Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 22
Technical content
© 2015 Bel Power Solutions, Inc. North America +1-866.513.2839 Asia-Pacific +86.755.29885888 Europe, Middle East +353 61 225 977 tech.support@psbel.com belpowersolutions.com BCD.00420_AE High efficiency up to 94.0% Wide input voltage range: 90-264 VAC Active power factor correction Always-On 10 W standby output (3.3 V) Hot-plug capability Parallel operation with active current sharing Full digital control for circuit loop and power management High density design: 30.25 W/in3 Compact form factor: 54.5 x 40.0 x 321.5 mm PMBus™ for control, programming and monitoring Fully protected (OTP, OCP, OVP, SCP) 4K Bytes of EEPROM for user information 2 Status LEDs: FAIL and OK with fault signaling Approved to the latest edition of following Safety Standards: UL/CSA60950-1, IEC / EN 60950-1 Designed to meet Class A emissions per CISPR 22 and EN55022 The PET1300-12-054xA is a 1300 Watt AC to DC power-factor-corrected (PFC) power supply that converts standard AC mains power into a main output of 12 VDC for powering intermediate bus architectures (IBA) in high performance and reliability servers, routers, and network switches. The PET1300-12-054xA meets international safety standards and displays the CE -Mark for the European Low Voltage Directive (LVD). High performance servers Routers Switches
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE PET 1300 - 12 - 054 X A Product Family PET Front-Ends Power Level
1300 W Dash V1 Output
12 V Dash Width
N: Normal R: Reversed Input A: AC The PET1300-12-054xA AC/DC power supply is a fully DSP controlled, highly efficient front-end power supply. It incorporates resonance-soft-switching technology and interleaved power trains to reduce component stresses, providing increased system reliability and very high efficiency. With a wide input operational voltage range and minimal linear derating of output power with input voltage and temperature, the PET1300-12-054xA maximizes power availability in demanding server, network, and other high availability applications. The supply is fan cooled and ideally suited for integration with a matching airflow paths. The PFC stage is an analogue solution; MCU is used to communicate with DSP chip on secondary side. The DC/DC stage uses soft switching resonant techniques in conjunction with synchronous rectification. An active OR-ing device on the output ensures no reverse load current and hence it is ideally suited for operation in redundant power systems. The always-on standby output with voltage level (3.3 Volts), provides power to external power distribution and management controllers. It is protected with an active OR-ing device for maximum reliability. Status information is provided with front-panel LEDs. In addition, the power supply can be controlled and the fan speed set via the I2C bus. The I2C bus allows full monitoring of the supply, including input and output voltage, current, power, and inside temperatures. Cooling is managed by a fan controlled by the DSP controller. The fan speed is adjusted automatically depending on the actual power demand and supply temperature and can be overridden through the I2C bus. Figure 1 - PET1300-12-054xA Block Diagram Logic Signals V1Sense+ L Buck Aux Converter VsbSense+ VsbSense- GND Vsb N PFC DC DC Digital Prim Controls V1Sense- I2C PWM Filter PE PWM Communication Bus APS Digital Sec Controls EEPROM FAN Analog Prim Controls
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE Figure 4 - Efficiency Measurement Curve General Condition: Ta = 0 … +60 °C unless otherwise noted. PARAMETER DESCRIPTION / CONDITION MIN NOM MAX UNIT Main Output V1 V1 nom Nominal Output Voltage 0.5 ∙I1 nom, Tamb = 25 °C
12.0 VDC
V1 set Output Setpoint Accuracy -0.5 +0.5 % V1 nom dV1 tot Total Regulation Vi min to Vi max, 0 to 100% I1 nom, Ta min to Ta max -3 +3 % V1 nom P1 nom Nominal Output Power V1 = 12 VDC 1296 W I1 nom Nominal Output Current V1 = 12 VDC, Vin >= 108 VAC 108 ADC v1 pp Output Ripple Voltage V1 nom, I1 nom, 20 MHz BW 180 mVpp dV1 Load Load Regulation Vi = Vi nom, 0 - 100% I1 nom 60 mV dV1 Line Line Regulation Vi =Vi min…Vi max 20 mV dIshare Current Sharing(abs (I1-I2 ), between any two units in parallel) when Bus load ≥ 27 A 4.5 A when Bus load < 27 A 5.6 A dVdyn Dynamic Load Regulation Iout:10%--60% of full load; 50%--100% of full load dI1/dt = 1A/μs, recovery within 1% of V1 nom -0.6 0.6 V Trec Recovery Time 0.5 1 mS tAC V1 Start-up Time from AC 2 sec tV1 rise Rise Time V1 = 10…90% V1 nom 3 mS CLoad Capacitive Loading Ta = 25 °C 11000 μF Standby Output VSB VSB nom Nominal Output Voltage 0.5 ∙ISB nom, Tamb = 25 °C
