I/O Terminal Sockets to Flexibly Build Systems

  • Mount either G7T I/O Relays or G3TA SSRs.
  • Compact size for both Input and Output I/O Terminal Sockets: 182 (102 for 8 I/O points) (W) × 85 (D) × 68 (H) mm.
  • Surge absorption circuits provided.
  • LED indicators as a standard feature.
  • DIN Track mounting.

Ordering Information

Accessories (Order Separately) Cables for I/O Relay Terminals

  • Cables with Loose Wires and Crimp Terminals: XW2Z-RY C
  • Cables with Loose Wires: XW2Z-RA C
  • Cables with Connectors: XW2Z-R
  • Cables with Connectors (1:2): XW2Z-RO and XW2Z-RI
  • Cables with Connectors (1:1): XW2Z-R C Refer to the XW2Z-R Datasheet for details. Shorting Bar Output Short-Circuit Module Sockets Indicator Module (with Surge Suppressing Function) Note: 1. Order the Indicator Module that is suited to the Relay coil voltage. 2. The Indicator Module for DC Relays has a multiple power supply common to 12 and 24 VDC. 3. The input current is as given below (reference values). 100/110 VAC: 1.14 to 1.38 mA 200/220 VAC: 1.40 to 1.71 mA 12/24 VDC: 4.83 to 5.90 mA 4. Weight: Approx. 6 g Accessories for DIN Track Mounting Refer to your OMRON website for details on the PFP- I/O classification I/O points Internal I/O common Rated voltage Model For inputs NPN (− common)

12 VDC P7TF-IS16 DC12

24 VDC P7TF-IS16 DC24

100/110 VDC P7TF-IS16 DC100/110 100/110 VAC P7TF-IS16 AC100/110 200/220 VAC P7TF-IS16 AC200/220 For outputs NPN (+ common)

12 VDC P7TF-OS16 DC12

24 VDC P7TF-OS16 DC24

PNP (− common)

12 VDC P7TF-OS16-1 DC12

24 VDC P7TF-OS16-1 DC24

8 NPN (+ common)

12 VDC P7TF-OS08 DC12

24 VDC P7TF-OS08 DC24

When ordering, specify the rated voltage. Model G78-04 Model G77-S Model P7TF-05 Type Applicable relay coil voltage Model Remarks For AC Relays 100 (110) VAC P70A AC100/110 Varistors 200 (220) VAC P70A AC200/220 For DC Relays 12/24 VDC P70D DC12/24 Diodes

P7TF-IS16_OS16_OS08 Accessories (Order Separately) Mountable I/O Relays Mountable I/O SSRs Note: “For inputs” and “for outputs” indicate the I/O relationship to a PLC. Input Relays and SSRs are mainly suitable for input signals to a PLC or other device. Output Relays are mainly suitable to switching loads that receive output signals from a PLC or other device. The Input and Output Relays and SSRs have different switching performances. Select a suitable Relay for the application. *Mounted as standard features to G7TC I/O Relay Terminals. Specifications Note: The above values are initial values. *Measurement: 1 A at 5 VDC. I/O classification Rated coil voltage Contact structure Case color Rated load (resistive load) Model For inputs

12 VDC

1 A at 24 VDC

1 A at 110 VAC

G7T-1122S DC12 *

24 VDC G7T-1122S DC24 *

100/110 VDC G7T-1122S DC100/110 * 100/110 VAC Transparent red G7T-1122S AC100/110 * 200/220 VAC G7T-1122S AC200/220 * For outputs

2 A at 220 VAC

G7T-1112S DC12 *

24 VDC G7T-1112S DC24 *

24 VDC G7T-1012S DC24

classification Rated input voltage Isolation Operation indicator Zero cross function Applicable load Model For inputs 5 to 24 VDC Photocoupler Yes --- Logic level supply current: 25 mA G3TA-IDZR02S DC5-24 4 to 24 VDC No G3TA-IDZR02SM 100 to 240 VAC Yes G3TA-IAZR02S AC100-240 For outputs

2 A at 100 to 240 VAC

24 VDC G3TA-OA202SZ DC24

24 VDC G3TA-OA202SL DC24

2 A at 5 to 48 VDC

24 VDC G3TA-ODX02S DC24

1 A at 48 to 200 VDC

24 VDC G3TA-OD201S DC24

Contact resistance* 10 mΩ max. Terminal block Permissible current 100 mA 10 A Dielectric strength 1,000 VAC, 50/60 Hz for 1 minute 2,000 VAC, 50/60 Hz for 1 minute Insulation resistance 100 MΩ min. (at 500 VDC) 1,000 M Ω min. (at 500 VDC) Vibration resistance 10 to 55 Hz with 1.0-mm double amplitude Shock resistance 200m/s2 Noise immunity Noise level: 1.6 kV; pulse width: 100 ns to 1 µs Ambient operating temperature 0 to 55°C (with no icing or condensation) Ambient operating humidity 35% to 85% Tightening torque for external connections 0.78 to 1.17 N·m LED color Red Green Coil surge absorption element Varistors Diodes (1 A, 400 V) Protection diode for inverse connection Diodes (2 A, Reverse withstand voltage: 400 V) Weight Approx. 360 g Approx. 400 g Approx. 350 g

