R3-SRR8 MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 5
Technical content
MODEL: R3S-RR8 R3S-RR8 SPECIFICATIONS ES-8934 Rev.3 Page 1/5 http://www.m-system.co.jp/ Remote I/O R3 Series REMOTE CONTROL RELAY CONTROL MODULE (Do 8 points, tension clamp terminal block) Functions & Features
- Controls remote control relays for lighting control with Fieldbus
- Applicable to the remote control relays already installed
- Monitors status of remote control relays with feedback inputs from signal lines Typical Applications
- Monitors and controls of lighting in buildings 27.5 (1.08) 130 (5.12) mm (inch) 120 (4.72) MODEL: R3S-RR8[1][2]
ORDERING INFORMATION
- Code number: R3S-RR8[1][2] Specify a code from below for each of [1] and [2]. (e.g. R3S-RR8W/Q)
- Specify the specification for option code /Q (e.g. /C01) NO. OF CHANNELS 8: 8 [1] COMMUNICATION MODE S: Single W: Dual [2] OPTIONS blank: none /Q: Options other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating
RELATED PRODUCTS
- Interface Module (model: R3-NC1, NC3, NE1, NM1, NDx, NF2, NFL1) Firmware version V2.00 or higher. R3-NF2 is available with firmware version V0.04 or higher. GENERAL SPECIFICATIONS Connection Internal bus: Via the Installation Base (model: R3-BSx) Output: Separable tension clamp terminal (applicable wire size: 0.2 to 1.5 mm2, stripped length 10 mm) Internal power: Via the Installation Base (model: R3-BSx) Isolation: Output to internal bus or internal power Input Data Length: 8 bit, 16 bit selectable with DIP switch Output data length: 8 bit, 16 bit selectable with DIP switch RUN indicator: Bi-color (red/green) LED; Red when the bus A operates normally; Green when the bus B operates normally; Amber when both buses operate normally. ERR indicator: Green LED; OFF in abnormality; ON in normal operating conditions. Input output status indicator: Red LED; 1 to 8: Output bit status, turns on with bit set ON. 9 to 16: Feedback input status, turns on with the input ON. OUTPUT SPECIFICATIONS Number of output: 8 points Common: All 8 points (12 terminal) Rated load voltage: 24 V AC ±10 % (supplied by the remote control transformer) Load voltage frequency: 50 / 60 Hz Maximum outputs provided at once: No limit Output ON duration: 100 msec. INSTALLATION Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base (model: R3-BSx) Weight: 200 g (0.44 lb) PERFORMANCE Data allocation: 1 Current consumption: 40 mA Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (output to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the
MODEL: R3S-RR8 R3S-RR8 SPECIFICATIONS ES-8934 Rev.3 Page 2/5 http://www.m-system.co.jp/ power supply module) EXTERNAL VIEW SW3 ON Status Indicator LED RUN LED ERR LED Functions FRONT VIEW SIDE VIEW Output Data Bit Input Data Bit ■ ■ EXTERNAL DIMENSIONS unit: mm (inch) 130 (5.12) 120 (4.72) POSITIONING GUIDE
MODEL: R3S-RR8 R3S-RR8 SPECIFICATIONS ES-8934 Rev.3 Page 3/5 http://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Output Circuit Comm. Circuit ERR LED RUN LED STATUS INDICATOR LED DIP SW Control Circuit OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8 COM COM
3 OUTPUT 2
Numbers in italic indicate LED No.s assigned to the front panel LEDs. * For dual redundant communication. INTERNAL POWER INTERNAL BUS A INTERNAL BUS B* OUTPUT TERMINAL ASSIGNMENT PIN No. FUNCTION
1 Do 1
2 COM
3 Do 2
4 COM
5 Do 3
6 COM
7 Do 4
8 COM
9 Do 5
10 COM
11 Do 6
12 COM
13 Do 7
14 COM
15 Do 8
16 COM
17 COM
18 COM
19 COM
20 COM
MODEL: R3S-RR8 R3S-RR8 SPECIFICATIONS ES-8934 Rev.3 Page 4/5 http://www.m-system.co.jp/ INPUT OUTPUT DATA BIT & DATA ALLOCATION ■ OUTPUT DATA BIT: 16 BITS (SW3-4: OFF) When output data bit is 16 bits, set each output with 2 bits. The table below shows data allocation. BIT SETTING OPERATION 0, 1 0, 0 No operation 1, 0 Output 1 ON 0, 1 Output 1 OFF 1, 1 Output 1 RESET 2, 3 0, 0 No operation 1, 0 Output 2 ON 0, 1 Output 2 OFF 1, 1 Output 2 RESET 4, 5 0, 0 No operation 1, 0 Output 3 ON 0, 1 Output 3 OFF 1, 1 Output 3 RESET 6, 7 0, 0 No operation 1, 0 Output 4 ON 0, 1 Output 4 OFF 1, 1 Output 4 RESET 8, 9 0, 0 No operation 1, 0 Output 5 ON 0, 1 Output 5 OFF 1, 1 Output 5 RESET 10, 11 0, 0 No operation 1, 0 Output 6 ON 0, 1 Output 6 OFF 1, 1 Output 6 RESET 12, 13 0, 0 No operation 1, 0 Output 7 ON 0, 1 Output 7 OFF 1, 1 Output 7 RESET 14, 15 0, 0 No operation 1, 0 Output 8 ON 0, 1 Output 8 OFF 1, 1 Output 8 RESET By set t ing wi th 2 bi ts, the module operates as shown above. ON or OFF can be set consecutively. To output ON twice successively, set ON (1, 0), RESET (1, 1), and then set ON (1, 0) again. ■ OUTPUT DATA BIT: 8 BITS (SW3-4: ON) When output data bit is 8 bits, set each output with 1 bit. The table below shows data allocation. BIT SETTING OPERATION
0 Output 1 OFF
1 Output 1 ON
0 Output 2 OFF
1 Output 2 ON
0 Output 3 OFF
1 Output 3 ON
0 Output 4 OFF
1 Output 4 ON
0 Output 5 OFF
1 Output 5 ON
0 Output 6 OFF
1 Output 6 ON
0 Output 7 OFF
1 Output 7 ON
0 Output 8 OFF
1 Output 8 ON
ON (or OFF) cannot be set consecutively, because when each bit is “1”, ON is set and when each bit is “0”, OFF is set.
MODEL: R3S-RR8 R3S-RR8 SPECIFICATIONS ES-8934 Rev.3 Page 5/5 http://www.m-system.co.jp/ ■ INPUT DATA BIT: 16 BITS (SW3-3: ON) When output data bit is 16 bits, display the status of feedback input for each output with 2 bits. The table below shows data allocation. BIT DISPLAY OPERATION
0 Feedback input for output 1 OFF
1 Feedback input for output 1 ON
0 Feedback input for output 2 OFF
1 Feedback input for output 2 ON
0 Feedback input for output 3 OFF
1 Feedback input for output 3 ON
0 Feedback input for output 4 OFF
1 Feedback input for output 4 ON
0 Feedback input for output 5 OFF
1 Feedback input for output 5 ON
0 Feedback input for output 6 OFF
1 Feedback input for output 6 ON
0 Feedback input for output 7 OFF
1 Feedback input for output 7 ON
0 Feedback input for output 8 OFF
1 Feedback input for output 8 ON
■ INPUT DATA BIT: 8 BITS (SW3-3: OFF) When output data bit is 8 bits, display the status of feedback input for each output with 1 bit. The table below shows data allocation. BIT DISPLAY OPERATION Specifications are subject to change without notice.