3.3 VDC
VSB set Output Setpoint Accuracy -1 +1 %V1nom dVSB tot Total Regulation Vi min to Vi max, 0 to 100% ISB nom, Ta min to Ta max -1.5 +1.5 %VSBnom PSB nom Nominal Output Power VSB = 3.3 VDC , normal airflow 10 W ISB nom Nominal Output Current VSB = 3.3 VDC, normal airflow 3 ADC VSB pp Output Ripple Voltage VSB nom, ISB nom, 20 MHz BW (See Section 5.1) 45 mVpp dVSB Droop 0 - 100% ISB nom 67 mV dVSBdyn Dynamic Load Regulation ΔISB = 50% ISB nom, ISB = 5 … 100% ISB nom, dIo/dt = 0.5 A/μs, recovery within 1% of V1 nom -3 3 %VSBnom Trec Recovery Time 250 μs tAC VSB Start-up Time from AC 3 sec tVSB rise Rise Time VSB = 10…90% VSB nom 4 20 mS CLoad Capacitive Loading Tamb = 25 °C 1000 μF
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE The front-end has 2 front LEDs showing the status of the supply. LED number one is green which indicates presence of AC power, LED number two is bi-colored: green and yellow, which indicates DC power presence or fault. For the position and states of the LEDs see Table 1. Table 1 - LED Status POWER SUPPLY CONDITION GREEN (OK) LED STATUS AMBER (FAIL) LED STATUS No AC power to all power supplies OFF OFF Power Supply Failure (includes over voltage, over current, over temperature and fan failure) OFF ON Power Supply Warning events where the power supply continues to operate (high temperature, high power and slow fan) OFF 1 Hz Blinking AC Present / 3.3 VSB on (PSU OFF) 1 Hz Blinking OFF Power Supply ON and OK ON OFF *When unit see fan failure, unit will shut down and can only be restarted by using PSON_L signal or AC input power recycling or PMBus commands. Refer to software spec. for detail. General Condition: Ta = 0 … +60 °C unless otherwise noted. PARAMETER DESCRIPTION/CONDITION MIN NOM MAX UNIT PSKILL_H/PSON_L/PRESENT_L VIL Input Low Level Voltage 0 0.8 V VIH Input High Level Voltage 2.0 3.6 V IIL, H Maximum Input Sink or Source Current 0 1 mA RpuSKILL_H Internal Pull Up Resistor on PSKILL_H 10 kΩ RpuPSON_L Internal Pull Up Resistor on PSON_L 10 kΩ RpuPRESENT_L Internal Pull Up Resistor on PRESENT_L None kΩ RLOW Resistance Pin to SGND for Low Level 0 1 kΩ RHIGH Resistance Pin to SGND for High Level 50 kΩ PWOK_H Output Vext Maximum External Pull Up Voltage 3.6 V VOL Output Low Level Voltage Isink < 2 mA 0 0.4 V VOH Output High Level Voltage Isource < 0.5 mA 2.4 3.6 V RpuPWOK_H Internal Pull Up Resistor on PWOK_H None kΩ ACOK_H Output Vext Maximum External Pull Up Voltage 3.6 V VOL Output Low Level Voltage Isink < 2 mA 0 0.4 V VOH Output High Level Voltage Isource < 0.5 mA 2.4 3.6 V RpuACOK_H Internal Pull Up Resistor on ACOK_H None kΩ SMB_ALERT_L Output Vext Maximum External Pull Up Voltage 12 V VOL Output Low Level Voltage Isink < 2 mA 0 0.4 V IOH Maximum High Level Leakage Current 10 uA RpuSMB_ALERT_L Internal Pull Up Resistor on SMB_ALERT_L None kΩ
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE Bel Power Solutions provide with its “Bel Power Solutions I2C Utility” a Windows® XP/Vista/Win7 compatible graphical user interface allowing the programming and monitoring of the PET1300-12-054xA Front-End. The utility can be downloaded on www.belpowersolutions.com and supports both the PSMI and PMBus™ protocols. The GUI allows automatic discovery of the units connected to the communication bus and will show them in the navigation tree. In the monitoring view the power supply can be controlled and monitored. Figure 7 - I2C Bus to DSP and EEPROM Table 2 - Accuracy for PMBus COMMOND 10% ~ 20% FULL LOAD 20% ~ 100% FULL LOAD REMARK Read_Iin < 0.5 A +/- 3% It is for corresponding to max input current Read_Iout +/- 2% +/- 2% It is for corresponding to max output current Read_Vin +/- 3% +/- 2.5 V Read_Vout +/- 2% +/- 2% Read_Pin --- +/- 15% It is for corresponding to max input power Read_Pout +/- 3% +/- 3% It is for corresponding to max output power The PRESENT_L is an output signal and it is used to sense the number of power supplies in the system (operational or not). This signal is connected to the power supply’s output ground. Electrical characteristics see 6.2.
