*) Factory setting

  • Thermocouple Type (SW1-5, 1-6, 1-7 , 1-8) SW1-5 SW1-6 SW1-7 SW1-8 Thermocouple type OFF OFF OFF OFF K (CA) ( ON OFF OFF OFF E (CRC) OFF ON OFF OFF J (IC) ON ON OFF OFF T (CC) OFF OFF ON OFF B (RH) ON OFF ON OFF R OFF ON ON OFF S ON ON ON OFF C (WRe 5-26) OFF OFF OFF ON N ON OFF OFF ON U OFF ON OFF ON L ON ON OFF ON P (Platinel II) OFF OFF ON ON (PR) ON ON ON ON PC Configurator setting
  • Conversion Rate (SW1-3) SW1-3 Conversion rate OFF 250 msec. ( ON 1 sec.
  • Burnout (SW1-4) SW1-4 Burnout OFF Upscale (*) ON Downscale
  • Extension (SW1-1, 1-2) SW1-1 SW1-2 Extension OFF OFF No extension ( ON OFF Discrete input, 8 or 16 points OFF ON Discrete output, 8 or 16 points TERMINAL ASSIGNMENTS +IN0 –IN0 +IN1 +CJ0 –CJ0 +CJ1 –IN1 –CJ1 NC NC +IN2 +CJ2 –IN2 –CJ2 +IN3 +CJ3 –CJ3 –IN3 NO. ID FUNCTION NO. ID FUNCTION 1 +CJ0 CJC + 0 10 +IN0 T/C + 0 2 –CJ0 CJC – 0 11 –IN0 T/C – 0 3 +CJ1 CJC + 1 12 +IN1 T/C + 1 4 –CJ1 CJC – 1 13 –IN1 T/C – 1

6 +CJ2 CJC + 2 15 +IN2 T/C + 2 7 –CJ2 CJC – 2 16 –IN2 T/C – 2 8 +CJ3 CJC + 3 17 +IN3 T/C + 3 9 –CJ3 CJC – 3 18 –IN3 T/C – 3

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 15/31 http://www.m-system.co.jp/ CIRCUIT DIAGRAM Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. Input Circuit Control Circuit 10 +IN0 ■ Input Connection Example +INn –INn +CJn –CJn 11 –IN0 1+CJ0 2–CJ0 +IN1 –IN1 +CJ1 –CJ1 +IN2 –IN2 +CJ2 –CJ2 +IN3 –IN3 +CJ3 –CJ3 INPUT 0 Input Circuit INPUT 1 Input Circuit INPUT 2 Input Circuit INPUT 3 T/C CJC SENSOR 24V DC FG Isolation Modbus/ TCP RJ-45 CONNECTOR EXTENSION CONNECTOR

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 16/31 http://www.m-system.co.jp/ RTD INPUT MODULE, 4 points MODEL: R7E-RS4 SPECIFICATIONS Isolation: Input 0 to input 1 to input 2 to input 3 to Ethernet to FG to power input Converted data range: Engineering unit value (°C, K) × 10 (integer); No multiplication for °F Linearization: Standard RTD: Pt 100 (JIS ’97, IEC), Pt 100 (JIS ’89), JPt 100 (JIS ’89), Pt 50 Ω (JIS ’81), Ni 100, Cu 10, Cu 50 Sensing current: ≤ 1 mA Input resistance: ≥ 1 MΩ Maximum leadwire resistance: 100 Ω per wire Conversion accuracy: ±1°C (±1.8°F); ±3°C (±5.4°F) for Cu 10 Conversion rate: 250 msec. or 1 sec. Response time: Conversion rate × 2 + 50 msec. (0 – 90 %) Temperature coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span RTD BURNOUT INDICATION (°C) CONFORMANCE Downscale Upscale RANGE (°C) Pt 100 (JIS ’97 , IEC) -240 +900 -200 to +850 Pt 100 (JIS ’89) -240 +900 -200 to +660 JPt 100 (JIS ’89) -236 +560 -200 to +510 Pt 50 Ω (JIS ’81) -236 +700 -200 to +649 Ni 100 -100 +252 -80 to +250 Cu 10 @ 25°C -212 +312 -50 to +250 Cu 50 -100 +200 -50 to +150 RTD BURNOUT INDICATION (°F) CONFORMANCE Downscale Upscale RANGE (°F) Pt 100 (JIS ’97 , IEC) -400 +1652 -328 to +1562 Pt 100 (JIS ’89) -400 +1652 -328 to +1220 JPt 100 (JIS ’89) -393 +1040 -328 to +950 Pt 50 Ω (JIS ’81) -393 +1292 -328 to +1200 Ni 100 -148 +486 -112 to +482 Cu 10 @ 25°C -350 +594 -58 to +482 Cu 50 -148 +392 -58 to +302 OPERATING MODE SETTING (*) Factory setting

