MODEL: R1M-A1 R1M-A1 SPECIFICATIONS ES-5660 Rev.19 Page 1/6 https://www.m-system.co.jp/ PC Recorders R1M Series PC RECORDER (contact input, 32 points) Functions & Features
- Industrial recorder on PC
- 32-point dry contact inputs
- Easy system expansion via Modbus RTU
- Recorded data exportable to spreadsheet applications [1.57] 115 [4.53] mm [inch] 175 [6.89] MODEL: R1M-A1[1]-[2][3]
ORDERING INFORMATION
- Code number: R1M-A1[1]-[2][3] Specify a code from below for each of [1] through [3]. (e.g. R1M-A1T-M2/MSR/Q)
- Specify the specification for option code /Q (e.g. /C01) [1] FIELD TERMINAL TYPE T: M3 screw terminals C1: FCN type connector (No CE conformance) [2] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [3] OPTIONS (multiple selections) PC Recorder Software Package (must be specified) /MSR: With Other Options blank: none /Q: Option other than the above (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating
RELATED PRODUCTS
- Connector terminal block (model: CNT)
- Special cable (model: FCN32) PACKAGE INCLUDES...
- PC Recorder Software CD
- 9-pin D-sub connector, straight type (1 m or 3.3 ft) GENERAL SPECIFICATIONS Connection Power input, transmission: Euro type connector terminal (Applicable wire size: 0.2 – 2.5 mm2 (AWG24 – 12), stripped length 7 mm) RS-232-C: 9-pin D-sub connector (male) (Lock screw No. 4-40 UNC) Input: M3 screw terminals (torque: 0.6N·m) or FCN type connector (Fujitsu FCN-365P040-AU) Screw terminal: Nickel-plated steel Housing material: Flame-resistant resin (gray) Isolation: Input to RS-232-C or RS-485 to power Count memory at power loss: Count value is not saved when the power supply is lost. Node address setting: Rotary switch; 1 – F (15 nodes) RUN indicator LED: Green light blinks in normal conditions. COMMUNICATION Baud rate: 38.4 kbps Communication: Half-duplex, asynchronous, no procedure Protocol: Modbus RTU ■ RS-232-C Standard: Conforms to RS-232-C, EIA Transmission distance: 10 meters max. ■ RS-485 Standard: Conforms to TIA/EIA-485-A Transmission distance: 500 meters max. Transmission media: Shielded twisted-pair cable (CPEV-S 0.9 dia.)
MODEL: R1M-A1 R1M-A1 SPECIFICATIONS ES-5660 Rev.19 Page 2/6 https://www.m-system.co.jp/ INPUT SPECIFICATIONS Input: Dry contact, 32 points Commons: All negatives Sensing: Approx. 5 V DC (pull-up resistance 22 kΩ) ≤ 1.5 V at ON ≥ 4 V at OFF Sampling rate: 50 msec.
- Totalizing Counter Function Number of input channels: 16 (ch.1 thr. 16 available both with instantaneous status and totalized value) Max. input frequency: 100 Hz Minimum pulse width: 5 ms Counter reset input: Pulse rising (ch.32 assigned) Max. counter value: 999 999 999 (reset to zero at overflow) INSTALLATION Power consumption
- AC: Approx. 10 VA
- DC: Approx. 7 W Operating temperature: -5 to +60°C (23 to 140°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 400 g (0.88 lb) PERFORMANCE Multi-transmission time: 5 msec. Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @ 1 minute (input to RS-232- C or RS-485 to power to FG) STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Installation Category II Pollution Degree 2 Input or RS-232-C/RS-485 to power: Reinforced insulation (300 V) Input to RS-232-C/RS-485: Basic insulation (300 V) RoHS Directive