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE Interconnect Diagram of PRESENT_L Signal The SMB_ALERT_L is an output signal and shall be an open collector with the pull-up resistor located at the receiving end and shall capable of sinking up to 4 mA. This signal indicates that the power supply is experiencing a problem that the user should investigate. This may be asserted due to Critical events or Warning events. See PMBUS specification for further details. Interconnect Diagram of SMB_ALERT_L Signal This is an input signal and is used to force the 12 V main output off if the supply is removed from the system. At the system level this pin will be connected to the output return directly. When this input is low the power supply will operate. If the input is floating the 12 V main output will turn off while the 3.3 VSB will remain on. This signal overrides all other on-and-off signals. On the power supply connector, this pin is shorter than the others so it is a last-make and first-break contact. See below Table 3 for Logic Table. Interconnect Diagram of PSKILL_H Signal
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE Table 3 - PS_KILL Signal Characteristics SIGNAL CHARACTERISTICS Signal Type: Input Signal to the power supply Accepts a ground input from the system. Pull-up to 3.3 VSB located in the power supply. PS_KILL = Low, PS_ON = Low ON PS_KILL = Open, PS_ON = Low or Open OFF PS_KILL = Low, PS_ON = Open OFF MIN MAX Source current, Vps_kill =Low 4 mA The PS_ON_L signal is an input signal used to remotely turn on/off the power supply. PS_ON_L is an active LOW signal that turns on the 12 V main output. In the low state this input will not source more than 4 mA of current. The 12 V output will be disabled when this input is driven HIGH, or open circuited. See Table 4 for Logic Table. Interconnect Diagram of PSON_L Signal Table 4 - PS_ON_L Signal Characteristics SIGNAL CHARACTERISTICS Signal Type: Input signal to the power supply Accepts an open collector/drain input from the system. Pull-up to 3.3 VSB located in power supply. PS_ON_L = Low, PS_KILL = Low ON PS_ON_L = Open, PS_KILL = Low or Open OFF PS_ON_L = Low, PS_KILL = Open OFF MIN MAX Output Source Current, VPS_ON_L= Low 4 mA PW_OK is an output signal and will be pulled HIGH by the power supply to indicate that all the outputs are within the regulation limits of the power supply. When 12 V main output is < 10.9 V or > 13.2 V, or if any of the outputs fail due to over current protection, over voltage protection, over temperature, or fan failure then this output will be driven LOW. In the event when AC mains power is lost, this signal will be driven LOW at least 20 mS before the +3.3 VSB output is lost. The output will be an open collector/drain. The start of the PW_OK delay time shall be inhibited as long as any power supply’s 12 V output is in current limit. See Table 5.
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE Interconnect Diagram of PW_OK Signal Table 5 - PW_OK Signal Characteristics SIGNAL CHARACTERISTICS Signal Type: Output signal from the power supply Open collector/drain (system side to provide pull-up, another pull-up to 3.3 VSB could also be located in the power supply) PW_OK = High Power OK PW_OK = Low Power Not OK MIN MAX Input Sink current, PW_OK = Low 4 mA Output Source current, PW_OK = High 2 mA This signal is an output signal and will be asserted, driven HIGH, by the power supply to indicate that the input voltage meets the minimum requirements of Section 3.1.3. After falling outside the input voltage requirements for more than 20 mS, the signal must be driven LOW. The output will be an open collector/drain. See below Table 6. Interconnect Diagram of AC_OK Signal Table 6 - AC_OK Signal Characteristics SIGNAL CHARACTERISTICS Signal Type: Output signal from the power supply Open collector/drain (system side to provide pull-up, another pull-up to 3.3 VSB could also be located in the power supply) AC_OK = High AC OK AC_OK = Low AC Low (Not OK) MIN MAX Input Sink current, AC_OK = Low 4 mA Output Source current, AC_OK = High 2 mA
