MODEL: R1C-GH R1C-GH SPECIFICATIONS ES-5956 Rev.12 Page 1/5 http://www.m-system.co.jp/ Remote I/O R1X Series THERMOCOUPLE & DC INPUT MODULE (16 points; CC-Link Ver.1.10/Ver.2.00) Functions & Features

  • 16-point thermocouple or DC inputs
  • CC-Link interface
  • CC-Link Version 1.10 and 2.00 can be switched at the startup (1.57) 115 (4.53) mm (inch) 175 (6.89) MODEL: R1C-GH2T-[1][2]

ORDERING INFORMATION

  • Code number: R1C-GH2T-[1][2] Specify a code from below for each [1] and [2]. (e.g. R1C-GH2T-M2/Q)
  • Specify the specification for option code /Q (e.g. /C01)
  • Use Ordering Information Sheet (No. ESU-5956). Default setting will be used if not otherwise specified. Factory default setting Input type: DC Voltage ±5 V Burnout protection: No burnout Cold junction compensation: No FIELD TERMINAL TYPE T: M3 screw terminals [1] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 47 – 66 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [2] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating

RELATED PRODUCTS

  • Resistor module (model: REM3-250)
  • R1X configurator software (model: R1CON) Downloadable at M-System’s web site. A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types. PACKAGE INCLUDES...
  • Terminating resistor (110 Ω, 0.5 W) GENERAL SPECIFICATIONS Connection Power input, CC-Link: Euro type connector terminal (applicable wire size: 0.2 to 2.5 mm2 (AWG24 to 12), stripped length 7 mm) Input: M3 screw terminals (torque 0.6 N·m) Configurator: 2.5 dia. miniature jack; RS-232-C level Screw terminal: Nickel-plated steel Housing material: Flame-resistant resin (gray) Isolation: Input to CC-Link (FG) to power PWR indicator: Green LED blinks in normal conditions. CC-Link COMMUNICATION Protocol: CC-Link V1.10 / V 2.00 Cable for comm. link: Specified by Mitsubishi Electric Required nodes V. 1.10: 4 V. 2.00: 1 (cyclic expansion: 4) Station No. setting: Rotary switch V. 1.10: Rotary switch; 1 – 61 V. 2.00: Rotary switch; 1 – 64 Baud rate setting: Rotary switch L RUN indicator: Red LED turns on in normal conditions. L ERR. indicator: Red LED turns on or blinks in an abnormality. SD indicator: Red LED turns on when transmitting. RD indicator: Red LED turns on when receiving. INPUT SPECIFICATIONS ■ Thermocouple or DC input, 16 points (Common negative for DC input)
  • Measuring range ±20 V, ±5 V, ±1 V: Atten. SW ON (3)

MODEL: R1C-GH R1C-GH SPECIFICATIONS ES-5956 Rev.12 Page 2/5 http://www.m-system.co.jp/

  • Measuring range ±0.8 V, ±0.2 V, ±50 mV, ±10m V: Atten. SW OFF (1) Input resistance: 300 kΩ Thermocouple types: PR, K, E, J, T, B, R, S, C, N, U, L, P Sampling rate: 150 millisec./16 points ■ A/D conversion output: 16-bit signed binary (negative range represented by 2’s complements) Engineering unit value is converted into A/D conversion data as shown below. Input type & range: A/D data (decimal) ±20 V: ±20000 ±5 V: ±5000 ±1 V: ±10000 ±0.8 V: ±8000 ±0.2 V: ±20000 ±50 mV: ±5000 ±10 mV: ±10000 Thermocouples: Temperature × 10 In order to change input type and range after shipment, the R1X configurator software (model: R1CON) is required. CC-Link version selector input: Ver. 1.10 with OFF at the startup. Ver. 2.00 with ON at the startup. Dry contact input (ON at detect. level ≤ 1.5 V) Sensing: approx. 5 V DC, 1 mA Valid only at the moment of the power supplied to the module. Firmware version 0B.00 or higher required. Confirm the firmware version using the R1X configurator software (model: R1CON) or consult M-System. ■ A/D CONVERSION DATA 0 1 2 3 4 5 6 7 8 910 11 12 13 14 15 RWr n+0 SIGN BIT INPUT 1 A/D CONVERSION DATA RWr n+1 SIGN BIT INPUT 2 A/D CONVERSION DATA RWr n+2 SIGN BIT INPUT 3 A/D CONVERSION DATA RWr n+3 SIGN BIT INPUT 4 A/D CONVERSION DATA RWr n+7 SIGN BIT INPUT 8 A/D CONVERSION DATA RWr n+11 SIGN BIT INPUT 12 A/D CONVERSION DATA RWr n+15 SIGN BIT INPUT 16 A/D CONVERSION DATA INSTALLATION Power consumption
  • AC: Approx. 10 VA
  • DC: Approx. 7 W Operating temperature: -5 to +60°C (23 to 140°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 400 g (0.88 lb) PERFORMANCE (% of measuring range) Accuracy DC input: ±0.3 % Thermocouple input: See the table on the end of this section. Cold junction compensation error: ±3°C or ±5.4°F max. (at 20°C ±10°C or 68°F ±18°F) Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) ±0.05 %/°C (±0.03 %/°F) for 10 mV range and T/C B (RH) Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @ 1 minute (input to CC-Link [FG] to power to ground [FG1]) Thermocouple Accuracy T/C USABLE RANGE (°C) ACCURACY (%) CONFORMANCE RANGE (°C) (PR) K (CA) E (CRC) -270 -270 to to to 1770 +1370 +1000 ±0.5 ±0.3 ±0.7 400 to to to 1770 1370 1000 J (IC) T (CC) B (RH) -210 -270 100 to to to +1200 +400 1820 ±0.7 ±1 .0 ±0.7 700 to to to 1200 400 1820 R S C ( WRe 5-26 ) -50 -50 to to to +1760 +1760 2320 ±0.7 ±0.7 ±0.7 400 400 to to to 1760 1760 2320 N U L P (Platinel II ) -270 -200 -200 to to to to +1300 +600 +900 1395 ±0.5 ±0.5 ±0.3 ±0.5 to to to to 1300 600 900 1395 T/C USABLE RANGE (°F) ACCURACY (%) CONFORMANCE RANGE (°F) (PR) K (CA) E (CRC) -454 -454 to to to 3218 +2498 +1832 ±0.5 ±0.3 ±0.7 752 to to to 3218 2498 1832 J (IC) T (CC) B (RH) -346 -454 212 to to to +2192 +752 3308 ±0.7 ±1 .0 ±0.7 1292 to to to 2192 752 3308 R S C ( WRe 5-26 ) -58 -58 to to to +3200 +3200 4208 ±0.7 ±0.7 ±0.7 752 752 to to to 3200 3200 4208 N U L P (Platinel II ) -454 -328 -328 to to to to +2372 +1112 +1652 1395 ±0.5 ±0.5 ±0.3 ±0.5 to to to to 2372 1112 1652 1395 Note: CJC error is not included.

