R5-TCTB MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
MODEL: R5T-CTB R5T-CTB SPECIFICATIONS ES-7555 Rev.3 Page 1/3 http://www.m-system.co.jp/ Remote I/O R5 Series AC CURRENT INPUT MODULE (clamp-on current sensor type CLSB use; screw terminal block; true RMS sensing) 137 (5.39) 18 (.71) (3.54) mm (inch) MODEL: R5T-CTB[1][2][3]
ORDERING INFORMATION
Code number: R5T-CTB[1][2][3] Specify a code from below for each [1] through [3]. (e.g. R5T-CTB2W/Q)
- Specify the specification for option code /Q (e.g. /C01/S01) [1] NO. OF CHANNELS 1: 1 channel 2: 2 channels [2] COMMUNICATION MODE S: Single W: Dual [3] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel
RELATED PRODUCTS
- Clamp-on current sensor (model: CLSB-05)
- Clamp-on current sensor (model: CLSB-10)
- Clamp-on current sensor (model: CLSB-20)
- Clamp-on current sensor (model: CLSB-40)
- Clamp-on current sensor (model: CLSB-60) The clamp-on current sensor, not included in the product package, must be ordered separately. Refer to the data sheet for the sensor for more information such as applicable wire diameter. GENERAL SPECIFICATIONS Connection Internal bus: Via the Installation Base (model: R5-BS) Input: M3.5 screw terminal block (torque 0.8 N·m) Internal power: Via the base (model: R5-BS) Screw terminal: Nickel-plated steel (standard) or stainless steel Isolation: Input 1 to input 2 to internal bus or internal power Input waveform RMS sensing: Up to 15 % of 3rd harmonic content Input range: Selectable with the side DIP SW RUN indicator: Bi-color (red/green) LED; Red when the bus A operates normally; Green when the bus B operates normally; Amber when both buses operate normally. Low-end cutout: Converted as 0 % for the input below 2 % INPUT SPECIFICATIONS Input (sensor & range) CLSB-05: 0 – 50A AC CLSB-10: 0 – 100A AC CLSB-20: 0 – 200A AC CLSB-40: 0 – 400A AC CLSB-60: 0 – 600A AC (Operational range for the CLSB-60 is limited up to approx. 109 % (65535). Frequency: 50 or 60 Hz Operational range: 5 – 115 % of rating Max. working voltage: 440 V AC (primary side) INSTALLATION Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base (model: R5-BS) Weight: 110 g (0.24 lb)
MODEL: R5T-CTB R5T-CTB SPECIFICATIONS ES-7555 Rev.3 Page 2/3 http://www.m-system.co.jp/ PERFORMANCE Conversion accuracy: ±0.5 % (at 5 – 100 % input) except the sensor accuracy Data range: Engineering unit value × 100 (binary without sign) Data allocation: 1 (2 for 2-channel type) Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Response time: ≤ 0.5 sec. (0 – 90 %) Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (input 1 to input 2 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module) EXTERNAL VIEW RUN RUN LED ON Input 1 Input 2 2 3 4 5 6 7 8 ˙ SIDE VIEW ˙ FRONT VIEW INPUT DATA DESCRIPTIONS ■ ANALOG DATA (AC CURRENT DATA.) 015 16-bit binary data. Integer obtained by multiplying unit value (A) by 100.
MODEL: R5T-CTB R5T-CTB SPECIFICATIONS ES-7555 Rev.3 Page 3/3 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) TERMINAL COVER 4–M3.5 TERMINAL SCREWS 7.2 (.28) LOCKING CLAMP 90 (3.54) 5.6 (.22) 18 (.71) POSITIONING GUIDE SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Input Circuit Input Circuit RUN LED Control Circuit Communication Circuit BUS CONNECTOR INTERNAL POWER INTERNAL BUS A INTERNAL BUS B* *For dual redundant communication. Note: The section enclosed by broken line is with 2-ch. option. INPUT 1 LOAD SOURCE k l CLAMP-ON SENSOR INPUT 2 LOAD SOURCE k l CLAMP-ON SENSOR DIP SW Specifications are subject to change without notice.