MODEL: R5-DS1A R5-DS1A SPECIFICATIONS ES-7562 Rev.7 Page 1/3 http://www.m-system.co.jp/ Remote I/O R5 Series 4 – 20 mA INPUT MODULE (2-wire transmitter excitation supply; re-transmitted output) 96.5 (3.80) 18 (.71) (3.54) mm (inch) 4321 9 8 76 MODEL: R5–DS1A[1][2]

ORDERING INFORMATION

  • Code number: R5-DS1A[1][2] Specify a code from below for each of [1] and [2]. (e.g. R5-DS1AW/Q)
  • Specify the specification for option code /Q (e.g. /C01) NO. OF CHANNELS 1: 1 channel OUTPUT Current A: 4 – 20 mA DC (Load resistance 600 Ω max.) [1] COMMUNICATION MODE S: Single W: Dual [2] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating GENERAL SPECIFICATIONS Connection Internal bus: Via the Installation Base (model: R5-BS) I/O: Euro type connector terminal (Applicable wire size: 0.2 – 2.5 mm2 (AWG24 - 12), stripped length 7 mm) Internal power: Via the base (model: R5-BS) Isolation: Input to output to internal bus or internal power Zero/Span adj. mode selector: Rotary switch; monitor mode, adj. mode and simulated output mode selectable RUN indicator: Bi-color (red/green) LED; Red when the bus A operates normally; Green when the bus B operates normally; Amber when both buses operate normally. SUPPLY OUTPUT Output voltage: 24 – 29 V DC with no load Current rating: ≤ 22 mA DC
  • Shortcircuit Protection Current limited: 30 mA max. Protected time duration: No limit INPUT SPECIFICATIONS ■ DC Current: 4 – 20 mA DC Input resistance: 250 Ω resistor incorporated OUTPUT SPECIFICATIONS Operational range: Approx. 0 – 24 mA DC INSTALLATION Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base (model: R5-BS) Weight: 100 g (3.53 oz) PERFORMANCE Conversion accuracy Input: ±0.05 % Output: ±0.1 % of the retransmitted range + input conversion accuracy Data range: 0 – 10000 of the input range Data allocation: 1 Temp. coefficient Output: ±0.02 %/°C (±0.01 %/°F) Response time: ≤ 0.2 sec. (0 – 90 %) Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (input to output to internal bus or internal power)

MODEL: R5-DS1A R5-DS1A SPECIFICATIONS ES-7562 Rev.7 Page 2/3 http://www.m-system.co.jp/

2000 V AC @ 1 minute (power input to FG; isolated on the

power supply module) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive EN 50581 FUNCTIONS

  • Zero/Span Adjustment Modes Monitor Mode Re-transmits the input signal as output in proportion. Output 0 % Adjustment Mode Adjusts the 0 % output signal using the front UP/DOWN buttons, in monitoring the output value with a multimeter. SW1 through SW3 switch the internal increments by 1, 5 and 10. Output 100 % Adjustment Mode Adjusts the 100 % output signal using the front UP/DOWN buttons, in monitoring the output value with a multimeter. SW4 through SW6 switch the internal increments by 1, 5 and 10. Simulated Output Mode Outputs the simulated signals of 0 %, 50 % and 100 %.
  • How to Operate 1) Start up in Monitor Mode (SW position = 0) and wait for 2 or 3 seconds. 2) Switch to another mode and go through the adjustments. 3) Reset the switch to the position ‘0’ so that the new setting is stored in the internal memory. EXTERNAL VIEW RUN LED Zero/Span Adj. Mode Selector 4321 9 8 76 4 5 6 1 2 3 RUN UP DOWN UP Button DOWN Button Euro Type Connector Terminals

MODEL: R5-DS1A R5-DS1A SPECIFICATIONS ES-7562 Rev.7 Page 3/3 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 4 5 6 1 2 3 6.5 (.26) 90 (3.54) LOCKING CLAMP 90 (3.54) 5.6 (.22) 18 (.71) POSITIONING GUIDE SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM 150Ω 100Ω INPUT 150Ω 100Ω 2-WIRE TRANSMITTER 100Ω 150Ω INPUT 2W-XMTR EXC ■ When Used as DC Supply ■ When Used as Current Input INTERNAL POWER INTERNAL BUS A INTERNAL BUS B* *For dual redundant communication. RUN LED Communication Circuit Excitation Supply Isolation BUS CONNECTOR 5 – Output Driver ROTARY SW Control Circuit OUTPUT UP/DOWN BUTTONS Specifications are subject to change without notice.