www.gminternational.com PSD5201 I.S. SIL3 Power Supply for Hazardous Area Equipment Intrinsically Safe Isolators > Power Supply
ORDERING INFORMATION
Bus Connector JDFT050, Bus Mounting Kit OPT5096. TECHNICAL DATA SIL 3 / SC 3 Output to Zone 0 Installation in Zone 2 High output capability Power Supply for Hazardous Area equipment Output short circuit proof Two port isolation, Supply/Output The PSD5201 is a single channel Power Supply able to drive measuring, process control equipment in Hazardous Area, providing isolation between supply and output. Typical applications are intrinsically safe high-power devices, transmitters or other equipment.
FEATURES
24 Vdc nom (21.5 to 30 Vdc), reverse polarity protected. Current consumption: 200 mA @ 24 Vdc with 150 mA nominal load, 210 mA @ 24 Vdc with short circuited output, typical. Power dissipation: 2.5 W @ 24 Vdc with 150 mA nominal load, typical. Output 150 mA @ 14.5 V (20 V no load, 36.4 Ω series resistance). Short circuit current: ≥ 155 mA. Isolation I.S. Out/Supply 1.5 kV. Environmental conditions Operating temperature: temperature limits –40 to +70 °C. Storage temperature: temperature limits –45 to +80 °C. Safety description Associated apparatus and non-sparking electrical equipment. Uo = 21.5 V, Io = 604 mA, Po = 3243 mW at terminals 13-14, 15-16. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C. Mounting DIN-Rail 35 mm, with or without Power Bus. Weight: about 145 g. Connection: by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm² (13 AWG). Dimensions: Width 22.5 mm, Depth 123 mm, Height 120 mm. OVERALL DIMENSIONS Functional Safety Management Certification: GM International is certified to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. In addition, GM International products have been granted I.S. certificates from the most credited Notified Bodies in the world. Data specified in this document are merely descriptive of the products and should be integrated with relevant technical specifications. Our products are in constant development and the information presented herein refers to the time of document issue. No statements concerning a certain condition or suitability for a certain application can be derived from our information. The information given does not release the user from the obligation of own judgment and verification. Terms & Conditions can be found at our website. For more information refer to istruction manual.
Additional installation diagrams may be found in Instruction Manual. Hazardous Area Safe Area/Zone 2 Functional Safety Management Certification: GM International is certified to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. In addition, GM International products have been granted I.S. certificates from the most credited Notified Bodies in the world. Data specified in this document are merely descriptive of the products and should be integrated with relevant technical specifications. Our products are in constant development and the information presented herein refers to the time of document issue. No statements concerning a certain condition or suitability for a certain application can be derived from our information. The information given does not release the user from the obligation of own judgment and verification. Terms & Conditions can be found at our website. For more information refer to istruction manual.