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE All outputs shall be capable of operating in a redundant current share mode. A maximum of 6 power supplies may be operated in parallel. All outputs shall incorporate an isolation device (Or-ing MOSFET or diode) for fault isolation. Filter capacitors that are located after the isolation device shall be of high reliability and shall be de-rated sufficiently to minimize failures. The 3.3 V output current sharing shall be of a droop type. The +12 V current sharing shall be a single wire type, active current sharing. Connecting the Ishare (current share) pins of each power supply together shall enable the current share feature. Shorting or opening of a current share pin shall not cause the output voltage to go out of steady state regulation. For 12 V output the Ishare (load sharing) voltage shall be a linear function Ishare [V] = 8 x Iout/108 (with 8 V at 108 A) for a single power supply (~74 mV/A). At light load, the load share becomes difficult because of low feedback signal. Refer to Table 2 for current sharing accuracy. The current balance accuracy is calculated as: 2*|I1-I2|/ (I1+I2), where the I1 is the PSU1 load current and I2 is the PSU2 load current. The outputs specified shall incorporate remote sense and will compensate for specified load cable drop. In the event of loss of remote sense, all outputs shall revert to internal sense so as to limit the outputs to less than 105% of nominal. Unless defined otherwise, all control signals shall be TTL compatible with respect to the output return and shall be isolated from the primary circuit and be SELV rated. All input signals shall be driven from an open collector with the pull-up resistor located in the power supply and shall be capable of sourcing up to 4 mA. General LVTTL signal levels are specified in below table except where explicitly specified otherwise. Table 7 - Low-Voltage TTL (LVTTL) Voltage Levels PARAMETER SYMBOL MIN MAX UNITS Output High Voltage Voh 2.4 3.6 V Output Low Voltage Vol 0 0.4 V Input High Voltage Vih 2.0 3.6 V Input Low Voltage Vil 0 0.8 V
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE NOTE: Most of the immunity requirements are derived from EN 55024: 1998/A2:2003. PARAMETER DESCRIPTION / CONDITION CRITERION ESD Contact Discharge IEC / EN 61000-4-2, ±8 kV, 25+25 discharges per test point (metallic case, LEDs, connector body) A ESD Air Discharge IEC / EN 61000-4-2, ±15 kV, 25+25 discharges per test point (non-metallic user accessible surfaces) A Radiated Electromagnetic Field IEC / EN 61000-4-3, 10 V/m, 1 kHz/80% Amplitude Modulation, 1 µs Pulse Modulation, 10 kHz…2 GHz A Burst IEC / EN 61000-4-4, level 3 AC port ±2 kV, 1 minute DC port ±1 kV, 1 minute A Surge IEC / EN 61000-4-5 4 kV CM 2 kV DM A RF Conducted Immunity IEC/EN 61000-4-6, Level 3, 10 Vrms, CW, 0.1 … 80 MHz A Voltage Dips and Interruptions IEC/EN 61000-4-11 1: Vi 230 V, 100% Load, Phase 0 °, Dip 100%, Duration 10 mS 2: Vi 230 V, 100% Load, Phase 0 °, Dip 100%, Duration 20 mS 3: Vi 230 V, 100% Load, Phase 0 °, Dip 100%, Duration > 20 mS A VSB: A, V1: B VSB, V1: B PARAMETER DESCRIPTION / CONDITION CRITERION Conducted Emission EN55022 / CISPR 22: 0.15 … 30 MHz, QP and AVG, single unit Class A EN55022 / CISPR 22: 0.15 … 30 MHz, QP and AVG, 2 units in rack system Class A Radiated Emission EN55022 / CISPR 22: 30 MHz … 1 GHz, QP, single unit Class A EN55022 / CISPR 22: 30 MHz … 1 GHz, QP, 2 units in rack system Class A Harmonic Emissions IEC61000-3-2, Vin = 115 VAC / 60 Hz, & Vin = 230 VAC/
50 Hz, 100% Load Class A