MODEL: R1C-GH R1C-GH SPECIFICATIONS ES-5956 Rev.12 Page 3/5 http://www.m-system.co.jp/ EXTERNAL VIEW T6 T7 T8 DB DA DG FG SLD A F G B C D E NAME FUNCTIONS A Power terminal block For power input B Network terminal block For wiring to CC-Link SETTING BAUD RATE C Baud rate setting 0 156 kbps (factory default) 1 625 kbps 2 2.5 Mbps 3 5 Mbps 4 10 Mbps Other than 0 – 4 Not valid; L ERR. turns on as a transmission error. D Station No. setting V. 1.10: Selectable within 1 – 61. (factory set to: 00) V. 2.00: Selectable within 1 – 64. (factory set to: 00) ID (color) FUNCTIONS E Status indicator LED L RUN (red) ON: Normal communication Transmission data error blinking: blinking: ON: Transmission data error OFF: Communication down (time-out error) L ERR. (red) Transmission data error OFF: Normal transmission SD (red) ON when transmitting RD (red) ON when receiving ID (color) FUNCTIONS F Power LED PWR (green) ON: Abnormality blinking, high speed: CC-Link Ver. 1.10 blinking, low speed: CC-Link Ver. 2.00 Master Version 2.00 with long ON time Master Version 1.10 with long OFF time G Con/f_igurator jack 2.5 dia. miniature jack; RS-232-C level

MODEL: R1C-GH R1C-GH SPECIFICATIONS ES-5956 Rev.12 Page 4/5 http://www.m-system.co.jp/ CONNECTION DIAGRAM SLD FG DG DB DA JACK Comm. Circuit Note 1: This device is not designed to cancel noise included in the input signals. Be careful to eliminate such noise by using shielded cables. Note 2: Be sure to maintain the same potential at all the common negative terminals for DC input. Note 3: CC-Link version selector input is valid only at the moment of the power turned on. Firmware version 0B.00 or higher. Use the R1X Configurator Software (model: R1CON) or consult M-System to confirm the firmware version. Caution: FG1 terminal is NOT a protective conductor terminal. T/C INPUT DC INPUT INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5 INPUT 6 INPUT 7 INPUT 8 INPUT 9 INPUT 10 INPUT 11 INPUT 12 INPUT 13 INPUT 14 INPUT 15 INPUT 16 CJC Sensor + ext. wire Power Circuit Input Circuit To Other CC-Link Devices FG1 U (+) V (–) POWER CONFIGURATOR CC-Link VERSION SELECTOR INPUT

MODEL: R1C-GH R1C-GH SPECIFICATIONS ES-5956 Rev.12 Page 5/5 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35 104 (4.09) 163 (6.42) 36–M3 INPUT TERMINALS 165 (6.50) 175 (6.89) 3–5 (.20) dia. MTG HOLES FOR WALL MOUNT. 6.2 (.24) 8 (.31) CJC SENSOR (model: CJM) 15.5 (.61) 3 (.12) 46 (1.81) DIN RAIL 35 mm wide Specifications are subject to change without notice.