PM5000 SCHNEIDER | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 14
Technical content
The PowerLogic™ PM5000 series power meters are the new benchmark in affordable, precision metering. The value you want, the precision you need. Compact, affordable power meters with high-end cost capabilities and basic mobile energy management. PowerLogic™ PM5000 series Technical Datasheet
Applications
Capable of essential cost management:
- Sub-billing/tenant metering (+1)
- Equipment sub-billing
- Energy cost allocation Also ideal for electrical network management:
- Track real-time power conditions
- Monitor control functions
- Provide basic power quality values
- Detect and capture voltage sag and swell events
- Monitor residual current
- Analyze equipment and network status
- BACnet/IP , EtherNet/IP , and DNP3.0 protocol support PB118061 METSEPM5760 (+1) Subjected to local regulations. BASIC MULTI-FUNCTION METERING FUNCTIONS AND CHARACTERISTICS Version: 1.0 - 04/02/2023 PLSED310052EN
Markets that can benefit from a solution that includes PowerLogic™ PM5000 series meters:
- Buildings
- Industry
- Healthcare
- Data Center and networks
- Infrastructure Power management solutions Schneider Electric provides innovative power management solutions to increase your energy efficiency and cost savings, maximize electrical network reliability and availability , and optimize electrical asset performance. Competitive advantages
- Easy to install and operate
- Easy for circuit breaker monitoring and control
- WAGES monitoring
- Data logging up to 16 parameters
- Power quality analysis up to 63rd harmonics
- Load management combined with alarm and timestamping
- High performance and accuracy
- Residual Current Monitoring (RCM) in PM56xx(+4) and PM57xx(+4)
- Voltage sag and swell detection with waveform capture
- MID ready compliance for legal billing application
- Onboard BACnet/IP , EtherNet/IP , and DNP3.0 protocol support
- PM5310R (+3) and PM5320R (+3) are enabled to connect with LVCT for faster installations Conformity of standardsBenefits System integrators’ benefit
- Ease of integration
- Ease of setup
- Cost effectiveness Panel builders’ benefit
- Ease of installation
- Cost effectiveness
- Aesthetically pleasing
- Simplified ordering
- Low Voltage DC control power option
- Analog inputs options End users’ benefit
- Ease of use
- Precision metering & sub-billing (+2)
- Billing flexibility
- Comprehensive, consistent and superior performance
- Maximize uptime, eliminate faults, and enhance safety
- Cybersecurity features (+2) Subjected to local regulations. (+3) PM5310R and PM5320R must be used with Schneider Electric’s “Quick Click” 3-in-1 LVCTs. (+4) PM5660, PM5661, PM5760, PM5761 must be used with Toroids.
- BS/EN/IEC 61557-12:2018/ AMD1:2021
- BS/EN/IEC 62052-11:2020 edition 2
- IEC 62052-31:2015
- BS/EN/IEC 62053-22:2020 edition 2
- BS/EN/IEC 62053-23:2020 edition 2
- IEEE 802.3
- EN 50470-1:2006
- EN 50470- 3:2006
- CE and UKCA as per IEC/BS 61010-1 edition 3
- cULus as per UL 61010-1 edition 3
- BS/EN/IEC 61010-2-30:2017
- BS/EN/IEC 61326-1: edition 3
- FCC part 15 Class B
- EN 55022 Class B
- BACnet/IP - BTL listed (B-ASC)
- EtherNet/IP - ODVA certified
- ANSI C12.1-2008 (PM55xx)
- ANSI C12.20 Class 0.2 & 0.5
- Align with cyber security guidelines as per IEC 62443
- Type A as per IEC 62020 for RCM Certified according to MID Directive, Annex "B" + Annex "D" for legal metrology relevant to active electrical energy meters (see Annex MI-003 of MID). Can be used for fiscal (legal) metrology. MID MID ready compliance, EN 50470-1/3 – Class C Meets IEC 61557-12 PMD/[SD|SS]/K70/0.5 for PM5100 and PM5300 Meets IEC 61557-12 PMD/[SD|SS]/K70/0.2 for PM5500, PM5600, PM5700
- Legal billing compliance – MID compliance is compulsory for billing applications across Europe – In addition to billing applications, for facility managers responsible for energy cost – MID means same level of quality as a billing meter BASIC MULTI-FUNCTION METERING FUNCTIONS AND CHARACTERISTICS Version: 1.0 - 04/02/2023 PLSED310052EN
PowerLogic™ PM5100, PM5300 and PM5500 series The PowerLogic™ PM5000 power meter is the ideal fit for cost management applications. Designed for use in both energy management systems and building management systems, it provides the measurement capabilities needed to allocate energy usage, perform tenant metering and sub- billing, pin-point energy savings, optimize equipment efficiency and utilization, and perform a high level assessment of the power quality of the electrical network. In a single 96 x 96 mm unit, with a graphical display , (plus optional remote display) all three phases, neutral and ground can be monitored simultaneously . The bright, anti-glare display features large characters and powerful backlighting for easy reading even in extreme lighting conditions and viewing angles. Easy to understand menus, text in 8 selectable languages, icons and graphics create a friendly environment to learn about your electrical network. Ethernet gateway and enhanced cyber security . These are highly accurate devices with global billing certifications.
- Cost management: Cost saving opportunities become clear once you understand how and when your facility uses electricity . The PowerLogic™ PM5000 series meters are ideal for: – Sub-billing / tenant metering: Allows a landlord, property management firm, condominium association, homeowners association, or other multi-tenant property to bill tenants for individual measured utility (electricity) usage depending on the local regulations. MID approved meters for billing applications across Europe. – Cost allocation: Allocate energy costs between different departments (HVAC, indoor and outdoor lighting, refrigeration, etc.), different parts of an industrial process or different cost centres. Cost allocation systems can help you save money by making changes to your operation, better maintaining your equipment, taking advantage of pricing fluctuations, and managing your demand.
