G2RV-STG3RV-STCommon Accessories Common Precautions Slim I/O Relay/Slim I/O Solid State Relay G2RV-ST/G3RV-ST Slim I/O relay realizes space saving thanks to high-density mounting and ultra-slim body
- 60% space saving from G2R series with 6.2 mm width.
- 60%* reduction in wiring time and user-friendly with a low insertion force thanks to Push-In Plus Technology.
- Larger hole and angled structure contribute to efficient wiring and standardization of wires up to AWG14, 2.5 mm2.
- Easy maintenance with improved LED visibility and color stopper voltage line identification.
- Low cutting force of short bars contribute to reducing health issues such as Tenosynovitis. * According to OMRON actual measurement data for both push-in plus terminal blocks and screw terminal blocks. Slim I/O Relay Types Common matter Common features of G2RV-ST/G3RV-ST For the recent information on models that have been certified for safety standards, refer to your OMRON website. Refer to Safety Precautions on page 22. Isolation plate IP20 IP20 Both easy replacement and detachment prevention of relays are achieved by locking and unlocking of stopper. Designed so that wires are hard come out even if release levers are touched unintentionally. Visibility is enhanced by release lever LED Easy and safe Short bar cutting force has been decreased to reduce the burden during assembly. Electrification of the short bar fracture plane is prevented by an isolation plate. DC common wiring also provides support for 2.5 mm 2 dia./AWG14 (2.0 mm2) needs Wiring work efficiency improvement Easy to see and easy insertion thanks to large-diameter wiring holes and tilted structure. Work judgment support is provided through mounting feeling enhancement. Work efficiency is enhanced by DIN rail sliding performance and short bar improvements. Note. Cutting force of 25 kg, so easily cut by needle-nose pliers Insertion feeling to let you know when mounting is complete. DIN rail tolerance is also supported through elasticity. Lock Unlock Maintainability is enhanced by color stoppers Wiring standardization is also supported by 2.5 mm 2 compatibility Coil voltage line identification Red: AC Blue: DC White: Multi (e.g. 24 VAC/VDC) IP20 IP20 Visibility from the front is improved by a structure where the actual release lever lights and by expanding the light emission area. Note. The third relay from the right is equipped with a label.
G2RV-STG3RV-STCommon Accessories Common Precautions Slim I/O Relay G2RV-ST Slim I/O relay realizes space saving thanks to high-density mounting and ultra-slim body
- 60% space saving from G2R series with 6.2 mm width technology.
- 6 0 % *1 reduction in wiring time and user-friendly with a low insertion force thanks to Push-In Plus Technology.
- Max. 6 A realized even with close-contact mounting.
- Au-plated contacts suitable for micro loads with a failure rate P value*2 of 1 mA at 100 mVDC.
- A transparent case that allows for easy on-site visual checks of contact state abnormalities.
- Easy relay replacement with a terminal structure that does not bend easily.
- Operation check using a test switch reduces inspection time.
- A coil surge absorption circuit equipped as standard. *1. According to OMRON actual measurement data for both push-in plus terminal blocks and screw terminal blocks. *2. Reference value
Features
For the recent information on models that have been certified for safety standards, refer to your OMRON website. Refer to Safety Precautions on page 22. Transparent case Relay contact Release lever Plug-in terminal Peace of mind as the terminal does not bend when replacing Easy confirmation of the situation Relay easily fixed/removed 88 mm 90 mm Terminal x 5
- Push-in Screw Mechanical indicator Release lever Operation display LED (Socket section) Operation verification which is linked to the contact Standard model/Micro load With latching lever (Test switch) Latching lever (Test switch) Circuit check operation Confirmation, reducing the inspection effort Latching lever (Test switch) Protective cover (Released state) Push-In Plus technology Short bar insertion holes Terminal (insertion) hole Release hole Protective cover (Locked condition)
G2RV-STG3RV-STCommon Accessories Common Precautions Model Number Structure Model Number Legend
Ordering Information
Note: Sockets are not sold individually. Terminal (Wire connection) Classification Latching lever (Test switch) Rated input voltage (V) Model Push-In Plus Terminal Standard No DC
12 G2RV-ST500 12 VDC
24 G2RV-ST500 24 VDC
24 G2RV-ST500 24 VAC/VDC
48 G2RV-ST500 48 VAC/VDC
100 G2RV-ST500 100 VAC
110 G2RV-ST500 110 VAC
200 G2RV-ST500 200 VAC
230 G2RV-ST500 230 VAC
AC/DC 24 G2RV-ST501 24 VAC/VDC Microloads No DC
12 G2RV-ST500-AP 12 VDC
24 G2RV-ST500-AP 24 VDC
24 G2RV-ST500-AP 24 VAC/VDC
48 G2RV-ST500-AP 48 VAC/VDC
100 G2RV-ST500-AP 100 VAC
110 G2RV-ST500-AP 110 VAC
200 G2RV-ST500-AP 200 VAC
230 G2RV-ST500-AP 230 VAC
12 G2RV-ST700 12 VDC
24 G2RV-ST700 24 VDC
24 G2RV-ST700 24 VAC/VDC
48 G2RV-ST700 48 VAC/VDC
100 G2RV-ST700 100 VAC
110 G2RV-ST700 110 VAC
200 G2RV-ST700 200 VAC
230 G2RV-ST700 230 VAC
AC/DC 24 G2RV-ST701 24 VAC/VDC Microloads No DC
12 G2RV-ST700-AP 12 VDC
24 G2RV-ST700-AP 24 VDC
24 G2RV-ST700-AP 24 VAC/VDC
48 G2RV-ST700-AP 48 VAC/VDC
100 G2RV-ST700-AP 100 VAC
110 G2RV-ST700-AP 110 VAC
200 G2RV-ST700-AP 200 VAC
230 G2RV-ST700-AP 230 VAC
(1) Basic model name G2RV: Slim I/O Relay (2) Sub type ST: Slim relay + integrated low profile socket (3) Terminal (wire connection) 50: Push-In Plus Terminal 70: Screw terminal (4) Latching lever (test switch) 0: Without latching lever 1: With latching lever (5) Contact structure Blank: Standard AP: Microloads (6) Rated input voltage 12, 24 VDC 24, 48 VAC/VDC 100, 110, 200, 230 VAC
G2RV-STG3RV-STCommon Accessories Common Precautions Relay for Maintenance Model Number Legend List of Models Note: Voltage is reduced within the socket for the slim I/O relay, so the rated input voltage and rated coil voltage of replacement relays are different. Accessories (order separately) Refer to page 29 for G2RV-ST/G3RV-ST Common Accessories. (1) No. of poles 1: 1 pole (2) Terminal S: plug-in (3) Latching lever (Test switch) Blank: Without latching lever I: With latching lever (4) Contact material Blank: Ag alloy AP: Ag alloy + Au plating (5) Types of relay for exchange G: G2RV-ST series equipped Relay (6) Rated coil voltage Number: 11, 21, 48 VDC G2RV-1-SI-G G2RV-1-S(-AP)-G Type Latching Lever (Test switch) Rated coil voltage (V) Model Applicable model Standard No DC
11 G2RV-1-S-G DC11 G2RV-ST700/500 12 VDC
21 G2RV-1-S-G DC21
48 G2RV-1-S-G DC48
Yes DC 21 G2RV-1-SI-G DC21 G2RV-ST701/501 24 VDC G2RV-ST701/501 24 VAC/VDC Microload No DC
11 G2RV-1-S-AP-G DC11 G2RV-ST700/500-AP 12 VDC
21 G2RV-1-S-AP-G DC21
G2RV-ST700/500-AP 24 VAC/VDC
48 G2RV-1-S-AP-G DC48
G2RV-ST700/500-AP 48 VAC/VDC G2RV-ST700/500-AP 100 VAC G2RV-ST700/500-AP 110 VAC G2RV-ST700/500-AP 200 VAC G2RV-ST700/500-AP 230 VAC