  • RTD Type (SW1-5, 1-6, 1-7 , 1-8) SW1-5 SW1-6 SW1-7 SW1-8 RTD Type OFF OFF OFF OFF Pt 100 (JIS ’97 , IEC) ( ON OFF OFF OFF Pt 100 (JIS ’89) OFF ON OFF OFF JPt 100 (JIS ’89) ON ON OFF OFF Pt 50 Ω (JIS ’81) OFF OFF ON OFF Ni 100 ON OFF ON OFF Cu 10 @ 25°C OFF OFF OFF ON Cu 50 ON ON ON ON PC Configurator setting
  • Conversion Rate (SW1-3) SW1-3 Conversion rate OFF 250 msec. ( ON 1 sec.
  • Burnout (SW1-4) SW1-4 Burnout OFF Upscale (*) ON Downscale
  • Extension (SW1-1, 1-2) SW1-1 SW1-2 Extension OFF OFF No extension ( ON OFF Discrete input, 8 or 16 points OFF ON Discrete output, 8 or 16 points TERMINAL ASSIGNMENTS INA0 INb0 INA1 NC INB0 NC INb1 INB1 NC NC INA2 NC INb2 INB2 INA3 NC INB3 INb3 NO. ID FUNCTION NO. ID FUNCTION

1 NC No connection 10 INA0 RTD 0-A

2 INB0 RTD 0-B 11 INb0 RTD 0-b

3 NC No connection 12 INA1 RTD 1-A

4 INB1 RTD 1-B 13 INb1 RTD 1-b

6 NC No connection 15 INA2 RTD 2-A

7 INB2 RTD 2-B 16 INb2 RTD 2-b

8 NC No connection 17 INA3 RTD 3-A

9 INB3 RTD 3-B 18 INb3 RTD 3-b

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 17/31 http://www.m-system.co.jp/ CIRCUIT DIAGRAM Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. Input Circuit Control Circuit

10 INA0

■ Input Connection Example INAn INBn INbn 2INB0

11 INb0

A B B 24V DC FG Isolation Modbus/ TCP RJ-45 CONNECTOR EXTENSION CONNECTOR

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 18/31 http://www.m-system.co.jp/ POTENTIOMETER INPUT MODULE, 4 points MODEL: R7E-MS4 SPECIFICATIONS Isolation: Input 0 to input 1 to input 2 to input 3 to Ethernet to FG to power input Converted data range: 0 – 10000 of the input range Potentiometer: Total resistance 100 Ω – 20 kΩ Minimum span: 50 % of total resistance Excitation: Approx. 0.2 V DC Conversion rate / conversion accuracy: 80 msec./±0.1 % Response time: Conversion rate × 2 + 50 msec. (0 – 90 %) Temperature coefficient: ±0.015 %/°C (±0.008 %/°F) OPERATING MODE SETTING (*) Factory setting Caution ! - SW1-5, 1-6, 1-7, 1-8 are unused. Be sure to turn off unused ones.