Acoustical Noise 46 dBA at 1 meter, 25 °C, 50% Load - AC Flicker IEC61000-3-3, Vin = 230 VAC / 60 Hz, 100% Load Pass PARAMETER MIN . TYP. MAX. UNITS CONDITION/COMMENTS T1 (Tout_rise) 0.5 100 mS Output voltage rise time from each main output T2 (Tsb_on_delay) 2500 mS Delay from AC being applied to 3V3 being within regulation T3 (Tac_on_delay) 3000 mS Delay from AC being applied to all output voltages being within regulation T4 (Tvout_holdup) 10 mS Time all output voltages, including 3V3, stay within regulation after loss of AC T5 (Tpw_ok_holdup) 5 mS Delay from loss of AC to de-assertion of PW_OK T6 (Tps_on_delay) 5 400 mS Delay from PS_ON_L active to output voltages within regulation limits T7 (Tps_on_pw_ok) 50 mS Delay from PS_ON_L de-active to PW_OK being de-asserted T8 (Tac_ok_off) 20 mS Delay from loss of AC input to de-assertion of AC_OK T9 (Tpw_ok_on) 100 1000 mS Delay from output voltages within regulation limits to PW_OK asserted at turn on T10 (Tpw_ok_off_12V) 1 700 mS Delay from PW_OK de-asserted to 12 VDC dropping out of regulation limits T11 (Tpw_ok_off_3V3) 20 mS Delay from PW_OK de-asserted to 3V3 dropping out of regulation limits T12 (Tsb_vout) 50 1000 mS Delay from 3V3 being in regulation to 12 VDC being in regulation at AC turn on. T13 (Tac_ok_on) 1500 mS Delay from AC being applied to assertion of AC_OK
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE Maximum electric strength testing is performed according to UL / CSA 60950-1, IEC/EN 60950-1. Input-to-output electric strength tests should not be repeated in the field. Bel Power Solutions will not honor any warranty claims resulting from electric strength field tests. PARAMETER DESCRIPTION / CONDITION MIN NOM MAX UNIT Agency Approvals Approved to the latest edition of the following standards: UL / CSA 60950-1 IEC / EN 60950-1 Approved by independent body (see CE Declaration) Isolation Strength Input (L/N) to case (PE) Basic Input (L/N) to output Reinforced Output to case (PE) Functional Electrical Strength Test Input to case 2121 VDC Input to output 4242 PARAMETER DESCRIPTION / CONDITION MIN NOM MAX UNIT TA Ambient Temperature Vi min to Vi max, I1 norm, ISB nom 0 +60 °C TS Storage Temperature Non-operational -40 +85 °C Altitude Operational, above Sea Level - 10,000 Feet Na Audible Noise Vi = 230 VAC, 50% Io nom, TA = 25°C 46 dBA Note: Refer to Figure 2&3 for Derating. PARAMETER DESCRIPTION / CONDITION MIN NOM MAX UNIT Dimensions Width 54.1 54.5 54.9 mm Height 39.6 40.0 40.4 Depth 321.1 321.6 322.1 M Weight 1.09 kg Otherwise stated, Tolerance: 0.5mm – 120mm: ±0.3mm; 120mm – 400mm: ±0.5mm. Figure 8 - Side View 1 321.6 ±0.5 27.7113.414 34.35 2.82 Reverse Air Flow Direction Normal Air Flow Direction NOTE: A 3D step file of the power supply casing is available on request.
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE Unit: Tyco Electronics P/N 1926736-2 or FCI 10122460-002LF Counter part: Tyco Electronics P/N 2-1926739-5 or FCI 10108888-R10253SLF (Bel Power Solutions P/N: ZES.00672) PIN NAME DESCRIPTION Output 6, 7, 8, 9, 10 V1 +12 VDC main output 1, 2, 3, 4, 5 PGND Power ground (return) Control Pins A1, B1, C1, D1, E1 VSB Standby positive output (+3.3 V) A2, B2 SGND Signal ground (return) C2 NC Reserved D2 NC Reserved E2 NC Reserved A3 PS_KILL Power supply kill (lagging pin) B3 NC Reserved C3 SDA I2C data signal line D3 V1_SENSE_R Main output negative sense E3 V1_SENSE Main output positive sense A4 SCL I2C clock signal line B4 PS_ON_L Power supply on input (connect to A2/B2 to turn unit on) C4 ALERT_L SMB Alert signal output D4 ISHARE 12 V current share signal (LS) E4 AC_OK AC input OK signal A5 A0 Address 0 B5 NC Reserved C5 PW_OK Power OK signal output (lagging pin) D5 A1 Address 1 E5 PRESENT_L Power supply present (lagging pin) E D C B A
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE ITEM DESCRIPTION ORDERING PART NUMBER SOURCE Bel Power Solutions I2C Utility Windows XP/Vista/7 compatible GUI to program, control and monitor PET Front-Ends (and other I2C units) N/A www.belpowersolutions.com Evaluation board Dual Connector Board Connector board to operate 2 PET units in parallel. Includes an on-board USB to I2C converter (use Bel Power Solutions I2C Utility as desktop software). VRA.00333.0 Bel Power Solutions Table 8 - Address Select A2 A1 A0 UNIT ADDRESS EEPROM ADDRESS 0 0 0 0xB0 0xA0 0 0 1 0xB2 0xA2 0 1 0 0xB4 0xA4 0 1 1 0xB6 0xA6 