TBEN-S1-8DXP TURCK | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 8
Technical content
Compact Multiprotocol I/O Module for Ethernet
8 Universal Digital Channels, Configurable as PNP Inputs or 2 A Outputs
Edition • 2023-02-23T12:00:09+01:00 Type TBEN-S1-8DXP ID 6814023 Supply Supply voltage 24 VDC Admissible range 18…30 VDC Total current max. 4 A per voltage group Total current V1 + V2 max. 5.5 A at 70 °C per mod- ule Voltage supply connection 2 × M8, 4-pin Operating current V1: max. 150 mA Sensor/actuator supply Supply ports C0-C3 from V1 short-circuit proof, 0.5 A for group C0-C3 Sensor/actuator supply Supply ports C4-C7 from V2 short-circuit proof, 0.5 A for group C4-C7 Electrical isolation galvanic isolation of the voltage groups V1 and V2, voltages up to 500 VAC System data Fieldbus transmission rate 10/100 Mbps Fieldbus connection technology 2 × M8, 4-pin Protocol detection automatic Web server default: 192.168.1.254 Service interface Ethernet via P1 or P2 BEEP functionality Supported Field Logic Controller (FLC) ARGEE Firmware Version 3.1.4.0 ARGEE Engineering Version 2.0.24.0 Modbus TCP Addressing Static IP, DHCP Supported function codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23 Number of TCP connections 8 Input register start address 0 (0x0000 hex) Output register start address 2048 (0x0800 hex) Ethernet/IP Addressing acc. to EtherNet/IP specification Quick Connect (QC) < 500 ms Device Level Ring (DLR) supported Class 3 connections (TCP) 3 Class 1 connections (CIP) 10 Input Assembly Instance 103 Output Assembly Instance 104 Configuration Assembly Instance 106 ■ PROFINET device, EtherNet/IP device or Modbus TCP slave ■ Integrated Ethernet switch ■ Supports 10 Mbps / 100 Mbps ■ 2x M8, 4-pin, Ethernet fieldbus connec- tion ■ Glass fiber reinforced housing ■ Shock and vibration tested ■ Fully potted module electronics ■ Protection classes IP65, IP67, IP69K ■ 4-pin M8 male connector for power sup- ply ■ Galvanically isolated voltage groups ■ ATEX Zone 2/22 ■ Input diagnostics per group ■ Max. 2 A per output ■ Output diagnostics per channel ■ One freely selectable digital channel per port ■ Programmable ARGEE
Compact Multiprotocol I/O Module for Ethernet Edition • 2023-02-23T12:00:09+01:00 PROFINET Version 2.35 Addressing DCP Conformance class B (RT) MinCycleTime 1 ms Fast Start-Up (FSU) < 500 ms Diagnostics acc. to PROFINET alarm handling Topology detection supported Automatic addressing supported Media Redundancy Protocol (MRP) supported System redundancy S2 Netload class 3 Digital inputs Number of channels 8 Connectivity inputs M8, 3-pin Input type PNP Type of input diagnostics Group diagnostics Switching threshold EN 61131-2 Typ 3, PNP Low level signal voltage < 5 V High level signal voltage > 11 V Low level signal current < 1.5 mA High level signal current > 2 mA Input delay 0.2 ms / 3 ms Electrical isolation Galvanically isolated to the fieldbus Voltage proof up 500 VDC Digital outputs Number of channels 8 Connectivity outputs M8, 3-pin Output type PNP Type of output diagnostics Channel diagnostics Output voltage 24 VDC from potential group Output current per channel 2 A, short-circuit proof Load type EN 60947-5-1: DC-13 Short-circuit protection yes Electrical isolation Galvanically isolated to the fieldbus Voltage proof up 500 VDC Standard/Directive conformity Vibration test Acc. to EN 60068-2-6 Acceleration up to 20 g Shock test acc. to EN 60068-2-27 Drop and topple acc. to EN 60068-2-31/IEC 60068-2-32 Electromagnetic compatibility Acc. to EN 61131-2 Approvals and certificates CE, FCC, UV-resistant in accordance with DIN EN ISO 4892-2A (2013) UL Certificate cULus LISTED 21 W2, Encl.Type 1 IND.CONT.EQ. Note on ATEX/IECEx The Quick Start Guide with information on use in Ex Zones 2 and 22 must be observed. General Information Dimensions (W x L x H) 32 x 144 x 32 mm Ambient temperature -40…+70 °C Storage temperature -40…+85 °C Altitude Max. 5000 m Protection class IP65 IP67 IP69K MTTF 248 years acc. to SN 29500 (Ed. 99) 20 °C Housing material PA6-GF30 Housing color Black Male connector material Nickel-plated brass Material label Polycarbonate Halogen-free yes Mounting 2 mounting holes 4.6 mm
Compact Multiprotocol I/O Module for Ethernet Edition • 2023-02-23T12:00:09+01:00 Note the numbering of the IO range: From firmware version 3.1.4.0 and higher slots C0 to C7 and channels CH0 to CH7 are counted. For more details on the corresponding change see man- ual.
