PMC Panel Mount Power Suppl y 24V 150W 1 Phase / PMCB24V150W1AX All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (March 2013, Rev. 00) PMC Highlights & Features – Universal AC input range from 85Vac to 264Vac wit hout power deBrating – Full Aluminum casing for light weight and corrosi on resistant handling – High MTBF > 700,000 hrs. as per Telcordia SRB332 – Overvoltage / Overcurrent / Over Temperature Prot ections – IP 20 Compliant (for PMCB24V150W1AJ) Safety Standards CB Certified for worldwide use Model Number: PMCB24V150W1AX Unit Weight : 0.48 kg Dimensions (L x W x D): 178 mm x 97 mm x 38 mm General Description The new Panel Mount Power Supply is the latest offe ring from one of the world’s largest power supply m anufacturers and solution providers B Delta. The product range offers a nomin al output voltage of 24V, a wide temperature range from B10°C to +70°C and a highly dependable minimum holdup time. The stateBofBtheBart design is made to withstand harsh industrial environments. What makes the product stands out from the crowd is its lightweight full aluminum body design which can withstand shock and vibration according to IEC60068B2. Delta’s Panel Mount Power Supply also o ffers overvoltage and overload protection. Using a wide input voltage range design, it is compatible worldwide. The input also includes DC operating voltage from 125B375Vdc. Best of all, this excellent design and quality does not come with a big price tag. Model Information PMC Panel Mount Power Supply Model Number Input Voltage Range Output Voltage Output Current PMCB24V150W1AX 85B264Vac (125B375Vdc) 24Vdc 6.25A Model Numbering PMC 24V 150W 1 A X PMC Series Output Voltage Output Power Single Phase Delta Standard A B Terminal Block Connector J B IP 20 Connector
PMC Panel Mount Power Suppl y 24V 150W 1 Phase / PMCB24V150W1AX All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (March 2013, Rev. 00) Specifications Input Ratings / Characteristics Nominal Input Voltage 100B240Vac Input Voltage Range 85B264Vac Nominal Input Frequency 50B60Hz Input Frequency Range 47B63Hz Nominal DC Input Voltage 125B250Vdc DC Input Voltage Range 125B375Vdc Input Current < 3.1A @ 115Vac, < 2.0A @ 230Vac Efficiency at 100% Load > 87% @ 115Vac, > 88% @ 230Vac Max Inrush Current < 60A @ 115Vac, < 120A @ 230Vac Power Factor NA Leakage Current < 1mA @ 240Vac Output Ratings / Characteristics Nominal Output Voltage 24Vdc Output Voltage Tolerance ± 2% (initial set point tolerance from factory) Output Voltage Adjustment Range 22B28Vdc Output Current 6.25A Output Power 150W Line Regulation < 0.5% typ. (@ 85B264Vac input, 100% load) Load Regulation < 1% typ. (@ 85B264Vac input, 0B100% load) PARD (20MHz) < 100mVpp Rise Time < 30ms @ nominal input (100% load) StartBup Time < 1000ms @ nominal input (100% load) HoldBup Time > 15ms @ 115Vac, > 80ms @ 230Vac (100% load) Dynamic Response (Overshoot & Undershoot O/P Voltag e) ± 5% @ 0B100% load StartBup with Capacitive Loads 8,000µF Max Mechanical Case Cover Alumin ium Dimensions (L x W x D) 178 mm x 97 mm x 38 mm Unit Weight 0.48 kg Indicator Green LED (DC OK) System Cooling Convection Terminal Input and Output PMCB24V150W1AA: M3.5 x 7 Pins (Rat ed 300V/15A) PMCB24V150W1AJ: M3.5 x 7 Pins (Rated 300V/20A) Wire PMCB24V150W1AA: AWG 22B14 PMCB24V150W1AJ: AWG 22B12 Noise Sound Pressure Level (SPL) <40dBA
PMC Panel Mount Power Suppl y 24V 150W 1 Phase / PMCB24V150W1AX All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (March 2013, Rev. 00) Environment Surrounding Air Temperature Operating B10°C to +70° C Storage B25°C to +85°C Power DeBrating > 50°C deBrate power by 2.5% / °C Operating Humidity < 95% RH Operating Altitude 3,000 Meters Shock Test (NonBOperating) IEC60068B2B27, 30G (300m/S²) for a duration of 18m s 3 times per direction, 18 times in total Vibration (NonBOperating) IEC60068B2B6, 10Hz to 500Hz @ 50m/S² (5G peak); 20 min per axis for all X, Y, Z direction Pollution Degree 2 Protections Overvoltage < 32V ±10%, SELV output, HiccBup Mode, NonBLatching (Auto recovery). Overload / Overcurrent > 120% of rated load current, HiccBup Mode, NonBLatching (Auto recovery). Over Temperature < 75°C Ambient Temp@ 100% load, NonBLatching (AutoBrecovery). Short Circuit HiccBup Mode, NonBLatching (AutoBrecovery when the fault is removed). Protection Against Shock Class I with PE* connection *PE: Primary Earth Reliability Data MTBF > 700,000 hrs, as per per Telcordia SRB332 Expected Cap Life Time 10 years (115Vac & 230Vac, 50% load @ 40°C)