  • Conversion Rate / Accuracy (SW1-3, 1-4) SW1-3 SW1-4 Conversion rate / Accuracy OFF OFF 80 msec. / ±0.1% ( ON OFF 40 msec. / ±0.2% OFF ON 20 msec. / ±0.4% ON ON 10 msec. / ±0.8%
  • Extension (SW1-1, 1-2) SW1-1 SW1-2 Extension OFF OFF No extension ( ON OFF Discrete input, 8 or 16 points OFF ON Discrete output, 8 or 16 points TERMINAL ASSIGNMENTS NC NC NC NC NC NC NO. ID FUNCTION NO. ID FUNCTION

1 NC No connection 10 H0 Pot H0

2 L0 Pot L0 11 S0 Pot S0

3 NC No connection 12 H1 Pot H1

4 L1 Pot L1 13 S1 Pot S1

6 NC No connection 15 H2 Pot H2

7 L2 Pot L2 16 S2 Pot S2

8 NC No connection 17 H3 Pot H3

9 L3 Pot L3 18 S3 Pot S3

Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. Input Circuit Control Circuit 10 H0 Hn 11 S0 2L0 INPUT 0 INPUT 1 INPUT 2 INPUT 3 Input Circuit Input Circuit Input Circuit Exc. Exc. Exc. Exc. ■ Input Connection Example Sn Ln POTENTIOMETER max. min. 24V DC FG Isolation Modbus/ TCP RJ-45 CONNECTOR EXTENSION CONNECTOR

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 19/31 http://www.m-system.co.jp/ AC CURRENT INPUT MODULE, 4 points (clamp-on current sensor CLSE use) MODEL: R7E-CT4E SPECIFICATIONS Isolation: Input 0 to input 1 to input 2 to input 3 to Ethernet to FG to power input Converted data range: Engineering unit value (A) × 100 (Integer) (Engineering unit value (A) × 1000 (Integer) for CLSE-R5) Input range (Optional) CLSE-R5: 0 – 5 A AC CLSE-05: 0 – 50 A AC CLSE-10: 0 – 100 A AC CLSE-20: 0 – 200 A AC CLSE-40: 0 – 400 A AC CLSE-60: 0 – 600 A AC Frequency: 50/60 Hz Overload capacity: 120 % continuous Operational range: 5 – 115 % of rating (Operational range for the CLSE-60 is limited up to approx. 109 % (65535).) (Note: Use for the circuit not exceed 480 V) Conversion rate / conversion accuracy: 80 msec./±0.5 % (The conversion accuracy does not include the accuracy of the sensor.) Response time: ≤ 1.0 sec. (0 – 90 %) Temperature coefficient: ±0.015 %/°C (±0.008 %/°F) OPERATING MODE SETTING (*) Factory setting

  • Input Range (SW1-5, 1-6, 1-7 , 1-8) SW1-5 SW1-6 SW1-7 SW1-8 Input range OFF OFF OFF OFF CLSE-60 ( ON OFF OFF OFF CLSE-40 OFF ON OFF OFF CLSE-20 ON ON OFF OFF CLSE-10 OFF OFF ON OFF CLSE-05 ON OFF ON OFF CLSE-R5 ON ON ON ON PC Configurator setting
  • Conversion Rate / Accuracy (SW1-3, 1-4) SW1-3 SW1-4 Conversion rate / Accuracy OFF OFF 80 msec. / ±0.5% ( ON OFF 40 msec. / ±0.5% OFF ON 20 msec. / ±1 .0% ON ON 10 msec. / ±2.0%
  • Extension (SW1-1, 1-2) SW1-1 SW1-2 Extension OFF OFF No extension ( ON OFF Discrete input, 8 or 16 points OFF ON Discrete output, 8 or 16 points TERMINAL ASSIGNMENTS NC NC NC NC NC NC NC NC NC NC NO. ID FUNCTION NO. ID FUNCTION

1 NC No connection 10 K0 AC current K0

2 NC No connection 11 L0 AC current L0

3 NC No connection 12 K1 AC current K1

4 NC No connection 13 L1 AC current L1

6 NC No connection 15 K2 AC current K2

7 NC No connection 16 L2 AC current L2

8 NC No connection 17 K3 AC current K3

9 NC No connection 18 L3 AC current L3

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 20/31 http://www.m-system.co.jp/ CIRCUIT DIAGRAM Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. Input Circuit Control Circuit 10 K0 ■ Input Connection Example Kn Ln 11 L0 INPUT 0 Input Circuit INPUT 1 Input Circuit INPUT 2 Input Circuit INPUT 3 LOAD SOURCE k l CLAMP-ON SENSOR 24V DC FG Isolation Modbus/ TCP RJ-45 CONNECTOR EXTENSION CONNECTOR

