LCD-7100 GAMEWELL-FCI | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
Features
- Listed per ANSI/UL 864 9th Edition
- 120 or 240 VAC (optional) input line voltage
- Front panel programming with day/night sensitivity adjustments
- 80-character alpha-numeric display
- One or two Style 4 (Class “B”) signaling line circuits. Style 6 (Class “A”) with optional CAOM Module
- Two Style Y (Class “B”) regulated notification appliance circuits rated for 1.5 amp. each. Style Z (Class “A”) with optional CAOM Module
- Suitable for pre-action deluge applications with optional MCOM Module
- Periodic trouble reminder
- Individual sensor drift compensation
- Dual-stage maintenance alerts (“dirty” and “very dirty”)
- Multilevel sensor sensitivity adjustments (front panel programmable) continued on the next page
7100 Series
S1869 3003549 7165-0694:219 (7100) 7300-0694:231 (LCD-7100) 7300-0694:241 (LDM-7100) 307-99-E 307-99-E Vol. II FM MEA Approved An ISO 9000-2000 Company
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0466 Rev. E2 page 2 of 3 www.gamewell-fci.com Description (Continued) Remote Station, Proprietary, and Central Station fire alarm systems. It allows ample space for wiring and room for bat- teries up to 7 A/H capacity. Features (Continued)
- Alarm verification per individual sensor
- Positive alarm sequence for sensors or monitor modules
- Four levels of system access using six (6), digit pass- words with up to five (5), user passwords per Level
- Duplicate and extra address indications
- March time (60 or 120 BPM)/temporal pattern/coded fours/California Code/user-defined zone coding
- Cross zoning
- System configuration programming and 280 event log stored in non-volatile memory
- Fan restart with sequential restart delay
- Upload/download of panel configuration between panel and FCP-7100 program (password protected feature)
- Up to sixty-four (64), 7100 panels in the E3 Broadband network with an optional INI-7100 Module Optional Accessories LCD-7100 The LCD-7100 remote serial display offers an 80-character alphanumeric readout for the remote display of all system events. It duplicates all the information on the 7100 Series panel display and provides key switch protected functions such as System Reset, Alarm Acknowledge, Trouble Acknowledge, Signal Silence, and Drill Test. LEDs on the LCD-7100 indicate Alarm, Supervisory, Sys- tem Trouble, Power Fault, Systems Silenced, NAC#1, and NAC#2 Silenced conditions. The LCD-7100 can be surface or semi-flush mounted on a standard four-gang electrical box. It can be installed up to 4,000 feet (1,219 m) from the main control panel. The 7100 Series fire alarm control panel supports up to five (5), remote LCD-7100 annunciators using one pair of twisted, non-shielded 18 AWG min. wire or serial communication and uses another pair of 16 AWG min. for operating volt- age. (For additional information, refer to the LCD-7100 data sheet, Part Number: 9020-0486). LDM-7100 The LED Driver Module (LDM-7100) is designed to mount in a UL Listed remote annunciator and provides outputs for remote panel switches and thirty-three (33), remote LEDs. Three (3), LDM-7100 modules may be installed in a single annunciator for a total of ninety-nine (99), LEDs per annun- ciator. This combination may be repeated up to five times for a total of fifteen (15), LDM-7100 panels installed at up to five (5), different locations. Maximum distances of up to 4,000 feet (1,219 m) can be achieved using one pair of twisted, non-shielded wire for serial communication and using another pair of straight-lay wire for operating voltage. (For additional information, refer to the LDM-7100 data sheet, Part Number: 9020-0519). CAOM The Class “A” Optional Module (CAOM) allows Style Y and Z (Class “B” and “A”) operation for both Notification Appli- ance Circuits and allows Style 4 and 6 (Class “B” and “A”) for both Signaling Line Circuits. It also provides disconnect switches for each signaling line circuit and a common dis- connect switch for both notification appliance circuits. MCOM The Municipal Connection Option Module (MCOM) pro- vides three (3) choices of outputs. It can be configured as a Municipal Circuit (City Box) output. It may also be set to serve as a Reverse Polarity output with a nominal voltage output of 24 VDC at 0.012 amp. maximum alarm and supervisory current. The MCOM’s third option provides a releasing solenoid output rated at:
- 24 VDC nominal voltage.