Compact Multiprotocol I/O Module for Ethernet Edition • 2023-02-23T12:00:09+01:00 Accessories It is strongly recommended to use only ready-made Ethernet ca- bles! Ethernet cable (example): M8-M8: PSGS4M-PSGS4M-4413-1M Ident. no. U-55718 M8-RJ45: PSGS4M-RJ45S-4413-1M Ident. no.: U-55725 M8-M12: RSSD-PSGS4M-4413-1M Ident. no.: U-58840 M8 x 1 Ethernet Accessories Actuator and sensor cable/PUR cable (example): M8 - open end ID No. 6625562 PSG3M-2/TXL M8-M8 ID No. 6625665 PKG3M-0,3-PSG3M/TXL ID No. 6627137 PKG3M-3-PSG3M/TXL M8 x 1 I/O Port Accessories Power supply cable (example): M8-M8 2 M (2.0 Amp) PKG 4M-2-PSG 4M Ident. No. U99-10815 M8-M8 2 M (4.0 Amp) PKGC 4M-2-PSGC 4M Ident. No. U-82319 M8 x 1 Voltage Supply
Compact Multiprotocol I/O Module for Ethernet Edition • 2023-02-23T12:00:09+01:00 Module Status LED LED Color Status Description ETH1 / ETH2 Green ON Ethernet link (100 Mbps) flashing Ethernet communication (100 Mbps) Yellow ON Ethernet link (10 Mbps) flashing Ethernet communication (10 Mbps) OFF No Ethernet link BUS Green ON Active connection to a master Flashing Steady flashing: Ready Sequence of 3 flashes in 2 seconds: FLC/ARGEE active Red ON IP address conflict or Restore Mode or Modbus timeout Flashing Blink/Wink command active Red/ Green Alternating Waiting for assignment of an IP address, DHCP or BootP OFF Power off Green On No diagnostics available Red On Diagnostics available Undervoltage diagnosis response is parameter dependent LED response master in the Beep network: Green 1 Hz, 250 ms off Cyclical IO data exchange Green/red 1 Hz, 250 ms red Cyclical IO data exchange, diagnostics available Green/red 1 Hz, alternating Discovery mode active ERR Red Discovery mode active, diagnostics available PWR Green On V1 and V2 power supply OK Red On V2 power supply off or V2 undervoltage Off V1 power supply off or V1 undervoltage LED Status I/O LED Color Status Description LED 0 … 7 Green ON Input or output active ON Output active with overload/short circuitRed Flashing Overload of the port supply. All LEDs of the affected group C0-C3 or C4-C7 are flashing. OFF Input or output inactive LED 7 White Flashing Blink/Wink command active
Compact Multiprotocol I/O Module for Ethernet Edition • 2023-02-23T12:00:09+01:00 Process Data Mapping of the Single Protocols For more details on the corresponding protocols see manual. Modbus TCP Register Addressing (16-bit) Offset Process Input Data: 0x0000, structure acc. to general register mapping Offset Process Output Data: 0x0800: Structure acc. to general register mapping Ethernet/IP Word Addressing (16-bit) Process Input Data (Station -> Scanner) Status Word is located in front of the general process data! Reg/ Word Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit3 Bit 2 Bit 1 Bit 0 GW status 0x0000 - FCE - - CFG COM V1 - V2 - - - - - - Diag Warn 0x0001 Structure