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 21/31 http://www.m-system.co.jp/ TOTALIZED PULSE INPUT MODULE, 8 points MODEL: R7E-PA8 SPECIFICATIONS Common: Positive or negative common (NPN/PNP) per 8 points Number of I/O: Input, 8 points Pulse Input status indicator: LED turns ON with contact ON Isolation: Input to Ethernet to FG to power input ■ External excitation (PNP, NPN input) Sensing voltage: 24 V DC ±10 %; ripple 5 %p-p max ON voltage / ON current: ≥ 16 V DC (input terminal - Cx) / ≤ 3.7 mA OFF voltage / OFF current: ≤ 5 V DC (input terminal - Cx) / ≤ 1 mA Voltage pulse input ON voltage / ON current: ≥ 16 V DC (input terminal - Cx) / ≤ 3.7 mA OFF voltage / OFF current: ≤ 5 V DC (input terminal - Cx) / ≤ 1 mA Input current: ≤ 5.5 mA per point at 24 V DC Input resistance: Approx. 4.4 kΩ ON delay: ≤ 2.0 msec. OFF delay: ≤ 2.0 msec. Max. Frequency: 100 Hz (This unit is designed to be able to accept a frequency up to 100 Hz, however,‘chattering’ contact must be avoided for accurate measuring of such high frequency. Use relays that do not cause any chattering.) Minimum ON/OFF pulse requirements: 5 ms Accumulated pulse count: 0 - 4 294 967 295 Max. accumulated pulse count: 1 000 - 4 294 967 295 (Factory default: 9 999 999) Overflow: 0 or 1 (Factory default: 0) OPERATING MODE SETTING (*) Factory setting Caution ! - SW1-3 through 1-8 are unused. Be sure to turn off unused ones.

  • Extension (SW1-1, 1-2) SW1-1 SW1-2 Extension OFF OFF No extension ( ON OFF Discrete input, 8 or 16 points OFF ON Discrete output, 8 or 16 points TERMINAL ASSIGNMENTS 5 6 PI3 C3 C4 PI4 16 17 18 7 8 9 PI5 PI6 PI7 C5 C6 1 2 Vʴ Vʵ C0 PI0 12 13 3 4 PI1 PI2 C1 C2 C7

1 V – Power (–) 10 V + Power (+)

2 C0 Common 11 PI0 Input 0

3 C1 Common 12 PI1 Input 1

4 C2 Common 13 PI2 Input 2

5 C3 Common 14 PI3 Input 3

6 C4 Common 15 PI4 Input 4

7 C5 Common 16 PI5 Input 5

8 C6 Common 17 PI6 Input 6

9 C7 Common 18 PI7 Input 7

NO. ID FUNCTION NO. ID FUNCTION

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 22/31 http://www.m-system.co.jp/ CIRCUIT DIAGRAM Caution: FG terminal is NOT a protective conductor terminal. PI0 PI7 PI1 PI2 PI3 PI4 PI5 PI6 Control Circuit Control Circuit ■ Input Circuit PI7 PNP connection NPN connection + − ■ Input Connection Examples 9C7 PI0

18 PI7

− + Voltage Pulse Input Connected

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 23/31 http://www.m-system.co.jp/ DC VOLTAGE OUTPUT MODULE, 2 points MODEL: R7E-YV2 SPECIFICATIONS Isolation: Output 0 to output 1 to Ethernet to FG to power input Converted data range: 0 – 10000 of the output range Output range Wide span voltage: -10 – +10 V DC, -5 – +5 V DC, 0 – 10 V DC, 0 – 5 V DC, 1 – 5 V DC Narrow span voltage: -1 – +1 V DC, 0 – 1 V DC, -0.5 – +0.5 V DC Operational range: -15 – +115 % of the output range (except -10 – +10 V DC); approx. -11.5 – +11.5 V DC (-10 – +10 V DC) Load resistance: ≥ 100 kΩ Conversion accuracy: ±0.1 % Response time: 250 msec. (0 – 90 %) Temperature coefficient: ±0.015 %/°C (±0.008 %/°F) OPERATING MODE SETTING (*) Factory setting Caution ! - SW1-3 is unused. Be sure to turn off unused ones.