- Network management: Improving reliability of the electrical network is key for success in any business. Monitoring values such as voltage levels, harmonics distortions, voltage unbalance, residual current, voltage sag and swell will help you to ensure proper operation and maintenance of your electrical network and equipment. PowerLogic™ PM5000 series meters are the perfect tool for: – Basic Power Quality monitoring: Power quality phenomena can cause undesirable effects such as heating in transformers, capacitors, motors, generators and misoperation of electronic equipment and protection devices. – Min/ Max monitoring (with timestamp): Understanding when electrical parameters, such as voltage, current and power demand, reach maximum and minimum values will give you the insight to correctly maintain your electrical network and assure equipment will not be damaged. – Alarming: alarms help you to be aware of any abnormal behaviour on the electrical network in the moment it happens. – WAGES monitoring: take advantage of the input metering on PM5000 meters to integrate measurements from third party devices such as water , air , gas, electricity or steam meters. – Residual current monitoring: measures leakage current flowing in TN & TT network system. – Voltage sags and swells: measures and captures wave form in the event of voltage sags and swells in the network.
- Main characteristics – Easy to install – Mounts using two clips, in standard cut out for DIN 96 x 96 mm, no tools required. Compact meter with 72 mm (77 mm for PM5500) depth connectable up to 690 V L-L without voltage transformers for installations compliant with category III. Optional remote display (PM5563). Ethernet gateway functionality via RS-485 port. – Easy to operate – Intuitive navigation with self-guided, language selectable menus, six lines, four concurrent values. Two LEDs on the meter face help the user confirm normal operation with a green LED - heartbeat/communications indicator , and the amber LED - customizable either for alarms or energy pulse outputs. Onboard web pages (PM5500) show real-time and logged information, and verify communications. – Easy circuit breaker monitoring and control – The PM5300 provides two relay outputs (high performance Form A type) with capability to command most of the circuit breaker coils directly . For Digital Inputs, monitored switches can be wired directly to the meter without external power supply by using whetting output voltage. – PM5500 series have 4 status inputs (digital) and 2 digital output (solid state) to use for WAGES monitoring, control and alarm annunciation. Accurate energy measurement for precise cost allocation: PM5100 PM5300 PM5500 PM5600 PM5700 PowerLogic™ PM5563 remote display rear ISO PowerLogic™ PM5563 remote display front ISO PowerLogic™ PM5563 meter PM5000 seriesPB118063PB118064 PB118062 BASIC MULTI-FUNCTION METERING FUNCTIONS AND CHARACTERISTICS Version: 1.0 - 04/02/2023 PLSED310052EN
*Applicable in specific meter models. 2 alarms for disturbance (Sag/ Swell). – Alarms can be visualized as Active (the ones that have picked up and did not drop out yet) or Historical (the ones that happened in the past). Alarms can be programmed and combined to trigger digital outputs and mechanical relays (PM5300). – The PM5000 series keeps an alarm log with the active and historical alarms with date and time stamping. SMTP protocol for receiving alarm conditions via email and text. SNTP protocol for date/time network synchronization.
- Load timer – A load timer can be set to count load running hours based on a minimum current withdraw, adjustable to monitor and advise maintenance requirements on the load.
- High Performance and accuracy – IEC 61557-12 Performance measuring and monitoring devices (PMD). Defines the performance expectation based on classes. It defines the allowable error in the class for real and reactive power and energy , frequency , current, voltage, power factor , voltage unbalance, voltage and current harmonics (odds), voltage THD, current THD, as well as ratings for temperature, relative humidity , altitude, start-up current and safety . It makes compliant meters readings comparable - they will measure the same values when connected to the same load. – These types of power quality parameters help to identify the source of harmonics that can harm transformers, capacitors, generators, motors and electronic equipment.
- Load management – Peak demands with time stamping are provided. Predicted demand values can be used in combination with alarms for basic load shedding applications.
- Alarming with time stamping – A different combination of set point driven alarms and digital alarms with 1s time stamping are available in the PM5000 family: Native multi-protocol support The PM55/PM56/PM5700 is now easier than ever to integrate into new and existing BMS systems. With native BACnet/IP protocol support, meters can simultaneously communicate via BACnet and Modbus in applications where multiple software systems are used (building management and energy management systems). The PM55/PM56/PM5700 series has been tested and certified in accordance with BACnet Testing Laboratories (BTL) requirements and Ethernet IP protocol as per ODVA requirements.
