PSC EATON | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 6

Technical content

V7-T6-10 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—April 2019 www.eaton.com

6.1 Power Supplies

General-Purpose and Sensor Power Supplies PSC Series Contents Description Page PSC Series PSC Series Product Description The PSC Compact series operates with universal AC input range and offers full power up to 55 °C. The output is adjustable from 24 to 28 volts and can support up to 3000 microfarads of load capacitance. All models in the series are certified according to IEC/EN/UL 60950-1 Information Technology Equipment (ITE) and UL 508 Industrial Control Equipment (ICE). The series is also fully compliant with RoHS Directive 2011/65/EU for environmental protection. NEC Class 2 and Limited Power Source (LPS) approvals are available for this product. Application Description The ultra-compact and competitively priced Eaton Compact DIN Rail Power Supply series is designed for industrial applications requiring highly reliable power supply within a tight space. Simple to operate with HMI displays and industrial ethernet. Features, Benefits and Functions

  • 30 W, 50 W and 100 W ratings
  • Ultra-compact size
  • Universal AC input voltage 100–240 Vac (120–375 Vdc)
  • Up to 87% efficiency at

230 Vac

  • Extreme low temperature cold start at –40 °C
  • Overvoltage / overcurrent / over-temperature protections
  • Under 100 W power output at 24 Vdc
  • Wide operating temperature range: –20 °C to +70 °C
  • Storage temperature: –20 °C to +85 °C
  • MTBF greater than 350,000 hours ensures uptime and reliability
  • Protection from overvoltage, short circuit, overcurrent and over temperature conditions
  • Plastic housings provide the durability required to withstand harsh environments
  • Finger-safe terminals
  • LED indicating light for DC OK simplifies troubleshooting
  • Redundancy modules keep loads up and running in the event of a device failure
  • NEC Class 2 rated model 1
  • 150% power surge output
  • IP20 protection degree
  • Earth connection is required
  • A green LED indicates output is present Standards and Certifications
  • UL 508
  • NEC Class 2
  • CE marked
  • RoHS compliant Note 1 The NEC Class 2 model is certified as an NEC Class 2 power source. This means that after a small startup window, the power supply cannot exceed a maximum of 100 W under any circumstances, including overload, short-circuit or internal failure.

Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—April 2019 www.eaton.com V7-T6-11 6.1Power Supplies General-Purpose and Sensor Power Supplies Catalog Number Selection Note: Catalog number selection breakdown shown below is for illustrative purposes only and not to be used to create new catalog number configurations. PSC Series Product Selection PSC Series Power Description Catalog Number

24 Vdc output single-phase power supplies

(100–240 Vac nominal input) 30 W, 1.25 A output, plastic housing PSC30E24RP 50 W, 2.1 A output, plastic housing PSC50E24RP 100 W, 4.0 A output, plastic housing PSC100E24RP PSC 10 E 24 R P Series PSC = Compact Power Supply Output Power 30 = 30 W 50 = 50 W 100 = 100 W Model E = Single-phase Output Voltage 24 = 24 Vdc Terminals R = Finger-safe Housing P = Plastic PSC100E24RP

V7-T6-12 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—April 2019 www.eaton.com General-Purpose and Sensor Power Supplies Technical Data and Specifications PSC Series PSC30E24RP PSC50E24RP PSC100E24RP Input Nominal voltage 100–240 Vac / 50–60 Hz 100–240 Vac / 50–60 Hz 100–240 Vac / 50–60 Hz AC input range 85–264 Vac 85–264 Vac 85–264 Vac DC input range 120–375 Vdc 120–375 Vdc 120–375 Vdc Input frequency range 47–63 Hz 47–63 Hz 47–63 Hz Inrush current limitation <35 A at 115 Vac, <60 A at 230 Vac <35 A at 115 Vac, <60 A at 230 Vac <35 A at 115 Vac, <60 A at 230 Vac Internal fuse T 3.15 A / 250 V T 3.15 A / 250 V T 3.15 A / 250 V Leakage current <1 mA at 240 Vac <1 mA at 240 Vac <1 mA at 240 Vac Output Power 30 W 50 W 91.2 / 96 W Nominal output voltage 24 Vdc ±2% 24 Vdc ±2% 24 Vdc ±2% Adjustment range 24–28 Vdc (Maximum power ≤ 30 W) 24–28 Vdc (Maximum power ≤ 50 W) 22–24 Vdc (Maximum power ≤ 91.2W) Nominal current 1.25 A 2.1 A 3.8 A Derating –10 °C to –20 °C (2% / °C), >55 °C (3.33% / °C) in Vertical in Vertical in Vertical Power derating–horizontal mounting N/A N/A N/A Startup with capacitive loads Max. 3,000 μF Max. 3,000 μF Max. 3,000 μF Max. power dissipation idling / nominal load approx. 0.5 W / 4.5 W 0.5 W / 7 W 0.4 W / 10 W Residual ripple/peak switching (20 M Hz) <75 mVpp <75 mVpp <75 mVpp Parallel operation PSG480R24RM / PSG960R24RM / With o-ring Diode PSG480R24RM / PSG960R24RM / With o-ring Diode PSG480R24RM / PSG960R24RM / With o-ring Diode Galvanic isolation Input/output 3.0K Vac 3.0K Vac 3.0K Vac Input/ground 3.0K Vac 3.0K Vac 3.0K Vac Output/ground 0.5K Vac 0.5K Vac 0.5K Vac General / physical data Housing material Plastic (PC), enclosed Plastic (PC), enclosed Plastic (PC), enclosed Signals Green LED DC OK Green LED DC OK Green LED DC OK MTBF >350,000 hr >350,000 hr >350,000 hr Dimensions (length) 75 mm 75 mm 75 mm Dimensions (width) 21 mm 30 mm 45 mm Dimensions (height) 89.5 mm 89.5 mm 100 mm Weight (kg) 0.11 kg 0.18 kg 0.325 kg Terminals Finger safe Finger safe Finger safe Wire size AWG 22-12 / AWG 20-12 AWG 22-12 / AWG 20-12 AWG 22-12 / AWG 20-12 Operating temperature –20 °C to +70 °C –20 °C to +70 °C –20 °C to +70 °C Storage temperature –40 °C to +85 °C –40 °C to +85 °C –40 °C to +85 °C Operating humidity 5 to 95% RH 5 to 95% RH 5 to 95% RH

Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—April 2019 www.eaton.com V7-T6-13 6.1Power Supplies General-Purpose and Sensor Power Supplies PSC Series, continued PSC30E24RP PSC50E24RP PSC100E24RP General / physical data, continued Vibration Operating IEC60068–2–6, sine wave: 10 Hz to 500 Hz at 19.6 m/s²; displacement of 0.35 mm, 60 min. per axis for all X, Y , Z directions IEC60068–2–6, sine wave: 10 Hz to 500 Hz at 19.6 m/s²; displacement of 0.35 mm, 60 min. per axis for all X, Y , Z directions IEC60068–2–6, sine wave: 10 Hz to 500 Hz at 19.6 m/s²; displacement of 0.35 mm, 60 min. per axis for all X, Y , Z directions Non-operating IEC60068–2–6, Random: 5 Hz to 500 Hz (2.09 Grms); 20 min. per axis for all X, Y , Z directions IEC60068–2–6, Random: 5 Hz to 500 Hz (2.09 Grms); 20 min. per axis for all X, Y , Z directions IEC60068–2–6, Random: 5 Hz to 500 Hz (2.09 Grms); 20 min. per axis for all X, Y , Z directions Shock (operating) Operating IEC60068–2–27, half sine wave: 10 G for a duration of 11 ms, shock for 1 direction (X axis) IEC60068–2–27, half sine wave: 10 G for a duration of 11 ms, shock for 1 direction (X axis) IEC60068–2–27, half sine wave: 10 G for a duration of 11 ms, shock for 1 direction (X axis) Non-operating IEC60068–2–27, half sine wave: 50 G for a duration of 11 ms, 3 shocks for each 3 directions IEC60068–2–27, half sine wave: 50 G for a duration of 11 ms, 3 shocks for each 3 directions IEC60068–2–27, half sine wave: 50 G for a duration of 11 ms, 3 shocks for each 3 directions Pollution degree 2 2 2 Altitude 2000 m 2000 m 2000 m Certification and protection Safety entry low voltage SELV (EN 60950) SELV (EN 60950) SELV (EN 60950) Electrical safety (of information technology equipment) N/A N/A N/A Industrial control equipment UL/C–UL listed to UL 508 UL/C–UL listed to UL 508 UL/C–UL listed to UL 508 Class 2 power supply UL/C–UL listed to UL 508 UL /C–UL listed to UL 508 UL/C–UL listed to UL 508 CE In conformance with EMC directive 2014/30/EU and low-voltage directive 2014/35/EU In conformance with EMC directive 2014/30/EU and low-voltage directive 2014/35/EU In conformance with EMC directive 2014/30/EU and low-voltage directive 2014/35/EU Immunity EN 55024, EN 61000–6–1, EN 61000–6–2 EN 55024, EN 61000–6–1, EN 61000–6–2 EN 55024, EN 61000–6–1, EN 61000–6–2 Emissions EN 55032, EN 55011, EN 61000–3–3, EN 61000–6–3, EN 61000–6–4 EN 55032, EN 55011, EN 61000–3–3, EN 61000–6–3, EN 61000–6–4 EN 55032, EN 55011, EN 61000–3–3, EN 61000–6–3, EN 61000–6–4 RoHS compliant Yes Yes Yes Safety and protection Current limitation at short–circuits approx. N/A N/A N/A Surge voltage protection against internal surge voltages No No No Protection degree IP20 IP20 IP20 Safety class Class I with primary earth connection Class I with primary earth connection Class I with primary earth connection

V7-T6-14 Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—April 2019 www.eaton.com General-Purpose and Sensor Power Supplies Power Derating Curves Vertical Mounting Position PSC30E24RP Vertical Mounting Position PSC50E24RP Vertical Mounting Position PSC100E24RP Dimensions Approximate Dimensions in mm Note: Dimensions are for reference only. PSC30E24RP 100 110 -25 -20 -15 -10 -5 0 51 0 15 20 25 Load (%) Ambient Temperature (°C) 30 35 40 45 50 55 60 65 70 100 110 -25 -20 -15 -10 -5 0 51 0 15 20 25 Load (%) Ambient Temperature (°C) 30 35 40 45 50 55 60 65 70 100 110 -25 -20 -15 -10 -5 0 51 0 15 20 25 Load (%) Ambient Temperature (°C) 30 35 40 45 50 55 60 65 70 21.0 ±0.5 89.5 ±0.5 5.5 0.3 ±0.2 78.0 ±0.5 75.0 ±0.5 0.3 ±0.2

Volume 7—Logic Control, Operator Interface and Connectivity Solutions CA08100008E—April 2019 www.eaton.com V7-T6-15 6.1Power Supplies General-Purpose and Sensor Power Supplies Approximate Dimensions in mm Note: Dimensions are for reference only. PSC50E24RP PSC100E24RP 30.0 ±0.5 78.6 ±0.5 75.0 ±0.5 89.5 ±0.5 5.5 45.0 +1.2/–0.5 78.6 ±0.5 75.0 ±0.5 100.0 ±0.5 5.5