- 0.005 amp. supervisory current.
- 0.710 amp. maximum alarm current.
- 2 ohms maximum line resistance. PTRM The Printer Transient Module (PTRM) provides RS-232 Isolator/Transient protecti on for the 7100’s RS-232 port (BSM connector J2). It is used in conjunction with a serial printer applied to the RS-232 port for permanent record keeping. INI-7100 The Intelligent Network Interface Module allows the 7100 Series fire alarm control panel to become the platform of a peer-to-peer, token ring, self-regenerative network com- prised of up to sixty-four (64), 7100 panels.
www.gamewell-fci.com 9020-0466 Rev. E2 page 3 of 3 Specifications Primary Input Power 120 VAC, 50/60 Hz @ 2.0 amps. or 240 VAC, 50/60 Hz @ 1.0 amp. Output Power 4 amps. @ 24 VDC (total) Non-resettable Power: 1.0 amp. max. 1.0 amp. max. from both circuits Resettable Power: 1.0 amp. max. Two (2) Notification Appliance Circuits: 1.5 amp. each @ 24 VDC Current: Supervisory Alarm 7100-1 (One SLC) 0.065 amp. 0.085 amp. 7100-1D (One SLC w/DACT) 0.085 amp. 0.105 amp. 7100-2 (Two SLC) 0.065 amp. 0.085 amp. 7100-2D (Two SLC w/DACT) 0.085 amp. 0.105 amp. LCD-7100 .012 amp. .023 amp. LDM-7100 .012 amp. .023 amp. (All LEDs lit) INI-7100-UTP,-FO 0.040 amp. 0.040 amp. Operating Temperature: 32° - 120° F (0° - 49° C) Relative Humidity: 85 % (non-condensing) Battery Charger Capacity: 31 A/H (Cabinet accommodates
12 A/H size batteries)
Alarm & Trouble Relay Contacts: Form “C”, 2 amps. @ 24 VDC (resistive)
Ordering Information
7100-1 7100 Addressable System, 1 SLC mounted in enclosure Dimensions: 19 3/8” x 19 3/8” (49 x 49 cm) Enclosure 7100-1D 7100 Addressable FACP w/DACT,
1 SLC mounted in enclosure
Dimensions: 19 3/8” x 19 3/8” (49 x 49 cm) Enclosure Basic Kits BK-7100-2 Basic System Kit, 2 SLC (BSM, Keypad Display, Transformer) BK-7100-2D Basic System Kit w/DACT, 2 SLC BK-7100-2-240V Basic System Kit, 2 SLC, 240 VAC BK-7100-2D-240V Basic System Kit w/DACT, 2 SLC Cabinets EN-7100 Enclosure (replacement) CS-7100M Metal Door (replacement) 7100-ENCL-M 7100 Enclosure Dimensions: 16.9” H x 14.4” W x 3” D l (43 H x 37 W x 7.7 D cm) NS-7100B NS-7100R Enclosure, E3 Series Broadband, black Enclosure, E3 Series Broadband, red Dimensions: 19 3/8” H x 19 3/8” W x 4” D (49 H x 49 W x 10 D cm) Ordering Information (Continued) Optional Modules LCD-7100 Remote Serial Annunciator, LCD Display (80-character) Dimensions: 4.25” H x 8.25” W x 1.90” (43 H x 37 W x 7.7 D cm) LDM-7100 Remote LED Driver Module Dimensions: 6” W x 4.50” (15.2 x 11.4 cm) CAOM Class A Option Combination Module with disconnect switches for both signaling line circuits and notification appliance circuits MCOM Municipal Connection Option Module for local energy city box reverse polar- ity signaling, or releasing solenoid PTRM Printer Transient Module INI-7100-FO Intelligent Network Interface Module, Fiber-Optic INI-7100-UTP Intelligent Network Interface Module, Unshielded, Twisted-Pair Replacement Parts T-7100 Transformer, 120 VAC input (replace- ment) T-7100-240 Transformer, 240 VAC input (replace- ment) BSM-7100-1 Replacement board for 7100-1 BSM-7100-1D Replacement board for 7100-1D