G2RV-STG3RV-STCommon Accessories Common Precautions Specifications Ratings Coil ratings Note: The operating characteristics are measured at ambient temperature of 23°C. * Operating voltage will be, for mounting in the upside down direction, 85% max. (Upside down: Direction in which the mechanical indicator faces down) Contact ratings *1. P level: λ60=0.1×10-6/times This value is the value in switching frequency 120 operations/min. *2. If the Au plating layer is destroyed, the number will be the same as the standard type. *3. Please energize under 32A total when use short bar connection. Rated input voltage Rated current Must operate voltage Must release voltage Power consumption Maximum allowable voltage AC DC Percentage of the rated voltage AC (VA) DC (mW) Percentage of the rated voltage50 Hz 60 Hz 12 VDC – – 27.9 mA 80% max.* 10% min. – Approx. 300 mW 110% 24 VDC – – 13.5 mA – Approx. 300 mW 100 VAC 6.8 mA 7.1 mA – Approx. 0.8 VA – 110 VAC 6.1 mA 6.4 mA – Approx. 0.8 VA – 200 VAC 6.1 mA 7.3 mA – Approx. 1.7 VA – 230 VAC 6.8 mA 8.2 mA – Approx. 1.7 VA – Item Standard (G2RV-ST700, 500, 701, 501) For microloads (G2RV-ST700-AP, 500-AP) *2 Contact configuration SPDT Load Resistive load (cosφ=1) Inductive load (cosφ=0.4, L/R=7ms) Resistive load (cosφ=1) Rated load 6 A at 250 VAC
6 A at 30 VDC
2.5 A at 250 VAC
2 A at 30 VDC
Rated carry current *3 6 A 50 mA Maximum switching voltage 440 VAC, 125 VDC 30 VAC, 36 VDC Maximum switching current 6 A 50 mA Maximum switching power 1,500 VA 180 W 500 VA
60 W –
(reference value) *1 10 mA at 5 VDC 1 mA at 100 mVDC
G2RV-STG3RV-STCommon Accessories Common Precautions Characteristics Note: Above values are initial values. * Value is at ambient temperature of 23°C. Item Standard (G2RV-ST700, 500, 701, 501) For microloads (G2RV-ST700-AP, 500-AP) Contact resistance * 100 m Ω max. Operate time * 20 ms max. Release time * AC, AC/DC: 40 ms max. DC: 20 ms max. Maximum operating frequency Mechanical: 18,000 operations/h Electrical: 1,800 operations/h (rated load) Insulation resistance 1,000 MΩ min. (at 500 VDC) Dielectric strength Between coil and contacts: 4,000VAC 50/60 Hz 1 min Contact between the same polarity: 1,000 VAC 50/60 Hz 1 min Vibration resistance Destruction: 10 to 55 to 10 Hz, single amplitude 0.50 mm (double amplitude 1.0 mm) Malfunction: 10 to 55 to 10 Hz, single amplitude 0.50 mm (double amplitude 1.0 mm) Shock resistance Destruction: 1,000 m/s2 Malfunction: Energized 200m/s2, Non-energized 100m/s2 Endurance * Mechanical 5,000,000 operations min. Electrical NO contact: 70,000 operations min. NC contact: 50,000 operations min. 5,000,000 operations min. Ambient operating temperature Operating: –40 to +55°C (with no icing or condensation) Ambient operating humidity Operating: 5 to 85% RH Weight Approx. 30 g Type of interruption Micro-disconnection Type of insulation Basic isolation: Coil-Contact, Live parts-Ground Pollution degree 2 Impulse withstand voltage 4.0 kV Test procedure A (Group mounting) Categories of environmental protection RT 1 Degree of protection by enclosure according to IEC 60529 IP20 Contact material Ag alloy Ag alloy + Au plating
G2RV-STG3RV-STCommon Accessories Common Precautions Approved standards UL (File No.E41643) * If the load voltage exceeds 250 VAC, please attach with a spacing of 12 mm min., or use a separate plate (XW5Z-EP12) or 4psc of isolation plate (P2RV-P3.1T). TÜV (File No.R50327609, EN 61810-1) * If the load voltage exceeds 250 VAC, please attach with a spacing of 12 mm min., or use a separate plate (XW5Z-EP12) or 4psc of isolation plate (P2RV-P3.1T). Reference Data Endurance curve (N.O. side) Switchi ng capacity of DC resistive load Model Contact form Operation coil ratings Contact ratings Operations G2RV-ST series SPDT 12 to 48 VDC 24 to 230 VAC
6 A at 250 VAC (Resistive load)
6 A at 30 VDC (Resistive load)
2 A at 400 VAC (Resistive load)*
6,000 12 mm 12 mm 12 mm Model Contact form Operation coil ratings Contact ratings Operations G2RV-ST series SPDT 12, 24 VDC 24, 48 VAC/VDC 100, 110, 200, 230 VAC 50,000 50,000 6,000 12 mm 12 mm 12 mm 100 1000 024 Opening and closing current (A)
250 VAC resistive load
30 VDC resistive load
30 VDC
250 VAC inductive load
Number of operations (x 103 operations) 0.1 1.0 10.0 20 60 100 140 180 220 DC switching voltage (V) DC breaking current (A)
G2RV-STG3RV-STCommon Accessories Common Precautions Dimensions (unit: mm) Slim I/O Relay + socket Push-In Plus Terminal Block Models without latching lever (without test switch) G2RV-ST500 G2RV-ST500-AP Note: For recommended ferrules, crimp tools, and types and gauges of wires, refer to 3. Recommended Ferrules and Crimp Tools on page 26. 6.2 30.9 27.1 7.1 82.2 34.8 74.2 47.4 30.93.4 47.4 63.9 G2RV G2RV G2RV-ST500(-AP) 24 VDC G2RV-ST500(-AP) 12 VDC G2RV G2RV-ST500(-AP) 24 VAC/VDC G2RV-ST500(-AP) 48 VAC/VDC G2RV-ST500(-AP) 100 VAC G2RV-ST500(-AP) 110 VAC G2RV-ST500(-AP) 200 VAC G2RV-ST500(-AP) 230 VAC Input circuit Input circuit(+) (-) (+) (-) Input circuit : Diode bridge Equipped with a coil surge absorption circuit as standard. : Light emitting diode Terminal Arrangement/Internal Connection Diagram (TOP VIEW) Models with latching lever (with test switch) G2RV-ST501 Note: For recommended ferrules, crimp tools, and types and gauges of wires, refer to 3. Recommended Ferrules and Crimp Tools on page 26. 6.2 76.2 47.4 30.9 30.97.1 47.4 63.9 27.1 82.2 34.8 G2RV G2RV 1111 Input circuitInput circuit G2RV-ST501 24 VDC G2RV-ST501 24 VAC/VDC : Diode bridge : Light emitting diode Terminal Arrangement/Internal Connection Diagram (TOP VIEW) Equipped with a coil surge absorption circuit as standard. (+) (-) (+) (-)
G2RV-STG3RV-STCommon Accessories Common Precautions Screw terminal Models without latching lever (without test switch) G2RV-ST700 G2RV-ST700-AP Note: For recommended ferrules, crimp tools, and types and gauges of wires, refer to 3. Recommended Ferrules and Crimp Tools on page 26. 29.67.1 46.1 62.6 6.2 27.1 82.2 34.8 74.2 46.1 29.63.4 Five, M2.6 G2RV G2RV G2RV G2RV-ST700(-AP) 24 VDC G2RV-ST700(-AP) 12 VDC G2RV-ST700(-AP) 24 VAC/VDC G2RV-ST700(-AP) 48 VAC/VDC G2RV-ST700(-AP) 100 VAC G2RV-ST700(-AP) 110 VAC G2RV-ST700(-AP) 200 VAC G2RV-ST700(-AP) 230 VAC Input circuit Input circuit Input circuit : Diode bridge : Light emitting diode Terminal Arrangement/Internal Connection Diagram (TOP VIEW) Equipped with a coil surge absorption circuit as standard. (+) (-) (+) (-) Models with latching lever (with test switch) G2RV-ST701 Note: For recommended ferrules, crimp tools, and types and gauges of wires, refer to 3. Recommended Ferrules and Crimp Tools on page 26. 29.67.1 46.1 62.6 6.2 27.1 82.2 34.8 76.2 46.1 29.63.4 Five, M2.6 G2RV G2RV G2RV-ST701 24 VDC G2RV-ST700(-AP) 24 VAC/VDC Input circuitInput circuit : Diode bridge : Light emitting diode Terminal Arrangement/Internal Connection Diagram (TOP VIEW) Equipped with a coil surge absorption circuit as standard. (+) (-) (+) (-)
G2RV-STG3RV-STCommon Accessories Common Precautions Relay for maintenance A2A1121114 30.5 3.5 0.5 2.41.8 5.2 5.04 5.04 322 16.2 Terminal Arrangement/ Internal Connection Diagram (TOP VIEW) (Input circuit) Models without latching lever G2RV-1-S-G G2RV-1-S-AP-G Models with latching lever (test switch) G2RV-1-SI-G A2A1121114 30.55.2 1.8 0.5 2.4 5.04 5.04 322 16.2 3.5 Terminal Arrangement/ Internal Connection Diagram (TOP VIEW) (Input circuit)
12 G2RV-STG3RV-STCommon Accessories Common Precautions
Slim I/O Solid State Relay G3RV-ST Slim I/O SSR realizes space saving thanks to high-density mounting and ultra-slim body
- 60% space saving from G3R-I/O series with 6.2 mm width technology.
