R1D-GH2 MSYSTEM | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 5
Technical content
MODEL: R1D-GH2 R1D-GH2 SPECIFICATIONS ES-5958 Rev.8 Page 1/5 http://www.m-system.co.jp/ Remote I/O R1X Series THERMOCOUPLE & DC INPUT MODULE (16 points; DeviceNet) Functions & Features
- 16-point thermocouple or DC inputs
- DeviceNet interface (1.57) 115 (4.53) mm (inch) 175 (6.89) MODEL: R1D-GH2T-[1][2]
ORDERING INFORMATION
- Code number: R1D-GH2T-[1][2] Specify a code from below for each [1] and [2]. (e.g. R1D-GH2T-M2/Q)
- Specify the specification for option code /Q (e.g. /C01)
- Use Ordering Information Sheet (No. ESU-5956). Default setting will be used if not otherwise specified. Factory default setting Input type: DC Voltage ±5 V Burnout protection: No burnout Cold junction compensation: No FIELD TERMINAL TYPE T: M3 screw terminals [1] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [2] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating
RELATED PRODUCTS
- Resistor module (model: REM3-250)
- R1X configurator software (model: R1CON)
- EDS file The EDS file and configurator software are downloadable at M-System’s web site. A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types. GENERAL SPECIFICATIONS Connection Power input, DeviceNet: Euro type connector terminal (applicable wire size: 0.2 to 2.5 mm2 (AWG24 to 12), stripped length 7 mm) Input: M3 screw terminals (torque 0.6 N·m) Configurator: 2.5 dia. miniature jack; RS-232-C level Screw terminal: Nickel-plated steel Housing material: Flame-resistant resin (gray) Isolation: Input to DeviceNet to power Power indicator: Green LED turns on with power supplied. DeviceNet COMMUNICATION Transmission cable: Approved for DeviceNet Node address setting: Rotary switch or software; 00 – 63 Baud rate setting: DIP switch or software MS (Module Status) indicator: Bi-color (green/red) LED indicates device status. NS (Network Status) indicator: Bi-color (green/red) LED indicates status of the communication link. Device Profile: Generic Device INPUT SPECIFICATIONS ■ Thermocouple or DC input, 16 points (Common negative for DC input)
- Measuring range ±20 V, ±5 V, ±1 V: Atten. SW ON (3)
- Measuring range ±0.8 V, ±0.2 V, ±50 mV, ±10m V: Atten. SW OFF (1) Input resistance: 300 kΩ Thermocouple types: PR, K, E, J, T, B, R, S, C, N, U, L, P Sampling rate: 150 millisec./16 points ■ A/D conversion output: 16-bit signed binary (negative range represented by 2’s complements)
MODEL: R1D-GH2 R1D-GH2 SPECIFICATIONS ES-5958 Rev.8 Page 2/5 http://www.m-system.co.jp/ Engineering unit value is converted into A/D conversion data as shown below. Input type & range: A/D data (decimal) ±20 V: ±20000 ±5 V: ±5000 ±1 V: ±10000 ±0.8 V: ±8000 ±0.2 V: ±20000 ±50 mV: ±5000 ±10 mV: ±10000 Thermocouples: Temperature × 10 In order to change input type and range after shipment, the R1X configurator software (model: R1CON) is required. 0 1 2 3 4 5 6 7 8 910 11 12 13 14 15 Ch. (1st) SIGN BIT INPUT 1 A/D CONVERSION DATA Ch. (1st+1) SIGN BIT INPUT 2 A/D CONVERSION DATA Ch. (1st+2) SIGN BIT INPUT 3 A/D CONVERSION DATA Ch. (1st+3) SIGN BIT INPUT 4 A/D CONVERSION DATA Ch. (1st+7) SIGN BIT INPUT 8 A/D CONVERSION DATA Ch. (1st+11) SIGN BIT INPUT 12 A/D CONVERSION DATA Ch. (1st+15) SIGN BIT INPUT 16 A/D CONVERSION DATA The R1D reserves 16 words at the Output Data Area (data sent from the R1D to the master) for the specified node address and sets the input data at this area. The Input Data Area (data sent to the R1D from the master) for the same node address is only reserved but unused. INSTALLATION Power consumption
- AC: Approx. 6 VA