- PM55/PM56/PM5700 Direct metering of neutral current – The PM55/PM56/PM5700 has a fourth CT for measuring neutral current. In demanding IT applications, where loads are non-linear (i.e. switching power supplies on computers/servers), measuring neutral current is essential to avoid overload and resulting outage. – Power Quality analysis – The PM5000 offers Total Harmonic Distortion (THD/thd), Total Demand – Distortion (TDD) measurements and individual harmonics (odd) magnitudes and angles for voltage and current: PM5100 PM5300 PM55/56/5700 Individual Harmonics magnitudes up to 15th magnitudes up to 31st magnitudes & angles up to 63rd PM5100 PM5300 PM55/56/5700 Set point driven alarms 29 29 29 or 33* Unary 4 4 4 Digital – 2 4 or 2 Boolean / Logic – – 10 Custom defined – – 5 PowerLogic™ PM5500 meter PowerLogic™ PM5300 meter PowerLogic™ PM5100 meter PM5000 series PB111777PB111772PB111768 BASIC MULTI-FUNCTION METERING FUNCTIONS AND CHARACTERISTICS Version: 1.0 - 04/02/2023 PLSED310052EN
PM5000 series feature selection PM5100 PM5300 PM5100 PM5110 PM5310 PM5310R (+5) PM5320 PM5320R (+5) PM5330 PM5340 Installation Fast installation, panel mount with integrated display b b b b b b b b Fast installation, DIN rail Accuracy Display Backlit LCD, multilingual, bar graphs, 6 lines, 4 concurrent values b b b b b b b b Power and energy metering 3-ph voltage, current, power , demand, energy , frequency , power factor b b b b b b b b Multi-tariff – – 4 4 4 4 4 4 MID ready compliance, EN50470-1/3, Annex B & Annex D Class C – PM5111 – – – – PM5331 PM5341 Power quality analysis THD, thd, TDD b b b b b b b b Harmonics, individual (odd) up to 15th 15th 31st 31st 31st 31st 31st 31st Waveform capture & sag/ I/Os and relays Digital inputs/ Digital output 1DO 1DO 2DI/2DO 2DI/2DO 2DI/2DO 2DI/2DO 2DI/2DO 2DI/2DO Alarms and control Alarms 33 33 35 35 35 35 35 35 Set point response time, seconds 1 1 1 1 1 1 1 1 Single and multi-condition alarms – – b b b b b b Memory for data logging – – 256KB 256KB 256KB 256KB 256KB 256KB Communications Serial ports with modbus protocol – 1 1 1 – – 1 – Ethernet port with Modbus TCP protocol – – – – 1 1 – 1 BACnet/IP protocol – – – – b b – b Onboard web server with Serial to Ethernet gateway – – – – – – – – Ref. number followed with METSE* PM5100 PM5110 PM5310 PM5310R (+5) PM5320 PM5320R (+5) PM5330 PM5340 *See table below for complete commercial reference numbers (+5) PM5310R and PM5320R must be used with Schneider Electric’s “Quick Click” 3-in-1 LVCTs PM5000 series BASIC MULTI-FUNCTION METERING FUNCTIONS AND CHARACTERISTICS Version: 1.0 - 04/02/2023 PLSED310052EN
(+6) 2 Ethernet ports for daisy chain, one IP address. PM5000 series feature selection PM5500 PM5600 PM5700 PM5560 PM5563 PM5563RD PM5570 PM5580 PM5650 PM5660 PM5760 Installation Fast installation, panel mount with integrated display b – – b b b b b Fast installation, DIN rail Accuracy Display Backlit LCD, multilingual, bar graphs, 6 lines, 4 concurrent values b – b b b b b b Power and energy metering 3-ph voltage, current, power , demand, energy , frequency , power factor b b b b b b b b Multi-tariff 8 8 8 8 8 8 8 8 MID ready compliance, EN50470-1/3, Annex B & Annex D Class C PM5561 – – – – – PM5661 PM5761 Power quality analysis THD, thd, TDD b b b b b b b b Harmonics, individual (odd) up to 63rd 63rd 63rd 63rd 63rd 63rd 63rd 63rd Waveform capture & sag/ swell detection – – – – – 8 cycles @ 128 samples/cycle – 8 cycles @ 128 samples/cycle I/Os and relays Digital inputs/ solid state Digital output 4DI/2DO 4DI/2DO 4DI/2DO 2DI/2DO 4DI/2DO 4DI/2DO 2DI/2DO 2DI/2DO Residual Current inputs – – – – – – 2 2 Alarms and control Alarms 52 52 52 50 52 54 54 56 Set point response time, seconds 1 1 1 1 1 1 1 1 Single and multi-condition alarms b b b b b b b b Boolean alarm logic b b b b b b b b Communications Serial ports with modbus protocol 1 1 1 1 1 1 1 1 Ethernet port with Modbus BACnet/IP protocol b b b b b b b b EtherNet/IP protocol b b b b b b b b DNP3.0 over Ethernet b b b b b b b b Onboard web server with web pages b b b b b b b b Serial to Ethernet gateway b b b b b b b b Ref. numbers with METSE* PM5560 PM5563 PM5563RD PM5570 PM5580 PM5650 PM5660 PM5760 *See table below for complete commercial reference numbers BASIC MULTI-FUNCTION METERING FUNCTIONS AND CHARACTERISTICS Version: 1.0 - 04/02/2023 PLSED310052EN