PMC Panel Mount Power Suppl y 24V 150W 1 Phase / PMCB24V150W1AX All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (March 2013, Rev. 00) Safety Standards / Directives UL60950B1 and CSA C22.2 No. 60950B1, CB scheme to IEC60950B1 CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC Material and Parts RoHS Directive 2011/65/EU Compliant Galvanic Isolation Input to Output 3.0 KVac Input to Ground 1.5 KVac Output to Ground 500 Vac EMC EMC / Emissions CISPR22, EN55022, FCC Title 47: Class B Immunity to Electrostatic Discharge IEC61000B4B2 Level 4 Criter ia A 1) Air Discharge: 15kV Contact Discharge: 8kV Radiated Field IEC61000B4B3 Level 3 Criteria A 1) 80MHzB1GHz, 10V/M with 1kHz tone / 80% modulation 2kV Surge IEC61000B4B5 Level 3 Criteria A 1) Common Mode 2) : 2kV Differential Mode 3) : 2kV Conducted IEC61000B4B6 Level 3 Criteria A 1) 150kHzB80MHz, 10Vrms Power Frequency Magnetic Fields IEC61000B4B8 Criter ia A 1) 10A/Meter Voltage Dips IEC61000B4B11 100% dip; 1 cycle (20ms); Self Recove rable Low Energy Pulse Test (Ring Wave) IEC61000B4B12 Lev el 3 Criteria A 1) Common Mode 2) : 2kV Differential Mode 3) : 1kV 1) Criteria A: Normal performance within the specification limits 2) Asymmetrical: Common mode (Line to earth) 3) Symmetrical: Differential mode (Line to line)
PMC Panel Mount Power Suppl y 24V 150W 1 Phase / PMCB24V150W1AX All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (March 2013, Rev. 00) Block Diagram Device Description 1) Input & Output terminal block connector 2) DC Voltage adjustment potentiometer 3) DC OK control LED (Green)
PMC Panel Mount Power Suppl y 24V 150W 1 Phase / PMCB24V150W1AX All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (March 2013, Rev. 00) Dimensions L x W x D: 178 x 97 x 38 mm Engineering Data DeBrating VS surrounding air temperature Fig. 1 De -rating for Vertical and Horizontal Mounting Orientation > 50°C de-rate power by 2.5% / °C Note 1. Power supply components may degrade, or be damaged, when the power supply is continuously used outside the shaded region, refer to the graph shown in Fig. 1. 2. If the output capacity is not reduced when the surrounding air temperature > 50°C, the device may run into Over Temperature Protection. When activated, the output voltage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition. 3. If the device has to be mounted in any other orientation, please do not hesitate to contact info@deltapsu.com for more details. 4. In order for the device to function in the manne r intended, it is also necessary to keep a safety distance of 20mm with adjacent units while the device is in operation. 5. Depending on the surrounding air temperature and output load delivered by the power supply, the device housing can be very hot!
PMC Panel Mount Power Suppl y 24V 150W 1 Phase / PMCB24V150W1AX All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (March 2013, Rev. 00) DeBrating VS AC input voltage Assembly & Installation Mounting ⒶⒶ ⒶⒶ Mounting holes for power supply assembly onto the mounting surface. Power supply shall be mounted on minimum 2 mounting holes using M3 screw minimum 5 mm length. ⒷⒷ ⒷⒷ This surface belongs to customer’s end system or panel where the power supply is mounted. ⒸⒸ ⒸⒸ Connector. Installation Fig. 2 Mounting Orientation /square6/square6 /square6/square6 Only use M3 screw ≤ 6 mm through the base mounting holes. This is to keep a safe distance between the screw and internal components. /square6/square6 /square6/square6 Recommended mounting tightening torque : 4~8Kgf.cm Side Mounting (Vertical) Base Mounting (Vertical) Side Mounting (Horizontal) ■ No output power deBrating across the entire input voltage range
PMC Panel Mount Power Suppl y 24V 150W 1 Phase / PMCB24V150W1AX All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (March 2013, Rev. 00) Safety Instructions Functions ■ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time StartBup Time The time required for the output voltage to reach 90% of its set value, after the input voltage is applied. Rise Time The time required for the output voltage to change from 10% to 90% of its set value. HoldBup Time Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time required for the output to reach 95% of its set value, after the input voltage is removed.
- To ensure sufficient convection cooling, always ma intain a safety distance of > 20mm from all ventila ted surfaces while the device is in operation.
- The device is not recommended to be placed on low thermal conductive surface, for example, plastics.
- Note that the enclosure of the device can become v ery hot depending on the ambient temperature and lo ad of the power supply. Do not touch the device while it is in operation or immediately after power is turned OFF. Risk of burning!
- Do not touch the terminals while power is being su pplied. Risk of electric shock.