- DC: Approx. 2 W Supply voltage to network: 11 – 25 V DC supplied through the network terminal block Supply current to network: 50 mA max. Operating temperature: -5 to +60°C (23 to 140°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 380 g (0.84 lb) PERFORMANCE (% of measuring range) Accuracy DC input: ±0.3 % Thermocouple input: See the table on the end of this section. Cold junction compensation error: ±3°C or ±5.4°F max. (at 20°C ±10°C or 68°F ±18°F) Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) ±0.05 %/°C (±0.03 %/°F) for 10 mV range and T/C B (RH) Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (input to DeviceNet to power to FG) Thermocouple Accuracy T/C USABLE RANGE (°C) ACCURACY (%) CONFORMANCE RANGE (°C) (PR) K (CA) E (CRC) -270 -270 to to to 1770 +1370 +1000 ±0.5 ±0.3 ±0.7 400 to to to 1770 1370 1000 J (IC) T (CC) B (RH) -210 -270 100 to to to +1200 +400 1820 ±0.7 ±1 .0 ±0.7 700 to to to 1200 400 1820 R S C ( WRe 5-26 ) -50 -50 to to to +1760 +1760 2320 ±0.7 ±0.7 ±0.7 400 400 to to to 1760 1760 2320 N U L P (Platinel II ) -270 -200 -200 to to to to +1300 +600 +900 1395 ±0.5 ±0.5 ±0.3 ±0.5 to to to to 1300 600 900 1395 T/C USABLE RANGE (°F) ACCURACY (%) CONFORMANCE RANGE (°F) (PR) K (CA) E (CRC) -454 -454 to to to 3218 +2498 +1832 ±0.5 ±0.3 ±0.7 752 to to to 3218 2498 1832 J (IC) T (CC) B (RH) -346 -454 212 to to to +2192 +752 3308 ±0.7 ±1 .0 ±0.7 1292 to to to 2192 752 3308 R S C ( WRe 5-26 ) -58 -58 to to to +3200 +3200 4208 ±0.7 ±0.7 ±0.7 752 752 to to to 3200 3200 4208 N U L P (Platinel II ) -454 -328 -328 to to to to +2372 +1112 +1652 1395 ±0.5 ±0.5 ±0.3 ±0.5 to to to to 2372 1112 1652 1395 Note: CJC error is not included.
MODEL: R1D-GH2 R1D-GH2 SPECIFICATIONS ES-5958 Rev.8 Page 3/5 http://www.m-system.co.jp/ EXTERNAL VIEW A H B C D GFE NAME FUNCTIONS A Power terminal block For power input B Network terminal block For wiring to DeviceNet C Baud rate setting 125, 250, 500 kbps (factory set to: 125 kpbs) D Node address setting Selectable within 00 – 63 (factory set to: 00) COLOR FUNCTIONS E NS (Network Status) Red ON: Critical communication error indicator LED blinking: Minor communication error Green ON: Communication established blinking: Communication down ---- OFF: Power Not supplied COLOR FUNCTIONS F MS (Module Status) Red ON: Critical failure indicator LED blinking: Minor failure Green ON: Normal conditions blinking: Device Not configured ---- OFF: Power Not supplied COLOR FUNCTIONS G Power LED Green ON: Power supplied ---- OFF: Power Not supplied H Configurator jack 2.5 dia. miniature jack; RS-232-C level
MODEL: R1D-GH2 R1D-GH2 SPECIFICATIONS ES-5958 Rev.8 Page 4/5 http://www.m-system.co.jp/ CONNECTION DIAGRAM CAN_L Drain CAN_H JACK Comm. Circuit Note 1: This device is not designed to cancel noise included in the input signals. Be careful to eliminate such noise by using shielded cables. Note 2: Be sure to maintain the same potential at all the common negative terminals for DC input. Caution: FG terminal is NOT a protective conductor terminal. T/C INPUT DC INPUT INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 INPUT 7 INPUT 8 INPUT 9 INPUT 10 INPUT 11 INPUT 12 INPUT 13 INPUT 14 INPUT 15 INPUT 16 CJC Sensor + ext. wire Power Circuit Input Circuit To Other DeviceNet Devices FG U (+) V (–) POWER CONFIGURATOR Unused Unused
MODEL: R1D-GH2 R1D-GH2 SPECIFICATIONS ES-5958 Rev.8 Page 5/5 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35 CAN_H Drain CAN_L V– T6 T7 T8 104 (4.09) 163 (6.42) 36–M3 INPUT TERMINALS 165 (6.50) 175 (6.89) FOR WALL MOUNT. [6 (.24)]40 (1.57) 6.2 (.24) 8 (.31) CJC SENSOR (model: CJM) 15.5 (.61) 3 (.12) 3–5 (.20) dia. MTG HOLES 46 (1.81) DIN RAIL 35 mm wide Specifications are subject to change without notice.