  • Output Range (SW1-5, 1-6, 1-7 , 1-8) SW1-5 SW1-6 SW1-7 SW1-8 Output range OFF OFF OFF OFF -10 – +10 V DC ( ON OFF OFF OFF -5 – +5 V DC OFF ON OFF OFF -1 – +1 V DC ON ON OFF OFF 0 – 10 V DC OFF OFF ON OFF 0 – 5 V DC ON OFF ON OFF 1 – 5 V DC OFF ON ON OFF 0 – 1 V DC ON ON ON OFF -0.5 – +0.5 V DC ON ON ON ON PC Configurator setting
  • Output at the Loss of Communication (SW1-4) SW1-4 Output at the loss of communication OFF Reset the output (to -15% or approx. -11 .5V DC) ON Hold the output ( (maintains the last data received normally)
  • Extension (SW1-1, 1-2) SW1-1 SW1-2 Extension OFF OFF No extension ( ON OFF Discrete input, 8 or 16 points OFF ON Discrete output, 8 or 16 points TERMINAL ASSIGNMENTS NC VH0 VL0 NC COM0 COM0 VH1 COM1 VL1 COM1 NO. ID FUNCTION NO. ID FUNCTION

1 NC No connection 6 NC No connection

2 COM0 Common 0 7 VH0 Wide span volt. 0 3 COM0 Common 0 8 VL0 Narrow span volt. 0 4 COM1 Common 1 9 VH1 Wide span volt. 1 5 COM1 Common 1 10 VL1 Narrow span volt. 1 CIRCUIT DIAGRAM Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. Output Circuit Control Circuit ■ Output Connection Examples

7 VH0

8 VL0

2 COM0

3 COM0

9 VH1

10 VL1

4 COM1

–COMn WIDE SPAN VOLTAGE VHn VLn + –COMn NARROW SPAN VOLTAGE 24V DC FG Isolation Modbus/ TCP RJ-45 CONNECTOR EXTENSION CONNECTOR

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 24/31 http://www.m-system.co.jp/ DC CURRENT OUTPUT MODULE, 2 points MODEL: R7E-YS2 SPECIFICATIONS Isolation: Output 0 to output 1 to Ethernet to FG to power input Converted data range: 0 – 10000 of the output range Output range: 4 – 20 mA DC Load resistance: ≤ 600Ω Conversion accuracy: ±0.1 % Response time: 250 msec. (0 – 90 %) Temperature coefficient: ±0.015 %/°C (±0.008 %/°F) OPERATING MODE SETTING (*) Factory setting Caution ! - SW1-3, 1-5 through 1-8 are unused. Be sure to turn off unused ones.

  • Output at the Loss of Communication (SW1-4) SW1-4 Output at the loss of communication OFF Reset the output (to -15%) ON Hold the output ( (maintains the last data received normally)
  • Extension (SW1-1, 1-2) SW1-1 SW1-2 Extension OFF OFF No extension ( ON OFF Discrete input, 8 or 16 points OFF ON Discrete output, 8 or 16 points TERMINAL ASSIGNMENTS NC NC NC COM0 NC COM1 NC NC NO. ID FUNCTION NO. ID FUNCTION

2 COM0 Common 0 7 I0 Current 0

3 NC No connection 8 NC No connection

4 COM1 Common 1 9 I1 Current 1

5 NC No connection 10 NC No connection

Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. Output Circuit Control Circuit Output Circuit 7 I0

