Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 6

Technical content

Features

 Built-in type identification automati- cally identifies this device as a monitor module to the control panel.  Powered directly by two-wire SLC loop. No additional power required.  High noise (EMF/RFI) immunity.  SEMS screws with clamping plates for ease of wiring.  Direct-dial entry of address: 01 –99  LED flashes green during normal operation (this is a programmable option) and latches on steady red to indicate alarm.  Built-in type identification automati- cally identifies this device as a monitor module to the panel. PID-SS  Powered directly by two-wire FACP . No additional power required.  High noise (EMF/RFI) immunity.  Tinned, stripped leads for ease of wiring.  Direct-dial entry of address: 01 – 99 CZI-SS  Supports compatible two-wire smoke detectors.  Supervises IDC wiring and connec- tion of external power source.  High noise (EMF/RFI) immunity.  SEMS screws with clamping plates for ease of wiring.  Direct-dial entry of address: 01 – 99  LED flashes during normal opera- tion (this is a programmable option).  LED latches steady to indicate alarm on command from control panel. Listings Listings and approvals below apply to the basic PIDP-SS, PID-SS, CZI-SS and DPID-SS monitor modules. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest status.  UL Listed: file S521.  CSFM approved: file 7300-1288:170. g2465mod.tif g2465duo.tif

PIDP-SS, PID-SS, CZI-SS, DPID-SS CS-2465 09/01/06Page 2 of 6 Specifications PIDP-SS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Maximum operating current: 375 µA (LED flashing). EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. PID-SS Nominal operating voltage: 15 to 32 VDC. Maximum operating current: 375 µA. EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x 0.5" (1.270 cm) deep. Wire length: 6" (15.24 cm) minimum. CZI-SS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Maximum operating current: 255 µA (LED flashing). EOL resistance: 3.9K ohms. External supply voltage (between Terminals T3 and T4): DC voltage: 18 to 28 volts power limited. Ripple volt- age: 0.1 V RMS maximum. Current: 90 mA per module maximum. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. DPID-SS Normal operating voltage range: 15 to 32 VDC. Maximum current draw: 5.7 mA (LED on). Maximum operating current: 750 µA (LED flashing). EOL resistance: 47K ohms. Maximum IDC wiring resistance: 1,500 ohms. Temperature range: 32° to 120°F (0° to 49°C). Humidity range: 10% to 93% (non-condensing). Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 2.125" (5.398 cm) deep. PID-SS Mini Monitor Module The PID-SS Mini Monitor Module can be installed in a single- gang junction directly behind the monitored unit. Its small size and light weight allow it to be in- stalled without rigid mounting. The PID-SS is in- tended for use in intelligent, two- wire systems where the indi- vidual address of each module is selected using rotary switches. It provides a two- wire initiating de- vice circuit for normally-open- contact fire alarm and security de- vices. PID-SS Applications — Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull sta- tions, waterflow devices, or other normally-open dry-contact de- vices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (pro- vided) terminates the circuit. PID-SS Operation — Each PID-SS uses one of 99 available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/ normal/short) of its Initiating Device Circuit (IDC). CZI-SS Interface Module The CZI-SS Interface Module is intended for use in intelligent, addressable systems, where the individual address of each mod- ule is selected using built-in rotary switches. This module al- lows intelligent panels to interface and monitor two-wire con- ventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being monitored must be UL compatible with this module. CZI-SS Applications — Use the CZI-SS to monitor a zone of two-wire smoke detectors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm End-of-Line Resistor (provided) ter- minates the end of the Style B or D (class B or A) circuit (maxi- mum IDC loop resistance is 25 ohms). Install ELR across termi- nals 8 and 9 for Style D application. CZI-SS Operation — Each CZI-SS uses one of 99 available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/ normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limi- tations on the loop). g2465min.wmf