- 60%* reduction in wiring time and user-friendly with a low insertion force thanks to Push-In Plus Technology.
- Maximum applicable load of 3 A (DC) and 2 A (AC) realized thanks to slim technology.
- The output DC type has a minimum applicable load of 100 µA and a leaked current of 10 µA or less.
- High-speed switching type (operation time of 0.2 ms or less, release time of 0.4 ms or less) added. * According to OMRON actual measurement data for both push-in plus terminal blocks and screw terminal blocks.
For the recent information on models that have been certified for safety standards, refer to your OMRON website. Refer to Safety Precautions on page 22. Short bar insertion holes Terminal (insertion) hole Release hole Terminal x 5 Push-in Screw Release lever Operation display LED (Socket section) Operation display LED (SSR section) Push-In Plus technology 88 mm 90 mm Release lever Plug-in terminal Relay easily fixed/removed Peace of mind as the terminal does not bend when replacing
G2RV-STG3RV-STCommon Accessories Common Precautions G3RV-ST Model Number Structure Model Number Legend (1) Basic model name G3RV: Slim I/O Solid State Relay (2) Sub type ST: Slim solid relay + integrated low profile socket (3) Terminal (wire connection) 500: Push-In Plus Terminal 700: Screw terminal (4) Output voltage specification A : AC output (triac) zero cross function available AL : AC output (triac) zero cross function not available D : DC output (MOS FET) (5) Operation and release time H : High speed type (6) Rated voltage input 12, 24 VDC 24, 48 VAC/VDC 100, 110, 200, 230 VAC
14 G2RV-STG3RV-STCommon Accessories Common Precautions
Note: Sockets are not sold individually. Terminal (wire connection) Applicable output load Zero cross function Rated input voltage (V) Model Push-In Plus Terminal DC load — DC
12 G3RV-ST500-D 12 VDC
24 G3RV-ST500-D 24 VDC
AC/DC 24 G3RV-ST500-D 24 VAC/VDC
48 G3RV-ST500-D 48 VAC/VDC
100 G3RV-ST500-D 100 VAC
110 G3RV-ST500-D 110 VAC
200 G3RV-ST500-D 200 VAC
230 G3RV-ST500-D 230 VAC
(high-speed opening and closing) DC 24 G3RV-ST500-D-H 24 VDC AC/DC 24 G3RV-ST500-D-H 24 VAC/VDC AC load Yes DC
12 G3RV-ST500-A 12 VDC
24 G3RV-ST500-A 24 VDC
24 G3RV-ST500-A 24 VAC/VDC
48 G3RV-ST500-A 48 VAC/VDC
100 G3RV-ST500-A 100 VAC
110 G3RV-ST500-A 110 VAC
200 G3RV-ST500-A 200 VAC
230 G3RV-ST500-A 230 VAC
12 G3RV-ST500-AL 12 VDC
24 G3RV-ST500-AL 24 VDC
AC/DC 24 G3RV-ST500-AL 24 VAC/VDC
48 G3RV-ST500-AL 48 VAC/VDC
100 G3RV-ST500-AL 100 VAC
110 G3RV-ST500-AL 110 VAC
200 G3RV-ST500-AL 200 VAC
230 G3RV-ST500-AL 230 VAC
DC load — DC 12 G3RV-ST700-D 12 VDC
24 G3RV-ST700-D 24 VDC
AC/DC 24 G3RV-ST700-D 24 VAC/VDC
48 G3RV-ST700-D 48 VAC/VDC
100 G3RV-ST700-D 100 VAC
110 G3RV-ST700-D 110 VAC
200 G3RV-ST700-D 200 VAC
230 G3RV-ST700-D 230 VAC
(high-speed opening and closing) DC 24 G3RV-ST700-D-H 24 VDC AC/DC 24 G3RV-ST700-D-H 24 VAC/VDC AC load Yes DC
12 G3RV-ST700-A 12 VDC
24 G3RV-ST700-A 24 VDC
24 G3RV-ST700-A 24 VAC/VDC
48 G3RV-ST700-A 48 VAC/VDC
100 G3RV-ST700-A 100 VAC
110 G3RV-ST700-A 110 VAC
200 G3RV-ST700-A 200 VAC
230 G3RV-ST700-A 230 VAC
12 G3RV-ST700-AL 12 VDC
24 G3RV-ST700-AL 24 VDC
AC/DC 24 G3RV-ST700-AL 24 VAC/VDC
48 G3RV-ST700-AL 48 VAC/VDC
100 G3RV-ST700-AL 100 VAC
110 G3RV-ST700-AL 110 VAC
200 G3RV-ST700-AL 200 VAC
230 G3RV-ST700-AL 230 VAC
G2RV-STG3RV-STCommon Accessories Common Precautions Solid state relay for maintenance List of Models * Different depending on the ambient temperature. For more details, refer to Load current vs. ambient rated temperature on page 18. Accessories (order separately) Refer to page 29 for G2RV-ST/G3RV-ST Common Accessories. Insulation method Operation Display Output (SSR) Zero cross Function Rated output Load * Rated input voltage (socket) Model Applicable model Photo-triac Yes (green) AC Yes 2 A (at 100 to
240 VAC)
12 VDC G3RV-202S DC12 G3RV-ST700/500-A 12 VDC
24 VDC
24 VAC/VDC G3RV-ST700/500-A 24 VAC/VDC
48 VAC/VDC
G3RV-ST700/500-A 48 VAC/VDC
100 VAC G3RV-ST700/500-A 100 VAC
110 VAC G3RV-ST700/500-A 110 VAC
200 VAC G3RV-ST700/500-A 200 VAC
230 VAC G3RV-ST700/500-A 230 VAC
12 VDC G3RV-202SL DC12 G3RV-ST700/500-AL 12 VDC
24 VAC/VDC G3RV-ST700/500-AL 24 VAC/VDC
G3RV-ST700/500-AL 48 VAC/VDC
100 VAC G3RV-ST700/500-AL 100 VAC
110 VAC G3RV-ST700/500-AL 110 VAC
200 VAC G3RV-ST700/500-AL 200 VAC
230 VAC G3RV-ST700/500-AL 230 VAC
DC – 3 A (at 5 to 24 VDC)
12 VDC G3RV-D03SL DC12 G3RV-ST700/500-D 12 VDC
24 VAC/VDC G3RV-ST700/500-D 24 VAC/VDC
G3RV-ST700/500-D 48 VAC/VDC
100 VAC G3RV-ST700/500-D 100 VAC
110 VAC G3RV-ST700/500-D 110 VAC
200 VAC G3RV-ST700/500-D 200 VAC
230 VAC G3RV-ST700/500-D 230 VAC
24 VDC G3RV-D03SL-H DC24
G3RV-ST700/500-D-H 24 VAC/VDC (1) Output voltage specification D: DC output 2: AC output (2) Rated current 02: AC output 2 A 03: DC output 3 A (3) Terminal S: Plug-in type (4) Zero cross functions Blank: Zero cross function available L: Zero cross function not available (5) Operation and release time H : High speed type (6) Rated voltage input Number: 12, 24, 48 VDC Model Number Legend
16 G2RV-STG3RV-STCommon Accessories Common Precautions
Rating (ambient temperature 25°C) Input G3RV-ST700/500-A series G3RV-ST700/500-AL series G3RV-ST700/500-D series High-speed type G3RV-ST700/500-D-H series Output Rated input voltage Rated current Must operate voltage Must release voltage Input voltage AC DC Percentage of the rated voltage50 Hz 60 Hz 12 VDC – – 15.0 mA 10.8 V max. 1 V min. ±10% 24 VDC – – 12.0 mA 21.6 V max. 100 VAC 6.2 mA 6.2 mA – 90 V max. 110 VAC 6.2 mA 6.2 mA – 99 V max. 200 VAC 6.7 mA 7.9 mA – 180 V max. 230 VAC 7.5 mA 8.8 mA – 207 V max. Rated input voltage Rated current Must operate voltage Must release voltage Input voltage AC DC Percentage of the rated voltage50 Hz 60 Hz 12 VDC – – 15.0 mA 10.8 V max. 1 V min. ±10% 24 VDC – – 12.0 mA 21.6 V max. 100 VAC 7.3 mA 7.3 mA – 90 V max. 110 VAC 7.3 mA 7.3 mA – 99 V max. 200 VAC 7.0 mA 8.1 mA – 180 V max. 230 VAC 7.7 mA 8.9 mA – 207 V max. Rated input voltage Rated current Must operate voltage Must release voltage Input voltage AC DC Percentage of the rated voltage50 Hz 60 Hz 12 VDC – – 8.0 mA 10.8 V max. 1 V min. ±10% 24 VDC – – 4.6 mA 21.6 V max. 100 VAC 6.8 mA 6.8 mA – 90 V max. 110 VAC 6.7 mA 6.7 mA – 99 V max. 200 VAC 6.7 mA 7.9 mA – 180 V max. 230 VAC 7.5 mA 8.8 mA – 207 V max. Rated input voltage Rated current Must operate voltage Must release voltage Input voltage AC DC Percentage of the rated voltage50 Hz 60 Hz Item G3RV-ST700/500-A(L) G3RV-ST700/500-D Rated load voltage 100 to 240 VAC (50/60 Hz) 5 to 24 VDC Load voltage range 75 to 264 VAC (50/60 Hz) 3 to 26.4 VDC Load current 0.1 to 2 A (Ambient temperature=25°C) 100 μA to 3 A (Ambient temperature=25°C) Inrush current resistance 30 A (10 ms) 30 A (10 ms) Permissible l2t; Joule integral value (reference value) 15A2s9 A 2 s Applied load capacity 400 W (Output voltage: 200 VAC) 72 W (Output voltage: 24 VDC)
