PMR Panel Mount Power Supply PMR 150 W series / PMR-□V150W1AT TECHNICAL DATASHEET All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated. www.DeltaPSU.com (December 2023, Rev. 00) PMR Highlights & Features

  • Universal AC input voltage
  • Built-in active PFC and conforms to harmonic current IEC/EN 61000-3-2, Class A and Class D
  • No load power consumption < 0.5 W
  • Low profile design: 30 mm height
  • Household appliance approvals according to IEC/EN 60335-1, IEC/EN 61558-1 and IEC/EN 61558-2-16
  • Wide operating temp -30°C ~70°C (Support -40°C cold start) Safety Standards CB Certified for worldwide use Model Number: PMR-☐V150W1AT Unit Weight: 0.35 kg (0.77 lb) Dimensions (L x W x H): 129 x 97 x 30 mm (5.08 x 3.82 x 1.18 inch) General Description PMR 150W series power supplies offers nominal output voltage of 12V/24V/36V/48V with a wide operating temperature range from - 30°C to +70°C and can withstand shock and vibration according to IEC 60068-2. The product is designed in a low 30 mm profile and comes with universal AC input voltage range at 90 Vac to 264 Vac. The PMR series is made for installation in narrow space while its built-in active PFC circuit provides high power factor values and conforms to harmonic current emission according to IEC/EN 61000-3-2, Class A and Class D. Model Information PMR Panel Mount Power Supply Model Number Input Voltage Range Rated Output Voltage Rated Output Current PMR-12V150W1AT 90-264 Vac (127-375 Vdc) 12 Vdc 12.5 A PMR-24V150W1AT 24 Vdc 6.5 A PMR-36V150W1AT 36 Vdc 4.3 A PMR-48V150W1AT 48 Vdc 3.3 A Model Numbering PM R – □V 150W 1 A T Panel Mount Product Type R – Standard Rack Type Series (1U) Output Voltage 12 – 12 V 24 – 24 V 36 – 36 V 48 – 48 V Output Power Single Phase Family Code: A Connector Type T – Terminal Block

PMR Panel Mount Power Supply PMR 150 W series / PMR-□V150W1AT TECHNICAL DATASHEET All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated. www.DeltaPSU.com (December 2023, Rev. 00) Specifications Model Number PMR-12V150W1AT PMR-24V150W1AT PMR-36V150W1AT PMR-48V150W1AT Input Ratings / Characteristics Nominal Input Voltage 100-240 Vac Input Voltage Range 90-264 Vac Nominal Input Frequency 50-60 Hz Input Frequency Range 47-63 Hz DC Input Voltage Range*1 127-375 Vdc Input Current 1.5 A typ. @ 115 Vac, 0.8 A typ. @ 230 Vac No Load Power Consumption 0.3 W max. @ 230 Vac 0.3 W max. @ 230 Vac 0.5 W max. @ 230 Vac 0.5 W max. @ 230 Vac Max Inrush Current (Cold Start) 45 A typ. @ 230 Vac Power Factor at 100% Load > 0.96 @ 115 Vac & > 0.93 @ 230 Vac Leakage Current < 0.5 mA @ 240 Vac *1 Power Supply can operate at DC Input voltage, please connect +pole to L, -pole to N and PE terminal to an earth wire or to the machine ground. Output Ratings / Characteristics*2 Nominal Output Voltage 12 Vdc 24 Vdc 36 Vdc 48 Vdc Factory Set Point Tolerance 12 Vdc ± 1% 24 Vdc ± 1% 36 Vdc ± 1% 48 Vdc ± 1% Output Current 0-12.5 A 0-6.5 A 0-4.3 A 0-3.3 A Line Regulation ± 0.5% typ. @ 115 Vac & 230 Vac Load Regulation ±0.5% typ. PARD*3 (20MHz) < 120 mVpp @ 0°C to 70°C 360 mVpp typ. @ -30°C to 0°C < 150 mVpp @ 0°C to 70°C 450 mVpp typ. @ -30°C to 0°C Rise Time 30 ms typ. @ 115 Vac & 230 Vac Start-up Time 500 ms typ. @ 115 Vac & 230 Vac Hold-up Time 30 ms typ. @ 115 Vac & 230 Vac Dynamic Response (Overshoot & Undershoot O/P Voltage) ± 10% @ 115 & 230 Vac input, 10-100% load (Slew Rate: 2.5 A/μS, 50% duty cycle @ 5 Hz & 10 KHz) Start-up with Capacitive Loads 8,000 µF Max 8,000 µF Max 6,000 µF Max 5,000 µF Max *2 For power de-rating from > 50°C to 70°C, see power de-rating on page 3. *3 PARD is measured with an AC coupling mode, and in parallel to end terminal with 0.1µF ceramic capacitor & 47µF electrolytic capacitor. PSU need to burn in > 5 minutes when AMB ≤ 0℃