Note: A2 = 1 is not implemented. NOTE: Reference: PMBus Power System Management Protocol Specification Part II – Command Language Revision 1.1. Commands not included in the table below are Not Implemented. Feature that are To Be Defined (TBD), or Not Implemented are shaded. R = Read-Only; RW = Read/Write; W = Write-Only. Table 9 - PMBus Commands COMMAND NAME BIT NAME CODE BIT VALUE ACCESS DATA BYTES REMARKS PAGE 00h - RW 1 Page 0 applies to + 12 V output Page 1 applies to + 3.3 V output Other Page values are considered invalid and will generate an INVALID_DATA error. OPERATION 01h 1 7-6 - RW 0b00 = OFF 0b10 = ON (Default) 5-0 0d R Not Implemented CLEAR_FAULTS 03h - W 0 Clear all bits in all status registers. CAPABILITY 19h R 1 PACKET_ERROR_CHECKING 7 0b1 Supported MAXIMUM_BUS_SPEED 6-5 0b01 400 kHz SMBALERT# 4 0b1 Supported RESERVED 3-0 0b0000 Reserved VOUT_MODE 20h - R 1
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE MODE 7-5 0b000 Linear PARAMETER 4-0 0b10111 N = -9 FAN_CONFIG_1_2 3Ah R 1 7 0b1 Fan1 Installed 6 0b0 Fan1 Commanded in Duty Cycle 5-4 0b01 Fan1 (2) Tachometer Pulses per Revolution 3 0b0 Fan2 Not Installed 2 0b0 Don’t Care 1-0 0b00 Don’t Care FAN_COMMAND_1 3Bh - RW 2 MIN = 0 0% MAX = 100 100% Values outside limits will generate INVALID_DATA error. Write request is executed only if the desired Fan speed is greater than what is required by the PSU. Fan Speed = FAN_COMMAND*21000RPM/100 STATUS_BYTE 78h R 1 STATUS bits remain set, even if the fault or warning is removed. They are reset by: CLEAR_FAULTS Command AC Recycle PSON Recycle BUSY 7 0b0 Not Implemented OFF 6 - VOUT_OV 5 - IOUT_OC 4 - VIN_UV 3 - TEMPERATURE 2 - CML 1 - NONE_OF_THE_ABOVE 0 0b0 Not Implemented STATUS_WORD 79h R 2 VOUT F - IOUT/POUT E - INPUT D - MFR C - POWER_GOOD# B - FANS A - OTHER 9 - UNKNOWN 8 0b0 Not Implemented STATUS_BYTE 7-0 - See STATUS_BYTE STATUS_VOUT 7Ah R 1 VOUT_OV_FAULT 7 - Asserts when an OV fault condition is detected on V1 output. SMB Alert Mask = 1 (Default) VOUT_OV_WARNING 6 0b0 Not Implemented VOUT_UV_WARNING 5 0b0 Not Implemented VOUT_UV_FAULT 4 - Asserts when an UV fault condition is detected on V1 output.
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE SMB Alert Mask = 1 (Default) VOUT_MAX_WARNING 3 0b0 Not Implemented TON_MAX_FAULT 2 - Asserts when V1 output is not in regulation 3s after PSON and AC is applied. SMB Alert Mask = 1 (Default) TOFF_MAX_WARNING 1 0b0 Not Implemented PWR_ON_TRACKING_ERROR 0 0b0 Not Implemented STATUS_IOUT 7Bh R 1 IOUT_OC_FAULT 7 - Asserts when an OC fault condition is detected on V1 output. SMB Alert Mask = 1 (Default) IOUT_OC_FAULT_LV 6 0b0 Not Implemented IOUT_OC_WARNING 5 0b0 Asserts when an OC warning condition is detected on V1 output. SMB Alert Mask = 0 (Default) IOUT_UC_FAULT 4 0b0 Not Implemented ISHARE_FAULT 3 0b0 Not Implemented PIN_LIMITING_MODE 2 0b0 Not Implemented POUT_OP_FAULT 1 0b0 Not Implemented POUT_OP_WARNING 0 0b0 Not Implemented STATUS_INPUT 7Ch R 1 VIN_OV_FAULT 7 0b0 Not Implemented VIN_OV_WARNING 6 0b0 Not Implemented VIN_UV_WARNING 5 0b0 Not Implemented VIN_UV_FAULT 4 0b0 Not Implemented UNIT_OFF_VIN_LOW 3 - Asserts when the PSU is disabled because of low input voltage. SMB Alert Mask = 1 (Default) IIN_OC_FAULT 2 0b0 Not Implemented IIN_OC_WARNING 1 0b0 Not Implemented PIN_OP_WARNING 0 0b0 Not Implemented STATUS_TEMPERATURE 7Dh R 1 OT_FAULT 7 - Asserts when an OT fault condition is detected. SMB Alert Mask = 1 (Default) OT_WARNING 6 - Asserts when an OT warning condition is detected. SMB Alert Mask = 1 (Default) UT_WARNING 5 0b0 Not Implemented UT_FAULT 4 0b0 Not Implemented RESERVED 3-0 0b0000 Reserved STATUS_CML 7Eh R 1 INVALID_COMMAND 7 - Asserts when the System tries to access unsupported commands, write to supported commands with read-only access, or read supported commands with write-only access. SMB Alert Mask = 0 (Default) INVALID_DATA 6 - Asserts when the System tries to write invalid data (including when PEC byte is incorrect) to supported commands with write access.