- Prevent any foreign metal, particles or conductors to enter the device through the openings during installation. It can cause: B B Electric shock; Safety Hazard; Fire; Product failure
- Warning: When connecting the device, secure Earth c onnection before connecting L and N. When disconnec ting the device, remove L and N connections before removing the Earth connection.
PMC Panel Mount Power Suppl y 24V 150W 1 Phase / PMCB24V150W1AX All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (March 2013, Rev. 00) Inrush Current Inrush Current is the first surge current seen on t he input side when AC input is applied to the power supply. It is the first pulse captured; see a typical picture for the inrush curr ent as seen in the power supply. Dynamic Response The power supply output voltage will remains within ±5% of its steady state value, when subjected to a dynamic loa d from 0 to 100% of its rated current. Overvoltage Protection The power supply’s overvoltage circuit will be acti vated when its internal feedback circuit fails. The output voltage shall not exceed its specifications defined on Page 3 under “Protections”. Overload & Overcurrent Protections The power supply’s Overload (OLP) and Over current (OCP) Protections will be activated when output current e xceeds 120% of I O (Max load). In such occurrence, the V O will start to droop and once the power supply has reached its maximum power limit, the protection is activated and the power supply will g o into “Hiccup mode” (AutoBRecovery). The power supply will recove r once the fault condition of the OLP and OCP is removed and I O is back within the specifications. Additionally, if the I O is < 120% but > 100% for a prolong period of time (depending on the load), the Over Temperature Protection (OTP) will be activated due to high temperature on critical components. The power supply will then go into “Hic cup mode” until power supply cool down. Over Temperature Protection As mentioned above, the power supply also has Over Temperature Protection (OTP). This is activated whe n the overload condition persists for an extended duratio n and the output current is below the overload trigger point but > 100% load. In the event of a higher operating condition at 100 % load, the power supply will run into OTP when the surrounding air temperature is > 75°C. When activated, the output v oltage will go into bouncing mode until the operating surrounding temperature drops to 50°C or output capacity is reduced as reco mmended in the deBrating graph. Short Circuit Protection The power supply’s output OLP/OCP function also pro vides protection against short circuits. When a short cir cuit is applied, the output current will operate in “Hiccup mode”, a s shown in the illustration in the OLP/OCP section on this page. T he power supply will return to normal operation after the sh ort circuit is removed.
PMC Panel Mount Power Suppl y 24V 150W 1 Phase / PMCB24V150W1AX All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (March 2013, Rev. 00) Operating Mode /square6/square6 /square6/square6 Redundancy Operation In order to ensure proper redundancy operation for the power supply unit (PSU), ensure that the output vol tage difference between the two units is kept at 0.45~0. 50V for 24V supplies. Follow simple steps given below t o verify: Step 1. Measure output voltage of PSU 1 and PSU 2. If PSU 1 is the master unit, then V O of PSU 1 must be higher than PSU 2. In order to set the output voltage, connect the pow er supply to 50% load and set the PSU 1 and PSU 2 output voltage. Step 2. Connect the right DRR module, 20A as per the system requirement to the power supply units PSU 1 and PSU 2 at V in 1 & V in 2 respectively. Step 3. Connect the system load from V out . Please note that output voltage V out from DRR module will be = V O (output voltage of power supply) – V drop * (in DRR module). Fig. 3 Redundancy / Parallel Operation Connection Diagram /square6/square6 /square6/square6 Parallel Operation + 2.5A + 2.5A = 7.5A) or current sharing, and thus increasing the power supply and system reliability. Though the PMCB24V150W1AX is not designed for current sharing, a good current sharing between two power supplies can be achieved by following simple steps as below (Refer to Fig. 3 for the Connection Diagram). St ep 1. Set output load condition for both supplies at 50% and measure the output voltages. Step 2. Adjust output voltages to the same level or within ±25mV difference. Step 3. Connect PSU 1 and PSU 2 with the DRRB20A module and measure at V in 1 & V in 2 to verify the voltage difference. Ensure the voltages are within ±25mV. Step 4. Output voltage from DRR module V out will be = V O (output voltage of power supply) – Vdrop * (in DRR module). *V drop will vary from 0.60V to 0.90V (Typical 0.65V) depending on the load current and surrounding air temperature.
PMC Panel Mount Power Suppl y 24V 150W 1 Phase / PMCB24V150W1AX All parameters are specified at 25°C ambient unless otherwise noted. www.DeltaPSU.com (March 2013, Rev. 00) Others Delta RoHS Compliant Restriction of the usage of hazardous substances The European directive 2011/65/EU limits the maximu m impurity level of homogeneous materials such as l ead, mercury, cadmium, chrome, polybrominated flame reta rdants PBB and PBDE for the use in electrical and electronic equipment. RoHS is the abbreviation for “Restriction of the use of certain hazardous substa nces in electrical and electronic equipment”. This product conforms to this standard.
Click to View Pricing, Inventory, Delivery & Lifecycle Information: Delta: PMC-24V150W1AA