G2RV-STG3RV-STCommon Accessories Common Precautions Characteristics * Operate time is 1/2cycle of load power supply + 1ms, and release time is 1/2 cycle of load power supply + 1ms + 1cycle of input power supply frequency. Approved standards UL (File No.E64562) TÜV (EN 62314) Item G3RV- ST700/500-A G3RV- ST700/500-AL G3RV- ST700/500-D-H
24 VAC/VDC
Output ON voltage drop 1.6 V (RMS) max. – Output ON resistance –0 . 3 Ω max. (at 24 VDC) Leaked current 5 mA max. (at 200 VAC, 50/60 Hz) 10 µA max. (at 24 VDC) Insulation resistance 100 MΩ min. (at 500 VDC) Dielectric strength Between input and output 2,500 VAC 50/60 Hz 1 min Vibration resistance Malfunction: 10 to 55 to 10 Hz double amplitude 0.70 mm Shock resistance 300m/s2 Ambient operating temperature Storage: –30 to +100°C (with no icing or no condensation) Operating: –30 to +55°C (with no icing or no condensation) Ambient operating humidity 45 to 85% RH Weight Approx. 30 g Pollution degree 2 The degree of protection by IEC60529 IP20 Rated impulse dielectric strength 4.0 kV/III Load category LC-A DC-12 Overload current profile 1.5Ie 1.1Ue 5s ON, 10s OFF, 10 cycles Rated insulation voltage 240 V Model Input ratings Contact ratings G3RV-ST700/500-D series 12, 24 VDC 24, 48 VAC/VDC 100, 110, 200, 230 VAC
24 VDC 3 A (resistive load) at 25°C
G3RV-ST700/500-A(L) series 12, 24 VDC 24, 48 VAC/DC 100, 110, 200, 230 VAC
240 VAC 2 A (resistive load) at 25°C
Model Input ratings Contact ratings G3RV-ST700/500-D series 12, 24 VDC 24, 48 VAC/VDC 100, 110, 200, 230 VAC
24 VDC 3 A (resistive load)
G3RV-ST700/500-A(L) series 12, 24 VDC 24, 48 VAC/VDC 100, 110, 200, 230 VAC
240 VAC 2 A (resistive load)
18 G2RV-STG3RV-STCommon Accessories Common Precautions
Load current vs. ambient rated temperature G3RV-ST700/500-A(L) series G3RV-ST700/500-D series Inrush Current Resistance: Non-repetitive Keep the inrush current to below the inrush current resistance value (i.e., below the broken line) if it occurs repetitively. Product mounting spacing 10 mm (Separate Mounting) Close mountin g (up to 8 units *) Product mounting spacing 10 mm (Separate Mounting) Close mountin g (up to 8 units *) * When eight or more are installed, install with 10 mm space between each. For details, please refer to Mounting on page 27. G3RV-ST700/500-A(L) series G3RV-ST700/500-D series −30 −20 0 40 60 80 100 55 Ambient temperature (°C) Load current (A) 2010 Ambient temperature (°C) Load current (A) 0.2 0.4 0.6 0.8 1.2 −30 −20 −10 0 10 20 30 40 50 60 55 During close mounting with 8 units −30 −20 0 40 60 80 100 55 20 25 Ambient temperature (°C) Load current (A) Ambient temperature (°C) Load current (A) 25 55 0.5 1.5 2.5 3.5 −30 −20 −10 0 10 20 30 40 50 60 During close mounting with 8 units Inrush current (A.Peak) 10 30 50 100 300 500 1,000 3,000 5,000 Energized time (ms) 010 30 50 100 300 500 1,000 3,000 5,000 Inrush current (A.Peak) Energized time (ms)
G2RV-STG3RV-STCommon Accessories Common Precautions G3RV-ST Dimensions (unit: mm) Solid state relay + socket Push-In Plus Terminal Block G3RV-ST500 Terminal Arrangement/ Internal Connection Diagram (TOP VIEW) Note: For recommended ferrules, crimp tools, and types and gauges of wires, refer to 3. Recommended Ferrules and Crimp Tools on page 26. A2- A1+ 13 (+) 14 (-) G3RV G3RV INPUT OUTPUT A2- A1+ 13 (+) 14 (-) INPUT OUTPUT G3RV A2- A1+ 13 (+) 14 (-) INPUT OUTPUT The information in parentheses in for a DC output. The information in parentheses in for a DC output. The information in parentheses in for a DC output. : Diode bridge : Light emitting diode Equipped with a coil surge absorption circuit as standard. G3RV-ST 24 VDC G3RV-ST 12 VDC G3RV-ST 24 VAC/VDC G3RV-ST 48 VAC/VDC G3RV-ST 100 VAC G3RV-ST 110 VAC G3RV-ST 200 VAC G3RV-ST 230 VAC Input circuit Input circuit Input circuit (+) (-) (+) (-) 6.2 7.1 3.4 63.9 27.1 82.2 34.8 74.2 Two, 47.4 Two, 30.9
20 G2RV-STG3RV-STCommon Accessories Common Precautions
Internal Connection Diagram (TOP VIEW) Note: For recommended ferrules, crimp tools, and types and gauges of wires, refer to 3. Recommended Ferrules and Crimp Tools on page 26. G3RV A2- A1+ 13 (+) 14 (-) INPUT OUTPUT G3RV A2- A1+ 13 (+) 14 (-) INPUT OUTPUT G3RV A2- A1+ 13 (+) 14 (-) INPUT OUTPUT The information in parentheses in for a DC output. The information in parentheses in for a DC output. The information in parentheses in for a DC output. : Diode bridge : Light emitting diode Equipped with a coil surge absorption circuit as standard. G3RV-ST 24 VAC/VDC G3RV-ST 48 VAC/VDC G3RV-ST 100 VAC G3RV-ST 110 VAC G3RV-ST 200 VAC G3RV-ST 230 VAC G3RV-ST 12 VDC G3RV-ST 24 VDC Input circuit Input circuit Input circuit (+) (-) (+) (-) 82.2 34.8 27.1 7.1 62.6 6.2 74.2 46.1 29.63.4 Five, M2.6Two, 29.6 Two, 46.1
G2RV-STG3RV-STCommon Accessories Common Precautions Solid state relay for maintenance G3RV-D03SL G3RV-202S(L) Terminal Arrangement/ Internal Connection Diagram (TOP VIEW) G3RV-D03SL (input circuit) Note: The load can be connected to either the positive or negative terminals. G3RV-202S(L) (input circuit) 30.5 2.4 15.8 5.2 3.51.8 5.04 3 14 13 A1 A2 Input Load 14 13 A1 A2 Input Load
22 G2RV-ST G3RV-STCommon Accessories Common Precautions
Be sure to read the Safety Precautions for All Relays in the website at the following URL: http://www.ia.omron.com/. Format of Warning Indications Meaning of Graphic Symbols for Ensuring Product Safety Ensure that the socket is not charged during wiring and maintenance. Not doing so may result in electric shock. Do not touch the terminal section of the G2RV-ST or the surrounding area while the power is being supplied. Doing so may result in electric shock. Minor electrical shock may occasionally occur. Do not touch the G3RV terminal section (i.e., current carrying parts) while the power is being supplied. The G3RV may rupture if short-circuit current flows. As protection against accidents due to short-circuiting, be sure to install protective devices, such as fuses and no-fuse breakers, on the power supply side. Minor electrical shock may occasionally occur. Do not touch the main circuit terminals on the G3RV immediately after the power supply has been turned OFF. Shock may result due to the electrical charge stored in the built-in snubber circuit. Note: G3RV-202S(L), G3RV-ST500/700-A(L) series models only Minor burns may occasionally occur. Do not touch the G3RV or the heat sink while the power is being supplied or immediately after the power supply has been turned OFF. The G3RV becomes extremely hot. Provide a space of at least 3 mm or place an insulating plate (P2RV-P3.1ST) between the G2RV-ST or G3RV-ST and ground and other adjacent components. Not doing so may result in an electric shock. When mounting the G2RV-ST or G3RV-ST with its input and output opposite to the input and output of an adjacent product, provide a space of at least 3 mm or place an insulating plate (P2RV-P3.1ST) between them. WARNING Indicates a potentially hazardous situation which, if not avoided, will result in minor or moderate injury, or may result in serious injury or death. Additionally, there may be significant property damage. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or in property damage. Precautions for Safe Use Indicates supplementary comments on what to do or avoid doing, to use the product safety. Precautions for Correct Use Includes operating precautions to ensure that the product will operate properly and that performance and functions will not be adversely affected. Indicates the possibility of electric shock under specific conditions. Used for general CAUTION, WARNING, or DANGER precautions for which there is no specified symbol. (This symbol is also used as the alerting symbol, but shall not be used in this meaning on the product.) Indicates the possibility of explosion or rupture under specific conditions. Indicates the possibility of injuries by high temperature under specific conditions. WARNING CAUTION
G2RV-ST G3RV-STCommon Accessories Common Precautions Transport
- Do not use the product if it has been dropped on the ground. Dropping the product may adversely affect performance.
- Do not drop the product or subject it to abnormal vibration or shock during transportation or mounting. Doing so may result in deterioration of performance, malfunction, or failure.
- Do not transport the product without it being packaged. Doing so may result in damage, malfunction, or failure.
- Do not transport the G3RV under the following conditions. Doing so may result in damage, malfunction, or deterioration of performance characteristics.
- High temperature, high humidity conditions
- Conditions such as temperatur e change that causes rapid condensation
- Condition where it is not packaged Operating and Storage Environments
- Do not use or store the product in the following locations. Doing so may result in damage, malfunction, or deterioration of performance characteristics.
- Storage in locations subject to ambient temperature outside the range -40 to 70°C (for G2RV) and -30 to 100°C (for G3RV), and usage in locations subject to ambient temperature outside the range -40 to 55°C (for G2RV) and -30 to 55°C (for G3RV).
- Locations subject to relative humidity outside the range 5% to 85% (for G2RV) and outside the range 45% to 85% (for G3RV).
- Locations subject to high temperature or high humidity.
- Conditions such as temperatur e change that causes rapid condensation ocations where corrosive gases or flammable gases are present
- Location where rainwater or water droplets gets splashed
- Location with splashes of wat er, oil, and chemicals, etc.
- Locations with much dust, salt, and iron powder
- Location with blockers
- Where static electricity or noise occurs
- Where strong electromagnetic field is generated
- Where there is a risk o f exposure to radioactivity
- Storage in a state with a load applied to the product
- Locations subject to ultravi olet rays from direct sunlight
- Do not use or store Sockets in environments that contain silicone gas, sulfidizing gas (e.g., SO 2 or H2S), or organic gas, or near materials that contain silicone. Doing so may cause the contacts to be unstable or to fail. Handling <G3RV>
- Keep the G3RV well ventilated. There is a risk of short-circuiting or burning due to G3RV overheating. Mounting
- Before you start wiring, please make sure that the socket is securely attached to the mounting rail. If the socket is unstable, it may come loose and risk of injury towards the workers.
- Please insert the flat-blade screwdriver to the bottom of the hole. If you do not insert the flat-blade screwdriver correctly, the cable will not be connected correctly.
- When lubricant such as oil is attached to the tip of the driver, the driver will fall off, with a risk of injury towards the workers.
- When replacing a relay, set the stopper to the unlocked state and then eject the relay with the ejector lever. In addition, press the stopper after replacement to change the state from unlocked to locked.
- To operate the stopper, you can change the state from locked to unlocked by gripping the stopper protruding part with the recommended needle-nose pliers. (Needle-nose pliers with a tip shape that is 4 mm wide or less and 3 mm thick or less.)
- Do not use cutting nippers to operate the stopper. Doing so may damage the stopper.
- If the stopper is operated with an exceedingly strong force, the stopper protruding part may be damaged and the stopper may drop out. Since the function of the stopper is to fix the ejector lever, use as a product is possible even in the event that the stopper is damaged or drops out because the functionality is satisfied even without a stopper in respect to vibrations and impacts. Usage
- Please select the load within the rated range. Doing so may result in damage, malfunction, or failure.
- Please use the power of the rated frequency. It may cause malfunction, failure, or risk of burnout. <G3RV>
- Install G3RV according to instructions Mounting on page 27. If you install in the wrong direction, abnormal heat is generated, and may lead to short-circuiting or burning the output element.
- G3RV is an SSR that generates heat. Please observe the ambient temperature setting range of G3RV. If installing in an enclosed space, set a fan, and ventilate.
- When mounting G3RV to DIN rail, firmly fits into the groove. If it is not properly installed, there is a risk of it falling. Precautions for Safe Use Locked state Unlocked state
24 G2RV-ST G3RV-STCommon Accessories Common Precautions
- For the current to be applied, make sure a wire size with margin is used. Otherwise, excessive heat generated by the wires may cause burning.
- Do not attempt to use the wire if the coat is torn. Not doing so may result in electric shock.
- Always turn OFF the power supply before performing wiring. Not doing so may cause electrical shock. <G3RV>
- The wires of the socket for G3RV socket should not be passed through the same duct as that being connected to the high-voltage power supply. Otherwise, inductive noise may damage the G3RV or cause it to malfunction. Push-In Plus Terminal Block
- Do not wire anything to the release holes.
- Do not tilt or twist a flat-blade screwdriver while it is inserted into a release hole on the terminal block. The terminal block may be damaged.
- Insert a flat-blade screwdriver into the release holes at an angle. The terminal block may be damaged if you insert the screwdriver straight in.
