PDRC-10 CUI | Alldatasheet
Document overview
- Manufacturer or author: Provided By www.digicamel.com(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 6
Technical content
cui.com date 06/13/2019 page 1 of 6 SERIES: PDRC-10 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY MODEL output voltage output current output power ripple and noise1 efficiency2 (Vdc) max (A) max (W) max (mVp-p) typ (%) PDRC-10-5 5 1.5 7.5 50 75 PDRC-10-12 12 0.83 10 50 79 PDRC-10-15 15 0.67 10 50 80 PDRC-10-24 24 0.42 10 50 80 Notes: 1. At full load, nominal input, 20 MHz bandwidth oscilloscope. 2. At nominal input. 3. All specifications are measured at Ta=25°C, nominal input voltage, and rated output load unless otherwise specified.
FEATURES
- low profile for building automation
- universal input (90~264 Vac)
- integrated fuse and surge protection
- 3,000 Vac input/output isolation voltage
- DC On/Low LED indicators
- over-voltage/current protection
- UL/cUL, TUV, CE certified PART NUMBER KEY Base Number PDRC-10 - XX Output Voltage Additional Resources: Product Page
cui.com date 06/13/2019 │ page 2 of 6CUI Inc │ SERIES: PDRC-10 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY INPUT parameter conditions/description min typ max units voltage 90 120 264 375 Vac Vdc frequency 47 63 Hz current at 90 Vac, full load 300 mA inrush current at 115 Vac, full load at 230 Vac, full load A A leakage current input to output 0.25 mA OUTPUT parameter conditions/description min typ max units capacitive load
5 Vdc output model
12 Vdc output model
15 Vdc output model
24 Vdc output model
3,500 1,800 1,500 560 µF µF µF µF initial set point accuracy ±1 % line regulation at full load, V in min to V in max ±1 % load regulation at Vi nom, 0~100% load ±1 % start-up time at Vi nom, full load at Vi nom, full load with max capacitive load 1.0 1.5 s s rise time at Vi nom, full load at Vi nom, full load with max capacitive load 150 500 ms ms hold-up time at 115 Vac, full load at 230 Vac, full load ms ms fall time at Vi nom, full load 150 ms transient recovery time at Vi nom, 100~50% load 2 ms switching frequency at Vi nom, full load 132 kHz temperature coefficient ±0.03 %/°C power back immunity at Vi nom, full load, for 1 second 7.5 Vdc Vdc Vdc Vdc DC ON indicator threshold at start-up (GREEN) 3.5 9.0 11.0 19.2 4.5 10.8 13.5 21.6 Vdc Vdc Vdc Vdc DC LOW indicator threshold after start-up (RED) 3.5 9.0 11.0 19.2 4.5 10.8 13.5 21.6 Vdc Vdc Vdc Vdc PROTECTIONS parameter conditions/description min typ max units over voltage protection at Vi nom, full load, auto recovery 5.75 6.5 16.5 Vdc Vdc Vdc Vdc over current protection hiccup, auto recovery (see curve) 125 185 % short circuit protection hiccup, auto recovery Additional Resources: Product Page
cui.com date 06/13/2019 │ page 3 of 6CUI Inc │ SERIES: PDRC-10 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY SAFETY & COMPLIANCE parameter conditions/description min typ max units isolation voltage input to output for 1 minute 3,000 4,242 Vac Vdc isolation resistance input to output at 500 Vdc 100 MΩ safety approvals UL 508, UL 1310, UL 60950-1, EN 60950-1 ISA 12.12.01 (Class I, Div 2, Groups A~D) safety class class I EMI/EMC EN 55022 Class B, EN 55032 Class B, EN 55024, ENV 50204, EN 61204-3, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2, EN 61000-6-3, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5,EN 61000-4-6, EN 61000-4-8, EN 61000-4-11 pollution degree 2 degree of protection IP20 MTBF as per Bellcore Issue 6 at 40 °C, GB 901,000 888,000 893,000 910,000 hours hours hours hours RoHS yes Notes: 4. The power supply is considered a component which will be installed into final equipment. The final equipment still must be tested to meet the necessary EMC directives. ENVIRONMENTAL parameter conditions/description min typ max units operating temperature see derating curves -40 71 °C storage temperature -40 85 °C humidity non-condensing 20 95 % altitude IEC 60068-2-13 4,850 m vibration meets IEC 60068-2-6 (Mounting on rail: 10~500 Hz, 2 G, along X,Y,Z axis, for 60 minutes on each axis) shock meets IEC 60068-2-27 (15 G, 11 ms, 3 axis, 6 faces, 3 times for each face) Additional Resources: Product Page
cui.com date 06/13/2019 │ page 4 of 6CUI Inc │ SERIES: PDRC-10 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY units: mm [inch] tolerance: unless otherwise noted TERMINAL CONNECTIONS TERMINAL Function 1 V- 2 V+ 3 L 4 N MECHANICAL parameter conditions/description min typ max units material plastic weight 65 g cooling natural convection input/output connector accepts 26~12 AWG wire MECHANICAL DRAWING INSTALLATION DIN RAIL TS35/7.5 or TS35/15 Cable flexible/solid, copper conductors only, 60/75°C Wire Range 26~12 AWG (0.2~2.5 mm2) Strip Length 4~5 mm Screw Torque 5 lb·in Position Vertical Cooling Natural convection, 25 mm clearance on all sides Additional Resources: Product Page
cui.com date 06/13/2019 │ page 5 of 6CUI Inc │ SERIES: PDRC-10 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY 100 Ambient Temperature (°C) Load (%) 40 50 61 -40 01 02 03 0 71 80 EFFICIENCY CURVES DERATING CURVES Temperature Derating Curve (Output Load vs. Ambient Tempearature) Load Current (%) Efficienc y (%) PDRC-10-24 Efficiency Curve (Efficiency vs. Load Current) (%) PDRC-10-24 Typical Over Current Protection Curve (Output Voltage vs. Time) CURRENT LIMITED CURVE Additional Resources: Product Page
date 06/13/2019 │ page 6 of 6CUI Inc │ SERIES: PDRC-10 │ DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website. CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use. CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness. Headquarters 20050 SW 112th Ave. Tualatin, OR 97062 800.275.4899 Fax 503.612.2383 cui.com techsupport@cui.com rev. description date 1.0 initial release 06/13/2019 The revision history provided is for informational purposes only and is believed to be accurate.
REVISION HISTORY
Additional Resources: Product Page