PMC Panel Mount Power Supply 12V 150W 1 Phase / PMC-12V150W1B□ All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2020, Rev. 04) PMC Highlights & Features
- Universal AC input range from 85Vac to 264Vac without power de-rating
- Full Aluminum casing for light weight and corrosion resistant handling
- High MTBF > 700,000 hrs. as per Telcordia SR-332
- Overvoltage / Overcurrent / Over Temperature Protections
- IP 20 Compliant (for PMC-12V150W1BJ)
- Certified according to IEC/EN/UL 62368-1 Safety Standards CB Certified for worldwide use Model Number: PMC-12V150W1B☐ Unit Weight: 0.54 kg (1.19 lb) Dimensions (H x W x D): 178 x 97 x 38 mm (7.01 x 3.82 x 1.50 inch) General Description Delta’s PMC series of panel mount power supply offers a nominal output voltage of 12V, a wide temperature range from -10°C to +70°C and a highly dependable minimum hold-up time. The state-of-the-art design is made to withstand harsh industrial environments. What makes the product stands out from the cr owd is its lightweight full aluminum body design , which can withstand shock and vibration according to IEC60068-2. The PMC series also offers overvoltage and overload protection. Using a wide input voltage range design, it is compatible worldwide. The input also includes DC operating voltage from 125 -375Vdc. Best of all, this excellent design and quality does not come with a big price tag. Model Information PMC Panel Mount Power Supply Model Number Input Voltage Range Rated Output Voltage Rated Output Current PMC-12V150W1BX 85-264Vac (125-375Vdc) 12Vdc 12.50A Model Numbering PMC 12V 150W 1 B ☐ PMC Series Output Voltage Output Power Single Phase With PFC Connector Type A – Terminal Block J – IP20 Connector* L – Front Face* *Options A J L
PMC Panel Mount Power Supply 12V 150W 1 Phase / PMC-12V150W1B□ All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2020, Rev. 04) Specifications Input Ratings / Characteristics Nominal Input Voltage 100-240Vac Input Voltage Range 85-264Vac Nominal Input Frequency 50-60Hz Input Frequency Range 47-63Hz Nominal DC Input Voltage 125-250Vdc DC Input Voltage Range 125-375Vdc Input Current < 1.7A @ 115Vac, < 1.0A @ 230Vac Efficiency at 100% Load > 87% @ 115Vac, > 88% @ 230Vac Max Inrush Current < 60A @ 115Vac, < 120A @ 230Vac Power Factor PF > 0.99 @ 115Vac, > 0.90 @ 230Vac Leakage Current < 1mA @ 240Vac Output Ratings / Characteristics Nominal Output Voltage 12Vdc Output Voltage Tolerance ± 2% (initial set point tolerance from factory) Output Voltage Adjustment Range 11-14Vdc Output Current 12.50A Output Power 150W Line Regulation < 0.5% typ. (@ 85-264Vac input, 100% load) Load Regulation < 1% typ. (@ 85-264Vac input, 0-100% load) PARD (20MHz) < 100mVpp Rise Time < 30ms @ nominal input (100% load) Start-up Time < 2000ms @ nominal input (100% load) Hold-up Time > 30ms @ 115Vac & 230Vac (100% load) Dynamic Response (Overshoot & Undershoot O/P Voltage) ± 5% @ 0-100% load Start-up with Capacitive Loads 8,000µF Max
PMC Panel Mount Power Supply 12V 150W 1 Phase / PMC-12V150W1B□ All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2020, Rev. 04) Mechanical Case Cover Aluminium Dimensions (L x W x H) 178 x 97 x 38 mm (7.01 x 3.82 x 1.50 inch) Unit Weight 0.54 kg (1.19 lb) Indicator Green LED DC OK Cooling System Convection Terminal PMC-12V150W1BA M3.5 x 7 Pins (Rated 300V/15A) PMC-12V150W1BJ M3.5 x 7 Pins (Rated 300V/20A) PMC-12V150W1BL M3.5 x 7 Pins (Rated 300V/20A) Wire PMC-12V150W1BA AWG 18-14 PMC-12V150W1BJ AWG 18-12 PMC-12V150W1BL AWG 18-14 Noise Sound Pressure Level (SPL) <40dBA Environment Surrounding Air Temperature Operating -10°C to +70°C Storage -25°C to +85°C Power De-rating > 50°C de-rate power by 2.5% / °C Operating Humidity < 95% RH Operating Altitude 0 to 5,000 Meters (16,400 ft.) Shock Test Non-Operating IEC60068-2-27, 30G (300m/S²) for a duration of 18ms 1 times per direction, 6 times in total Vibration Non-Operating IEC60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak); 60 min per axis for all X, Y, Z direction Pollution Degree 2 Protections Overvoltage 16V +10%/-5%, SELV output, Hiccup Mode, Non-Latching (Auto-Recovery). Overload / Overcurrent > 115% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery). Over Temperature < 75°C Ambient Temp@ 100% load, Non-Latching (Auto-Recovery). Short Circuit Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed). Protection Against Shock Class I with PE* connection *PE: Primary Earth