- Do not allow the flat-blade screwdriver to fall out while it is inserted into a release hole.
- Do not bend the wire past its natural bending radius or pull on it with excessive force. Doing so may cause the wire disconnection. Do not insert more than one wire into each terminal (insertion) hole.
- To prevent wiring materials from smoking or ignition, confirm wire ratings and use the wiring materials given in the following table. Disposal
- When disposing of the product, do not put into the fire.
- Do not use or store the product in the following locations. Doing so may result in damage, malfunction, or deterioration of performance characteristics.
- Where vibration or shock is directly transmitted to the body
- Where the socket could come into contact with a solvent or alkaline agent
- When installing the short bar, insert it into the insertion hole, and insert until all terminals are all the way in.
- To remove the short bar, insert a screwdirver beneath the hole on top of the short bar and lift up. Start lifting up from either end, lift up all screwdriver in order, and then remove the short bar. Recommended Wire Stripping length (Ferrules not used) 0.5 to 2.5 mm2/ AWG20 to AWG14 stranded wire 8 mm Precautions for Correct Use Orient correctly and push all the way in. Completely inserted All terminals are inserted all the way in. Incomplete insertion All terminals are not inserted all the way in. Incomplete insertion Incorrect installation Some terminals not inserted completely. Correct Incorrect Incorrect
G2RV-ST G3RV-STCommon Accessories Common Precautions
- If using a short bar, install the short bar before performing wiring work.
- A push-in Plus terminal block type and a screw terminal type have different insertion positions, so a mixed installation using the same short bar is not possible.
- Do not insert short bar in the hole for wire or screw driver, it may cause the result of failure of pull out. If insert short bar in the hole for wire or screw driver and try to pull out, it may cause damage for short bar or socket and failure in electric conductivity.
- Please insert P2RVC terminal into the short bar insertion hole of G2RV-ST/G3RV-ST. If insert P2RVC into the release hole or terminal (insertion) hole wrongly, P2RVC may stuck and can not remove and it may cause result of damage on P2RVC and G2RV- ST/G3RV-ST. Please turn off the power of input and output side and remove PLC interface unit when replacing mounting relays and SSRs for maintenance.
- When replacing relays, there is a possibility the relay will pop out and fall. Take care to prevent the relay from falling during replacement.
- When replacing a relay, remove it by tilting it to the left as shown in the figure below because the protrusion to prevent pop-out relay will get in the way.
- Dedicated accessories for G2RV-SR/G3RV-SR are not compatible and cannot be used. Short Bars
- PYDN-6.2-020@
- PYDN-6.2-030@
- PYDN-6.2-040@
- PYDN-6.2-100@
- PYDN-6.2-200@ PLC interface unit
- P2RVC-8-I-5-1
- P2RVC-8-I-5
- P2RVC-8-I-7-1
- P2RVC-8-O-5-1
- P2RVC-8-O-5
- P2RVC-8-O-7-1 Push-In Plus Terminal Block 1. Connecting Wires to the Push-In Plus Terminal Block Part Names of the Terminal Block Connecting Wires with Ferrules and Solid Wires Insert the solid wire or ferrule straight into the terminal block until the end strikes the terminal block.
- If a wire is difficult to connect because it is too thin, use a flat-blade screwdriver in the same way as when connecting stranded wire. Connecting Stranded Wires Use the following procedure to connect the wires to the terminal block. (1) Hold a flat-blade screwdriver at an angle and insert it into the release hole. The angle should be between 10°and15°. If the flat-blade screwdriver is inserted correctly, you will feel the spring in the release hole. (2) With the flat-blade screwdriver still inserted into the release hole, insert the wire into the terminal hole until it strikes the terminal block. (3) Remove the flat-blade screwdriver from the release hole. Checking Connections
- After the insertion, pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the terminal block.
- If you use a ferrule with a conductor length of 10 mm, part of the conductor may be visible after the ferrule is inserted into the terminal block, but the product insulation distance will still be satisfied. 2. Removing Wires from the Push-In Plus Terminal Block Use the following procedure to remove wires from the terminal block. The same method is used to remove stranded wires, solid wires, and ferrules. (1) Hold a flat-blade screwdriver at an angle and insert it into the release hole. (2) With the flat-blade screwdriver still inserted into the release hole, remove the wire from the terminal insertion hole. (3) Remove the flat-blade screwdriver from the release hole. Release hole Terminal (Insertion) hole Release hole Terminal (Insertion) hole Ferrules or solid wire (2) 10 to 15° Flat-blade screwdriver(1) (3) (2) (1) (3) Stranded Wires (2) 10 to 15° Wire Flat-blade screwdriver(1) (3) (2) (1) (3)
26 G2RV-ST G3RV-STCommon Accessories Common Precautions
- Recommended ferrules and Crimp Tools Recommended ferrules Note: 1.Make sure that the outer diameter of the wire is smaller than the inner diameter of the insulating sleeve of the recommended ferrule. 2. Make sure that the ferrule processing dimensions conform to the following figure. 3. If you use AWG24 to AWG22 (0.25 to 0.34 mm 2) wires, UL certification will not apply. Recommended Flat-blade Screwdriver Use a flat-blade screwdriver to connect and remove wires. Use the following flat-blade screwdriver. The following table shows manufacturers and models as of 2015/ Dec. * OMRON's exclusive purchase model XW4Z-00B is available to order as SZF 0-0 ,4×2,5 (manufactured by Phoenix Contact). Screw Terminal
- Screw terminal
- Tightening Torque 0.36 to 0.46 N • m
- Electric wiring Use the electric wire of specified size as shown above. The length of the that is not covered is 8 mm. Recommended Flat-blade Screwdriver/ Phillips Screwdriver Use a Phillips screwdriver or flat-blade screwdriver to remove the product from a DIN rail and connect and remove the electric wires. Use a Phillips screwdriver with the shape specified below and a flat- blade screwdriver in the table below. The following table shows manufacturers and models as of 2015/Dec. * OMRON's exclusive purchase model XW4Z-00B is available to order as SZF 0-0,4×2,5 (manufactured by Phoenix Contact). Applicable wire Ferrules Conduct length (mm) Stripping length (mm) (Ferrules used) Recommended ferrules (mm2) (AWG) Phoenix Contact product Weidmuller product Wago product 0.25 24 8 10 AI 0,25-8 H0.25/12 216-301 0.34 22 8 10 AI 0,34-8 H0.34/12 216-302 0.5 20 8 10 AI 0,5-8 H0.5/14 216-201 10 12 AI 0,5-10 H0.5/16 216-241 0.75 18 8 10 AI 0,75-8 H0.75/14 216-202 10 12 AI 0,75-10 H0.75/16 216-242 1/1.25 18/17 8 10 AI 1-8 H1.0/14 216-203 10 12 AI 1-10 H1.0/16 216-243 1.25/1.5 17/16 8 10 AI 1,5-8 H1.5/14 216-204 10 12 AI 1,5-10 H1.5/16 216-244 2.0/2.5 14 10 12 AI 2,5-10 H2.5/16DS Recommended crimp tool CRIMPFOX6 CRIMPFOX6T-F CRIMPFOX10S PZ6 roto Variocrimp4 Model Manufacturer ESD 0,40×2,5 Wera SZS 0,4×2,5 SZF 0-0,4×2,5 * Phoenix Contact 0.4×2.5×75 302 Wiha AEF.2,5×75 Facom 210-719 Wago SDI 0.4×2.5×75 Weidmuller 8 to 10 mm 2.6 mm max. 3.0 mm max. Side 0.4 mm 2.5 mm dia. 2.5 mm Front Wired type Applicable wire size Stripping length Stranded wires, without ferrule 0.5 to 2.5 mm2 8 mm Stranded wires, with ferrule and plastic collar 0.5 to 2.5 mm2 8 mm Stranded wires with ferrule, without plastic collar 0.5 to 2.5 mm2 8 mm Single wire 0.5 to 2.5 mm 2 8 mm Model Manufacturer ESD 0,40×2,5 Wera SZS 0,4×2,5 SZF 0-0,4×2,5 * Phoenix Contact 0.4×2.5×75 302 Wiha AEF.2,5×75 Facom 210-719 Wago SDI 0.4×2.5×75 Weidmuller Stripping length 8 mm Screw terminal Side Recommended Phillips Screwdriver Recommended Flat-blade Screwdriver 0.4 mm 2.5 mm dia. 2.5 mm 2.5 mm Front
G2RV-ST G3RV-STCommon Accessories Common Precautions <G2RV> Operating latching lever (test switch) When operating the latching lever for G2RV-ST701/501 series, use a 2.5 mm width flat-blade screwdriver.