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE SMB Alert Mask = 0 (Default) PEC_FAIL 5 - Asserts when the received PEC byte is incorrect. SMB Alert Mask = 0 (Default) MEMORY_FAULT 4 0b0 Not Implemented PROCESSOR_FAULT 3 0b0 Not Implemented RESERVED 2 0b0 Reserved OTHER_COMM_FAULT 1 0b0 Asserts when the communication between monitoring components inside the PSU is lost. SMB Alert Mask = 0 (Default) OTHER_MEMORY_FAULT 0 0b0 Not Implemented STATUS_OTHER 7Fh R 1 RESERVED 7 0b0 Reserved RESERVED 6 0b0 Reserved INPUT A FUSE 5 0b0 Not Implemented INPUT B FUSE 4 0b0 Not Implemented INPUT A ORING 3 0b0 Not Implemented INPUT B ORING 2 0b0 Not Implemented OUTPUT ORING 1 - Asserts when a fault is detected on the V1 ORing device. SMB Alert Mask = 0 (Default) RESERVED 0 0b0 Reserved STATUS_MFR_SPECIFIC 80h R 1 RESERVED 7 0b0 Reserved RESERVED 6 0b0 Reserved RESERVED 5 0b0 Reserved RESERVED 4 0b0 Reserved VSB_UV_FAULT 3 - Asserts when an UV fault condition is detected on Vsb output. SMB_Alert Mask = 0 (Default) VSB_OV_FAULT 2 - Asserts when an OV fault condition is detected on Vsb output. SMB_Alert Mask = 0 (Default) PHASE_SHARE_FAULT 1 - Asserts when there is a current imbalance between DCDC Phases. SMB_Alert Mask = 0 (Default) HOLDUP_FAULT 0 - Asserts when V1 goes out of regulation if Bulk voltage level is reduced. SMB_Alert Mask = 0 (Default) STATUS_FANS_1_2 81h R 1 FAN1_FAULT 7 - Asserts when a Fan fault condition is detected. SMB Alert Mask = 1 (Default) FAN2_FAULT 6 0b0 Not Implemented FAN1_WARNING 5 0b0 Not Implemented FAN2_WARNING 4 0b0 Not Implemented FAN1_SPEED_OVERRIDE 3 - Asserts when the Fan is running according to the speed defined by the System. SMB Alert Mask = 0 (Default) FAN2_SPEED_OVERRIDE 2 0b0 Not Implemented
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE AIR_FLOW_FAULT 1 0b0 Not Implemented AIR_FLOW_WARNING 0 0b0 Not Implemented READ_VIN 88h - R 2 Linear Format, N = -1 READ_IIN 89h - R 2 Linear Format, N = -6 READ_VOUT 8Bh - R 2 Linear Format, N = -9 Refer to Section 8.3.1 of PMBus Spec Part II Revision 1.1 READ_IOUT 8Ch - R 2 Linear Format, N = -3 READ_TEMPERATURE_1 8Dh - R 2 Linear Format, N = -2 Inlet Temperature READ_TEMPERATURE_2 8Eh - R 2 Linear Format, N = -2 Outlet Temperature READ_TEMPERATURE_3 8Fh - R 2 Linear Format, N = -2 ORing FET Temperature READ_FAN_SPEED_1 90h - R 2 Linear Format, N = 5 READ_POUT 96h - R 2 Linear Format, N = 1 READ_PIN 97h - R 2 Linear Format, N = 1 MFR_ID 99h - R CNT+9 ID = Bel Power Format: ASCII MFR_MODEL 9Ah - R CNT+16 MODEL = PET1300-12-054xA Format: ASCII MFR_REVISION 9Bh - R CNT+3 REVISION = vvv Format: ASCII MFR_LOCATION 9Ch - R 2 LOCATION = xx Format: ASCII MFR_DATE 9Dh - R CNT+4 DATE = yyww Format: ASCII MFR_SERIAL 9Eh - R CNT+18 SERIAL = xxzzzzzzzzvvvuuuuu Format: ASCII CALIBRATION_POINTER C0h - RW 2 For Bel Power Solutions Use Only CALIBRATION_DATA C1h - RW 2 For Bel Power Solutions Use Only