PM5000 technical specifications PM5100 PM5300 PM5500 PM5600 PM5700 Use on LV and MV systems b Basic metering with THD and min/max readings b Instantaneous rms values Current Average, per phase, neutral and ground (PM5500) b Voltage Average, per phase L–L and L–N b Frequency Any available phase b Real, reactive, and apparent power Total and per phase Signed, Four Quadrant True Power Factor Average and per phase Signed, Four Quadrant Displacement PF Average and per phase Signed, Four Quadrant % Unbalanced I, V L-N, V L-L b Direct monitoring of neutral current – b b b Energy values Accumulated Active, Reactive and Apparent Energy Received/Delivered; Net and absolute; Time Counters Demand value Current average Present, Last, Predicted, Peak, and Peak Date Time Active power Present, Last, Predicted, Peak, and Peak Date Time Reactive power Present, Last, Predicted, Peak, and Peak Date Time Apparent power Present, Last, Predicted, Peak, and Peak Date Time Peak demand with timestamping D/T for current and three powers b Demand calculation Sliding, fixed and rolling block, thermal methods b Synchronisation of the measurement window to input, communication command or internal clock b Settable Demand intervals b Demand synchronization with pulse input – b Other measurements I/O timer b Operating timer b Load timer b Alarm counters and alarm logs b Power quality measurements THD, thd (Total Harmonic Distortion) I, V L-N, V L-L I, V L-N, V L-L TDD (Total Demand Distortion) b Individual harmonics (odds) 15th (PM5110) 31st 63rd Neutral Current metering with ground current calculation – – b Waveform capture and sag/swell detection – – – 8 cycles @ 128 samples/cycle Data recording Min/max of instantaneous values, plus phase identification (+7) b Alarms with 1s timestamping (+7) b Data logging 2 fixed parameters kWh and kVAh with configurable interval & duration (e.g. 2 parameters for minimum 60 days at 15–minute intervals) Up to 14 selectable parameters with configurable interval and duration (e.g. 6 parameters for minimum 90 days at 15–minute intervals) Min/max log b b b Maintenance, alarm and event logs b b Customisable data logs – b RTC with battery back up 3 years (when meter is in Power OFF condition) Display resolution 5 digits for Energy and other parameters with auto scaling Preset Energy and Energy scaling Available in selected references PM5000 series (+7) Stored in non-volatile memory BASIC MULTI-FUNCTION METERING FUNCTIONS AND CHARACTERISTICS Version: 1.0 - 04/02/2023 PLSED310052EN
PM5000 technical specifications PM5100 PM5300 PM5500 PM5600 PM5700 Inputs / Outputs / Mechanical Relays Digital inputs – 2 4 in PM5560, PM5561, PM5562, PM5563, PM5580, PM5650 2 in PM5570, PM5660, PM5661, PM5760, PM5761 Digital outputs 1 (kWh only) 2 2 (Solid state) Form A Relay outputs – 2 – Analog inputs – – 2 for PM5570 – – Residual Current inputs – – 2 for PM5660 2 for PM5760 Timestamp resolution in seconds 1 1 1 1 1 Whetting source – 24 V DC, 8 mA – – – Type of measurement: True rms on three-phase (3P , 3P + N) 64 samples per cycle 128 samples per cycle Measurement accuracy IEC 61557-12 PMD/[SD|SS]/K70/0.5 PMD/[SD|SS]/K70/0.2 Active Energy Class 0.5S as per IEC 62053-22/ Class 0.5 as per IEC 61557-12/ ± 0.5% Class 0.2S as per IEC 62053-22/ Class 0.2 as per IEC 61557-12/ ± 0.2% Reactive Energy Class 2 as per IEC 62053-23/ Class 1.0 as per IEC 61557-12/ ± 1.0% Class 2 as per IEC 62053-23/ Class 1.0 as per IEC 61557-12/ ± 1.0% Active Power Class 0.5 as per IEC 61557-12/ ± 0.5% Class 0.2 as per IEC 61557-12/ ± 0.2% Apparent Power Class 0.5 as per IEC 61557-12/ ± 0.5% Class 0.5 as per IEC 61557-12/ ± 0.5% Reactive Power Class 1.0 as per IEC 61557-12/ ± 1.0% Class 1.0 as per IEC 61557-12/ ± 1.0% Current, Phase Class 0.5 as per IEC 61557-12/ ±0.5 % Class 0.2 as per IEC 61557-12/ ±0.15 % Voltage, L-N Class 0.5 as per IEC 61557-12/ ± 0.5 % Class 0.2 as per IEC 61557-12/ ± 0.1 % Frequency Class 0.05 as per IEC 61557-12/ ±0.05 % Class 0.05 as per IEC 61557-12/ ±0.05 % Power Factor Class 0.5 as per IEC 61557-12/ ±0.005 count Class 0.5 as per IEC 61557-12/ ±0.005 count Voltage unbalance Class 5/ ±5% Class 2/ ±2% Voltage harmonics Class 5/ ±5% Class 2/ ±2% Voltage THD Class Class 5/ ±5% Class 2/ ±2% Current harmonics Class 5/ ±5% Class 2/ ±2% Current THD Class Class 5/ ±5% Class 2/ ±2% MID Directive EN50470-1, EN50470-3 Annex B and Annex D (Optional model references) Class C Input-voltage (up to 1.0 MV AC max, with voltage transformer) Nominal Measured Voltage range
20 V L-N / 35 V L-L to 400 V L-N /690 V L-L
absolute range 35 V L-L to 760 V L-L
20 V L-N / 20 V L-L to 400 V L-N /690 V L-L