PMC Panel Mount Power Supply 12V 150W 1 Phase / PMC-12V150W1B□ All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2020, Rev. 04) Reliability Data M TBF > 700,000 hrs, as per Telcordia SR-332 Expected Cap Life Time 10 years (115Vac & 230Vac, 50% load @ 40°C) Safety Standards / Directives Electrical Safety SIQ Bauart EN 60950-1, EN 62368-1 U L/cUL recognized UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395) UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) C B scheme IEC60950-1, IEC 62368-1 CCC GB4943 CE In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU Galvanic Isolation Input to Output 3.0 KVac Input to Ground 1.5 KVac O utput to Ground 0.5 KVac EMC E MC / Emissions CISPR32, EN55032, FCC Title 47: Class B, GB9254 Immunity to Electrostatic Discharge IEC61000-4-2 Level 4 Criteria A1) Air Discharge: 15kV Contact Discharge: 8kV Radiated Field IEC61000-4-3 Level 3 Criteria A1) 80MHz-1GHz, 10V/M with 1kHz tone / 80% modulation 2kV Surge IEC61000-4-5 Level 3 Criteria A1) Common Mode2): 2kV Differential Mode3): 1kV Conducted IEC61000-4-6 Level 3 Criteria A1) 150kHz-80MHz, 10Vrms Power Frequency Magnetic Fields IEC61000-4-8 Criteria A1) 10A/Meter Voltage Dips IEC61000-4-11 100% dip; 1 cycle (20ms); Self Recoverable Low Energy Pulse Test (Ring Wave) IEC61000-4-12 Level 3 Criteria A1) Common Mode2): 2kV Differential Mode3): 1kV 1) Criteria A: Normal performance within the specification limits 2) Asymmetrical: Common mode (Line to earth) 3) Symmetrical: Differential mode (Line to line)
PMC Panel Mount Power Supply 12V 150W 1 Phase / PMC-12V150W1B□ All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2020, Rev. 04) Block Diagram Device Description 1) I nput & Output terminal block connector 2) DC Voltage adjustment potentiometer 3) DC OK control LED (Green) PMC-12V150W1BL: Front Face PMC-12V150W1BA: Terminal Block PMC-12V150W1BJ: IP20 Connector
PMC Panel Mount Power Supply 12V 150W 1 Phase / PMC-12V150W1B□ All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2020, Rev. 04) Dimensions PMC-12V150W1BA: Terminal Block L x W x H: 178 x 97 x 38 mm (7.01 x 3.82 x 1.50 inch) PMC-12V150W1BJ: IP20 Connector L x W x H: 178 x 97 x 38 mm (7.01 x 3.82 x 1.50 inch)
PMC Panel Mount Power Supply 12V 150W 1 Phase / PMC-12V150W1B□ All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2020, Rev. 04) PMC-12V150W1BL: Front Face L x W x H: 178 x 97 x 38 mm (7.01 x 3.82 x 1.50 inch) Engineering Data Output Load De-rating VS Surrounding Air Temperature Fig. 1 De-rating for Vertical and Horizontal Mounting Orientation > 50°C de-rate power by 2.5% / °C Note 1. Power supply components may degrade, or be damaged, when the power supply is continuously used outside the shaded region, refer to the graph shown in Fig. 1. 2. If the output capacity is not reduced when the surrounding air temperature > 5 0°C, the device may run into Over Temperature Protection. When activated, the output voltage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as necessary to keep the device in working condition. 3. In order for the device to function in the manner intended, it is also necessary to keep a safety distance as recommended in the safety instructions while the device i s in operation. 4. Depending on the surrounding air temperature and output load delivered by the power supply, the device housing can be very hot! 5. If the device has to be mounted in any other orientation, please do not hesitate to contact info@deltapsu.com for more details.
PMC Panel Mount Power Supply 12V 150W 1 Phase / PMC-12V150W1B□ All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2020, Rev. 04) De-rating VS AC input voltage Assembly & Installation Mounting Ⓐ Mounting holes for power supply assembly onto the mounting surface. Power supply shall be mounted on minimum 2 mounting holes using M3 screw minimum 5 mm length. Ⓑ This surface belongs to customer’s end system or panel where the power supply is mounted. Ⓒ Connector. Side Mounting (Vertical) Base Mounting (Vertical) Side Mounting (Horizontal) Fig. 2 Recommended Mounting Orientations
- Use flexible cable (stranded or solid) with the following sizes: PMC-12V150W1BA PMC-12V150W1BJ PMC-12V150W1BL AWG 18-14 AWG 18-12 AWG 18-14 7mm. ■ No output power de-rating across the entire input voltage range
PMC Panel Mount Power Supply 12V 150W 1 Phase / PMC-12V150W1B□ All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2020, Rev. 04) Installation Safety Instructions Accessories L-02: Latch P-03: Bracket These accessories are used to mount the panel mount power supply onto a DIN rail. Only use M3 screw ≤ 6 mm (0.23 inch) through the base mounting holes. This is to keep a safe distance between the screw and internal components.