PMR Panel Mount Power Supply PMR 150 W series / PMR-□V150W1AT TECHNICAL DATASHEET All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated. www.DeltaPSU.com (December 2023, Rev. 00) Mechanical Case Chassis Aluminum Case Cover SGCC Dimensions (L x W x H) 129 x 97 x 30 mm (5.08 x 3.82 x 1.18 inch) Unit Weight 0.35 kg (0.77 lb) Indicator Green LED (DC OK) Cooling System Convection Terminal M3.5 x 7 Pins (Rated 300 V / 20 A) Wire AWG 18-12 Current rating can refer to page 6 “Wire AWG Table” Environment Surrounding Air Temperature Operating -30°C to +70°C ( -40°C Cold Start ) Storage -40°C to +85°C Power De-rating > 50°C de-rate power by 2% / °C < 100Vac de-rate power by 1% / V (90% load @ 90 Vac) Operating Humidity 20 to 90% (Non-Condensing) Operating Altitude 0 to 5,000 Meters (0 to 16,400 ft) Shock Test Non-Operating IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction Vibration Operating IEC 60068-2-6, Sine Wave: 10 Hz to 500 Hz @ 2G;10Min per cycle,60min for X,Y,Z direction Over Voltage Category II (Compliance to EN 62477-1 OVC III with 2000 meters altitude) Pollution Degree 3 Protections Overvoltage 13.2 V - 16.8 V SELV Output, Latch Mode 26.4 V - 33.6 V SELV Output, Latch Mode 39.6 V - 48.6 V SELV Output, Latch Mode 52.8 V - 64.8 V SELV Output, Latch Mode Overload / Overcurrent 110-175% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery) Over Temperature Latch Mode Short Circuit Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) Protection Against Shock Class I with PE*4 connection *4 PE: Protection Earth Reliability Data MTBF > 700,000 hrs as per Telcordia SR-332 (I/P: 230 Vac, O/P: 100% Load, Ta: 25°C) Expected Cap Life Time 10 years (230 Vac, 50% load @ 40°C)

PMR Panel Mount Power Supply PMR 150 W series / PMR-□V150W1AT TECHNICAL DATASHEET All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated. www.DeltaPSU.com (December 2023, Rev. 00) Safety Standards / Directives Safety Entry Low Voltage SELV Electrical Safety TUV Bauart UL/cUL CB scheme EAC BSMI CCC EN 62368-1, EN 60335-1 UL 62368-1, and CAN/CSA C22.2 No. 62368-1 IEC 62368-1, IEC 60335-1, IEC/EN 61558-1/-2-16 TP TC 004/2011 CNS 15598-1 GB 4943.1 CE In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU UKCA In conformance with Electromagnetic Compatibility Regulations 2016 and Electrical Equipment (Safety) Regulations 2016 Galvanic Isolation Input to Output 4.0 KVac Input to Ground 2.0 KVac Output to Ground 1.25 KVac EMC*5 Emissions (CE & RE) CISPR 32, EN/BS EN 55032, KS C 9832, AS/NZS CISPR32 & Compliance to FCC Title 47, EN/BS EN 55014-1 , EN/BS 61000-6-3 , EN/BS EN 61000-6-4 : Class B Immunity EN/BS EN 55035, KS C 9835, & Compliance to EN/ BS EN 55014-2 , EN/BS EN 61000-6- 1 , EN/BS EN 61000-6-2 Electrostatic Discharge IEC 61000-4-2 Level 4 Criteria A1) Air Discharge: 15 kV Contact Discharge: 8 kV Radiated Field IEC 61000-4-3 Level 3 Criteria A1)

80 MHz – 1 GHz, 10 V/M, 80% Modulation (1 kHz)

1.4 GHz – 6 GHz, 3 V/M, 80% Modulation (1 kHz)

IEC 61000-4-4 Level 3 Criteria A1) 2 kV Surge IEC 61000-4-5 Level 4 Criteria A1) Common Mode4): 4 kV Differential Mode5): 2 kV Conducted IEC 61000-4-6 Level 3 Criteria A1) 150 kHz-80 MHz, 10 Vrms Power Frequency Magnetic Fields IEC 61000-4-8 Level 4 Criteria A1)