- Applicable flat-blade screwdriver Flat-blade screwdriver with parallel cutting edge: shaft diameter 2.5 mm (3.0 mm max.)
- Always turn OFF the power supply before operating latching lever.
- Return to its original state after using the latching lever.
- Do not use the latching lever as a switch.
- Operation durability of the latching lever is 100 times or more.
- Do not keep the latching lever ON for a long period of time (24 hours or more) in order to maintain the operation check function. Method of operation of the latching lever (test switch) Keep the protective cover open when using the latching lever. Move until the latching lever clicks to the ON position (ON state). After use latching lever, in order to prevent malfunction, return the switch to contact normal position (OFF state), and make sure the protective cover is firmly closed. Using the latching lever Example: check the operation of the relay and the sequence circuit Input ratings Smoothing capacitors are used in the internal circuits of AC/DC- type G2RV-ST devices. AC/DC-type G2RV-ST devices driven by the sensor may not operate normally due to the characteristics of the smoothing capacitor. When driving such devices by the sensor, use the DC specification settings. <G3RV>
- Since the G3RV uses electronic components, do not allow it to fall, vibrate, or apply shock that exceeds the criteria. Doing so may result in failure, malfunction, or deterioration of performance.
- Tighten screw terminal for G3RV at torque 0.36 to 0.46 N · m. It may cause short-circuit failure or burning.
- Please use the voltage and current suitable for the input and output terminal portion of G3RV. It may cause short-circuit failure or burning. Mounting <The SSR Mounting Pitch (Panel Mounting)> * When five or more are installed, install with 10 mm space between each. * Please ask distributor or sales when need assistance in detail of mounting pitch. <Relationship of SSR and duct (duct depth)> Shaft diameter 2.5 mm (3.0 mm max.) Driver with a thick shaft cannot be used. Wide flat-blade screwdriver Parallel cutting edge flat-blade screwdriver <Protective cover: locked> <Protective cover: disengage> Contact normal position Contact operating position (on-state) Close protective cover Open protective cover SSR 10 mm min. 30 mm min. 80 mm min. 60 mm min. Duct or other object blocking airflow Vertical Direction Height of SSR Duct or other object blocking airflow Duct or other object blocking airflow Duct or other object blocking airflow Do not enclose the SSR in a duct of the same height. It will interfere with the heat dissipation of SSR. Use ducts that have a shallow depth, to provide a sufficient ventilation area. If the ducts cannot be made lower, place the SSR on a metal base so that it is not surrounded by the ducts. Incorrect Example Countermeasure 1 Countermeasure 2 Duct or other object blocking airflow Recommended height of the duct is 1/2 or less of the height of the SSR Duct or other object blocking airflow Duct or other object blocking airflow AirflowSSR SSR SSR Vertical Direction Metal base Mounting surface Mounting surface Mounting surface
28 G2RV-ST G3RV-STCommon Accessories Common Precautions
<Ventilation Outside the Control Panel>
- If the air inlet or air outlet has a filter, clean the filter regularly to prevent it from clogging to ensure an efficient flow of air.
- Do not place objects that may obstruct the proper ventilation for outside or inside the inlet or exhaust port, and in the outside vicinity.
- A heat exchanger, if used, should be located in front of the G3RV to ensure the efficiency of the heat exchanger.
- Please observe the ambient temperature of G3RV. The rated current of the G3RV is measured at an ambient temperature of 25°C.
- The G3RV uses a semiconductor in the output element. This causes the temperature inside the control panel to increase due to heating resulting from the flow of electrical current through the load. The G3RV reliability can be increased by adding a ventilation fan to the control panel to dispel this heat, thus lowering the ambient temperature of the G3RV. (It suggests that life expectancy is doubled by each 10°C reduction in ambient temperature.) EMI The G3RV is a Class A product (for industrial environments). When used in a residential environment, it may cause radio interference. In such case, the user may be required to take appropriate measures. SSR Inlet Be aware of airflow Exhaust (Axial fan) SSRSSR Duct or other object blocking airflow
G2RV-ST G3RV-STCommon Accessories Common Precautions Note: Use for wiring to the adjacent socket. * Replace the box (@) in the model number with the code for the covering color. @ color selection: R = red, S = blue, Y = yellow Label Separate Plate Isolation plate PLC interface unit * Please make sure applicable models, P2RVC can not be used other combination than the above table. Parts for DIN Track Mounting * When mounting DIN Track, please use End Plate (PFP-M). Refer to your OMRON website for details on PFP-@. For G2RV-ST/G3RV-ST Common Accessories (order separately) Appearance Pitch No. of poles Colors Model * Minimum order (Quantity) Maximum energizing current 6.2 mm 20 Red (R), Blue (S), Yellow (Y) PYDN-6.2ST-200@ 10 32 A Appearance Model Minimum order (Sheet) (Pieces per sheet) XW5Z-P2.5LB1 5 (1 sheet/72 pieces) Appearance Model XW5Z-EP12 Appearance Model P2RV-P3.1ST Appearance I/O classification Connection method Common process Applicable Models * Model For input Push-In PNP G2RV-ST500-AP P2RVC-8ST-I-5-1 NPN P2RVC-8ST-I-5 Screw PNP G2RV-ST700-AP P2RVC-8ST-I-7-1 For output Push-In PNP G2RV-ST500 G2RV-ST501 G3RV-ST500 P2RVC-8ST-O-5-1 NPN P2RVC-8ST-O-5 Screw PNP G2RV-ST700 G2RV-ST701 G3RV-ST700 P2RVC-8ST-O-7-1 Appearance Type Model Minimum order (Quantity) DIN Tracks 1 m PFP-100N 0.5 m PFP-50N End Plate * PFP-M Spacer PFP-S Coming Soon
30 G2RV-ST G3RV-STCommon Accessories Common Precautions
*1. Use the P2RVC-8-I-@-1(PNP) as the PLC interface unit when connecting to the CJ1W-ID232/ID262 (or a unit with an equivalent terminal arrangement). *2. Use the P2RVC-8-I-@-1(PNP) as the PLC interface unit when connecting to the CJ1W-ID231/ID261 (or a unit with an equivalent terminal arrangement). Name Appearance Cable length L (mm) Connecting Cables Applicable Connectors Cables with Loose Wires P2RV-A@C
8 I/O
1,000 P2RV-A100C Various devices 2,000 P2RV-A200C 3,000 P2RV-A300C 5,000 P2RV-A500C OMRON PLC Connecting Cables with Connectors (1:4) P2RV-4-@C 32 output points 1,000 P2RV-4-100C PLC I/O Units with MIL connectors (1:4) CJ1W-OD232/OD262, etc. 2,000 P2RV-4-200C 3,000 P2RV-4-300C 5,000 P2RV-4-500C OMRON PLC Connecting Cables with Connectors (1:4) P2RV-4-@IMC 32 input points 1,000 P2RV-4-100IMC PLC I/O Units with MIL connectors (1:4) CJ1W-ID232/ID262, etc. *1 2,000 P2RV-4-200IMC 3,000 P2RV-4-300IMC 5,000 P2RV-4-500IMC OMRON PLC Connecting Cables with Connectors (1:4) P2RV-4-@IFC 32 input points 1,000 P2RV-4-100IFC PLC I/O Units with Fujitsu connectors (1:4) CJ1W-ID231/ID261, etc. *2 2,000 P2RV-4-200IFC 3,000 P2RV-4-300IFC 5,000 P2RV-4-500IFC OMRON PLC Connecting Cables with Connectors (1:1) P2RV-A @C-OMR GRT1 8 output points 500 P2RV-A050C-OMR GRT1 Slice I/O Units (1:1) For inputs: GRT1-ID8-1 For outputs: GRT1-OD8-1 1,000 P2RV-A100C-OMR GRT1 8 input points
