PID-95 GAMEWELL-FCI | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 2
Technical content
Features
Monitors dry-contact devices. LED for alarm annunciation. Supervises DC power in. Field programmable. Priority interrupt. Plate-mounted version available for surface or flush mounting in 4" (11 cm) square, 4.688" (11.908 cm), or double gang boxes. Microsoft® Windows® is a registered trademark of Microsoft® Corporation. CS-2044ph1.wmf PID-95PID-95P An ISO 9000-2000 Company APPROVED FM SIGNALING S521 7300-1288:147 MEA Approved
12 Clintonville Road, Northford, CT 06472-1610 USA Tel: (203) 484-7161 Fax: (203) 484-7118
CS-2044 Rev. A page 2 of 2 www.gamewell-fci.com Engineer’s Specifications Addressable interface devices shall be provided for the monitoring and supervision of contact type devices con- nected to the Fire Alarm Control Panel. The devices shall monitor a normally open dry contact. The addressable interface devices shall communicate to the main control panel via the analog addressable circuit. The interface device shall be Gamewell-FCI PID-95 or PID-95P . Specifications PID-95 Standby Current: 0.0005 A Alarm Current: 0.0015 A Operating Temperature: 0° C to 49° C (32°F to 120 °F) Relative Humidity: 85%, non-condensing Mounting: 4" (10.16 cm) square backbox with blank cover plate PID-95P Standby Current: 0.0005 A Alarm Current: 0.0015 A Operating Temperature: 0° C to 49° C (32°F to 120°F) Relative Humidity: 85%, non-condensing Mounting: 4" (11 cm) 4.688" (11.908 cm), double gang Backbox.
Ordering Information
PID-95 Addressable point identification device for monitoring contact devices. PID-95P Addressable input interface device mounted on 4.688" (11.908 cm) plastic plate. 70839 Trim ring for flush-mounting on the PID-95P .