30 A/Meter

IEC 61000-4-11 0% residual; 1 cycle, Criteria B2) 40% residual; 10 cycle, Criteria C3) 70% residual; 25 cycle, Criteria C3) Harmonic Current Emission IEC/EN/BS EN 61000-3-2, Class A & Class D Voltage Fluctuation and Flicker IEC/EN/BS EN 61000-3-3 Voltage Sag Immunity SEMI F47 – 0706 80% of 200 Vac 70% of 200 Vac 50% of 200 Vac

160 Vac, 1000 ms

140 Vac, 500 ms

100 Vac, 200 ms

Criteria A1) Criteria A1) Criteria A1) 1) Criteria A: Normal performance within the specification limits 2) Criteria B: Output out of regulation, or shuts down during test. Automatically restored to normal operation after test. 3) Criteria C: Output out of regulation, shuts down during test (Need to recycle AC power cord to normal operation after test) 4) Asymmetrical: Common mode (Line to earth) 5) Symmetrical: Differential mode (Line to line) *5 Power supply is considered a component in the end-user's system. Please contact our local sales to get more information about the power supply EMC test setup.

PMR Panel Mount Power Supply PMR 150 W series / PMR-□V150W1AT TECHNICAL DATASHEET All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated. www.DeltaPSU.com (December 2023, Rev. 00) Block Diagram EMI Filter PFC Converter & Inrush current limit & Filter DC/DC Converter Output Rectifier Filter Over Temperature Protection PWM Control & Over Power Protection Feedback Control Photo Coupler Photo Coupler & Over Voltage Protection Vo+ Vo- DC OutputAC Input L N Transformer & Power Stage Device Descriptions 1) Input & Output terminal block connector 2) DC voltage adjustment potentiometer 3) DC OK control LED (Green)

PMR Panel Mount Power Supply PMR 150 W series / PMR-□V150W1AT TECHNICAL DATASHEET All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated. www.DeltaPSU.com (December 2023, Rev. 00) Dimensions L x W x H: 129 x 97 x 30mm (5.08 x 3.82 x 1.18 inch) Wire AWG Table Current rating for PVC Wire AWG 6 AWG 52.5 A 20 AWG 6.5 A 8 AWG 37.5 A 22 AWG 5.0 A 10 AWG 29.0 A 24 AWG 3.5 A 12 AWG 22.5 A 26 AWG 2.5 A 14 AWG 16.5 A 28 AWG 2.0 A 16 AWG 12.0 A 30 AWG 1.5 A 18 AWG 9.0 A

PMR Panel Mount Power Supply PMR 150 W series / PMR-□V150W1AT TECHNICAL DATASHEET All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated. www.DeltaPSU.com (December 2023, Rev. 00) Engineering Data Output Load De-rating VS Surrounding Air Temperature Output Load De-rating VS Input Voltage AC Input DC Input Fig. 1 De-rating for Horizontal Mounting Orientation > 50°C de-rate power by 2.0% / °C Note 1. Power supply components may degrade, or be damaged, when the power supply is continuously used outside the shaded region, refer to the graph shown in Fig. 1 & Fig. 2. 2. The PSU will be bouncing and start up time will not exceed 5s when ambient temperature at ‐30 °C. 3. If the output capacity is not reduced when the surrounding air temperature >50°C, the device will run into Over Temperature Protection. When activated, power supply will latch off, until the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition, and require removal/re-application of input AC voltage in order to restart. 4. In order for the device to function in the manner intended, it is also necessary to keep a safety distance as recommended in the safety instructions while the device is in operation. 5. Depending on the surrounding air temperature and output load delivered by the power supply, the device can be very hot!  No output power de -rating for the input voltage from 100 Vac to 264 Vac & 127 Vdc to 375 Vdc Fig. 2 De-rating for AC Input Voltage < 100Vac de-rate power by 1% / V (90% load @ 90 Vac) No de-rate power for DC Input

PMR Panel Mount Power Supply PMR 150 W series / PMR-□V150W1AT TECHNICAL DATASHEET All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated. www.DeltaPSU.com (December 2023, Rev. 00) Assembly & Installation Ⓐ Base Mounting: Fig.3 shows the mounting hole locations for power supply assembly onto a metal mounting surface. Ⓑ This surface belongs to customer’s end system or panel where the power supply is mounted. Ⓒ Connector Base Mounting (Horizontal) * If the device has to be mounted in any other orientation, please leave a message via the Contact Us form.

