PDB-N-D ETAL | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
Features
The Power-D-Box® is a compact 2U power distribution system made of aluminium in an enclosure with anodised front plate. Protection of the loads is by means of hydraulic-magnetic circuit breakers. l Plug-in type circuit breakers, 8345-.01.-W0, extendable in service, with or without auxiliary contact, load per way 0.1…125 A l Extremely compact design (installation depth 310 mm) l Standard redundant design (2 x 3, 2 x 4, 2 x 6) l Group signalling for redundant line entry A and/or B is standard l To be used with industrially manufactured power distribution modules (X8345-D01), protected against brush contact l Labelling strips for individual marking l Blank covers (bulk shipped) l isolated cable clamp rail (X 223 260 01) optional as accessory l Integral jumper ground to plus pole (freely configurable by the customer as an option) l Other versions are available upon request (e.g. with series fuse, separate circuits, non-redundant circuits, customer-specific marking, protected plus pole etc.) High Power-D-Box® 19“ Power-D-Box® length 84 modules (426.72 mm) height 2 U (88.90 mm) material: aluminium with and without auxiliary contact module X8345-S01KW102-M Rated voltage DC 48 V, DC 65 V, DC 80 V (other voltage ratings upon request) Load
125 A per plug-in unit (when using
circuit breakers rated 80 A plus, total load of the neighbouring slots must not exceed 160 A) Total current per supply 232 A total current at ambient temperature -30...60 °C (-22 °F...140 °F) UL/CSA: 230 A total current at ambient temperature -30...+50 °C Fire resistance (IEC 60695, part 2-2) self-extinguishing Terminal design* Supply feed 35...95 mm 2, flexible, screw-type terminal 25...95 mm2 with wire end ferrule Loads 1.5...35 mm2, flexible, screw-type terminal 1.5...35 mm2 with wire end ferrule Signalling screw-type terminal 1.5 mm2 Ground bolt (M8) Weight approx. 7.5 Kg Conformity CE to EN60950-1 *(detailed values on page 4)
Ordering information
PDB Standard Power-D-Box® 19“ with interchangeable ETSI flange - 19“ Protected pole N negative pole protected Module D X8345-D01* xx Number of ways (total) Main terminals R on the rear Load terminals R on the rear F on the front PDB - N - D 08 - R F ordering example *technical data on www.e-t-a.de High Power-D-Box®: PDB - N - D 06 - RF: load current max. 65 A with 2 x 3 ways PDB - N - D 06 - RR: load current max. 125 A with 2 x 3 ways PDB - N - D 08 - RF: load current max. 65 A with 2 x 4 ways PDB - N - D 08 - RR: load current max. 125 A with 2 x 4 ways PDB - N - D 10 - RF: load current max. 65 A with 2 x 5 ways PDB - N - D 10 - RR: load current max. 85 A with 2 x 5 ways PDB - N - D 12 - RF: load current max. 65 A with 2 x 6 ways PDB - N - D 12 - RR: load current max. 85 A with 2 x 6 ways PDB - N - D 16 - RR: load current max. 6 x 85 A + 10 x 30 A with 2 x 8 ways Preferred types Approvals Authority Standard Rated voltage Current ratings UL UL60950-1 max. DC 80 V max. 125 A* per channel CSA C22.2 No 60950-1-07 max. DC 80 V max. 125 A* per channel * depending on type, see preferred types max. total current of neighbouring channels 160A
www.e-t-a.de Modular High Power-D-Box® 1630 LineLINE ETA.8345-x01x-W0xx-xxxxxx-xxA LOADLOADA1- A1+ A2- A2+ A3- A3+ A4- A4+ A5- A5+ A6- A6+ B1- B1+ B2- B2+ B3- B3+ B4- B4+ B5- B5+ B6- AC ANC BC BNC GND GND A terminal on the rear side supply screw type terminals 95 mm2 load group A screw terminals max. 35 mm2 screw terminals for front or rear side terminal GND signalisation A/B terminal on the rear side load group B screw terminals max. 35 mm2 screw terminals for front or rear side terminal B NCNC LOAD NC LOAD NC LOAD NC LOAD NC LOAD NC LOAD NC LOAD NC LOAD NC LOAD NC LOAD NC LOAD NC NO C LINE C C Line C Line C Line C Line C Line C Line C Line C Line C Line C Line C Line C A2 A1 xxA E-T-A 111A3A4A5A6B1 B B2B3B4B5B6 LINE C LINE C ETA.8345-x01x-W0xx-xxxxxx-xxA LOAD NC NO xxA E-T-A 111 ETA.8345-x01x-W0xx-xxxxxx-xxA LOAD NC NO xxA E-T-A 111 ETA.8345-x01x-W0xx-xxxxxx-xxA LOAD NC NO xxA GND jumper optional E-T-A 111 High Power-D-Box Schematic diagrams
www.e-t-a.de Modular High Power-D-Box® 1630 Modular High Power-D-Box® Load terminals front Load terminals rear 245 9.659.65 310 12.212.2245 310 225 8.868.86 160 6.306.30 225 160 optional isolated cable clamp rail optional cable clamp rail optional isolated cable clamp rail A1 A2 A3 A4 A5 A6 B1 B2 B3 B4 B5 B6 cable guiding operation area screw driver cable guiding operation area ratchet wrench hexagon socket screw 515 (ETS) 20.3 465 (19“) 18.3 76.2 (19“) 2.99 531.4 (ETS) 20.9 482.6 (19“) 19.0 75 (ETS) 2.95 88.9 (2HE) 3.50 Dimensions
www.e-t-a.de Modular High Power-D-Box® 1630 Accessories Cable clamp rail (fitted when delivered) X 223 260 01 consisting of 2 mounting brackets 1 rod 6 screws
1 Insulating sleeve
Grounding connector incl. mounting material (connection plus to earth) X 223 259 01 consisting of: 2 grounding connectors 4 nuts All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications wit- hout notice is reserved. Product markings may not be exactly as the ordering codes. Errors and omissions excepted. load terminals supply feed terminals max current load rear rear terminal 95 mm2 232 A PDB - N - D 06 - RF 10 mm2 65 A 1.5 to 1.8 Nm 15 to 20 Nm PDB - N - D 06 - RR 35 mm2 125 A 3.2 to 3.7 Nm 15 to 20 Nm PDB - N - D 08 - RF 10 mm2 65 A 1.5 to 1.8 Nm 15 to 20 Nm PDB - N - D 08 - RR 35 mm2 125 A 3.2 to 3.7 Nm 15 to 20 Nm PDB - N - D 10 - RF 10 mm2 65 A 1.5 to 1.8 Nm 15 to 20 Nm PDB - N - D 10 - RR 16 mm2 85 A 2.5 to 3 Nm 15 to 20 Nm PDB - N - D 12 - RF 10 mm2 65 A 1.5 to 1.8 Nm 15 to 20 Nm PDB - N - D 12 - RR 16 mm2 85 A 2.5 to 3 Nm 15 to 20 Nm PDB - N - D 16 - RR 16 mm2/ 4 mm2 6 x 85 A / 10 x 30 A 2,5 to 3 Nm (16 mm2) 0,6 to 0,8 Nm (4 mm2) 15 to 20 Nm Grounding M8 - 12-15 Nm Terminal group signalisation 1.5 mm2 - 0.22 bis 0.25 Nm