absolute range 20 V L-L to 828 V L-L Impedance 5 MΩ Frequency nominal 50 or 60 Hz ±5 % 50 or 60 Hz ±10 % Input-current (configurable for 1 or 5 A secondary CTs) I nominal 5 A – Measured Amps with over range Starting current: 5 mA Operating range: 50 mA to 8.5 A Starting current: 5 mA Operating range: 50 mA to 10 A (with Crest Factor) Withstand Continuous 20 A, 10 s/hr 50 A, 1 s/hr 500 A Impedance < 0.3 mΩ Frequency nominal 50 or 60 Hz ±5 % 50 or 60 Hz ±10 % Burden <0.026 VA at 8.5 A AC control power Operating range 100 - 277 V AC L-N / 415 V L-L +/-10 % CAT III 300V class per IEC 61010 100-480 V AC ±10 % CAT III 600V class per IEC 61010 Burden <5 W,11 VA at 415V L-L <5W/16.0 VA at 480 V AC Frequency 45 to 65 Hz Ride through time at maximum burden 80 mS typical at 120V AC 100 mS typical at 230 V AC 100 mS typical at 415 V AC 35 ms typical at 120 V L-N 129 ms typical at 230 V L-N DC control power Operating range 125–250 V DC ±20 % (100 to 300 V DC) Burden <4 W at 250 V DC typical 3.1 W at 125 V DC, max. 5 W Ride-through time 50 mS typical at 125 V DC and maximum burden LV DC control power 20-60 V DC ±10 % CAT III Burden 4.1 W max. – – b PM5580 – – PM5000 series BASIC MULTI-FUNCTION METERING FUNCTIONS AND CHARACTERISTICS Version: 1.0 - 04/02/2023 PLSED310052EN
PM5000 technical specifications PM5100 PM5300 PM5500 PM5600 PM5700 Outputs Relay outputs Max output frequency –
0.5 Hz maximum
(1 s ON / 1 s OFF - min times) – – – Switching current, at resistive load – 250 V AC at 8.0 Amps, 25 k cycles 30 V DC at 2.0 Amps, 75 k cycles 30 V DC at 5.0 Amps, 12.5 k cycles – – – Isolation – 2.5 kV rms – – – Digital outputs Max load voltage 40 V DC 40 V AC / 60 V DC (PM5500 and PM 5650)
30 V AC / 40 V DC (PM5660, PM5661, PM5760, PM5761)
Max load current 20 mA 125 mA (Solid state) On Resistance 50 Ω max 8 Ω Meter constant from 1 to 9,999,999 pulses per k_h (kWh, kVAh, kVARh) Pulse width for Digital Output 50 % duty cycle Pulse frequency for Digital Output 25 Hz max. Leakage current 0.3 micro Amps 1 micro Amps Isolation 5 kV rms 2.5 kV rms for 60 s Optical outputs Pulse width (LED) 200 ms Pulse frequency 2.5 kHz. max 2.5 kHz. max Meter constant from 1 to 9,999,999 pulses per k_h (kWh, kVAh, kVARh) Status Inputs ON Voltage – 18.5 to 36 V DC 15 to 30 V AC / 15 to 60 V DC max OFF Voltage – 0 to 4 V DC 0 to 6 V AC / 0 to 6 V DC Input Resistance – 110 k Ω 100 k Ω Maximum Frequency –
2 Hz (T ON min =
T OFF min = 250 ms)
25 Hz (T ON min = T OFF min = 20 ms)
Response Time – 20 ms 10 ms Opto Isolation – 5 kV rms 2.5 kV rms for 60 s Whetting output – 24 V DC/ 8 mA max - Input Burden – 2 mA @24V DC 2 mA @ 24 V AC/DC 2.5 mA @ 60 V AC/DC Analog inputs (PM5570) – 4 - 20 mA DC (nominal), Accuracy: 1% of full-scale reading, Impedance < 20 Ω, Operating voltage:
24 V DC max
(PM5660, PM5661, PM5760, PM5761) Type A as per IEC 62020 5 uA to 1200 uA (nominal), 1500 uA max (continuous), Input type: AC 45 to 65 Hz, Burden: 150 Ω, Default toroid: 1000 turns Mechanical characteristics Product weight 380 g 430 g 450 g 450 g 450 g IP degree of protection (IEC 60529) IP54 front display , IP30 rear side (IP65 front side with Optional accessory kit METSEIP65OP96X96FF) Dimensions W x H x D [protrusion from cabinet] 96 x 96 x 72 mm (77 mm for PM5500) (depth of meter from housing mounting flange) [13 mm] Mounting position Vertical Panel thickness 6 mm maximum LVCT (+8) inputs for PM5310R and PM5320R - Nominal voltage of 0.333V Measurement range - 0.00333V - 0.4V - - - PM5000 series (+8) PM5310R and PM5320R must be used with Schneider Electric’s “Quick Click” 3-in-1 LVCTs BASIC MULTI-FUNCTION METERING FUNCTIONS AND CHARACTERISTICS Version: 1.0 - 04/02/2023 PLSED310052EN
PM5000 technical specifications PM5100 PM5300 PM5500 PM5600 PM5700 Environmental characteristics Operating temperature Operating temperature -25 °C to 70 °C Display (reduced display performance at -25 º C) -25 °C to 70 °C Storage temperature -40 °C to 85 °C Humidity range 5 to 95 % RH at 50 °C (non-condensing) Pollution degree 2 Altitude 2000 m CAT III / 3000 m CAT II 3000 m max. CAT III Mission profile / Life span >15 years Protective treatment Conformal coating Electromagnetic compatibility Harmonic current emissions – – IEC 61000-3-2 Flicker emissions – – IEC 61000-3-3 Electrostatic discharge IEC 61000-4-2 Immunity to radiated fields IEC 61000-4-3 Immunity to fast transients IEC 61000-4-4 Immunity to surge IEC 61000-4-5 Conducted immunity 150 kHz to 80 MHz IEC 61000-4-6 Immunity to magnetic fields IEC 61000-4-8 