  • Use flexible cable (stranded or solid) of AWG No.18-12. User should calculate and select the suitable wire specification insulation stripping length should not exceed 0.275” or 7 mm. (Refer to Fig. 3). Installation of Mounting Accessories Fig. 3 Assembly Reference

PMR Panel Mount Power Supply PMR 150 W series / PMR-□V150W1AT TECHNICAL DATASHEET All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated. www.DeltaPSU.com (December 2023, Rev. 00) Fig. 4 Mounting Screw Safety Instructions

  • If user’s mounting orientation is not according to the recommended mounting orientations, please consult Delta for further information.
  • To ensure sufficient convection cooling, always maintain a safety distance of ≥ 50 mm (1.97 inch) from all ventilated surfaces while the device is in operation.
  • The device is not recommended to be placed on low thermal conductive surface. For example, plastics.
  • The enclosure of the device can become very hot depending on the ambient temperature and load of the power supply. Do not touch the device while it is in operation or immediately after power is turned OFF. Risk of burning!
  • Do not touch the terminals while power is being supplied. Risk of electric shock.
  • Prevent any foreign metal, particles or conductors from entering the device through the openings during installation. It may cause: Electric shock; Safety Hazard; Fire; Product failure
  • The power supply must be mounted by metal screws onto a grounded metal surface. It is highly recommended that the Earth terminal on the connector be connected to the grounded surface.  Only use M3 screw ≤ 3 mm (0.20 inch) through the base mounting holes. This is to keep a safe distance between the screw and internal components.

PMR Panel Mount Power Supply PMR 150 W series / PMR-□V150W1AT TECHNICAL DATASHEET All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated. www.DeltaPSU.com (December 2023, Rev. 00) Functions Start-up Time The time required for the output voltage to reach 90% of its final steady state set value, after the input voltage is applied. Rise Time The time required for the output voltage to change from 10% to 90% of its final steady state set value. Hold-up Time Time between the collapse of the AC input voltage, and the output falling to 95% of its steady state set value. ■ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time Inrush Current Inrush current is the peak, instantaneous, input current measured and, occurs when the input voltage is first applied. For AC input voltages, the maximum peak value of inrush current will occur during the first half cycle of the applied AC voltage. This peak value decreases exponentially during subsequent cycles of AC voltage. Dynamic Response The power supply output voltage will remains within ± 10% of its steady state value, when subjected to a dynamic load from 10% to 100%.

PMR Panel Mount Power Supply PMR 150 W series / PMR-□V150W1AT TECHNICAL DATASHEET All parameters are specified at 25°C ambient and nominal AC input unless otherwise indicated. www.DeltaPSU.com (December 2023, Rev. 00) Overload & Overcurrent Protections (Auto-Recovery) The power supply’s Overload (OLP) and Overcurrent (OCP) Protections will be activated when output current exceeds 110% of IO (Max load). In such occurrence, the V O will start to droop and once the power supply has reached its maximum power limit, the protection is activated and the power supply will go into “Hiccup mode” (Auto-Recovery). The power supply will recover once the fault condition of the OLP and OCP is removed and IO is back within the specifications. It is not recommended to prolong the duration of Io when it is <110% but >100%, since it may cause damage to the PSU. Short Circuit Protection (Auto-Recovery) The power supply’s output OLP/OCP function also provides protection against short circuits. When a short circuit is applied, the output current will operate in “Hiccup mode”, as shown in the illustration in the OLP/OCP section on this page. The power supply will return to normal operation after the short circuit is removed. Overvoltage Protection (Latch Mode) The power supply’s overvoltage circuit will be activated when its internal feedback circuit fails. The output voltage shall not exceed its specifications defined on under “Protections”. Power supply will latch, and require removal/re-application of input A C voltage in order to restart. The power supply should be latch, and require removal /re- apply of input AC voltage in order to restart. Over Temperature Protection (Latch Mode) As described in Engineer ing data section, the power supply also has Over Temperature Protection (OTP). In the event of a higher operating temperature at 100% load, the power supply will run into OTP when the operating temperature is beyond what is recommended in the de-rating graph. When activated, the output voltage will go into latch mode until the temperature drops to its normal operating temperature as rec ommended in the de -rating graph. Others Attention Delta provides all information in the datasheets on an “AS IS” basis and does not offer any kind of warranty through the information for using the product. In the event of any discrepancy between the information in the catalog and datasheets, the datasheet s shall prevail (please refer to www.DeltaPSU.com for the latest datasheets information). Delta shall have no liability of indemnification for any claim or action arising from any error for the provided information in the datasheets. Customer shall take it s responsibility for evaluation of using the product before placing an order with Delta. Delta reserves the right to make changes to the information described in the datasheets without notice. Manufacturer and Authorized Representatives Information Manufacturer Thailand Delta Electronics (Thailand) PCL. 909 Pattana 1 Rd., Muang, Samutprakarn, 10280 Thailand Taiwan Delta Electronics, Inc.