MODEL: R30RS4 R30RS4 SPECIFICATIONS ES-9003 Rev.3 Page 1/6 https://www.m-system.co.jp/ Remote I/O R30 Series RTD INPUT MODULE (4 points, isolated) Functions & Features
- 4 channels for RTD input remote I/O module
- Isolation between input channels
- Input range of each channel is individually adjustable with PC configurator 25 [.98] mm [inch] [3.86] 110 [4.33] MODEL: R30RS4S[1]
ORDERING INFORMATION
- Code number: R30RS4S[1] Specify a code from below for [1]. (e.g. R30RS4S/Q)
- Specify the specification for option code /Q (e.g. /C01/SET) NO. OF CHANNELS 4: 4 COMMUNICATION MODE S: Single [1] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating EX-FACTORY SETTING /SET: Preset according to the Ordering Information Sheet (No. ESU-9003) CAUTION ■ UNUSED INPUT CHANNELS Set unused channels to "CH disabled" with PC Configurator software (model: R30CFG). Otherwise, unused channels left open are to be burnout status, setting a data error at the PLC or other host devices.
RELATED PRODUCTS
- PC configurator software (model: R30CFG) Downloadable at M-System’s web site. For connecting to PC, use commercially available Mini-B type USB cable. (provided by user) GENERAL SPECIFICATIONS Connection Internal bus: Via the Installation Base (model: R30BS) Input: M3 separable screw terminal (torque 0.5 N·m) Internal power: Via the Installation Base (model: R30BS) Solderless terminal: Refer to the drawing at the end of the section. Recommended manufacturer: Japan Solderless Terminal (Solderless terminals with insulation sleeve do not fit.) Applicable wire size: 0.25 to 0.75 mm2 Screw terminal: Nickel-plated steel Isolation: Input 1 to input 2 to input 3 to input 4 to internal bus or internal power Input range: Selectable with PC configuration software (model: R30CFG) Conversion rate: Selectable with PC configuration software (model: R30CFG) Burnout: Selectable among upscale, downscale or no burnout with PC configurator software (model: R30CFG) Linearization: Standard Status indicator LED: RUN, ERR (refer to the instruction manual) ■Recommended solderless terminal size - M3 (unit: mm) 12 max. 6 max. 3 max. 3.2 dia.
MODEL: R30RS4 R30RS4 SPECIFICATIONS ES-9003 Rev.3 Page 2/6 https://www.m-system.co.jp/ INPUT SPECIFICATIONS Module type: Analog input, 4 points RTD: Pt 100 (JIS ’97, IEC), Pt 100 (JIS ’89), JPt 100 (JIS ’89), Pt 50Ω (JIS ’81), Ni 100, Cu 10, Cu 50 Sensing current: Max. 1 mA Allowable leadwire resistance: Max. 100 Ω per wire Temperature range RTD ˚C USABLE RANGE CONFORMANCE RANCE Pt 100 (JIS’97 , IEC) -240 – +900 -200 – +850 Pt 100 (JIS’89) -240 – +900 -200 – +660 JPt 100 (JIS’89) -236 – +560 -200 – +510 Pt 50Ω (JIS’81) -236 – +700 -200 – +649 Ni 100 -100 – +252 -80 – +250 Cu 10@25˚C -212 – +312 -50 – +250 Cu 50 -100 – +200 -50 – +150 RTD ˚F USABLE RANGE CONFORMANCE RANCE Pt 100 (JIS’97 , IEC) -400 – +1652 -328 – +1562 Pt 100 (JIS’89) -400 – +1652 -328 – +1220 JPt 100 (JIS’89) -393 – +1040 -328 – +950 Pt 50Ω (JIS’81) -393 – +1292 -328 – +1200 Ni 100 -148 – +486 -112 – +482 Cu 10@25˚C -350 – +594 -58 – +482 Cu 50 -148 – +392 -58 – +302 Burnout value: Upper 32767 , Lower -32768 INSTALLATION Current consumption: 50 mA max. Operating temperature: -10 to +55°C (14 to 131°F) Storage temperature: -20 to +65°C (-4 to +149°F) Operating humidity: 10 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base (model: R30BS) Weight: 160 g (0.35 lb) PERFORMANCE Conversion accuracy: ±1°C (±1.8°F) except ±3°C (±5.4°F) for Cu 10 @ 25°C Conversion rate: 250 msec. or 500 msec. selectable Converted data range °C, K: Engineering unit value × 10 (integer) (Default setting) °F: Engineering unit value (integer) * Scaling of converted data is configurable with the configurator software (model: R30CFG). Refer to the software manual for details. Data allocation: 4 Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Input delay time: 50 msec. Response time: Conversion rate × 2 + 50 msec. (0 – 90 %) Burnout response time: ≤ 1 sec. Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (input 1 to input 2 to input 3 to input 4 to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated on the
power supply module) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive
MODEL: R30RS4 R30RS4 SPECIFICATIONS ES-9003 Rev.3 Page 3/6 https://www.m-system.co.jp/ CONFIGURATOR SOFTWARE SETTING The following parameters can be set with using PC Configurator Software (model: R30CFG) Refer to the users manual for the R30CFG for detailed operation of the software program. ■ CHANNEL INDIVIDUAL SETTING PARAMETER SETTING RANGE DEFAULT SETTING Unused setting CH enabled CH disabled CH enabled Input type Pt 100 (JIS ’97 , IEC) Pt 100 (JIS ’89) JPt 100 (JIS ’89) Pt 50 Ω (JIS ’81) Ni 100 Cu 10 @ 25˚C Cu 50 Pt100 ( JIS ’97 , IEC) Burnout Upscale Downscale None Upscale Unit degC degF K degC Fine zero adjustment -320.00 – +320.00 (%) 0.00 (%) Fine gain adjustment -3.2000 – +3.2000 1 .0000 Zero base -3 200.0 – +3 200.0 (degC, K) -32 000 – +32 000 (degF) 0.0 Full base -3 200.0 – +3 200.0 (degC, K) -32 000 – +32 000 (degF) 0.0 Scaled range Zero -32 000 – +32 000 0 Scaled range Span -32 000 – +32 000 10 000 ■ CHANNEL BATCH SETTING PARAMETER SETTING RANGE DEFAULT SETTING Conversion rate 250 ms 500 ms 500 ms Simulate input Normal input Simulated data Normal input
MODEL: R30RS4 R30RS4 SPECIFICATIONS ES-9003 Rev.3 Page 4/6 https://www.m-system.co.jp/ EXTERNAL VIEW RUN ERR RUN LED Input Terminal Block ERR LED ■ FRONT VIEW ■ BOTTOM VIEW ■ SIDE VIEW Lock Tab Base Fixing Screw Specifications Positioning Guide Terminal Cover Terminal Fixing Screw TERMINAL ASSIGNMENTS NC INB1 NC INB2 NC NC INB3 NC INB4 NC INA1 INb1 INA2 INb2 NC INA3 INb3 INA4 INb4 NC NO. ID FUNCTION NO. ID FUNCTION
1 INA1 RTD 1-A 11 NC No connection
2 INb1 RTD 1-b 12 INB1 RTD 1-B
3 INA2 RTD 2-A 13 NC No connection
4 INb2 RTD 2-b 14 INB2 RTD 2-B
5 NC No connection 15 NC No connection
6 INA3 RTD 3-A 16 NC No connection
7 INb3 RTD 3-b 17 INB3 RTD 3-B
8 INA4 RTD 4-A 18 NC No connection
9 INb4 RTD 4-b 19 INB4 RTD 4-B
10 NC No connection 20 NC No connection
MODEL: R30RS4 R30RS4 SPECIFICATIONS ES-9003 Rev.3 Page 5/6 https://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch] ᶃ ᶄ ᶅ ᶆ ᶍ ᶎ ᶏ ᶐ ᶇ ᶈ ᶉ ᶊ ᶋ ᶌ ᶑ ᶒ ᶓ ᶔ ᶕ ᶖ 110 [4.33] 25 [.98] 98 [3.86] 20–M3 SCREW [.24] SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Comm. Circuit Control Circuit A B B INAn INbn INBn Input 1 Input 2 Input 3 Input 4 INA1 INB1 INA2 INB2 INb1 INb2 INA3 INB3 INA4 INB4 INb3 INb4 RUN indicator ERR indicator Input Circuit Input Circuit Input Circuit Input Circuit INTERNAL POWER INTERNAL BUS ■Input Connection Examples BUS CONNECTOR
MODEL: R30RS4 R30RS4 SPECIFICATIONS ES-9003 Rev.3 Page 6/6 https://www.m-system.co.jp/ Specifications are subject to change without notice.