P7TF-IS16_OS16_OS08 Internal Circuits P7TF-IS16 For AC (NPN input/- common) For DC (NPN input/- common) Note: Pin numbers are indicated for convenience. The mark can be used to determine orientation. I/O indications on Screw Terminals 20Connector pin No. mark Screw terminals Connector pin No. C10 C11 C12 C13 C14 C15− Connector Pin Configuration Top View I/O indications on Screw Terminals 20Connector pin No. mark + 0 C10 C11 C12 C13 C14 C15− Screw terminals Connector pin No. Connector Pin Configuration Top View

P7TF-IS16_OS16_OS08 P7TF-OS16 (NPN output/+ common) P7TF-OS16-1 (PNP output/- common) P7TF-OS08 (NPN output/+ common) Note: Pin numbers are indicated for convenience. The mark can be used to determine orientation. I/O indications on Screw Terminals 20Connector pin No. mark C10 C11 C12 C13 C14 C15− C10 C11 C12 C13 C14 C15 Screw terminals Connector pin No. Connector Pin Configuration Top View I/O indications on Screw Terminals Connector pin No. mark + 0 C10 C11 C12 C13 C14 C15− Screw terminals Connector pin No. Connector Pin Configuration Top View I/O indications on Screw Terminals 20Connector pin No. mark + 0 C7− Screw terminals Connector pin No. Connector Pin Configuration Top View

P7TF-IS16_OS16_OS08 Dimensions (Unit: mm) I/O Terminal Sockets P7TF-IS16 182 Thirty-six, M3.5 3426 108 35.3 + 0.2 32.5 P7TF-OS16 P7TF-OS16-1 182 Thirty-six, M3.5 108 35.3 + 0.2 32.5 P7TF-OS08 102 Twenty, M3.5 108 35.3 +0.2 32.5

P7TF-IS16_OS16_OS08 Accessories (Order Separately) Shorting Bar G78-04 Use this piece for short-circuiting across terminals. Max. current flow: 20 A 4.5 12.513.3 R1.8 R1.0 37.8 2.510 10 10 7.8 0 −0.1 3.6 0 −0.1 Output Short-Circuit Module G77-S The output of the I/O Relay Terminal can be obtained without relays through the G77-S Output Short-Circuit Module. Refer to Connection Example for SPDT Relays on page 7 for details. Note that the G77-S Output Short-Circuit Module is not available for inputs. 32 max. 39 max. 1.6 2.4 0.5 29 max. 33.5 max. 10 max. 4 Four, 1-dia. holes 3.15 10 max. 15±0.1 Terminal Arrangement/ Internal Connections (Bottom View) (The coil has no polarity.) 12.5±0.2 62±0.1 4 dia. or M3 19 max. 71.5 max. 12.5±0.2 60.5 max. 19.5 35.5 Five, M3.5 × 8 screws with square washers 2 3 Internal Connections (Top View) Sockets (Can be used for G7T models with SPST-NO, SPST-NC, or SPDT specifications or G3TA models.) Mounting Hole Dimensions Note: Terminal 1 is positive when the G3TA or Indicator Module is employed. P7TF-05 Can be used for sequences that use Slim Relays and for applications that develop to SPDT contacts on I/O Relay Terminals. To use SPDT on the P7TF I/O Terminal Socket, insert an Output Short-Circuit Module on the I/O Terminal, and combine the Block Base with an SPDT Relay on the output from the Output Short- Circuit Module. Specifications * Measurement conditions: 1 A at 5 VDC using the voltage drop method Contact resistance * 10 mΩ max. Dielectric strength 2,000 VAC for 1 minute Insulation resistance 1,000 MΩ min. (at 500 VDC) Vibration resistance 10 to 55 to 10 Hz with 0.5-mm single amplitude (1.0-mm double amplitude) Shock resistance 1,000m/s2 Ambient operating temperature −40 to 70°C (with no icing or condensation) Ambient operating humidity 5% to 85% Weight Approx. 28 g Note: Terminal 1 is positive when the I/O SSR is employed. 29.5 max. 32.5 max. 39 max. 0.5 1.6 Two, 1-dia. holes 2.6 8.5 max. (+) (−) DC AC There is no coil polarity for AC Relays. Indicator Module (with Surge Suppressing Function) P70 Remove the transparent style strip of the P7TF-05 socket and mount this module and it will function as an operation indicator with the surge suppression.

