Switch-disconnector 4p, 63A Part no. PN1-4-63 Catalog No. 265999 EL-Nummer (Norway) 0004358827 Similar to illustration Delivery program Product range Switch-disconnectors Protective function Disconnectors/main switches Standard/Approval IEC Installation type Fixed Construction size PN1 Description Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113. Isolating characteristics to IEC/EN 60947-3 and VDE 0660. Busbar tag shroud to VDE 0160 Part 100. Number of poles 4 pole Standard equipment Box terminal Switch positions I, 0 Rated current = rated uninterrupted current In = Iu A 63 Short-circuit protection max. fuse gL-characteristic A gL 125 Technical data General Standards IEC/EN 60947 Protection against direct contact Finger and back-of-hand proof to DIN EN 50274/VDE 0106 part 110 Climatic proofing Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 Ambient temperature Ambient temperature, storage °C - 40 - + 70 Operation °C -25 - +70 Mechanical shock resistance (10 ms half-sinusoidal shock) according to IEC 60068-2-27 g 20 (half-sinusoidal shock 20 ms) Safe isolation to EN 61140 Between auxiliary contacts and main contacts V AC 500 between the auxiliary contacts V AC 300 Mounting position Mounting position Vertical and 90° in all directions With residual-current release XFI: - NZM1, N1, NZM2, N2: vertical and 90° in all directions with plug-in adapter elements - NZM1, N1, NZM2, N2: vertical, 90° right/left with withdrawable unit: - NZM3, N3: vertical, 90 ° left - NZM4, N4: vertical with remote operator: - NZM2, N(S)2, NZM3, N(S)3, NZM4, N(S)4: vertical and 90° in all directions Direction of incoming supply as required Degree of protection Device In the area of the HMI devices: IP20 (basic protection type) Enclosures With insulating surround: IP40 With door coupling rotary handle: IP66 Terminations Tunnel terminal: IP10 Phase isolator and band terminal: IP00 Switch-disconnectors Rated surge voltage invariability Uimp 07/10/2020 Eaton 265999 ED2020 V70.0 EN 1 / 6
Rated operational voltage Ue V AC 690 Rated operating frequency f Hz 50/60 Rated current = rated uninterrupted current In = Iu A 63 Overvoltage category/pollution degree III/3 Rated insulation voltage Ui V 690 Use in unearthed supply systems V ≦ 690 Other technical data (sheet catalogue) Weight Temperature dependency, Derating Effective power loss Rated short-circuit making capacity 690 V 50/60 H Ic kA 2.8 Rated short-time withstand current t = 0.3 s Icw kA 2 t = 1 s Icw kA 2 Rated conditional short-circuit current With back-up fuse A gG/gL gG/gL: 63 400 … 415 V kA 100
690 V kA 80
With downstream fuse A gG/gL gG/gL: 63 400 … 415 V kA 100
690 V kA 10
Rated making and breaking capacity Rated operational current Ie A AC-22/23A
415 V Ie A 160
690 V Ie A 160
Lifespan, mechanical Operations 20000 Max. operating frequency Ops/h 120 Lifespan, electrical AC-1
400 V 50/60 Hz Operations 10000
415 V 50/60 Hz Operations 10000
690 V 50/60 Hz Operations 7500
400 V 50/60 Hz Operations 1000
415 V 50/60 Hz Operations 1000
690 V 50/60 Hz Operations 1000
Standard equipment Box terminal Optional accessories Screw connection Tunnel terminal connection on rear Copper conductors and cables Box terminal Solid mm2 1 x (10 - 16) 2 x (6 - 16) Stranded mm2 1 x (10 - 70) 3) 2 x (6 - 25) 3) Up to 95 mm² can be connected depending on the cable manufacturer. Tunnel terminal Solid mm2 1 x 16 Stranded 1-hole mm2 1 x (25 - 95) Bolt terminal and rear-side connection Direct on the switch Solid mm2 1 x (10 - 16) 07/10/2020 Eaton 265999 ED2020 V70.0 EN 2 / 6
2 x (6 - 16) Stranded mm2 1 x (25 - 70) 3) 2 x 25 3) Up to 95 mm² can be connected depending on the cable manufacturer. Al conductors, Al cable Tunnel terminal Solid mm2 1 x 16 Stranded 1-hole mm2 1 x (25 - 95) Bolt terminal and rear-side connection Direct on the switch Solid mm2 1 x (10 - 16) 2 x (10 - 16) Stranded mm2 1 x (25 - 70) 3) 2 x 25 Cu strip (number of segments x width x segment thickness) Box terminal min. mm 2 x 9 x 0.8 max. mm 9 x 9 x 0.8 Copper busbar (width x thickness) mm Bolt terminal and rear-side connection Screw connection M6 Direct on the switch min. mm 12 x 5 max. mm 16 x 5 Design verification as per IEC/EN 61439 Technical data for design verification Rated operational current for specified heat dissipation In A 63 Equipment heat dissipation, current-dependent Pvid W 4.52 Operating ambient temperature min. °C -25 Operating ambient temperature max. °C 70 IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements. 