PIDP-SS, PID-SS, CZI-SS, DPID-SS CS-2465 09/01/06 Page 3 of 6 Mounting Diagram for standard-sized modules DPID-SS Dual Monitor Module The DPID-SS Dual Monitor Module is intended for use in intel- ligent, two-wire systems. It provides two independent two-wire initiating device circuits (IDCs) at two separate, consecutive ad- dresses. It is capable of monitoring normally open contact fire alarm and supervisory devices; or either normally open or nor- mally closed security devices. The module has a single panel- controlled LED. NOTE: The DPID-SS provides two Style B (Class B) IDC circuits ONLY. Style D (Class A) IDC circuits are NOT supported in any application. DPID-SS Applications — The DPID-SS automatically assigns itself to two addressable points, starting with the original ad- dress. For example, if the DPID-SS is set to address “56”, then it will automatically assign itself to addresses “56” and “57”. NOTE: “ones” addresses on the DPID-SS are 0, 2, 4, 6, or 8 only. Terminals 6 and 7 use the first address, and terminals 8 and 9 use the second address. Avoid duplicating addresses on the system. Installation PIDP-SS, DPID-SS, and CZI-SS modules mount directly to a stan- dard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installation instructions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regulations. These modules are intended for power- limited wiring only. The PID-SS module is intended to be wired and mounted with- out rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances, and regu- lations. Product Line Information PIDP-SS Monitor module. PID-SS Monitor module, miniature. CZI-SS Monitor module, two-wire detectors DPID-SS Monitor module, dual, two independent Class B circuits. SMB500 Optional surface-mount backbox. g2465mt2.wmf

PIDP-SS, PID-SS, CZI-SS, DPID-SS CS-2465 09/01/06Page 4 of 6 Fig. 2 PID-SS: Typical two-wire Style B initiating device circuit configuration. WIRING DIAGRAM: PID-SS Fig. 1 DPID-SS: Typical dual two-wire Style B initiating device circuit configuration. g2465w1.wmf WIRING DIAGRAM: DPID-SS g2465w2.wmf Wiring Diagrams The following wiring diagrams are included: 1) DPID-SS, typical dual two-wire Style B initiating device circuit configuration. 2) PID-SS, typical two-wire Style B initiating device circuit configuration. 3) PIDP-SS, typical two-wire initiating circuit configuration, NFPA Style B. 4) PIDP-SS, typical four-wire fault-tolerant initiating circuit configuration, NFPA Style D. 5) PIDP-SS, typical two-wire initiating circuit configuration for security systems (with alarm versus short capability). 6) CZI-SS, interface two-wire conventional detectors, NFPA Style B. 7) CZI-SS, interface two-wire conventional detectors, NFPA Style D.

PIDP-SS, PID-SS, CZI-SS, DPID-SS CS-2465 09/01/06 Page 5 of 6 Fig. 3 PIDP-SS: Typical two-wire initiating device circuit configuration, NFPA Style B.  Connect modules to listed compatible Gamewell control panels only.  All wiring shown is supervised and power limited.  Install contact closure devices per manufacturers’ installation instructions.  Any number of UL-listed contact closure devices may be used.  DO NOT MIX fire alarm initiating, supervisory, or security devices on the same circuit. WIRING DIAGRAMS THIS PAGE: PIDP-SS Fig. 4 PIDP-SS: Typical four-wire fault-tolerant initiating circuit configuration, NFPA Style D. Fig. 5 PIDP-SS: Typical two-wire initiating circuit configuration for security systems (with alarm versus short capability). 6720wir2.wmf 6720wir3.wmf 6720wir4.wmf

PIDP-SS, PID-SS, CZI-SS, DPID-SS CS-2465 09/01/06Page 6 of 6 Gamewell-FCI

12 Clintonville Road

Northford, CT 06472-1610 Phone: 203-484-7161 Fax: 203-484-7118 www.gamewell-fci.com A Honeywell Company © 2006 Gamewell-FCI Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell-FCI assumes no responsibility for their use. Data and design are subject to change without notice. Installation and wiring instructions shipped with the product shall always be used for actual installation. For more information, contact Gamewell-FCI. Fig. 6 CZI-SS: Interface two-wire conventional detectors, NFPA Style B.  Connect modules to listed compatible control panels only.  Terminal wiring must be power limited.  DO NOT MIX fire alarm initiating, supervisory, or security devices on the same circuit.  DO NOT LOOP wire under terminals. Break wire run to provide supervision of connections.  Detectors must be UL listed compatible with module.  Install detectors per manufacturers’ installation instructions.  Power to the interface module must be externally switched to reset the detectors. An RCE-SS relay control module can be used to switch power from a standard power supply. WIRING DIAGRAMS THIS PAGE: CZI-SS Fig. 7 CZI-SS: Interface two-wire conventional detectors, NFPA Style D. 6720wir6.wmf 6720wir5.wmf