- To ensure sufficient convection cooling, always maintain a safety distance of >20mm (0.78 inch) from all ventilated surfaces while the device is in operation.
- The device is not recommended to be placed on low thermal conductive surface, for example, plastics.
- Note that the enclosure of the device can become very hot depending on the ambient temperature and load of the power supply. Do not touch the device while it is in operation or immediately after power is turned OFF. Risk of burning!
- Do not touch the terminals while power is being supplied. Risk of electric shock.
- Prevent any foreign metal, particles or conductors to enter the device through the openings during installation. It can cause: Electric shock; Safety Hazard; Fire; Product failure
- Warning: When connecting the device, secure Earth connection before connecting L and N. When disconnecting the device, remove L and N connections before removing the Earth connection.
PMC Panel Mount Power Supply 12V 150W 1 Phase / PMC-12V150W1B□ All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2020, Rev. 04) Functions ■ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time Start-up Time The time required for the output voltage to reach 90% of its set value, after the input voltage is applied. Rise Time The time required for the output voltage to change from 10% to 90% of its set value. Hold-up Time Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time required for the output to reach 95% of its set value, after the input voltage is removed. Inrush Current Inrush Current is the first surge current seen on the input side when AC input is applied to the power supply. It is the first pulse captured; see a typical picture for the inrush current as seen in the power supply. Dynamic Response The power supply output voltage will remains within ±5% of its steady state value, when subjected to a dynamic load from 0% to 100% of its rated current.
PMC Panel Mount Power Supply 12V 150W 1 Phase / PMC-12V150W1B□ All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2020, Rev. 04) Overload & Overcurrent Protections (Auto-Recovery) The power supply’s Overload (OLP) and Over current (OCP) Protections will be activated when output current (I O) exceeds its specification as defined on Page 3 under “Protections. In such occurrence, the output voltage (VO) will start to droop and once the power supply has reached its maximum power limit, the protection is activated and the power supply will go into “Hiccup mode” (Auto- Recovery). The power supply will recover once the fault condition of the OLP and OCP is removed and I O is back within the specifications. It is not recommended to prolong the duration of I O when it is less than OLP/OCP point, but greater than 100%, since it may cause damage to the PSU. Short Circuit Protection (Auto-Recovery) The power supply’s output OLP/OCP function also provides protection against short circuits. When a short circuit is applied, the output current will operate in “Hiccup mode”, as shown in the illustration in the OLP/OCP section on this page. The power supply will return to normal operation after the short circuit is removed. Overvoltage Protection (Auto-Recovery) The power supply’s overvoltage circuit will be activated when its internal feedback circuit fails. The output voltage shall not exceed its specifications defined on Page 3 under “Protections”. Over Temperature Protection (Auto-Recovery) As mentioned above, the power supply also has Over Temperature Protection (OTP). This is activated when the overload condition persists for an extended duration and the output current is below the overload trigger point but >100% load. In the event of a higher operating condition at 100% load, the power supply will run into OTP when the surrounding air temperature is >75°C . When activated, the output voltage will go into bouncing mode until the operating surrounding temperature drops to 50°C or output capacity is reduced as recommended in the de-rating graph.
PMC Panel Mount Power Supply 12V 150W 1 Phase / PMC-12V150W1B□ All parameters are specified at 25°C ambient and AC input unless otherwise indicated. www.DeltaPSU.com (November 2020, Rev. 04) Others PFC – Norm EN 61000-3-2 Line Current harmonic Typically, the input current waveform is not sinusoidal due to the periodical peak charging of the input capacitor. In industrial environment, complying with EN 61000-3-2 is only necessary under special conditions. Complying to this standard can have some technical drawbacks, such as lower efficiency as well as some commercial aspects such as higher purchasing costs, Frequently, the user does not profit form fulfilling this standard, therefore, it is important to know whether it is mandatory to meet this standard for a specific application. This product conforms to this standard. Attention Delta provides all information in the datasheets on an “AS IS” basis and does not offer any kind of warranty through the information for using the product. In the event of any discrepancy between the information in the catalog and datasheets, the datasheet s shall prevail (please refer to www.DeltaPSU.com for the latest datasheets information). Delta shall have no liability of indemnification for any claim or action arising from any error for the provided information in the datasheets. Customer shall take its responsibility for evaluation of using the product before placing an order with Delta. Delta reserves the right to make changes to the information described in the datasheets without notice.