CALIBRATION_COMMAND C2h - 2 For Bel Power Solutions Use Only RESERVED F-1 0d R Reserved COMMIT_TO_FLASH 0 - RW 0 = No Action 1 = Commit RAM to Flash READ_VSTBY C3h - R 2 For Bel Power Solutions Use Only Same format as READ_VOUT READ_ISTBY C4h - R 2 For Bel Power Solutions Use Only Same format as READ_IOUT READ_VOUT_INT C5h - R 2 For Bel Power Solutions Use Only Same format as READ_VOUT BOOTLOADER_STATUS_REQUES T C7h RW 2 For Bel Power Solutions Use Only BOOTLOADER_PAGE_DATA C8h - W - For Bel Power Solutions Use Only PRODUCT_ID_NUMBER C9h R 2 For Bel Power Solutions Use Only Refer to Table 3 FW_REV CAh R 2 For Bel Power Solutions Use Only SEC_DSP_MAJOR F-C - M = 0 to 9 SEC_DSP_MINOR B-8 - m = 0 to 9 i.e: Mm = 25 Revision 2.5 PRI_DSP_MAJOR 7-4 - M = 0 to 9 PRI_DSP_MINOR 3-0 - m = 0 to 9 i.e: Mm = 13 Revision1.3 SEC_CTRL1 CCh R For Bel Power Solutions Use Only SEC_CTRL2 CDh R For Bel Power Solutions Use Only
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE SEC_STAT CEh R For Bel Power Solutions Use Only PRI_STAT CFh R For Bel Power Solutions Use Only MFR_SPECIFIC_00 (PSU_CONTROL) D0h 2 RESERVED F-1 0d R Reserved EEPROM_WP 0 - RW EEP Write-Protect (WP) Control 0 = Enable WP (Default) 1 = Disable WP MFR_SPECIFIC_05 (FW_VERSION) D5h - R length is fixed at 8 Ascii characters. Each field will be an Ascii value stored in one byte. * For example: aa.bb.cc, where aa is development stage (P0, P1 ... A0); bb is primary mcu firmware revision (00 ~ 99); cc is secondary mcu firmware revision (00 ~ 99). NO BYTE COUNT MFR_SPECIFIC_09 (SMB_ALERT_MASKING) D9h - RW 7 Refer to Table 4 NO BYTE COUNT Table 10 - Product ID Number BIT(S) DESCRIPTION REMARKS F-A Product Family TBD 9-8 Communication Protocol 0b00 = Reserved 0b01 = Reserved 0b10 = PMBus 0b11 = Reserved 7-0 Product Part Number TBD Table 11 - SMB_ALERT Masking BYTE BYTE DESCRIPTION BIT BIT DESCRIPTION DEFAULT
0 GLOBAL_MASK 7 Not Implemented -
6 Not Implemented -
5 Not Implemented -
4 Not Implemented -
3 Not Implemented -
2 Not Implemented -
1 Not Implemented -
0 Global Mask. Clear to disable SMB_ALERT 1
1 STATUS_VOUT 7 VOUT_OV_FAULT Mask 1
4 VOUT_UV_FAULT Mask 1
2 TON_MAX_FAULT Mask 1
0 Not Implemented -
2 STATUS_IOUT 7 IOUT_OC_FAULT Mask 1
© 2015 Bel Power Solutions, Inc. 866.513.2839 tech.support@psbel.com belpowersolutions.com BCD.00420_AE
3 STATUS_TEMPERATURE 7 OT_FAULT Mask 1
6 OT_WARNING Mask 1
4 STATUS_INPUT 7 Not Implemented -
3 UNIT_OFF_VIN_LOW Mask 1
5 STATUS_FANS_1_2 7 FAN1_FAULT Mask 1
3 FAN1_SPEED_OVERRIDE Mask 0
6 STATUS_CML 7 INVALID_COMMAND Mask 0
6 INVALID_DATA Mask 0
5 PEC_FAIL Mask 0
NUCLEAR AND MEDICAL APPLICATIONS - Products are not designed or intended for use as critical components in life support systems, equipment used in hazardous environments, or nuclear control systems. TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date manufactured. Specifications are subject to change without notice.