Immunity to voltage dips IEC 61000-4-11 Immunity to damped oscillatory waves – – IEC 61000-4-12 Radiated and conducted emissions FCC part 15, EN 55022 Class B Safety Europe CE, as per IEC 61010-1 Ed. 3, IEC 62052-11 & IEC 61557-12 U.S. and Canada cULus as per UL 61010-1 (Edition 3) Measurement category (Voltage & Current inputs) CAT III up to 400 V L-N / 690 V L-L Dielectric As per IEC/UL 61010-1 (Edition 3) Protective Class II, Double insulated for user accessible parts Communication RS-485 port Modbus RTU, Modbus ASCII (7 or 8 bit), JBUS 2-Wire, 9600,19200 or 38400 baud, Parity - Even, Odd, None, 1 stop bit if parity Odd or Even, 2 stop bits if None; (Optional in PM51x and PM53x) Ethernet port: 10/100 Mbps; Modbus TCP/IP – 1 Optional 2 (daisy chain only , 1 IP address) Native Ethernet/IP & DNP3.0 over Ethernet – – Yes Yes Yes FTP / FTPS – – Yes Yes Yes SNMP , SNTP , SMTP – – Yes Yes Yes HTTPS – – Yes Yes Yes Firmware and language file update Meter firmware update via the communication ports Isolation 2.5 kVrms, double insulated Human machine interface Display type Monochrome Graphics LCD Resolution 128 x 128 pixels Backlight White LED Viewable area (W x H) 67 x 62.5 mm Keypad 4-button Indicator Heartbeat / Communication activity Green LED Energy pulse output / Active alarm (configurable) Optical, amber LED Wavelength 590 to 635 nm Maximum pulse rate 2.5 kHz BASIC MULTI-FUNCTION METERING FUNCTIONS AND CHARACTERISTICS Version: 1.0 - 04/02/2023 PLSED310052EN
Comm. ref numbers Description METSEPM5100 Power Meter , 600V AC L-L/ 5A or 1A input, 415V AC L-L or 250V DC control power , Cl 0.5S, 15th harmonic, 1DO METSEPM5110 Power Meter , 600V AC L-L/ 5A or 1A input, 415V AC L-L or 250V DC control power , Cl 0.5S, 15th harmonic, 1DO, RS-485 METSEPM5111 Power Meter , 600V AC L-L/ 5A or 1A input, 415V AC L-L or 250V DC control power , Cl 0.5S, 15th harmonic, 1DO, RS-485, MID METSEPM5310 Power Meter , 600V AC L-L/ 5A or 1A input, 415V AC L-L or 250V DC control power , Cl 0.5S, 31st harmonic, 256 kB, 2DI/2DO, RS-485 METSEPM5310R Power Meter , 600V AC L-L/ RJ45 LVCT input, 415V AC L-L or 250V DC control power , Cl 0.5S, 31st harmonic, 256 kB, 2DI/2DO, RS-485 METSEPM5320 Power Meter , 600V AC L-L/ 5A or 1A input, 415V AC L-L or 250V DC control power , Cl 0.5S, 31st harmonic, 256 kB, 2DI/2DO, Ethernet METSEPM5320R Power Meter , 600V AC L-L/ RJ45 LVCT input, 415V AC L-L or 250V DC control power , Cl 0.5S, 31st harmonic, 256 kB, 2DI/2DO, Ethernet METSEPM5330 Power Meter , 600V AC L-L/ 5A or 1A input, 415V AC L-L or 250V DC control power , Cl 0.5S, 31st harmonic, 256 kB, 2DI/2DO/2-Relay , RS-485 METSEPM5331 Power Meter , 600V AC L-L/ 5A or 1A input, 415V AC L-L or 250V DC control power , Cl 0.5S, 31st harmonic, 256 kB, 2DI/2DO/2-Relay , RS-485, MID METSEPM5340 Power Meter , 600V AC L-L/ 5A or 1A input, 415V AC L-L or 250V DC control power , Cl 0.5S, 31st harmonic, 256 kB, 2DI/2DO/2-Relay , Ethernet METSEPM5341 Power Meter , 600V AC L-L/ 5A or 1A input, 415V AC L-L or 250V DC control power , Cl 0.5S, 31st harmonic, 256 kB, 2DI/2DO/2-Relay , Ethernet, MID METSEPM5560 Power Meter , 690V AC L-L/ 5A or 1A input, 480V AC L-L or 250V DC control power , Cl 0.2S, 63rd harmonic, 1.1 MB, 4DI/2-DO, RS-485, Ethernet METSEPM5561 Power Meter , 690V AC L-L/ 5A or 1A input, 480V AC L-L or 250V DC control power , Cl 0.2S, 63rd harmonic, 1.1 MB, 4DI/2-DO, RS-485, Ethernet, MID METSEPM5562 Power Meter , 690V AC L-L/ 5A or 1A input, 480V AC L-L or 250V DC control power , Cl 0.2S, 63rd harmonic, 1.1 MB, 4DI/2-DO, RS-485, Ethernet, RMI CAN approved, Hardware lockable METSEPM5562MC Power Meter , 690V AC L-L/ 5A or 1A input, 480V AC L-L or 250V DC control power , Cl 0.2S, 63rd harmonic, 1.1 MB, 4DI/2-DO, RS-485, Ethernet, RMI CAN approved, Factory sealed METSEPM5563 Power Meter , 690V AC L-L/ 5A or 1A input, 480V AC L-L or 250V DC control power , Cl 0.2S, 63rd harmonic, 1.1 MB, 4DI/2-DO, RS-485, Ethernet, DIN mount, No display METSEPM5563RD Power Meter , 690V AC L-L/ 5A or 1A input, 480V AC L-L or 250V DC control power , Cl 0.2S, 63rd harmonic, 1.1 MB, 4DI/2-DO, RS-485, Ethernet, DIN mount, Remote display METSEPM5570 Power Meter , 690V AC L-L/ 5A or 1A input, 480V AC L-L or 250V DC control power , Cl 0.2S, 63rd harmonic, 1.1 MB, 2DI/2AI/2-DO, RS-485, Ethernet METSEPM5580 Power Meter , 690V AC L-L/ 5A or 1A input, 24 to 64V DC control power , Cl 0.2S, 63rd harmonic, 1.1 MB, 4DI/2-DO, RS-485, Ethernet METSEPM5650 Power Meter , 690V AC L-L/ 5A or 1A input, 480V