500 P2RV-A050IC-OMR GRT1
1,000 P2RV-A100IC-OMR GRT1 OMRON PLC Connecting Cables with Connectors (1:1) P2RV-A@C-OMR NX 8 output points 500 P2RV-A050C-OMR NX PLC I/O Units with screw-less clamp terminal block (1:1) For inputs: NX-ID4442 For outputs: NX-OD4256 1,000 P2RV-A100C-OMR NX 8 input points
500 P2RV-A050IC-OMR NX
1,000 P2RV-A100IC-OMR NX End A End B Device end PLC interface unit end L L 300 L 300 L 300 L L Removable terminal block
G2RV-ST G3RV-STCommon Accessories Common Precautions Name Appearance Cable length L (mm) Connecting Cables Applicable Connectors Schneider Electric PLC Connecting Cables P2RV-@C-SCH-@ 32 input points
500 P2RV-050C-SCH-A
Schneider Electric PLCs with 32-point connectors (1:4) For inputs: 140 DDI 353 00 For outputs: 140 DDO 353 00 1,000 P2RV-100C-SCH-A 2,000 P2RV-200C-SCH-A 3,000 P2RV-300C-SCH-A 5,000 P2RV-500C-SCH-A 32 output points
500 P2RV-050C-SCH-B
1,000 P2RV-100C-SCH-B 2,000 P2RV-200C-SCH-B 3,000 P2RV-300C-SCH-B 5,000 P2RV-500C-SCH-B 16 input points
500 P2RV-050C-SCH-C
Schneider Electric PLCs with 16-point connectors (1:2) For inputs: BMX DDI 1602 For outputs: BMX DDO 1602 1,000 P2RV-100C-SCH-C 2,000 P2RV-200C-SCH-C 3,000 P2RV-300C-SCH-C 5,000 P2RV-500C-SCH-C 16 output points
500 P2RV-050C-SCH-D
1,000 P2RV-100C-SCH-D 2,000 P2RV-200C-SCH-D 3,000 P2RV-300C-SCH-D 5,000 P2RV-500C-SCH-D Siemens PLC Connecting Cables P2RV-@C-SIM-@ 32 input points
500 P2RV-050C-SIM-A
32-point connectors (1:4) For inputs: 6ES7 321-1BL00-0AA0 For outputs: 6ES7 322-1BL00-0AA0 1,000 P2RV-100C-SIM-A 2,000 P2RV-200C-SIM-A 3,000 P2RV-300C-SIM-A 5,000 P2RV-500C-SIM-A 32 output points
500 P2RV-050C-SIM-B
1,000 P2RV-100C-SIM-B 2,000 P2RV-200C-SIM-B 3,000 P2RV-300C-SIM-B 5,000 P2RV-500C-SIM-B 16 input points
500 P2RV-050C-SIM-C
16-point connectors (1:2) For inputs: 6ES7 321-1BH02-0AA0 1,000 P2RV-100C-SIM-C 2,000 P2RV-200C-SIM-C 3,000 P2RV-300C-SIM-C 5,000 P2RV-500C-SIM-C 32 input points
500 P2RV-050C-SIM-D
32-point connectors (1:4) For inputs: 6ES7 421-1BL-0AA0 For outputs: 6ES7 422-1BL-0AA0 1,000 P2RV-100C-SIM-D 2,000 P2RV-200C-SIM-D 3,000 P2RV-300C-SIM-D 5,000 P2RV-500C-SIM-D 32 output points
500 P2RV-050C-SIM-E
1,000 P2RV-100C-SIM-E 2,000 P2RV-200C-SIM-E 3,000 P2RV-300C-SIM-E 5,000 P2RV-500C-SIM-E L 300 End A End B Device end PLC interface unit end L 300 L 300 L 300 L 300
32 G2RV-ST G3RV-STCommon Accessories Common Precautions
Ratings / characteristices Electrical schematic Input P2RVC-8ST-I-@-1 (PNP) P2RVC-8ST-I-5 (NPN) Output P2RVC-8ST-O-@-1 (PNP) P2RVC-8ST-O-5 (NPN) PLC interface unit Rated voltage 30 VAC/DC Rated current 0.5 A/poles, 2 A/unit Ambient operating temperature −40 to 55°C Vibration resistance Destruction 10 to 55 to 10 Hz, single amplitude 0.50 mm (double amplitude 1.0 mm) Malfunction 10 to 55 to 10 Hz, single amplitude 0.50 mm (double amplitude 1.0 mm) Shock resistance Destruction 300 m/s2 Malfunction 100 m/s2 Coming Soon
G2RV-ST G3RV-STCommon Accessories Common Precautions Dimensions (unit: mm) PLC interface unit Push-IN P2RVC-8ST-I-5(-1) P2RVC-8ST-O-5(-1) 12.7 7×6.2 49.6 Screw P2RVC-8ST-I-7-1 P2RVC-8ST-O-7-1 49.6 12.7 66.9 7×6.2
34 G2RV-ST G3RV-STCommon Accessories Common Precautions
Dimensions (unit: mm) Short Bars Parts for DIN Track Mounting Refer to your OMRON website for details on the PFP-@. (Except for PLC interface unit) Common Accessories (order separately) Note: Use the Short Bars for crossover wiring within one Socket or between Sockets. * Replace the box (@) in the model number with the code for the covering color. Pitch No. of poles L (Length) Colors Model * Maximum carry current 6.2 mm 20 124 Red (R) Blue (S) Yellow (Y) PYDN-6.2ST-200@ 32 A PYDN-6.2ST-200@ 2.2 15.6 124 Separate Plate XW5Z-EP12 Isolation plate P2RV-P3.1ST 7.1 88.288.2 82.2 34.8 27.1 74.2 3.4 81.3 3.1
G2RV-ST G3RV-STCommon Accessories Common Precautions Safety Precautions When mounting a short bar
- Intermediate pins can be bent by a tool and cut off for use.
- The short bar can be cut to as many poles as needed. Insert the tool from the plastic part side, and cut along the groove in the plastic part between the terminals. When cutting, take care not to break or deform the terminals. However, since the metal on the cut surface will be exposed, human safety and insulation countermeasures between adjacent products must be ensured. Such countermeasures include using insulating plate model P2RV-P3.1-ST or taking an equivalent insulation countermeasure.
- When cutting the short bar or its pins, do not touch the conductive part. If the conductive part is deformed, contact failure may result.
- When cutting the product, check that there is no person nearby and take care that a cut off piece does not fly off. Mounting a separate plate
- Use a flat-blade screwdriver to tighten the center top screw and secure the plate. Loosen the screw to remove the plate from the DIN rail.
- When using both an isolation plate and short bar together, use without removing the insulating plate will be possible if you cut the joining parts. Furthermore, the joining parts can be cut easily by using needle-nose pliers to cut them.
- After mounting to a DIN rail, check that the product is correctly held in place.
- When removing the PLC interface, place a finger at the place below and pull it out. Precautions for Correct Use Bend Cut off Cut Isolation plate IP20 IP20 IP20 IP20 Conductive part M4 Screw Joining parts
Terms and Conditions Agreement Read and understand this catalog. Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron.com/global/ or contact your Omron representative for published information. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions.
Authorized Distributor: Kyoto, JAPAN Contact : www.ia.omron.com Regional Headquarters OMRON ASIA PACIFIC PTE. LTD. 438B Alexandra Road, #08-01/02 Alexandra Technopark, Singapore 119968 Tel: (65) 6835-3011 Fax: (65) 6835-2711 OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A. Tel: (1) 847-843-7900 Fax: (1) 847-843-7787 OMRON (CHINA) CO., LTD. Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China Tel: (86) 21-5037-2222 Fax: (86) 21-5037-2200 OMRON EUROPE B.V. Wegalaan 67-69, 2132 JD Hoofddorp The Netherlands Tel: (31) 2356-81-300 Fax: (31) 2356-81-388 Note: Do not use this document to operate the Unit. OMRON Corporation Industrial Automation Company Cat. No. J265-E1-01 0922 (0922) ©OMRON Corporation 2022 All Rights Reserved. In the interest of product improvement, specifications are subject to change without notice.