R3G190-RC05-03 EBMPAPST | Alldatasheet

Document overview

  • Manufacturer or author: MK_4183 / 2016-10-11
  • PDF pages: 5

Technical content

EC centrifugal fan - RadiCal backward curved, single inlet R3G190-RC05-03 ebm-papst Mulfingen GmbH & Co. KG Bachmühle 2 · D-74673 Mulfingen Phone +49 7938 81-0 Fax +49 7938 81-110 info1@de.ebmpapst.com www.ebmpapst.com Limited partnership · Headquarters Mulfingen County court Stuttgart · HRA 590344 General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen County court Stuttgart · HRB 590142 Nominal data Type R3G190-RC05-03 Motor M3G055-BI Phase 1~ Nominal voltage VAC 230 Nominal voltage range VAC 200 .. 240 Frequency Hz 50/60 Type of data definition ml Speed (rpm) min-1 3200 Power input W 83 Current draw A 0.75 Min. ambient temperature °C -25 Max. ambient temperature °C 60 ml = Max. load · me = Max. efficiency · fa = Running at free air · cs = Customer specs · cu = Customer unit Subject to alterations Item no. 51030-5-9980 · ENG · Revision 89188 · Release 2016-04-29 · Page 1 / 5

EC centrifugal fan - RadiCal backward curved, single inlet R3G190-RC05-03 Technical features Mass 1.1 kg Size 190 mm Surface of rotor Thick layer passivated Material of electronics housing Die-cast aluminium Material of impeller PA plastic Number of blades 7 Direction of rotation Clockwise, seen on rotor Type of protection IP 54 Insulation class "B" Max. permissible ambient motor temp. (transp./ storage) + 80 °C Min. permissible ambient motor temp. (transp./storage) - 40 °C Mounting position Any Condensate discharge holes None, open rotor Operation mode S1 Motor bearing Ball bearing Technical features - Output 10 VDC, max. 1.1 mA - Tach output - Output limit - Motor current limit - Soft start - Control input 0-10 VDC / PWM - Control interface with SELV potential safely disconnected from the mains - Overvoltage detection - Over-temperature protected electronics / motor - Line undervoltage detection EMC interference immunity Acc. to EN 61000-6-2 (industrial environment) EMC harmonics Acc. to EN 61000-3-2/3 EMC interference emission Acc. to EN 61000-6-3 (household environment) Touch current acc. IEC 60990 (measuring network Fig. 4, TN system) <= 3.5 mA Motor protection Locked-rotor protection Cable exit Variable Protection class I (if protective earth is connected by customer) Product conforming to standard EN 60335-1; CE Approval CCC; UL 2111; CSA C22.2 No.77; EAC Item no. 51030-5-9980 · ENG · Revision 89188 · Release 2016-04-29 · Page 2 / 5

EC centrifugal fan - RadiCal backward curved, single inlet R3G190-RC05-03 Product drawing

1 Accessory part: Inlet nozzle 09576-2-4013, not included in the standard scope of delivery

2 Connection line PVC AWG20, 3x brass lead tips crimped

3 Connection line PVC AWG22, 4 x brass lead tips crimped

4 Depth of screw max. 5 mm Item no. 51030-5-9980 · ENG · Revision 89188 · Release 2016-04-29 · Page 3 / 5

EC centrifugal fan - RadiCal backward curved, single inlet R3G190-RC05-03 Connection screen No. Conn. Designation Colour Function / assignment CON10 L black Power supply 230 VAC, 50-60 Hz, see type plate for voltage range CON11 N blue Neutral conductor CON12 PE green/yellow Protective earth

1 GND blue GND connection for control interface

2 0-10V PWM yellow Control input 0-10 V or PWM, electrically isolated 3 10 V / max. 1,1 mAred Voltage output 10 VDC 1.1 mA, electrically isolated, short-circuit-proof

4 Tacho white Tach output: Open collector, 1 pulse per revolution, electrically isolated

Item no. 51030-5-9980 · ENG · Revision 89188 · Release 2016-04-29 · Page 4 / 5

EC centrifugal fan - RadiCal backward curved, single inlet R3G190-RC05-03 Charts: Air flow 50 Hz qv m³/h cfm Pfs Pa in wg 100 200 300 400 500 600 0 100 200 300 100 200 300 400 500 600 700 0.5 1 1.5 2 2.5 ρ = 1.15 kg/m³ ± 2 % Measurement: LU-171430-1 Air performance measured as per ISO 5801 Installation category A. For detailed information on the measuring set-up, please contact ebm-papst. Suction-side noise levels: LwA measured as per ISO 13347 / LpA measured with 1m distance to fan axis. The values given are valid under the measuring conditions mentioned above and may vary according to the actual installation situation. With any deviation from the standard set-up, the specific values have to be checked and reviewed with the unit installed. Measured values U V 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 230 f Hz n min-1 3420 3360 3200 3275 3000 3000 3000 3000 2400 2400 2400 2400 1800 1800 1800 1800 Ped W I A 0.67 0.70 0.75 0.73 0.45 0.50 0.60 0.56 0.23 0.26 0.31 0.29 0.10 0.11 0.13 0.12 LpAin dB(A) LwAin dB(A) qV m3/h 695 600 435 290 610 535 405 265 490 430 320 210 365 320 240 160 pfs Pa 150 300 400 119 261 337 167 216 121 qV cfm 410 355 255 170 360 315 235 155 290 250 190 125 215 190 140 pfs inH2O 0.00 0.60 1.20 1.61 0.00 0.48 1.05 1.35 0.00 0.31 0.67 0.87 0.00 0.17 0.38 0.49 U = Supply voltage · f = Frequency · n = Speed (rpm) · Ped = Power input · I = Current draw · LpAin = Sound pressure level inlet side · LwAin = Sound power level inlet side · qV = Air flow pfs = Pressure increase Item no. 51030-5-9980 · ENG · Revision 89188 · Release 2016-04-29 · Page 5 / 5