acc. to general register mapping Process Output Data (Scanner -> Station) Control-Word is located in front of the general process data! Reg/ Word Bit Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit3 Bit 2 Bit 1 Bit 0 Control 0x0000 Reserved 0x0001 Structure acc. to general register mapping PROFINET: Byte addressing (8-bit) Offset Process Input Data: 0x0000, structure acc. to general register mapping Offset Process Output Data: 0x0000: Structure acc. to general register mapping General Register Mapping Address details are relative. Observe offset of respective protocol Channel Assignment/Port/Pin: - - - - - - - - Ch7 Ch6 Ch5 Ch4 Ch3 CH2 CH1 CH0Channel - - - - - - - - DX7 DX6 DX5 DX4 DX3 DX2 DX1 DX0 Port Pin - - - - - - - - C7 Process Input Data: Reg/ Word Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit3 Bit 2 Bit 1 Bit 0 Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit3 Bit 2 Bit 1 Bit 0 MSB LSB Digital Inputs 8DIP 0x0000 0x0000 - - - - - - - - DX7 DX6 DX5 DX4 DX3 DX2 DX1 DX0 Diagnostics 0x0001 0x0002 ERR7 ERR6 ERR5 ERR4 ERR3 ERR2 ERR1 ERR0 - - - - - - VERR CH47 VERR CH03 Latch input 0x0002 0x0004 - - - - - - - - DX7 DX6 DX5 DX4 DX3 DX2 DX1 DX0 Counter Ch0 0x0003 0x0006 Counter value LSB 0x0004 0x0008 Counter value MSB Frequency Ch0 0x0005 0x000A Frequency MSB Frequency LSB Status 0x0006 0x000C - - - - - - - - Status PWM Diagnos- tics Ch3 OUT ERR PWM Diagnos- tics Ch7 OUT ERR Module Status 0x0009 0x0012 - FCE - - - COM V1 - V2 - - - - - - DIAG Process Output Data: Reg/ Word Bit Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit3 Bit 2 Bit 1 Bit 0 Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit3 Bit 2 Bit 1 Bit 0 MSB LSB
Compact Multiprotocol I/O Module for Ethernet Edition • 2023-02-23T12:00:09+01:00 Digital Outputs 8DXP 0x0000 0x0000 - - - - - - - - DX7 DX6 DX5 DX4 DX3 DX2 DX1 DX0 Latch Reset 0x0001 0x0002 - - - - - - - - DX7 DX6 DX5 DX4 DX3 DX2 DX1 DX0 RST PWM Ch3 0x0003 0x0006 - - - - - - - - Duty cycle PWM Ch7 0x0004 0x0008 - - - - - - - - Duty cycle Legend: V1 Undervoltage V1 CFG I/O configuration error V2 Undervoltage V2 FCE I/O-ASSISTANT Force Mode active Cx Port x Px Pin x DIx Digital input channel x DOx Digital output channel x Diag Module diagnostics available ERR x Overcurrent output channel x VERRVxCHyz Overcurrent supply VAUXx channel y to z PWMOUTERR Overcurrent PWM output VERRVxPyCz Overcurrent supply VAUXx, pin y, port z VAUXxPyCz Supply VAUXx, pin y, port z CNT_RST Counter reset
Compact Multiprotocol I/O Module for Ethernet Edition • 2023-02-23T12:00:09+01:00 Accessories Type code Ident-No. Dimension drawing TBNN-S0-DRS-01 6814040 Adapter for Setting Up TBEN-S Module Groups on a DIN Rail TBNN-S0-STD-01 6814043 Adapter for Setting Up TBEN-S Module Groups on a Mount- ing Plate TB-SG-S 100014866 Protective housing for TBEN-S block I/O modules for use in ATEX Zone 2/22