AC L-L or 250V DC control power , Cl 0.2S, 63rd harmonic, 1.1 MB, 4DI/2-DO, RS-485, Ethernet, Wave Form Capture and Sag/swell METSEPM5660 Power Meter , 690V AC L-L/ 5A or 1A input, 480V AC L-L or 250V DC control power , Cl 0.2S, 63rd harmonic, 1.1 MB, 2DI/2-DO, RS-485, Ethernet, Residual Current Monitor METSEPM5661 Power Meter , 690V AC L-L/ 5A or 1A input, 480V AC L-L or 250V DC control power , Cl 0.2S, 63rd harmonic, 1.1 MB, 2DI/2-DO, RS-485, Ethernet, Residual Current Monitor , MID METSEPM5760 Power Meter , 690V AC L-L/ 5A or 1A input, 480V AC L-L or 250V DC control power , Cl 0.2S, 63rd harmonic, 1.1 MB, 2DI/2-DO, RS-485, Ethernet, Wave Form Capture and Sag/swell, Residual current monitor METSEPM5761 Power Meter , 690V AC L-L/ 5A or 1A input, 480V AC L-L or 250V DC control power , Cl 0.2S, 63rd harmonic, 1.1 MB, 2DI/2-DO, RS-485, Ethernet, Wave Form Capture and Sag/swell, Residual current monitor , MID For selection of compatible current transformers with 5 A output in Schneider range: Refer PLSED310169EN in solid core and split core IEC type For Residual Current Monitoring Toroids (Vigirex) - Closed Toroids, A Type (applicable for PM5660, PM5661, PM5760, PM5761) 50437 TA30 - closed toroid A type, for RCM enabled power meters, 30 mm inner diameter , rated current 65 Amps, 1000 turns 50438 PA50 - closed toroid A type, for RCM enabled power meters, 50 mm inner diameter , rated current 85 Amps, 1000 turns 50439 IA80 - closed toroid A type, for RCM enabled power meters, 80 mm inner diameter , rated current 160 Amps, 1000 turns 50440 MA120 - closed toroid A type, for RCM enabled power meters, 120 mm inner diameter , rated current 250 Amps, 1000 turns 50441 SA200 - closed toroid A type, for RCM enabled power meters, 200 mm inner diameter , rated current 400 Amps, 1000 turns 50442 GA300 - closed toroid A type, for RCM enabled power meters, 300 mm inner diameter , rated current 630 Amps, 1000 turns Accessories for Closed Toroids (applicable for PM5660, PM5661, PM5760, PM5761)
56055 Magnetic ring/ Iron screen accessory for TA30 toroid sensor
56056 Magnetic ring/ Iron screen accessory for PA50 toroid sensor
56057 Magnetic ring/ Iron screen accessory for IA80 toroid sensor
56058 Magnetic ring/ Iron screen accessory for MA120 toroid sensor
Residual Current Monitoring Toroids (Vigirex) - Split Toroids, OA Type (applicable for PM5660, PM5661, PM5760, PM5761)
50420 TOA80 - split toroid OA type, 80 mm inner diameter , rated current 160 Amps, 1000 turns
50421 TOA120 - split toroid OA type, 120 mm inner diameter , rated current 250 Amps, 1000 turns
56053 L1 type - rectangular sensor , width 280 x height 115 mm, rated current 1600 Amps, 1000 turns
56054 L2 type - rectangular sensor , width 470 x height 160 mm, rated current 3200 Amps, 1000 turns
BASIC MULTI-FUNCTION METERING COMMERCIAL REFERENCE NUMBERS Version: 1.0 - 04/02/2023 PLSED310052EN
Please contact your Schneider Electric representative for complete ordering information. Comm. ref numbers Description 0.333V (1/3 Volts), 3-in-1 CTs with RJ45 connectors for PM53x0R LVCT enabled power meter METSECTV25006 LVCT Solid core 3 in 1 with RJ45 cable, 25 mm phase center , 60 Amps, 0.333V output METSECTV25010 LVCT Solid core 3 in 1 with RJ45 cable, 25 mm phase center , 100 Amps, 0.333V output METSECTV25013 LVCT Solid core 3 in 1 with RJ45 cable, 25 mm phase center , 125 Amps, 0.333V output METSECTV25016 LVCT Solid core 3 in 1 with RJ45 cable, 25 mm phase center , 160 Amps, 0.333V output METSECTV35006 LVCT Solid core 3 in 1 with RJ45 cable, 35 mm phase center , 60 Amps, 0.333V output METSECTV35010 LVCT Solid core 3 in 1 with RJ45 cable, 35 mm phase center , 100 Amps, 0.333V output METSECTV35012 LVCT Solid core 3 in 1 with RJ45 cable, 35 mm phase center , 120 Amps, 0.333V output METSECTV35013 LVCT Solid core 3 in 1 with RJ45 cable, 35 mm phase center , 125 Amps, 0.333V output METSECTV35015 LVCT Solid core 3 in 1 with RJ45 cable, 35 mm phase center , 150 Amps, 0.333V output METSECTV35016 LVCT Solid core 3 in 1 with RJ45 cable, 35 mm phase center , 160 Amps, 0.333V output METSECTV35020 LVCT Solid core 3 in 1 with RJ45 cable, 35 mm phase center , 200 Amps, 0.333V output METSECTV35025 LVCT Solid core 3 in 1 with RJ45 cable, 35 mm phase center , 250 Amps, 0.333V output METSECTV45025 LVCT Solid core 3 in 1 with RJ45 cable, 45 mm phase center , 250 Amps, 0.333V output METSECTV45030 LVCT Solid core 3 in 1 with RJ45 cable, 45 mm phase center , 300 Amps, 0.333V output METSECTV45040 LVCT Solid