10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements. 10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects Meets the product standard's requirements. 10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements. 10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated. 10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated. 10.2.7 Inscriptions Meets the product standard's requirements. 10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated. 10.4 Clearances and creepage distances Meets the product standard's requirements. 10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated. 10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated. 10.7 Internal electrical circuits and connections Is the panel builder's responsibility. 10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility. 10.9.3 Impulse withstand voltage Is the panel builder's responsibility. 10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility. 10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. 10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be observed. 07/10/2020 Eaton 265999 ED2020 V70.0 EN 3 / 6
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed. Technical data ETIM 7.0 Low-voltage industrial components (EG000017) / Switch disconnector (EC000216) Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Switch disconnector (ecl@ss10.0.1-27-37-14-03 [AKF060013]) Version as main switch Yes Version as maintenance-/service switch Yes Version as safety switch No Version as emergency stop installation Yes Version as reversing switch No Number of switches 1 Max. rated operation voltage Ue AC V 690 Rated operating voltage V 690 - 690 Rated permanent current Iu A 63 Rated permanent current at AC-23, 400 V A 0 Rated permanent current at AC-21, 400 V A 0 Rated operation power at AC-3, 400 V kW 0 Rated short-time withstand current lcw kA 2 Rated operation power at AC-23, 400 V kW 30 Switching power at 400 V kW 0 Conditioned rated short-circuit current Iq kA 0 Number of poles 4 Number of auxiliary contacts as normally closed contact 0 Number of auxiliary contacts as normally open contact 0 Number of auxiliary contacts as change-over contact 0 Motor drive optional No Motor drive integrated No Voltage release optional No Device construction Built-in device fixed built-in technique Suitable for ground mounting Yes Suitable for front mounting 4-hole No Suitable for front mounting centre No Suitable for distribution board installation Yes Suitable for intermediate mounting Yes Colour control element Black Type of control element Rocker lever Interlockable Yes Type of electrical connection of main circuit Frame clamp Degree of protection (IP), front side IP20 Degree of protection (NEMA) 07/10/2020 Eaton 265999 ED2020 V70.0 EN 4 / 6
① Blow out area, minimum clearance to adjacent parts 07/10/2020 Eaton 265999 ED2020 V70.0 EN 5 / 6
Additional product information (links) IL01203004Z (AWA1230-1913) Circuit-breaker, Switch-Disconnector IL01203004Z (AWA1230-1913) Circuit-breaker, Switch-Disconnector ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL01203004Z2015_11.pdf Weight http://ecat.moeller.net/flip-cat/?edition=HPLEN&startpage=17.171 Temperature dependency, Derating http://ecat.moeller.net/flip-cat/?edition=HPLEN&startpage=17.172 Effective power loss http://ecat.moeller.net/flip-cat/?edition=HPLEN&startpage=17.174 CurveSelect characteristics program http://www.eaton.eu/DE/Europe/Electrical/CustomerSupport/ConfigurationTools/CharacteristicsProgram/index.htm Eaton configurator http://www.eaton.eu/DE/Europe/Electrical/CustomerSupport/ConfigurationTools/ConfiguratorCircuitBreaker/index.htm additional technical information for NZM power switch ftp://ftp.moeller.net/DOCUMENTATION/PDF/nzm_technic_de_en.pdf 07/10/2020 Eaton Industries GmbH http://www.eaton.eu © 07/2020 by Eaton Industries GmbH Eaton 265999 ED2020 V70.0 EN