MODEL: R1M-A1 R1M-A1 SPECIFICATIONS ES-5660 Rev.19 Page 3/6 https://www.m-system.co.jp/ PC RECORDER SOFTWARE PC Recorder Software Package (model: MSRPAC-2010) is included with purchases of this model. Refer to the MSRPAC-2010 data sheet for the contents of the package and the requirements for the PC to be prepared by the user. EXTERNAL VIEW RS-485 Connector Power Terminals Node Address Setting Rotary SW Configurator Jack RUN Indicator LED RS-232-C 9-pin Connector ABBR. PIN NO. EXPLANATION OF FUNCTION BA (SD) 2 Transmitted Data BB (RD) 3 Received Data AB (SG) 5 Signal Common CB (CS) 7 Clear to Send CA (RS) 8 Request to Send 1 Not Used. 4 DO NOT connect. Connec ting may 6 cause malfunctions. 1 5 6 9 ■ RS-232-C INTERFACE MODBUS WIRING CONNECTION R1M R1M R1M CONNECTOR RS-232-C RS-485 *1 *1 *1. Internal terminating resistor is used when the device is at the end of a transmission line. *2. Install shielded cables to all sections and ground them at single point. *2FG RS-485
MODEL: R1M-A1 R1M-A1 SPECIFICATIONS ES-5660 Rev.19 Page 4/6 https://www.m-system.co.jp/ CONNECTION DIAGRAM Note: In order to improve EMC performance, bond the FG terminal to ground. Caution: FG terminal is NOT a protective conductor terminal. RS-232-C Term. Resist. Output Circuit When the device is located at the end of a transmission line via twisted-pair cable, (when there is no cross-wiring), close across the terminal T2 – T3 with the attached jumper pin (or with a leadwire). When the device is not at the end, remove the jumper pin. Power Circuit Shielded Twisted-pair Cable To Other PC Recorders Jumper *FG U (+) V (–) POWER D-SUB CONNECTOR ch.1 ch.2 ch.3 ch.4 ch.5 ch.6 ch.7 ch.8 COM (–) ch.9 ch.10 ch.11 ch.12 ch.13 ch.14 ch.15 ch.16 COM (–) ch.17 ch.18 ch.19 ch.20 ch.21 ch.22 ch.23 ch.24 COM (–) ch.25 ch.26 ch.27 ch.28 ch.29 ch.30 ch.31 Count Reset Input ch.32 COM (–) Input Circuit Input Circuit A10 A12 A11 A13 A15 A14 A16 B16 ch.1 ch.2 ch.3 ch.4 ch.5 ch.6 ch.7 ch.8 ch.9 ch.10 ch.11 ch.12 ch.13 ch.14 ch.15 ch.16 COM (–) A10 A12 A11 A13 A15 A14 A16 ch.17 CN1 ch.18 ch.19 ch.20 ch.21 ch.22 ch.23 ch.24 ch.25 ch.26 ch.27 ch.28 ch.29 ch.30 ch.31 Count Reset Input ch.32 ■ FCN TYPE CONNECTOR ■ M3 SCREW TERMINALS CN2 B16 COM (–)
MODEL: R1M-A1 R1M-A1 SPECIFICATIONS ES-5660 Rev.19 Page 5/6 https://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch] ■ M3 SCREW TERMINALS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35 T1 T2 T3 T4 T5 T6 T7 104 [4.09] 163 [6.42] 36–M3 INPUT TERMINALS 165 [6.50] 175 [6.89] 3–5 [.20] dia. MTG HOLES FOR WALL MOUNT. 6.2 [.24] 15.5 [.61] (6 [.24])40 [1.57] 3 [.12] 46 [1.81] DIN RAIL 35 mm wide ■ FCN TYPE CONNECTOR T1 T2 T3 T4 T5 T6 T7 104 [4.09] 163 [6.42] 165 [6.50] 175 [6.89] 3–5 [.20] dia. MTG HOLES FOR WALL MOUNT.FCN TYPE INPUT CONNECTOR (6 [.24])40 [1.57] 40 [1.57] Connector Pin Assignment A1 B1 A16 B16 CN1 CN2 See Caution below Caution: DO NOT APPLY EXCESSIVE FORCE onto the connector. The connector may be destroyed. 15.5 [.61] 3 [.12] 46 [1.81] DIN RAIL 35 mm wide
MODEL: R1M-A1 R1M-A1 SPECIFICATIONS ES-5660 Rev.19 Page 6/6 https://www.m-system.co.jp/ SYSTEM CONFIGURATION EXAMPLES RS-485 TC/DC Inputs (model: R1M-GH) Contact Inputs (model: R1M-A1) Contact Outputs (model: R1M-D1) When the cable distance between the PC and the R1Ms is long, insert an RS-232-C/RS-485 Converter for isolation. RS-232-C RS-232-C/RS-485 Converter (model: R2K-1) Specifications are subject to change without notice.