core 3 in 1 with RJ45 cable, 45 mm phase center , 400 Amps, 0.333V output METSECTV45050 LVCT Solid core 3 in 1 with RJ45 cable, 45 mm phase center , 500 Amps, 0.333V output METSECTV45060 LVCT Solid core 3 in 1 with RJ45 cable, 45 mm phase center , 600 Amps, 0.333V output METSECTV45063 LVCT Solid core 3 in 1 with RJ45 cable, 45 mm phase center , 630 Amps, 0.333V output METSECTV29006 LVCT Solid core 3 in 1 with RJ45 cable, 29 mm phase center , 60 Amps, 0.333V output METSECTV29010 LVCT Solid core 3 in 1 with RJ45 cable, 29 mm phase center , 100 Amps, 0.333V output METSECTV29012 LVCT Solid core 3 in 1 with RJ45 cable, 29 mm phase center , 120 Amps, 0.333V output METSECTV29013 LVCT Solid core 3 in 1 with RJ45 cable, 29 mm phase center , 125 Amps, 0.333V output METSECTV29015 LVCT Solid core 3 in 1 with RJ45 cable, 29 mm phase center , 150 Amps, 0.333V output METSECTV29016 LVCT Solid core 3 in 1 with RJ45 cable, 29 mm phase center , 160 Amps, 0.333V output METSECTV29020 LVCT Solid core 3 in 1 with RJ45 cable, 29 mm phase center , 200 Amps, 0.333V output METSECTV70080 LVCT Solid core 3 in 1 with RJ45 cable, 70 mm phase center , 800 Amps, 0.333V output METSECTV70100 LVCT Solid core 3 in 1 with RJ45 cable, 70 mm phase center , 1000 Amps, 0.333V output METSECTV70125 LVCT Solid core 3 in 1 with RJ45 cable, 70 mm phase center , 1250 Amps, 0.333V output Cables for PM5563 and PM5563RD METSEPM5CAB03 RJ25 cable assembly for interfacing PM5563 meter and PM5RD remote display with 0.3 meter cable length METSEPM5CAB1 RJ25 cable assembly for interfacing PM5563 meter and PM5RD remote display with 1.0 meter cable length METSEPM5CAB10 RJ25 cable assembly for interfacing PM5563 meter and PM5RD remote display with 10 meter cable length METSEPM5CAB3 RJ25 cable assembly for interfacing PM5563 meter and PM5RD remote display with 3 meter cable length METSEPM5CAB4 RJ25 cable assembly for interfacing PM5563 meter and PM5RD remote display with 4 meter cable length Other related products or accessories METSEPM5RD Remote display unit for PM5563 power meter supplied with mounting bracket, gasket, anti-rotation pin and RJ25 cable METSEPMCABxy METSEPM51HK Hardware kit for PM51xx comprises 2 retainer clips and spare connectors for - Voltage in, Control power in, Digital IO & RS-485 METSEPM53HK Hardware kit for PM51xx comprises 2 retainer clips and spare connectors for - Voltage in, Control power in, Digital IO, Relay & RS-485 METSEPM51_3RSK Revenue sealing kit for PM51XX & PM53XX METSEPM55RSK Revenue sealing kit for PM55XX METSEPM55HK Hardware kit for PM55xx Current Transformer commercial reference numbers for PM53xxR BASIC MULTI-FUNCTION METERING COMMERCIAL REFERENCE NUMBERS Version: 1.0 - 04/02/2023 PLSED310052EN
Please see the appropriate Installation Guide for accurate and complete information on the installation of this product. PM5100/PM5300 meter parts PM5500/PM5600/PM5700 meter parts PM5100/PM5300 Series meter mounting PM5000 series meter dimensions PM5500/PM5600/PM5700 series meter mounting PM5000 series overviewPB111278 DB445087 DB445086 DB445085 PB111277 PB111291 PM5000 series Menu selection buttons LED indicators Navigation or menu selections Maintenance and alarm notification area A B C D Relay output (PM5300 only) Voltage inputs Control power Current inputs Status inputs/digital outputs Communications port: Ethernet (PM5300 only) or RS-485) E F G H I J Voltage inputs RS-485 comms Digital inputs Current inputs Digital outputs Ethernet ports Control power E F G H I J K 101.2 (4.02) 91.5 (3.60) 91.5 (3.60) (2.99) 112 (4.40) PM5000 PM5100/PM5300 PM5500/PM5600/PM5700 (3.50) mm (in) (3.78) (3.78) 101.2 (4.02) 91.5 (3.60) (3.19) (3.70) CLIC K CLIC K< 6.4 (< 0.25) mm (in) CLAC K CLACK 92.0+0.8 (3.62)+0.03 92.0+0.8 (3.62)+0.03 CLIC K CLIC K CLAC K CLAC K < 6.4 (< 0.25) 92.0+0.8 (3.62)+0.03 92.0+0.8 (3.62)+0.03 mm (in) Current Transformer commercial reference numbers for PM53xxR BASIC MULTI-FUNCTION METERING DIMENSIONS AND CONNECTION Version: 1.0 - 04/02/2023 PLSED310052EN 13
Schneider Electric Industries SAS 35, Rue Joseph Monier CS 30323
92506 Rueil Malmaison Cedex
Capital social 928 298 512 € www.se.com February 2023 PowerLogic™ PM5000 series PLSED310052EN © 2023 - Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. As standards, specifications and designs develop from time to time, please ask for confirmation of the information given in this document. Over 75 % of Schneider Electric products have been awarded the Green Premium ecolabel. www.se.com