MODEL: R3S-YS4 R3S-YS4 SPECIFICATIONS ES-8939 Rev.5 Page 1/4 http://www.m-system.co.jp/ Remote I/O R3 Series DC CURRENT OUTPUT MODULE (4 points, isolated, tension clamp terminal block) 27.5 (1.08) 130 (5.12) mm (inch) 120 (4.72) MODEL: R3S-YS4[1][2]
ORDERING INFORMATION
- Code number: R3S-YS4[1][2] Specify a code from below for each of [1] and [2]. (e.g. R3S-YS4W/H/Q)
- Specify the specification for option code /Q (e.g. /C01/SET) NO. OF CHANNELS 4: 4 [1] COMMUNICATION MODE S: Single W: Dual [2] OPTIONS (multiple selections) Load Resistance blank: ≤ 300 Ω /H: ≤ 600Ω Other Options blank: none /Q: Option other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating EX-FACTORY SETTING /SET: Preset according to the Ordering Information Sheet (No. ESU-8370) GENERAL SPECIFICATIONS Connection Internal bus: Via the Installation Base (model: R3-BSx) Output: Separable tension clamp terminal (applicable wire size: 0.2 to 1.5 mm2, stripped length 10 mm) Internal power: Via the Installation Base (model: R3-BSx) Isolation: Output 1 to output 2 to output 3 to output 4 to internal bus or internal power Output hold function: Setting for communication error with side DIP SW RUN indicator: Bi-color (red/green) LED; Red when the bus A operates normally; Green when the bus B operates normally; Amber when both buses operate normally. ERR indicator: Bi-color (red/green) LED; Red with output abnormality; Green in normal operating conditions. OUTPUT SPECIFICATIONS Output range: 4 – 20 mA DC Load resistance: 300 Ω max. (600 Ω max. with Option /H) INSTALLATION Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base (model: R3-BSx) Weight: 200 g (0.44 lb) PERFORMANCE Conversion accuracy: ±0.05 % Data range: 0 – 10000 of the output range Data allocation: 4 Current consumption: 180 mA (260 mA with Option /H) Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Response time: ≤ 0.2 sec. (0 – 90 %) Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (output 1 to output 2 to output 3 to output 4 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
power supply module) FUNCTIONS ■OUTPUT HOLD or OUTPUT OFF In normal conditions, the module outputs the signal from the preferred bus A. When an error is detected, the output is switched to the data from the bus B.
- Output Hold
MODEL: R3S-YS4 R3S-YS4 SPECIFICATIONS ES-8939 Rev.5 Page 2/4 http://www.m-system.co.jp/ If both are in error, the module holds the signal and stands by until one of the communications recovers.
- Output OFF If both are in error, the module outputs -15 % and stands by until one of the communications recovers. At the startup, it outputs -15 % until the communication is established and normal data is received. EXTERNAL VIEW RUN LED ERR LED ■ FRONT VIEW ■ SIDE VIEW SW3 Output Hold ON EXTERNAL DIMENSIONS unit: mm (inch) 130 (5.12) 120 (4.72) POSITIONING GUIDE
MODEL: R3S-YS4 R3S-YS4 SPECIFICATIONS ES-8939 Rev.5 Page 3/4 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Unused channels left open are equal to the wire breakdown, which turns the red ERR LED on and sets a burnout flag at the PLC or the host device. Unused channels can be specified and set so on the PC Configurator Software (model: R3CON) without needing to short at the field terminals.
- Unused Output Channels Close across the unused output terminals as shown below. Output Circuit Output Circuit Output Circuit Output Circuit Comm. Circuit Control Circuit *1. For dual redundant communication. *2. To use shield line, connect it to SLD terminal and ground the terminal 20. Note: Do not use void terminals. INTERNAL POWER OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 RUN LED ERR LED DIP SW OUTPUT 1 Cross-wire OUTPUT 2 OUTPUT 3 OUTPUT 4 SLD SLD SLD SLD SLD SLD INTERNAL BUS A INTERNAL BUS B*1 BUS CONNECTOR
MODEL: R3S-YS4 R3S-YS4 SPECIFICATIONS ES-8939 Rev.5 Page 4/4 http://www.m-system.co.jp/ OUTPUT TERMINAL ASSIGNMENT PIN No. FUNCTION COM1 NC
4 SLD
6 COM2
8 SLD
12 COM3
14 SLD
16 COM4
18 SLD
19 SLD
20 SLD
Specifications are subject to change without notice.