P7TF-IS16_OS16_OS08 Connection Example for SPDT Relays The following is an application example for the P7TF-05 using an SPDT Relay on a terminal of the P7TF- OS16/OS08. Note: If more than one G77-S Output Short-Circuit Module is employed, the voltage output of the terminals on the P7TF is as follows: P7TF-OC16: The positive side (the lower row) connects to the common line internally. P7TF-OC16-1: The negative side (the upper row) connects to the common line internally. + 01234567 8 9 1 01 11 21 31 4 15 − C0 C1 C2 C3 C4 C5 C6 C7 C 8 C9 C10 C11 C12 C13 C14 C15

12 VDC or 24 VDC

(Depends on the model.) L0 L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11 L12 L13 L14 L16 L15 G7T (SPDT) P7TF-05 NO contact NO contact load SPDT contact load NC contact G7T (SPST-NO) *Use the G77-S Output Short-Circuit Module in place of the G7T I/O Relay. With the G77-S voltage output is available between terminals 15 and C15. The maximum current is determined according to the controller. AC (DC power supply is also possible.) Independent commons can also be used.

P7TF-IS16_OS16_OS08 Safety Precautions Be sure to read the Common Precautions for I/O Relay Terminal in the website at the following URL: http://www.ia.omron.com/. Warning Indications General I/O Relays and I/O Relay Terminal can be combined as follows to from I/O Relay Terminal: *Relays are not mounted to the P7TF I/O Terminal Socket. Mount I/O Relays or I/O SSRs to the sockets. Specify the rated voltage in the same way as when ordering the P7TF I/O Terminal Socket.  Combinations of AC Input Relays/SSRs and DC Input Relays/ SSRs cannot be used with the same I/O Terminal Socket. This is because specifications for coil surge absorption elements are different. Relays/SSRs with different voltage specifications cannot be used with the same I/O Terminal Socket. (For example, a 100-VAC Input Relay/SSR and a 200-VAC Input Relay/SSR, or a 12-VDC Output Relay/SSR and a 24-VDC Output Relay cannot be used with the same I/O Terminal Socket.) This is because specifications of operation indicator circuits are different.  Only use I/O Terminal Sockets, I/O Relays, and I/O SSRs with the same specifications for rated voltage.  I/O Terminal Socket are color coded, as shown below, according to input/output and AC/DC specifications.  Indicators indicate the pr esence or absence of signals. Use the display lever inside each relay for fault diagnosis. (Some relays do not have this lever depending on the specifications.)  Each relay must be pressed down until its hold-down hooks engage completely. Heating or malfunction can result if relays are not mounted properly.  Unlabeled terminals are not electrically connected. Use these for repeater terminals.  Indicator positions and relay orientation differ between Input and Output I/O Terminal Socket. This is to aid in differentiating Input I/O Terminal Sockets from Output Terminal Sockets and in following signal flow.  DC Input I/O Terminal Sockets and Output I/O Terminal Sockets with G3TA-OD@@@@ have positive and negative terminals, with the positive terminals normally being on the top of the I/O Relay Terminal Socket. Reversing positive and negative terminals will prevent operation.  DIN tracks are generally used to mount I/O Relay Terminal. For screw mounting, a 210-mm DIN track is available that can be used as an adapter in combination with End Plates (PFP-M, two required).  A Shorting Bar is provided to connect four terminals. The current capacity of the shorting bar is 20 A. As long as this current capacity is not exceeded, the shorting bar can be used in combination as shown below to connect more than four terminals.  Special Connecting Cables ar e provided for connections to OMRON SYSMAC PLC I/O Units with Connectors. Connecting Cables with two connectors, however, come in two types: Cables for Input Blocks (XW2Z-RI) and Cables for Output Blocks (XW2Z- RO). Be sure to purchase the correct Cable for the application. Microload Switching  Input Relays (DC coil type) and I/O SSRs (DC input type) can be mounted onto an Output I/O Terminal Socket. Precautions for Correct Use Supplementary comments on what to do or avoid doing, to prevent failure to operate, malfunction or undesirable effects on product performance. Precautions for Correct Use I/O Terminal Socket * Replaceable Relay I/O Relay I/O SSR For outputs DC P7TF-OS16 P7TF-OS16-1 P7TF-OS08 G7T-1112S (SPST-NO type) G7T-1012S (SPST-NC type) AC G3TA-OA202SZ G3TA-OA202SL DC G3TA-ODX02S G3TA-OD201S For inputs DC P7TF-IS16 (DC) G7T-1122S DC G3TA-IDZR02S(M) AC P7TF-IS16 (AC) AC G3TA-IAZR02S I/O terminal label I/O terminal indicators I/O Relay case For outputs DC Yellow Green Transparent For inputs DC Red Green Green AC Red Red Red

Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT , MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Re medy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environmen ts. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT , INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT , WARRANTY , NEGLIGENCE OR STRICT LIABILITY . Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall no t be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine , system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions. 2018.4 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2018 All Right Reserved.