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 25/31 http://www.m-system.co.jp/ DISCRETE INPUT EXTENSION MODULE, 8 points MODEL: R7E-EA8 SPECIFICATIONS Common: Positive or negative common (NPN/PNP) per 8 points Number of I/O: Input, 8 points Maximum inputs applicable at once: No limit (at 24 V DC) Input status indicator: LED turns ON with contact ON Isolation: Input to internal circuits Rated input voltage: 24 V DC ±10 %; ripple 5 %p-p max. ON voltage / current: ≥ 15 V DC (input – COM) / ≥ 3.5 mA OFF voltage / current: ≤ 5 V DC (input – COM) / ≤ 1 mA Input current: ≤ 5.5 mA per point at 24 V DC Input resistance: Approx. 4.4 kΩ ON delay: ≤ 2.0 msec. OFF delay: ≤ 2.0 msec. TERMINAL ASSIGNMENTS NC COM NO. ID FUNCTION NO. ID FUNCTION

1 COM Common 6 NC No Connection

2 X0 Input 0 7 X1 Input 1

3 X2 Input 2 8 X3 Input 3

4 X4 Input 4 9 X5 Input 5

5 X6 Input 6 10 X7 Input 7

■ Input Circuit 10 X7 9X5 8X3 7X1 5X6 4X4 3X2 2X0 COM 1COM 2X0 10 X7 Control Circuit ■ Input Connection Examples 2X0 COM – + 10 X7 PNP Connection 2X0 COM – + 10 X7 NPN Connection EXTENSION CONNECTOR

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 26/31 http://www.m-system.co.jp/ DISCRETE INPUT EXTENSION MODULE, 16 points MODEL: R7E-EA16 SPECIFICATIONS Common: Positive or negative common (NPN/PNP) per 16 points Number of I/O: Input, 16 points Maximum inputs applicable at once: No limit (at 24 V DC) Input status indicator: LED turns ON with contact ON Isolation: Input to internal circuits Rated input voltage: 24 V DC ±10 %; ripple 5 %p-p max. ON voltage / current: ≥ 15 V DC (input – COM) / ≥ 3.5 mA OFF voltage / current: ≤ 5 V DC (input – COM) / ≤ 1 mA Input current: ≤ 5.5 mA per point at 24 V DC Input resistance: Approx. 4.4 kΩ ON delay: ≤ 2.0 msec. OFF delay: ≤ 2.0 msec. TERMINAL ASSIGNMENTS NC COM XB XA XD XC XE XF NO. ID FUNCTION NO. ID FUNCTION – +– + Input Circuit Control Circuit ■ Input Circuit XB 15 X9 XF XD 14 X7 13 X5 12 X3 11 X1 9XE 8XC 7XA 6X8 5X6 4X4 3X2 2X0 COM 1COM 2X0 18 XF Control Circuit ■ Input Connection Examples 2X0 COM 18 XF PNP Connection 2X0 COM 18 XF NPN Connection EXTENSION CONNECTOR

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 27/31 http://www.m-system.co.jp/ NPN TRANSISTOR OUTPUT EXTENSION MODULE, 8 points MODEL: R7E-EC8A SPECIFICATIONS Common: Negative common (NPN) per 8 points Number of I/O: Output, 8 points Maximum outputs applicable at once: No limit (at 24 V DC) Output status indicator: LED turns ON with contact ON Isolation: Output to internal circuits Rated load voltage: 24 V DC ±10 % Rated output current: 0.25 A per point, 2.0 A per common Residual voltage: ≤ 1.2 V Leakage current: ≤ 0.1 mA ON delay: ≤ 0.5 msec. OFF delay: ≤ 1.5 msec. (When driving an inductive load, connect a diode in parallel with the load.) TERMINAL ASSIGNMENTS +24 V 0 V NO. ID FUNCTION NO. ID FUNCTION 1 0 V 0 V (common) 6 +24 V 24 V DC

2 Y0 Output 0 7 Y1 Output 1

3 Y2 Output 2 8 Y3 Output 3

4 Y4 Output 4 9 Y5 Output 5

5 Y6 Output 6 10 Y7 Output 7

■ Output Circuit 1 0V 10 Y7 9 Y5 8 Y3 7 Y1 5 Y6 4 Y4 3 Y2 +24V +24V6 10 Y7 1 0V Control Circuit ■ Output Connection Example 2Y0 +24V 10 Y7 EXTENSION CONNECTOR

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 28/31 http://www.m-system.co.jp/ NPN TRANSISTOR OUTPUT EXTENSION MODULE, 16 points MODEL: R7E-EC16A SPECIFICATIONS Common: Negative common (NPN) per 16 points Number of I/O: Output, 16 points Maximum outputs applicable at once: No limit (at 24 V DC) Output status indicator: LED turns ON with contact ON Isolation: Output to internal circuits Rated load voltage: 24 V DC ±10 % Rated output current: 0.25 A per point, 2.0 A per common Residual voltage: ≤ 1.2 V Leakage current: ≤ 0.1 mA ON delay: ≤ 0.5 msec. OFF delay: ≤ 1.5 msec. (When driving an inductive load, connect a diode in parallel with the load.) TERMINAL ASSIGNMENTS +24V YB YA YD YC YE YF NO. ID FUNCTION NO. ID FUNCTION 1 0 V 0 V (common) 10 +24 V 24 V DC +24V 18 YF 1 0V Control Circuit Output Circuit Control Circuit ■ Output Circuit YD 16 YB YF 15 Y9 14 Y7 13 Y5 12 Y3 11 Y1 9 YE 8 YC 7 YA 6 Y8 5 Y6 4 Y4 3 Y2 +24V ■ Output Connection Example 2Y0 +24V

18 YF EXTENSION CONNECTOR

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 29/31 http://www.m-system.co.jp/ PNP TRANSISTOR OUTPUT EXTENSION MODULE, 8 points MODEL: R7E-EC8B SPECIFICATIONS Common: Positive common (PNP) per 8 points Number of I/O: Output, 8 points Maximum outputs applicable at once: No limit (at 24 V DC) Output status indicator: LED turns ON with contact ON Isolation: Output to internal circuits Rated load voltage: 24 V DC ±10 % Rated output current: 0.25 A per point, 2.0 A per common Residual voltage: ≤ 1.2 V Leakage current: ≤ 0.1 mA ON delay: ≤ 0.5 msec. OFF delay: ≤ 1.5 msec. (When driving an inductive load, connect a diode in parallel with the load.) TERMINAL ASSIGNMENTS +24 V 0 V NO. ID FUNCTION NO. ID FUNCTION 1 0 V 0 V 6 +24 V 24 V DC (common) ■ Output Circuit 1 0V 10 Y7 9 Y5 8 Y3 7 Y1 5 Y6 4 Y4 3 Y2 +24V +24V6 10 Y7 1 0V Control Circuit ■ Output Connection Example 2Y0 +24V 10 Y7 EXTENSION CONNECTOR

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 30/31 http://www.m-system.co.jp/ PNP TRANSISTOR OUTPUT EXTENSION MODULE, 16 points MODEL: R7E-EC16B SPECIFICATIONS Common: Positive common (PNP) per 16 points Number of I/O: Output, 16 points Maximum outputs applicable at once: No limit (at 24 V DC) Output status indicator: LED turns ON with contact ON Isolation: Output to internal circuits Rated load voltage: 24 V DC ±10 % Rated output current: 0.25 A per point, 2.0 A per common Residual voltage: ≤ 1.2 V Leakage current: ≤ 0.1 mA ON delay: ≤ 0.5 msec. OFF delay: ≤ 1.5 msec. (When driving an inductive load, connect a diode in parallel with the load.) TERMINAL ASSIGNMENTS +24V YB YA YD YC YE YF NO. ID FUNCTION NO. ID FUNCTION 1 0 V 0 V 10 +24 V 24 V DC (common) ■ Output Circuit YD 16 YB YF 15 Y9 14 Y7 13 Y5 12 Y3 11 Y1 9 YE 8 YC 7 YA 6 Y8 5 Y6 4 Y4 3 Y2 +24V +24V10 18 YF 1 0V Control Circuit ■ Output Connection Example 2Y0 +24V

MODEL: R7E R7E SPECIFICATIONS ES-7807 Rev.13 Page 31/31 http://www.m-system.co.jp/ Specifications are subject to change without notice.